NFS2-3030/E: Fire Alarm Control Panel Installation Manual
NFS2-3030/E: Fire Alarm Control Panel Installation Manual
NFS2-3030/E
Installation Manual
E1
ECN 08-364
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH, NIS, Notifier Integrated Systems, and NOTIFIRENET are all trademarks; and Acclimate Plus, FlashScan, NION, NOTIFIER, ONYX, ONYXWorks, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Friday, August 29, 2008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information: Product name and version number (if applicable) Printed manual or online Help Topic Title (for online Help) Page number (for printed manual) Brief description of content you think should be improved or corrected Your suggestion for how to correct/improve documentation Send email messages to: [email protected] Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Section 1: About This Manual.................................................................................................. 7
1.1: Standards and Other Documents....................................................................................................................7 1.2: UL 864 Compliance.......................................................................................................................................8 1.2.1: Products Subject to AHJ Approval......................................................................................................8 1.3: Related Documents ........................................................................................................................................8 1.4: Cautions and Warnings ................................................................................................................................10
Section 3: Installation............................................................................................................. 19
3.1: Preparing for Installation .............................................................................................................................19 3.2: Installation Checklist ...................................................................................................................................19 3.3: Mounting a Cabinet .....................................................................................................................................20 3.4: Laying Out Equipment in Cabinet and Chassis ...........................................................................................22 3.5: Attaching the CPU & Chassis......................................................................................................................23 3.5.1: Mounting in CHS-M3........................................................................................................................23 3.5.2: Mounting in the CA-2 Audio System Chassis ..................................................................................24 3.5.3: Mounting Chassis in Backbox...........................................................................................................25 3.5.4: Memory-Backup Battery ...................................................................................................................25 3.6: Attaching Option Boards .............................................................................................................................26 Mounting procedures............................................................................................................................27 3.7: Connecting the Network Communications Module ....................................................................................27 3.8: Connecting the Loop Control and Expander Modules ...............................................................................28 3.8.1: Mounting Instructions .......................................................................................................................28 3.8.2: Audio Applications with Chassis CA-2 ...........................................................................................29 3.8.3: Setting SLC Loop Number ................................................................................................................29 3.8.4: Enabling External Power Supervision...............................................................................................29 3.8.5: Installing a Multi-layer Module into the Chassis ..............................................................................29 3.9: Form-C Relays on the CPU .........................................................................................................................32 3.10: Connecting Power Sources and Outputs....................................................................................................33 3.10.1: Overview .........................................................................................................................................33 3.10.2: Connecting the Power Supply .........................................................................................................34 3.10.3: Checking AC Power ........................................................................................................................34 3.10.4: Auxiliary Power Supply Connections .............................................................................................34 3.11: UL Power-limited Wiring Requirements ...................................................................................................35 3.12: ULC Remote Connection Feature .............................................................................................................35 3.13: Installing Printers.......................................................................................................................................36 3.13.1: Printer Installation Sequence ...........................................................................................................37 3.13.2: Configuring the Printer....................................................................................................................38 PRN Printer Settings.............................................................................................................................38 Keltron Printer VS4095/5 Settings.......................................................................................................38 3.14: Wiring a Signaling Line Circuit (SLC)......................................................................................................39 3.14.1: SLC Overview .................................................................................................................................39
NFS2-3030/E Installation Manual P/N 52544:E1 02/05/2008 5
Table of Contents
3.14.2: SLC Capacity...................................................................................................................................39 3.14.3: SLC Installation ...............................................................................................................................40 3.15: Connecting a PC for Programming............................................................................................................40
Index ........................................................................................................................................ 61
Underwriters Laboratories (UL) UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers - Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1971 Visual Signaling Appliances UL 1076 Proprietary Burglar Alarm Systems UL 2017 Standard for General-Purpose Signaling Devices and Systems
Underwriters Laboratories of Canada (ULC) ULC-S527-99 Standard for Control Units for Fire Alarm Systems ULC S524 Standard for the Installation of Fire Alarm Systems
Other EIA-485 and EIA-232 Serial Interface Standards NEC Article 300 Wiring Methods
UL 864 Compliance
NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Canadian Electrical Code, Part 1
Related Documents FCPS-24S6/FCPS-24S8 Field Charger/Power Supply Networking NotiFireNet Manual, Network Version 5.0 & Higher NCM-W/F Installation Document NCS Network Control Station, Network Version 5.0 & Higher Manual NCA-2 Network Control Annunciator Manual NCA Network Control Annunciator Manual ONYXWorks Workstation System Components Annunciator Control System Manual ACM-8R Annunciator Control Module Manual ACT-1 Installation Document LCD-80 Manual LCD-160 Manual LDM Series Lamp Driver Annunciator Manual SCS Smoke Control Manual (Smoke and HVAC Control Station) Manual DPI-232 Manual TM-4 Installation Document (Reverse Polarity Transmitter) UDACT Manual (Universal Digital Alarm Communicator/Transmitter) ACT-2 Installation Document VEC 25/50 Manual RM-1 Series Remote Microphone Installation Document RA400Z Remote LED Annunciator Document UZC-256 Universal Zone Coder Manual UZC-256 Programming Manual XP Transponder Manual XP10-M Ten Input Monitor Module Installation Document XP6-C Supervised Control Module Installation Document XP6-MA Six Zone Interface Module Installation Document XP6-R Six Relay Control Module Installation Document XPIQ Audio Transponder Manual 51977
Document Number 51584 51533 51658 52482 51482 52342 Document Number 15842 15342 52527 15037 51850 15885 15712 51499 51490 50050 51118 50686 51138 I56-508 15216 15976 15888 I56-1803 I56-1805 I56-1806 I56-1804 51013
NOTE: Where used in this manual, the term CPU refers to the main circuit board for the fire alarm control panels central processing unit (see Section 2.2 System Components for a more detailed list of part numbers.)
WARNING: SUMMARY IN BOLD INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL INJURY.
10
2.1.2 Options
Refer to Section 2.2 System Components for descriptions of the various optional modules. Rubberized keypad with a standard QWERTY keyboard layout, a 640-character LCD display, indicator LEDs, and switches.
11
System Overview
System Components
Separately ordered Loop Control Modules and Loop Expander Modules provide up to ten SLC loops. Optional equipment includes: ACS devices, UDACT Universal Digital Alarm Communicator/Transmitter, ACM-8R remote relay module to provide additional relay points, and audio/voice components.
