0% found this document useful (0 votes)
48 views

FST Dfs Jbus

The J-Bus driver supports connections over RS-232 and RS-485 using half duplex communication. The FieldServer can be configured as a J-Bus client or server to perform read and write operations. As a client, it supports functions to read coil status, input status, holding registers, input registers, and force or preset single coils and registers. As a server, it can perform the same read operations in response to client requests.

Uploaded by

Eric Dunn
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views

FST Dfs Jbus

The J-Bus driver supports connections over RS-232 and RS-485 using half duplex communication. The FieldServer can be configured as a J-Bus client or server to perform read and write operations. As a client, it supports functions to read coil status, input status, holding registers, input registers, and force or preset single coils and registers. As a server, it can perform the same read operations in response to client requests.

Uploaded by

Eric Dunn
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Protocol Driver

Driver Version: 4.01 Document Revision: 6

FieldServer Driver - Serial


FS-8700-62

J-BUS
Description The J-Bus driver supports connections over RS-232 and RS-485 (Half Duplex). The FieldServer can be configured as a client or server using the J-Bus protocol. Fieldserver Mode Client Server Formal Driver Type J-Bus is a Serial protocol that can be used for a Client or Server transactions. Compatibility Matrix FieldServer Model FS-X2010 FS-X2011 FS-X40 FS-X30 Connection Information Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability Devices tested Device MGE UPS Tested (FACTORY, SITE) Site RS-232 or RS-485 110; 300; 600; 1200; 2400; 4800; 9600; 19200; 28800; 38400; 57600; 115200 Baud 7,8 1 Odd, Even, None, Mark, Space Yes (For RS-485) Compatible with this driver Yes (Using P1 or R1) Yes (Using P1 or R1) Yes Yes Nodes 1 - 255 1 - 255 Comments J-Bus station Address of the node(s) J-Bus station Address of the node(s)

Bold text indicates default values.

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: [email protected] Website: www.fieldserver.com Page 1 of 3

Protocol Driver

Connection configurations No connection diagram possible (multiple unknown connections supported) Communications functions Supported Functions at a Glance Data Types Supported FieldServer Data Type Analog Input Digital Input Analog Register Digital Output Read Operations supported FieldServer as a Client (Function code) (1) Read coil status (2) Read input status (3) Read holding registers (4) Read input registers (11) Fetch comm Event (Write not supported) Write (Control) Operations supported FieldServer as a Client (5) Force single coil (6) Preset single register (10) Poll 484 (Modicon 484 device) (15) Force multiple coils (16) Preset multiple registers (126) Force single Coil-127 (Only for coil 127) Unsupported Functions and Data Types Function Programming messages (07) Read Exception status (08-xx) Diagnostic Sub-functions (12) Fetch comm event log (17) Report Slave_ID (20) Read general reference (21) Write general reference (22) Mask 4 register (23) Read/Write 4 register (24) Read FIFO Queue FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: [email protected] Website: www.fieldserver.com Page 2 of 3 Reason FieldServer is a data transfer device, and as such, programming messages are not required FieldServer as a Server (5) Force single coil (6) Preset single register (10) Poll 484 (Modicon 484 device) (15) Force multiple coils (16) Preset multiple registers (126) Force single Coil-127 (Only for coil 127) FieldServer as a Server (Function code) (1) Read coil status (2) Read input status (3) Read holding registers (4) Read input registers (11) Fetch comm Event (Write not supported) Description (or Device Data Type) FLOAT, UInt16, SInt16 , Byte BIT, , Packed_Bit, FLOAT, UInt16, SInt16 , Byte BIT, , Packed_Bit,

Protocol Driver

THIS PAGE INTENTIONALLY LEFT BLANK

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: [email protected] Website: www.fieldserver.com Page 3 of 3

You might also like