Central Processing Unit (CPU) and Keypad/Display The central processing unit for the NFS2-3030 system can be ordered with a keypad/display (P/N CPU2-3030D) or without a keypad/display (P/N CPU2-3030ND). CPU2-3030D serves as primary display version for ULC applications. CPU2-3030ND is intended for use in network applications; LEDs and momentary switches on the printed circuit board mimic those on the keypad to enable operation and troubleshooting at the panel when it is used without a local primary display. Power supply The main power supply is AMPS-24/AMPS-24E, which provides +24 VDC power and a battery charger for a basic system. Auxiliary power supplies and/or battery chargers are available to customize large systems. Enclosures Four cabinet sizes are available; doors and backboxes are ordered separately. A size backboxes hold one row of modules, B size backboxes hold two rows, C size backboxes hold three rows, and D size backboxes hold four rows. See Section 2.4 System Cabinets for basic description. A variety of dress panels, trim rings, and blank modules are available to accompany specific combinations of system equipment; contact Notifier for a complete parts list. SLC Loops: LCM-320, LEM-320 To provide one SLC loop, connect one LCM-320 to the panel. Connect an LEM-320 to the LCM-320 to provide a second loop. Up to five pairs of modules can be installed on the panel to provide a maximum of ten SLC loops. Network Connection Connect a wire or fiber version of the NCM to provide a connection to the NotiFireNet (network version 5.0 or higher). Annunciators The NFS2-3030 supports ACM-24AT/ACM-48A (and their expanders) with either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 (and their expanders) with 64 points at an address and Notifiers other ACS devices. (See Section 2.5 Compatible Equipment if looking for specific ACS devices.)
12
System Components
System Overview
Audio System Voice evacuation applications are documented in the Audio System manuals: Digital Audio Series Manual, and the AA-series Audio Amplifiers Manual.
13
System Overview
Product Diagram
*J1, Network Connection (NUP), Cable P/N 75556 *J7 SLC Loop Control and Expander Modules (LCM-320, LEM-320) Cable P/N 75565
J6 Security switch connection J5 Trouble bus connection J2 LCD Connection J4 Backlight connection
SW3 Acknowledge SW4 Signal Silence SW5 System Reset SW6 Lamp Test
J13 Power connections (non-power-limited). See Section 3.10 Connecting Power Sources and Outputs.
Lithium battery for backup of on-board memory (See Section 3.5.4 Memory-Backup Battery) J9 Keypad Connection
TB6 Accessory Power (See Section 3.10 Connecting Power Sources and Outputs)
Note: Dotted line indicates location of optional keypad & LCD display *Circuits marked with an asterisk are supervised by communication loss. See Appendix A, Electrical Specifications for details.
CPU23030.wmf
Product Diagram
System Overview
The keyboard/display assembly is shown in Figure 2.2. As shown in Figure 2.3, LEDs on the keyboard/display are repeated on the printed circuit board. This enables operation and troubleshooting when the panel is used without the display assembly.
Controls Active (Keypad only) LED1 Power (Green) LED3 Fire Alarm (Red) LED8 Pre-Alarm (Red) LED7 Security (Blue) LED9 Supervisory (Yellow) LED6 System Trouble (Yellow) LED12 Other Event (Yellow) LED10 Signals Silenced (Yellow) LED11 Point Disabled (Yellow) LED5 CPU Failure (Yellow) LED4 Factory Use Only
3030-LEDSUL9th.wmf, 3030NCA2keypad.wmf
LEDs on Keypad
CPU-3030D-ACS.cdr
15
System Overview
System Cabinets
See Section 3.10, Connecting Power Sources and Outputs, on page 33 for basic wiring connections; see the AMPS-24/E Manual for complete details. Refer to the AMPS-24/E Manual to determine whether your system requires an auxiliary power supply.
DR-B4, ADDR-B4
DR-C4, ADDR-C4
DR-D4, ADDR-D4
The CPU and adjacent first-row modules mount in chassis CHS-M3. Additional rows of modules mount in the cabinet using CHS-4, CHS-4N, CHS-4L, or other chassis compatible with CAB-4 series enclosures. Some additional components available in the CAB-4 series include: DP-DISP. An Inner Dress Panel for covering the backbox area surrounding various modules; for use in the top row. BMP-1. Blank Module Plate for covering an unused module position. Provides another location for mounting option boards such as TM-4 or NCM. BP2-4. Battery dress panel. DP-1B. Dress plate, covers an entire row. ADP-4B. Annunciator dress panel; for use in all but the top row.
For information on audio chassis and dress panels, refer to the DVC and DAA Audio Series Manual.
16
Compatible Equipment
System Overview
17
System Overview
RA400 Remote Annunciator RA400Z Remote Annunciator with diode RKS-S Remote Security Keyswitch (Not ULC-listed) RPJ-1 Remote Phone Jack RPT-485F EIA-485 Repeater (Fiber) RPT-485W EIA-485 Repeater (Wire) RPT-485WF EIA-485 Repeater (Wire/Fiber) RM-1 Remote Microphone RM-1SA Remote Microphone SCS-8, SCE-8 Smoke Control System SDX-551 Intelligent Photoelectric Detector SDX-551TH Intelligent Photoelectric and Thermal Detector
Compatible Equipment
SDX-751 Intelligent Photoelectric Detector STS-1 Security Tamper Switch (Not ULC-listed) TM-4 Transmitter Module UDACT Universal Digital Alarm Communicator Transmitter UZC-256 Universal Zone Coder VeriFire Tools Upload/Download Software XPIQ Quad Intelligent Audio Transponder (Audio Applications) XP6-C Supervised Control Module XP6-R Six Relay Control Module XP10-M Ten Input Monitor Module XP6-MA Six Zone Interface Module
Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous Editions of UL 864
NOTE: The products in this list have not received UL 864 9th Edition certification and may only be used in retrofit applications (see Section 1.2, UL 864 Compliance, on page 8).
ACM-16AT Annunciator Control Module ACM-32A Annunciator Control Module ACPS-2406 Auxiliary Charger/Power Supply AEM-16AT Annunciator Expander Module AEM-32A Annunciator Expander Module AFM-16A Annunciator Fixed Module AFM-32A Annunciator Fixed Module AMG-1/E Audio Message Generator APS-6R Auxiliary Power Supply BGX-101L Addressable Manual Pull Station CHG-120 Battery Charger FCPS-24 Field Charger/Power Supply IPX-751 Advanced Multi-Sensor Intelligent Detector MMX-1 Addressable Monitor Module NCA Network Communications Annunciator VS4095 Keltron Printer (Dress plate P-40) (Not ULC-listed) PRN-4, PRN-5 80-Column Printers RFX Wireless Transmitter (version 2.0 and higher) (Not ULC-listed): SDRF-751 Wireless Photo/Thermal Smoke Detector; 5817CB Wireless Monitor Module XPIQ Quad Intelligent Audio Transponder (NAC Applications) XP5-C Transponder Control Module XP5-M Transponder Monitor Module XPC-8 Transponder Control Module XPM-8 Transponder Monitor Module XPM-8L Transponder Monitor Module XPP-1 Transponder Processor XPR-8 Transponder Relay Module
18
Section 3: Installation
3.1 Preparing for Installation
Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate temperature. The area should be readily accessible with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely. Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appropriate knockouts. (Refer to Section 3.11 UL Powerlimited Wiring Requirements for selection guidelines.) Before installing the fire alarm system, read the following: Review the installation precautions at the front of this manual. Installers should be familiar with the standards and codes specified in Section 1.1 Standards and Other Documents. All wiring must comply with the National and Local codes for fire alarm systems. Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a separate battery cabinet; this space is for internal battery installation. Review installation instructions in Section 3.2 Installation Checklist.
WARNING: RISK OF IRREPARABLE EQUIPMENT DAMAGE MAKE SURE TO INSTALL SYSTEM COMPONENTS IN THE SEQUENCE LISTED BELOW. FAILURE TO DO SO CAN DAMAGE THE CONTROL PANEL AND OTHER SYSTEM COMPONENTS.
WARNING: RISK OF IRREPARABLE EQUIPMENT DAMAGE WEAR A STATIC DISCHARGE STRAP ON WRIST TO PREVENT EQUIPMENT DAMAGE.
4. 5. 6.
DVC Digital Voice Command Manual, DAA Digital Audio Amplifiers Manual, AA-series Audio Amplifiers Manual Annunciators and other ACS devices Installation document for the specific device (such as ACS Manual, ACM-8R Manual, etc.) Remote Data Port devices LCD-160 Manual Table 3.1 Installation Checklist (1 of 2)
19
Installation
Mounting a Cabinet
8. 9.
Wire the Signaling Line Circuits (Notification Appliance Circuits and Initiating Device Circuits) Calculate the proper battery rating. Main Power Supply Manual Install main power supply & batteries in Section 3.10 Connecting Power Sources and Outputs separate enclosure. Run cable to main Section 3.11 UL Power-limited Wiring Requirements & optional power supplies, DC power outputs, relays, etc.
Refer to: Section 3.13 Installing Printers NotiFireNet Version 5.0 & Higher Manual, and/or Installation document for specific device(s) Section 3.14 Wiring a Signaling Line Circuit (SLC) and the SLC Wiring Manual
Main Power Supply Manual BB-100/200 Cabinet Installation Instructions Auxiliary power supply and/or Auxiliary power supply manuals and/or battery charger external battery charger manuals. Note: If using multiple power supplies with one set of batteries, refer to main power supply manual for connection requirements. Check that all mounting holes are secured to insure a proper Earth Ground connection. Connect wire shielding to Earth Ground. Remove insulator from lithium battery Section 3.5.4 Memory-Backup Battery on CPU Apply AC power to the control panel by placing the external circuit breaker to the ON position. Do NOT connect batteries until AC power is checked (see next step). Check AC power. Section 3.10.3 Checking AC Power Connect the batteries using interconnect cable as described in power supply manual. Install the dress panels, doors and CAB-3/CAB-4 Series Cabinet Installation Document covers. Program the control panel. Programming Manual. Field test the system. Section 5 Testing the System Table 3.1 Installation Checklist (2 of 2)
CAUTION: UNLESS YOU ARE FAMILIAR WITH THE PLACEMENT OF COMPONENTS WITHIN THIS BACKBOX, ONLY USE THE KNOCKOUT LOCATIONS PROVIDED FOR CONDUIT ENTRY.
20
Mounting a Cabinet
Installation
Follow the instructions below. 1. 2. 3. 4. 5. 6. 7. Mark and pre-drill holes for the top two keyhole mounting bolts. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.11 UL Power-limited Wiring Requirements.) Using the keyholes, mount the backbox over the two screws. Mark the location for the two lower holes, remove the backbox and drill the mounting holes. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all fasteners securely. Feed wires through appropriate knockouts. Install CPU and other components according to this section, before installing hinges and door (see CAB-3/CAB-4 Series Cabinet Installation Document).
CAB-4 Series backbox, D-size (four-row) CAB-4 Series backbox, A-size (one-row)
CAB4cabinetmountingholes.cdr
21
Installation
Positions 3 and 4 of CHS-M3 can hold up to four layers of equipment Figure 3.2 Chassis CHS-M3 including option boards and annunciators (door-mounted in front of CHS-M3). See Figure 3.4 for possible configurations of these four layers. The BMP-1 Blank Module Plate covers unused positions and also provides a location to doormount some option boards (see BMP-1 Product Installation Drawing for details). CA-2 The CA-2 Audio Chassis assembly includes hardware to mount an audio command center installation in two rows of a CAB-4 backbox. Equipment will be located in the chassis as shown in Figure 3.6. See Section 3.5.2, Mounting in the CA-2 Audio System Chassis and the CA-2 Installation Document.
Half-chassis for control panel and optional pair of Loop Control and Expander Modules. Back plate Microphone and handset well
22
CA2chassisassembly.wmf
CHS-M3.cdr
Installation
Layer 4 door-mounted*
Layer 4 mounted to PEM studs and tab-slot; Layer 3 suspended from Layer 4
*Note: If CHS-4N is used, door-mounting is only for use with ACM-24AT and ACM-48A series annunciators.
Figure 3.4 Configuring Equipment in Chassis (Side View): Positions 3 and 4 of CHS-M3, All 4 Positions of CHS-4N Second, third, and fourth rows of equipment use any chassis compatible with CAB-4 series backboxes, such as CHS-4N (shipped as part of CHS-4MB) or CHS-4L. Refer to the CAB-3/CAB-4 Series Cabinet Installation Document for a complete list. Some equipment (such as annunciators) can be door-mounted as shown in Figure 3.9; refer to your equipments documentation for instructions. Examples of option boards are LCM-320, LEM-320, wire and fiber versions of the NCM, TM-4, and DPI-232; see Section 3.6 Attaching Option Boards. The documentation shipped with your equipment may also contain device-specific instructions.
NOTE: It is recommended that system design take into consideration the UL requirements for minimum separation of power-limited and non-power-limited wiring; for example, having all nonpower-limited circuits grouped in one area of the cabinet (see Section 3.11 UL Power-limited Wiring Requirements and your power supply manual).
2.
CHS-M3-options.cdr
23
Installation
3.
Place the board over the stand-offs so that mounting holes line up with those on the chassis. Secure all stand-offs with screws provided.
CPU standoffs at Positions 1 and 2: 1.5 inch (38.1 mm) for use with CPU2-3030D or 0.25 inch (6.35 mm) for use with CPU2-3030ND
Chassis-mounting slots CPU2-3030ND (without keypad/display) CPU2-3030D (with keypad/display) NCA-2 (see NCA-2 Manual)
CAUTION: IT IS CRITICAL THAT ALL MOUNTING HOLES OF THE FIRE ALARM CONTROL PANEL ARE SECURED WITH A SCREW OR STAND-OFF TO INSURE CONTINUITY OF EARTH GROUND.
24
CHS-M3.cdr
Installation
The NFS2-3030 mounts in the upper half-chassis. (Refer to Figure 3.6 and Figure 3.7.) If first mounting an optional LCM-320/LEM-320 pair behind the FACP, refer to Section 3.8.2, Audio Applications with Chassis CA-2. Mount the NFS2-3030 to its half-chassis without removing the half-chassis from the back plate. Refer to Memory-Backup Battery on page 25 for removal of insulator.
Upper half-chassis NFS2-3030
Slide the tabs at the bottom of the control panel into the inner slot at the bottom of the chassis. (See the DVC Manual for details)
Figure 3.7 Mounting the NFS2-3030 onto the CA-2 Half-chassis Refer to the DVC Manual for installation of the DVC, microphone and handset into the CA-2.
Installation
3.
CPU2-3030D only: Disconnect wiring and remove CPU2-3030D from backbox (3 screws at top, lift board tabs out of slot) and remove keypad (4 screws on back, LCD display stays attached). Remove battery from under clip (use fingers, because screwdriver could damage components) and insert new battery.
4.
CAUTION: THE BATTERY USED IN THIS DEVICE MAY PRESENT A RISK OF FIRE OR CHEMICAL BURN IF MISTREATED. DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 212F (100C), OR INCINERATE. REPLACE BATTERY WITH NOTIFIER P/N 31004 "(RAYOVAC LITHIUM 3 VOLT BR2335)" ONLY. USE OF ANOTHER BATTERY MAY PRESENT A RISK OF FIRE OR EXPLOSION.
5. 6. 7.
CPU2-3030D only: Replace keyboard, reinstall CPU2-3030D into chassis, and reconnect wiring. Follow system power-up procedures. Dispose of used battery promptly. Keep away from children. Do not disassemble and do not dispose of in fire.
To mount option boards in the front of the chassis, use stand-offs built into the chassis arms.
To mount option boards against the CHS-M3 backplate, attach stand-offs to the chassis studs.
When applicable, slide tabs at bottom of option boards into the matching slot.
Figure 3.8 Mounting Option Boards in CHS-M3 As described in Section 3.4 Laying Out Equipment in Cabinet and Chassis, up to eight option boards can be mounted in CHS-M3 to the right of the CPU; additional modules can be mounted in other chassis. There are no slots in the first (back) two layers, but option boards with tabs (such as NCM-W) will still fit in those positions.
26
CHS-M3.cdr
Installation
Option boards can be door-mounted behind a single-space blank plate (see Figure 3.9), and mounted in any CAB-4 compatible chassis.
Mount single-space blank plate onto compatible dress panel
tm4adp4.cdr
Mount option board onto stand-offs on the blank plate Fasten option board to the plate with four screws (included).
Note: Mounting instructions for option boards are the same in various dress panels.
Mounting procedures
1. 2. 3. Install four 1 inch (25.4 mm) stand-offs onto the chassis as shown in Figure 3.8. Place the first option board over the stand-offs so that holes line up. If no more option boards will be mounted in that position, securely fasten all stand-offs with screws (provided with module). If mounting a second or third option board, attach another layer of stand-offs and repeat steps 2-3. Note: Set the switches on an option board before mounting another layer in front of it. If mounting a pair of SLC loop modules, refer to Section 3.8 Connecting the Loop Control and Expander Modules and to Section 3.8.5 Installing a Multi-layer Module into the Chassis. For the top (fourth) layer of option boards, slide the tab at the bottom of the board into the slots on the chassis, and lay the board back onto the top of the chassis so that the studs line up with mounting holes on the option board. Securely fasten all stand-offs with screws provided with module. If mounting the option board behind a blank module plate in a dress plate or annunciator backbox, see Figure 3.9 and the BMP-1 Product Installation Drawing. This dress plate is suitable for option boards, which do not need to be visible or accessible when the door is closed. If mounting a pair of loop control/expander modules, see Section 3.8 Connecting the Loop Control and Expander Modules.
4.
5.
6.
7.
NOTE: Mounting two pairs of loop-control and -expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position.
Installation
version of the NCM can be mounted behind the DVC on its chassis; see the DVC Manual for instructions. If using the Digital Audio Amplifier, the DAAs wire or fiber version of the NCM can be mounted on the DAA chassis; see the DAA Manual for instructions. 1. Mount the NCM in the selected position. If another board is going to be mounted in the slot immediately in front of it, use stand-offs to secure it in place. Otherwise use the screws provided. Connect J1 on the CPU to J3 on the NCM using the network cable provided (P/N 75556). Do not connect two NCMs via NUP ports (aka NUP to NUP). When installing an NCM: Connect Channel A and/or Channel B as described in the NCM Installation Document.
2. 3.
NOTE: See the NotiFireNet Version 5.0 & Higher Manual and NCM Installation Document for system configuration information. See the BMP-1 Product Installation Drawing if considering mounting the module (wire version) behind blank module plate in a dress plate or annunciator backbox.
NOTE: Over-bending fiber-optic cable can damage it. Do not exceed a 3 inch (7.62 cm) minimum bend radius.
After all loop-control and loop-expander modules are mounted in the cabinet, connect the SLC loops to TB1 on each loop-control and loop-expander module as shown in Figure 3.16. Daisy-chain the loop-control modules as shown in Figure 3.15. The ribbon-cable connection runs from header J7 on the CPU to header J1 (Data in) on the first loop-control module, from J3 (Data out) on that unit to J1 on the next unit in the chain, and likewise for up to five loop-control modules. Each module should be assigned a unique SLC loop number (see below); loop number does not need to match the modules location in this daisy-chain.
28
Installation
FlashScan devices can operate in either FlashScan or, for retrofit applications, CLIP mode. Each LCM-320 or LEM-320 running a FlashScan SLC can support up to 159 detectors and 159 modules. CLIP loops are limited to 99 detectors and 99 modules. These and other capacity restrictions for CLIP mode loops are discussed in Section 3.14 Wiring a Signaling Line Circuit (SLC). Refer to the SLC Wiring Manual for wiring requirements and specific details.
CAUTION: DO NOT PROGRAM MORE THAN 99 ADDRESSES ON A CLIP-MODE SLC LOOP, BECAUSE THIS WILL SLOW THE SYSTEM DOWN AND COMPROMISE THE RESPONSE TIME OF THE PANEL TO DISPLAY OFF-NORMAL EVENTS.
Figure 3.10 Mounting First Pair of Loop Control and Expander Modules in CA-2 The first pair of loop control and expander modules should be mounted behind the DVC as shown in Figure 3.10, or in the row immediately below the CA-2. Any additional loop control and expander modules should be mounted in the row immediately below the CA-2.
CA23030LCMLEM.wmf
29
Installation
Stand-off locations
J3 Data Out to next LCM-320 J1 Data In from control panel or from previous LCM-320 Ground Fault LEDs: D32 Loop Expander Module Ground Fault D28 Loop Control Module Ground Fault
LCM-320.wmf
LEM-320.wmf
J2 LEM-320 Connection
LCM-320 Connection
LCM-320
SW1 Set to assign a unique SLC loop number Note: Do not cut any jumpers on LCM-320 or LEM-320.
LEM-320
WARNING: RISK EQUIPMENT DAMAGE. USE SPECIFIED STAND-OFF MOUNTING LOCATIONS ONLY. SEE FIGURES 3.11 AND 3.12. DO NOT USE CORNER HOLES FOR INSTALLATION PURPOSES.
J1
J2
B+
A+ BSLC
A-
The long-pin end plugs directly into the back of the Loop Control Module board.
J1
Stand-off locations
The short-pin end plugs directly into the top of the Loop Expander Module plug.
TB1
!
LEM-LCM.cdr
J1
J2
CAUTION: IF THE STACKER-CONNECTOR IS INSTALLED UPSIDE-DOWN, THE SHORT-PIN END OF THE PLUG CAN FAIL TO MAKE A SECURE CONNECTION WHEN PLUGGED THROUGH THE LOOP CONTROL MODULE.
Figure 3.12 Connecting Loop Control Modules with Loop Expander Modules
30
Installation
Top Slot
voice-mount-mod.cdr
Module Screw
Chassis
Bottom Slots
Figure 3.14 Inserting Pair of Loop Control and Expander Modules into CHS-4L
The red stripe on the ribbon cable is indicated by the dark line NOTE: The red stripe on the ribbon cable indicates position 1. Position 1 of the ribbon cable should line up with position 1 on J7 of the CPU and J1 and J3 of the LCM-320.
J7 on CPU
J1 on LCM-320 Data in
3030LCMchainrv2.wmf
WARNING: INSTALL THE RIBBON CABLE AS SHOWN. DO NOT FORCE OR MODIFY THE CABLE TO FIT ANY OTHER WAY. EQUIPMENT DAMAGE CAN RESULT FROM INCORRECT ALIGNMENT.
Figure 3.15 Connecting Multiple Pairs of Loop Control and Expander Modules
CHS-4L-LEM-LCM.cdr
31
Installation
LCM-SLC.cdr
The Supervisory and Security contacts can also be configured as Alarm contacts by setting switches SW1 and SW2 away from the factory default positions shown in Figure 3.17.
SW1 set to Security SW2 set to Supervisory Move switch to opposite position to convert to Alarm relays.
3030-2-relays.wmf
32
LEM-SLC.cdr
Installation
WARNING: SEVERAL SOURCES OF POWER CAN BE CONNECTED TO THE CONTROL PANEL. BEFORE SERVICING THE CONTROL PANEL, DISCONNECT ALL SOURCES OF INPUT POWER INCLUDING THE BATTERY. WHILE ENERGIZED, THE CONTROL PANEL AND ASSOCIATED EQUIPMENT CAN BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES.
3.10.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical connections include the following: Primary power source. +24VDC, delivered through AMPS-24/AMPS-24E main power supply. If AMPS-24/E is mounted in a separate cabinet, power-supply wiring must be in conduit (for cabinet placement information see Section 3.4 Laying Out Equipment in Cabinet and Chassis and the AMPS-24/E Manual. Secondary power source. +24 VDC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary (battery) power is required to support the system during loss of primary power. External power sources. +24VDC auxiliary power supplies that are UL/ULC-listed for fire protective service. Accessory power for peripheral devices. TB3 (TB6 on previous AMPS-24/E versions) on the CPU draws power from primary, secondary and external sources to pass +24 VDC power to devices within the same enclosure as the CPU. If those devices have outputs, the outputs must be power-limited. Power rating is limited by the AMPS-24/24E primary power source, which is +24VDC and 5 Amps max. Refer to the Power Supplies Calculations Table of the AMPS-24/24E Manual for further details.
NOTE: The CPU ships with an insulator to prevents its lithium battery from discharging. To preserve the battery, this insulator should be left in place as long as possible before applying AC power. Some installers may find it convenient to remove the insulator before mounting all equipment.
NOTE: If using multiple power supplies with one set of batteries, refer to main power supply manual for connection requirements.
33
Installation
CPU2-3030
3030-AMPS-24rev2.wmf
Orange
Brown
Black
Black
Red
NOTE: For power supply connection wiring for previous versions of the AMPS-24/E, refer to the AMPS-24/E manual.
CAUTION: WHILE CHECKING AC POWER, MAKE SURE BATTERIES ARE NOT CONNECTED.
Component CPU
Red
Status The green Power indicator will come on when power is coming from the main power supply. The yellow Trouble indicator will come on until batteries are connected. The green AC indicator will come on when AC is supplied. The yellow Trouble indicator will come on until batteries are connected. The yellow Trouble indicator comes on because batteries are not connected.
34
Installation
NFS2-3030
3030ULWIRING.cdr
Power-limited circuits
Separating non-power-limited and power limited circuits within the backbox with adhesive squares
Figure 3.19 Typical Wiring in a Four-Row Backbox Some devices (such as ACM-8R and LDM-R32) are power-limited only when connected to powerlimited sources. When one of these devices is connected to a non-power-limited source, the powerlimited marking must be removed, and at the time of installation, each non-power-limited circuit connected to these modules must be identified in the space provided on the cabinet door label.
NOTE: Relays are power-limited only when connected to power-limited sources for the relay outputs.
amps24cab3wiring.cdr
35
Installation
Installing Printers
Disconnecting UDACT for Annual Testing Install UDACT as the last device on the EIA485 line, with a listed key switch such as AKS-1B installed on the EIA-485 line. In this case only, install the ELR between the EIA-485 wires just in advance of the key switch (see Figure 3.20). The key switch should be installed so that key-removed is the closed position; it should be located inside the same backbox as the UDACT, as close to the UDACT as possible.
NOTE: During testing when the key switch is turned, the panel will report a communication failure for the UDACTs address.
UDACT
CPU
Figure 3.20 Wiring a Key Switch to Disconnect UDACT During Annual Testing
3030-UDACT-switch.cdr
36
6769cov.tif
Installing Printers
Installation
2.
DC IN +
3030-keltron.cdr
Figure 3.21 Printer Connections 3. 4. If installing a Keltron Printer VS4095/5, connect 24 VDC non-resettable power from a UL-listed power supply to the Keltron printer as shown in Figure 3.21 (14 AWG). If installing a PRN series printer, plug it into your AC power source. Note: PRN printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Because a secondary power source is not provided, use a separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. Plug the DB-25 connector end of the custom cable into the EIA-232 port of your printer. Tighten securely. Configure the printer as described in Section 3.13.2 Configuring the Printer.
5. 6.
NOTE: Depending on which version of the AMPS-24/E is being used, the terminal block designations may differ from those listed. Please refer to the AMPS-24/E manual.
37
3030-keltronpower.cdr
3030-printer.cdr
Installation
Installing Printers
*Protocol: When printing in graphics mode, set I/O Serial Protocol to Robust XON/OFF.
Set the printer DIP switches SP1 and SP2 according to settings in Table 3.4.
38
Installation
FlashScan devices can operate in either FlashScan or, for retrofit applications, in CLIP mode. Older models of CLIP devices only support addresses up to address 99. CLIP loops are limited to 99 detectors and 99 modules.
NOTE: Response times for CLIP loops may vary. CLIP loops must be tested to assure that actuation of notification appliances occurs within 10 seconds after activation of an initiating device. Systems with response time that exceed 10 seconds must be approved by the AHJ.
The following configuration guidelines may be used to improve the response times of CLIP loops: 1. 2. 3. All manual pull stations must be assigned addresses from 1-20. Loops must be programmed for Rapid Poll (refer to the programming manual for specific instructions). Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module.
39
Installation
B+ A+ B- A- TB1
B+ A+ B- A- TB1
B+ A+ B- A-
SLC loop connections are the same for Loop Expander and Control Modules
40
3030-slcloops.cdr
Section 4: Applications
4.1 Overview
A listing of chapters and topics covered in this section:
Chapter Section 4.3 NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit) Section 4.4 NFPA 72 Proprietary Fire Alarm Systems Section 4.5 Fire/Security Applications Covers the following topics How to install a UDACT with the CPU for use as a NFPA Central or Remote Station Fire Alarm System (Protected Premises Unit) How to set up a Protected Premises Unit to communicate with a listed compatible Protected Premises Receiving Unit. How to use the CPU as a combination Fire/Security system, including the following: Installing a Security Tamper Switch into the cabinet Circuit Wiring
Municipal Box (Auxiliary) Municipal Box applications require a TM-4 Transmitter module. Refer to the Transmitter Module TM-4 installation document for installation details.
Power Supervision Relay (EOLR-1) (Not required for FlashScan type codes that provide built-in power supervision.) Non-resettable 24 VDC Power from + a listed source Device to be Supervised
N.C. Supervision Relay Contact Part of EOLR-1 (Not required for FlashScan type codes that provide built-in power supervision.)
FCM-1
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.
3030-external-power-suptpH.wmf
41
Applications
NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)
4.3 NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)
The figure below shows typical wiring diagram for a NFPA 72 Central Station Fire Alarm System (Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using the Universal Digital Alarm Communicator/Transmitter (UDACT) and NFS2-3030. Connect and program the UDACT according to the directions given in The UDACT Instruction Manual.
NOTE: An NFPA 72 Central Station requires 24 hours of standby power; an NFPA 72 Remote Station requires 60 hours of standby power.
EIA-485 (ACS Mode) TB7 on control panel Supervised and power-limited EIA-485 and power wiring
NOTE: Install a 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3 and 4 if last or only device on EIA-485 line.
Figure 4.2 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: This application can also be done with the TM-4 Transmitter; refer to the TM-4 Transmitter Module manual for more details.
NOTE: The following models do not comply with requirements for AC loss delay reporting when used with Central Station Protected Premises systems: AA-30, AA-120, AA-100, APS-6R, CHG120.
42
3030-UDACT.cdr
Applications
Type code: Superv Receiving Unit Compatible With NFS2-3030 Type code: Trouble Mon PRN series printer UPS
Type code: Relay Zone mapping: ZF04 NFS2-3030 Protected Premises Unit Type code: Relay Zone mapping: ZF01 & ZF02
Note: Remote printers require 120 VAC, 50/60Hz primary power. A secondary power source (battery backup) is not provided; the use of a separate Uninterruptable Power Supply (UPS) 50 watt minimum, UL-listed for Fire Protective Signaling is recommended. A UPS is required for NFPA 72 Proprietary Protected Premises Receiving Unit Applications.
Figure 4.3 Typical Proprietary Fire Alarm Systems Wiring Connections: Block View
43
Applications
Fire/Security Applications
Figure 4.4 Typical Proprietary Fire Alarm Systems Wiring Connections: Detail View
44
3030-Rcvg-wirtpH.wmf
Fire/Security Applications
Applications
If the system has arming and disarming capability, a ringback signal from the Central Station to the arming location is required for Grade A operation. The ringback signal informs the Protected Premises Control Panel that the signal to arm/disarm has been received by the Central Station. A single SLC loop may be used for both Fire and Security Device Connections.
There are five software type IDs associated with security operation: ACCESS MONITOR alarm, AREA MONITOR, EQUIP MONITOR, SECURITY-L, and SYS MONITOR. There is also one software function, Security Delay (SDEL). These software elements are essential to all aspects of security operation, including Control-By-Event (CBE) programming. Devices with the type IDs ACCESS MONITOR and EQUIP MONITOR do not automatically display at the LCD or require state change acknowledgment. State changes in devices with these software types may be output at a printer. Refer to this panels Programming manual for more information about the characteristics of software type IDs.
WARNING: XP TRANSPONDER CIRCUITS (XPP-1, XPM-8, XPC-8, XPR-8, XPM-8L) ARE NOT SUITABLE FOR SECURITY APPLICATIONS.
Connect to J6 Security
3030-sts1.cdr
45
Applications
Fire/Security Applications
4.5.5 Programming
The control panel can communicate with any number of security devices. To do so, program the points as follows: 1. 2. Select the address of the module(s) to be used for security. Select one of the type codes described in Section 4.5.2 General Security Requirements.
For detailed instruction on programming Type Codes, refer to the Programming Manual.
FMM-1
46
3030-burg-FMMtpH.wmf
Fire/Security Applications
Applications
red (+)
RKSFMM101.wmf
RKS-S (front)
RKS-S (rear)
WARNING: XP TRANSPONDER CIRCUITS (XPP-1, XPM-8, XPC-8, XPR-8, XPM-8L) ARE NOT SUITABLE FOR SECURITY APPLICATIONS.
SLC Out
SLC In
RKSFMM-btpH.wmf
FMM-1
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.
47
Applications
Fire/Security Applications
The minimum security equipment required is as follows: Multiple MM Monitor Modules per Protected Area One Group Interface for security alarm One Group Interface to generate trouble arming system Contact Switch for Each Entry/Exit Door RKS-S Key Switch MM Monitor Modules Remote Annunciator for Each Entry/Exit Door (ACM-24AT, ACM-48A, ACM-16AT, ACM-32A) Security Devices
TENANT A
Key
Motion Detector Contact Switch Contact Switch with MM Module
RKS-S Remote Key Switch with MM Module MM Security Access Monitor Remote Annunciator MM MM CM CM Group Interface * Pull Station Smoke Detector * Group Interface must be physically located in either the protected premises or the Central Station
Entry/Exit Door
48
Area6_b.cdr
Fire/Security Applications
Applications
Zone Map: ZB Custom Label: Motion Detection 2. Programming of Logic Equations Logic Equation for 1 minute exit delay: ZLa* = DEL(01:00, 00:00, address of key switch) Logic Equation for Trouble arming system: ZLb* = AND (ZA, address of key switch, NOT(Zla)) Logic Equation to arm system: ZLc* = AND (ZLa, NOT(ZLb)) Logic Equation providing 30-second entry delay: ZLd* = SDEL(00:30, 00:30, ZA) Logic Equation for Security Alarm: ZLe* = AND (ZLc, OR (ZLd)) *Follow the following restrictions on values: a < b < c < d <e 3. Programming Group Interfaces Group Interface for Trouble when system is armed while access point(s) active A. CM programming Address: LXXMYYY (arbitrary) Type ID: RELAY Zone Map: ZLb Custom Label: Arming Trouble Group Output Signal Silence: No Walk Test: Yes/No (Installer Specified) Switch Inhibit: Yes B. MM Programming Address: LXXMYYY (arbitrary) Type ID: TROUBLE MON Zone Map: (none) Group Interface for Security Alarm A. CM programming Address: LXXMYYY (arbitrary) Type ID: RELAY Zone Map: ZLe Custom Label: Security Group Output Signal Silence: No Walk Test: Yes/No (Installer Specified) Switch Inhibit: Yes B. MM Programming Address: LXXMYYY (arbitrary) Type ID: SECURITY-L Zone Map: (none)
MM CM
49
Applications
Releasing Applications
Monitor ZLe
System Status (red is armed) System Alarm (red is alarm)
acm-24atface.cdr
Monitor LXXMYY
Monitor LXXMYY
Entry/Exit Door 1 Status (red is unsecured) Entry/Exit Door 2 Status (red is unsecured)
Table 4.1 NFPA Standards for Releasing Applications Refer to installation documents for the individual SLC loop device for voltage and maximum current requirements.
4.6.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate control modules. Program control module FCM-1 for the appropriate Type Code according to the chart below: Type Code: RELEASE CKT For use in UL applications Do not use REL-47K Cannot use power-limited wiring Supervised for open circuit only Supervised for power loss Type Code: REL CKT ULC For use in UL or ULC applications Requires REL-47K at solenoid Power-limited wiring Supervised for open circuit and shorts Supervised for power loss
50
Applications
4.6.3 Wiring
Make sure to keep total system current within the limits of the power supply. You can power the module from the power supply of the control panel or any UL-listed 24 VDC regulated powerlimited power supply for Fire Protective Signaling. For more information, refer to the Device Compatibility Document. References to wiring diagrams for releasing applications: To connect a releasing device to control module FCM-1, refer to Section 4.7. To connect an NBG-12LRA Agent Release-Abort Station, refer to Section 4.9.
4.7 Connecting a Releasing Device to FCM-1 Control Modules (Retrofit applications only)
Typical Connections Figure 4.11 shows typical connections for wiring a releasing device to this module. For ULC applications, REL-47K is required; see chart in Circuit Requirements below.
Non-resettable 24 VDC Power + SLC from FACP or LCM/LEM
Brown REL-47K
Red FCM-1
(Use with Type Code Rel Ckt ULC, or see Circuit Requirement 3.)
Note: See Circuit Requirements below. Devices for use in releasing applications must be programmed as type code RELEASE CIRCUIT or REL CKT ULC.
Figure 4.11 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Control Module Circuit Requirements When connecting releasing devices to FCM-1 control modules, note the following: 1. For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000); for NFPA 16 applications, set the Soak Timer (0600-0900 seconds). Refer to the NFS2-3030 Programming Manual for instructions on setting the Soak Timer. For applications using power-limited circuits: a) Use an End-of-Line device (P/N REL-47K) with FCM-1 modules. Connect the an End-ofLine device as shown in Figure 4.11. b) All wiring for releasing circuits is supervised against open and shorts. c) Program the releasing circuit for Type Code REL CKT ULC. 3. For applications not requiring power-limited circuits: a) End-of-Line devices (P/N REL-47K) are not required; however, the releasing device circuit is not supervised against shorts. b) Limited energy cable cannot be used for wiring of a releasing device circuit. c) Maintain a 0.25 inch (6.35 mm) spacing between the releasing circuit device wiring and any power-limited circuit wiring. d) In non-power-limited applications, program the releasing circuit for Type Code RELEASE CKT.
NFS2-3030/E Installation Manual P/N 52544:E1 02/05/2008 51
2.
Relconn-controlmodtpH.wmf
Applications
NOTE: As per UL 864 9th edition, a supervisory signal must be indicated at the panel whenever a releasing circuit is physically disconnected. Use a monitor module to monitor dry contacts off the switch. See figure 4.12. Refer to the SLC Manual for detailed wiring information.
FCM-1-REL
Module polarities are shown in alarm condition. All wiring shown is supervised and power-limited. (+) (-) SLC (-) SLC (+)
FCM-1-REL
52
fcm-1-1rel-z.wmf
fcm-1-rel-y.wmf
gasdisconnect.wmf
Applications
Critical Requirements. When connecting a releasing device to the FCM-1-REL module, note the following: 1. 2. 3. 4. 5. See Power Considerations on page 52 for information on monitoring 24 VDC power. Do not T-tap or branch a Style Y or Style Z circuit. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the FCM-1REL. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections. All applications using the FCM-1-REL are power-limited: a. b. 6. Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT. Circuits are supervised against opens and shorts.
Refer to the NFS2-3030 Programming Manual for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the NFS2-3030 Programming Manual.
Violet FMM-101 Manual Release Yellow Violet Normal ELR mode R-47K supervised and power-limited Release
Red
Black Red
3030-NBG12LRAtpH.wmf
System Common ()
24 VDC power from FACPs main power supply 24 VDC UL-listed releasing device Brown Red
FCM-1
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.
53
Applications
NOTE: See Circuit Requirements for Section 4.7, Connecting a Releasing Device to FCM-1 Control Modules (Retrofit applications only), on page 51.
NOTE: Devices for use in releasing applications must be programmed as type code RELEASE CIRCUIT or REL CKT ULC.
54
WARNING: RELEASING DEVICES SHOULD BE PHYSICALLY DISCONNECTED. DO NOT USE SOFTWARE DISABLE FUNCTIONS IN THE PANEL AS LOCKOUT.
Check that the green POWER LED lights. Check that all status LEDs are off. Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work. Before proceeding: a) notify the fire department and the central alarm receiving station if transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding devices are disregarded during the test period; and c) when necessary, disable activation of alarm notification appliances and speakers to prevent their sounding. Activate an Initiating Device Circuit using an alarm initiating device or an addressable initiating device on the SLC and check that all programmed active notification appliances function. Reset the alarm initiating device, the control panel, and any other associated equipment. In voice alarm applications, confirm that the proper tone(s) and/or messages sound during alarm conditions. Select the paging function and confirm that the message can be heard in the affected fire zones. Repeat the above step with each Initiating Device Circuit and each addressable device.
NOTE: SLC Resistance Values: The total DC resistance of the SLC pair cannot exceed 50 ohms. For instructions on how to measure the total DC resistance of a populated SLC pair, refer to the Measuring Loop Resistance section of the SLC Wiring Manual (P/N 51253). The minimum DC resistance between conductors of an unpopulated SLC pair cannot be less than 1 K ohms. Measure DC resistance on an unpopulated loop as shown in Figure 5.1 on page 56.
continued
NFS2-3030/E Installation Manual P/N 52544:E1 02/05/2008 55
Zero Ohms to ground will cause a ground fault. On systems equipped with a firefighters telephone circuit, make a call from a telephone circuit and confirm a ring indication. Answer the call and confirm communication with the incoming caller. End the call and repeat for each telephone circuit in the system. Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or an addressable initiating device on the SLC, and check that programmed active notification appliances sound, and alarm indicators illuminate. Measure the battery voltage with notification appliances active. Replace any battery with a terminal voltage less than 21.6 VDC and reapply AC Power.
NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due to a recent power outage, allow the batteries to charge for 48 hours before testing.
Return all circuits to their pretest condition. Check that all status LEDs are off and the green POWER LED is on. Notify fire, central station and/or building personnel when you finish testing the system.
Step 1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel. Step 2. Measure and record the resistance at SLC Out. Step 3. Measure and record the resistance at SLC Return. The minimum resistance is the lesser of two and three. STEP 2 SLC Out SLC Out STEP 3
SLC-meas5.cdr
WARNING: BATTERIES CONTAIN SULFURIC ACID, WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND DAMAGE TO FABRICS.
If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes with water for at least 15 minutes. Water and household baking soda provides a good neutralizing solution for Sulfuric Acid. If Sulfuric Acid gets into eyes, seek immediate medical attention. Ensure proper handling of the battery to prevent short circuits.
56
Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins.
CAUTION: SHORTING THE BATTERY LEADS CAN DAMAGE THE BATTERY, EQUIPMENT, AND COULD CAUSE INJURY TO PERSONNEL.
57
Maximum current
58
Wire Requirements
Electrical Specifications
Wire Requirements Twisted-unshielded pair, 12 to 18 AWG (3.25 to 0.75mm2). 50 ohms, maximum per length of Style 6 & 7 loops. 50 ohms per branch maximum for Style 4 loop. Twisted-shielded pair. Untwisted, unshielded wire, in conduit or outside of conduit. NOTE: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads.
Distance (feet/meters) 12,500 ft (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m) 10,000 ft (3048 m) 5,000 ft (304.8 m) 3,700 ft (1,127.76 m)
Typical Wire Type 12 AWG (3.31 mm2) 14 AWG (2.08 mm2) 16 AWG (1.31 mm2) 18 AWG (0.82 mm2) 12 AWG (3.31 mm2) 12 to 16 AWG (3.31 mm2 to 1.31 mm2) 18 AWG (0.82 mm2)
EIA-485 ACS Connection (power limited) EIA-485 RDP Connection (power limited) EIA-232 (power limited) IDC Initiating Device Circuit NAC Notification Appliance Circuit
Connects to ACS devices such as annunciators and UDACT Connects to RDP devices such as LCD-160 Connects to Printers or PC. FMM-1, FMM-101 (power limited) FCM-1 (power limited)
Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG (0.75mm2) minimum. Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG (0.75mm2) minimum. Twisted-shielded pair. 18 AWG (0.75mm2) minimum. 12-18 AWG Maximum circuit resistance is 20 ohms. 12-18 AWG. MPS-24A: At alarm current level, no more than a 1.2 V drop at the end of the circuit, or sized to provide the minimum rated operating voltage of the appliances used. 12-18 AWG. 5 ohms maximum per circuit for class A or B, or sized to provide the minimum rated operating voltage of the appliances used. 12-18 AWG. Size wire so that no more than 1.2 V drop across wire run from supply source to end of any branch. 12 AWG in conduit
16 AWG/1.30mm2
16 AWG/1.30mm2
To meet 1.2 V drop, or sized to provide the minimum rated operating voltage of the appliances used. To meet 5 ohms maximum circuit resistance, or sized to provide the minimum rated operating voltage of the appliances used. To meet 1.2 volt drop
Releasing Module
FCM-1-REL
20 ft (6.1 m) maximum
12 AWG (3.25mm2)
Table A.1 Wire Requirements Relay Output circuits are Common 30VDC, 2A (see Section 3.9 Form-C Relays on the CPU). Power output circuits: TB6 on the CPU draws power from primary, secondary and external sources to pass +24 VDC power to devices within the same enclosure as the CPU. If those devices have outputs, the outputs must be power-limited. Power rating is determined by the power source(s). See Section 3.10.1 Overview, and the AMPS-24 Manual for more details.
59
The NCA-2 or Network Control Station (NCS) may be employed as a Display and Control Center. In the event that communication fails between the panels and the Control Center, the panels will continue to function in local/standalone mode.
60
Index
A
AC Power, also see Power 34 Acceptance Test 55 ACM-8R 35 ADP-4B 16 Agent Release-Abort Station 53 Alarm Relays see Relays 32
F
FCM-1 51 FCM-1-REL 52 FCPS-24S6/S8 58 Fire/Security Applications 44 FMM-1 46 Form-C Relays, also see Relays 32
B
Backboxes 12, 16 Mounting 20 Battery Battery Calculations 58 Battery Checks 56 Memory-Backup Battery 25 Blank Modules 12, 16 BMP-1 16, 22 BP2-4 16
I
Indicating Device Circuits, also see NACs 58 Installation Checklist 19 Preparation 19
K
Keltron Printer, also see Printers 38
L
LCM-320/LEM-320, see SLC Loop Modules LDM-R32 35
C
CAB-4 Series, also see Backboxes 16 Cabinets, also see Backboxes 12, 16, 22 Canadian Applications 60 Central Receiving Unit, also see UDACT Manual 46 Chassis CHS-4L 16 CHS-M3 16, 22, 31 Circuit Board, also see CPU 14 Control Panel Circuit Board, also see CPU 14 CPU 12, 14 Drawing 14 Installation Steps 23
M
Main Power Supply 15 Maintenance 55, 56 Manual Pull Station 39 Memory-Backup Battery Insulator 25 Mounting Backboxes and Doors 20
N
NACs Specifications 58 NBG-12LRA 53 NCM-W/F Mounting 27 Networking 27 NFPA Applications NFPA 72 Central Station Fire Alarm System 42 NFPA 72 Remote Station Fire Alarm System 42 Overview 41 Protected Premises Unit 42 Non-Power-Limited Circuits UL Wiring Requirements 35 Notification Appliance Circuits, also see NACs 58
D
DC Power, also see Power 34 Display and Control Center (DCC), see Programming Manual Doors 12, 16 DP-1B 16 DP-DISP 16 Dress Panels 12, 16
E
Electrical Connections 33 Electrical Specifications 58 Enclosures, see Backboxes 16 External Power Supervision 41
61
OW
Index
O
Operating Power 58 Operational Checks 55 Output Relays, also see Form-C Relays Specifications 32
P
PC Connection 40 Periodic Testing 55 Power 34 AC Power Checklist 34 AC Power Connections 34 Auxiliary Power 34 DC Power Connections 34 Installation Steps 33 Main Power Supply 15 Power Supply Calculations 58 Power-Limited Wiring Requirements 35 Specifications 33 PPU 42 Printers 37, 38 Installation 36 PRN Printer Settings 38 Proprietary Fire Alarm Systems 43 Proprietary Security Alarm, also see Security 46 Protected Premises Receiving Unit 43
Supplemental Documentation 8 System Features 11 Limitations 12 Options 11 System Description 11 System Current Draws, also see Your Power Supply Manual 58
T
Testing 55 TM-4 35 Trouble Relays, also see Relays 32
U
UDACT 36, 42 UL Non-Power-Limited Wiring Requirements 35 UL Requirements 35 ULC Remote Connection Feature 35 Upload/Download Software 40
V
VeriFire Tools 40
W
Wiring, also see SLC 39 Non-Power-Limited Wiring Requirements 35 Proprietary Security Alarm Applications 46 UL Non-Power-Limited Wiring Requirements 35 Wire Requirements 58
R
Receiving Unit 43 Related Documentation 8 Releasing 50 FCM-1 connections 51 FCM-1-REL connections 52 NBG-12LRA 53 Remote Connection Feature 35
S
Security Proprietary Security Alarm Applications Wiring 46 Security Relays, also see Relays 32 Security Tamper Switch 45 Service 55 Signalling Line Circuit, also see SLC 39 SLC Loop Modules External Power Supervision 41 SLC Loop Number 29 SLC, also see SLC Wiring Manual Specifications 58 SLC, see SLC Wiring Manual Specifications 58 STS-1, also see Security 46 Supervisory and Security Contacts -Configuring as Alarm Contacts 32 Supervisory Relays, also see Relays 32
62 NFS2-3030/E Installation Manual P/N 52544:E1 02/05/2008
Limited Warranty
Honeywell International Inc. warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department. This writing constitutes the only warranty made by Honeywell International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident. HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL INTERNATIONAL INC.S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by Honeywell International Inc. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
Warn-HL-05-2007.fm
63
World Headquarters 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.notifier.com