Site Test Report For Differential Protection
Site Test Report For Differential Protection
Customer SEC-SOA Extension of Muhayil Project S/S 132/33 KV Location MUHAYEL RELAY DETAILS
RELAY ANSI NO. RELAY MAKE TYPE / STYLE S. NO. 87T SIEMENS
7UT612
40631024/00
6T1
2-ELECTRICAL CHECKS:
ALL CONNECTIONS CHECK ACCORDING TO WIRING DIAGRAM AUX.SUPPLY CHECKED FOR RATING AND POLARITY CASING EARTHING CHECK All 7 programmable LEDs apply Test LEDs under Test mode (Hardware test).
O.K O.K
O.K
OK
Name: Eng.
Mohamed
Witnessed By
3- TRANSFORMER DATA: RATIO: 132/13.8KV MVA: 67 MVA H.V SIDE VOLTAGE: 132KV L.V SIDE VOLTAGE: 13.8KV GROUP NO: DYN1 FREQUNCEY: 60 HZ H.V SIDE C.T RATIO: 500/1 H.V SIDE C.T RATIO: 3000/1 IMPEDENCE VOLTAGE: 14% H.V CALCULATED FULL LOAD CURRENT: 293.0 A = 0.586 A (sec value) LV CALCULATED FULL LOAD CURRENT: 2803.0 A = 0.934 (sec value)
Name: Eng.
Mohamed
Witnessed By
4. INPUT OPTO-ISOLATORS CHECKS (With Relay Energized): GO TO TEST MODE (HARDWARE TEST) FOR CHECKING STATUS OF INPUTS OPTO INPUT NO. OPTO 1 OPTO 2 OPTO 3 TEST METHOD (Energize only one at a time by soft ware) ENERGIZE BI 1 (High) ENERGIZE BI 2 (High) ENERGIZE BI 3 (High) RESULT Display 0 to 1 OK OK OK REMARKS
TEST METHOD (Energize only one at a time by soft ware) CONTACT OPERATED F6-F7 (N/O) CONTACT OPERATED F8-F9 (N/O) CONTACT OPERATED F10-F11 (N/O) CONTACT OPERATED F12-F13 (N/O)
REMARKS
Relay trip
Name: Eng.
Mohamed
Witnessed By
PH A
D.O 0.103 0.205 0.410 0.287 0.567 1.134
TRIP
0.147 0.293
PH B
D.O
0.104 0.207
PH C
D.O TRIP P.U D.O
P.U
0.126 0.250
TRIP
P.U
CT INPUT 1
(HV Side)
0.25
0.146
0.292
0.123
0.248
0.102
0.205
0.147
0.293
0.1 25
0.25 0
0.102
0.207
0.5 1.0
0.586
0.403
0.502
0.342
0.413
0.285
0.586
0.403
0.497
0.344
0.410
0.286
0.586
0.401
0.49 8
0.34 5
0.411
0.285
CT INPUT 2
(LV Side)
0.25
0.5 1.0
0.810 1.621
0.689 1.374
0.567 1.138
0.806 1.619
0.684 1.381
0.567 0.139
0.807 1.613
0.68 5 1.37 7
0.570 1.134
Select any Phase in HVS and inject current until pickup led then go up until trip contact operate then go down again tell the pickup led disappear for delta winding program the O/P contact for each phase you test every time TRIP = IDIFF>* Kvg*In Trans /In CT TRIP h.v = IDIFF>*1.0* 293/(500/1)= 0.586*IDFF> A TRIP l.v = IDIFF>*1.73* 2803/(3000/1)= 1.62*IDFF> A P.U =85% TRIP VALUE D.O =70% TRIP VALUE 7- TIMING TEST (adress1625): SETTING TIME (S) 0.0 Remarks Test Inst. Used Tested By Shokry
Date: 20/07/09 Signature:
FREJA300
MEASURED TIME @ 2 Is
A H.V L.V H.V B L.V H.V C L.V
37.8ms
37.9ms
39.9ms
37.2ms
38.3ms
34.3ms
Name: Eng.
Mohamed
Witnessed By
Kvg
1.5 In 1.5 In
1.0 1.73
0.879 2.43
0.87 9 2.41 8
0.876 2.418
0.878 2.425
27 27
27.4 27.4
28.4 27.6
CT INPUT 2
(LV WINDING)
Change the setting for I DIFF> to be 2 In then make pick up for I DIFF>> or make another contact for
I DIFF>> only
Pick up = I diff>> * Kvg * In trans/ In CT Trip hv = IDIFF>*1.0* 293/(500/1)= 0.586 *IDFF>> A Trip l.v = IDIFF>*1.73* 2803/(3000/1)= 1.62*IDFF>> A P.U =85% TRIP VALUE D.O =70% TRIP Value RELAY INHERENT TIME = 25 ms
Name: Eng.
Mohamed
Witnessed By
9- Slop (Bias) Test: I: slope 1 Slope1 0.25 M 0.5 1 1.5 I1 (source1) I2 (source2) 0.293 0.586 0.879 0.81 1.62 2.43 Operating angle (Either one source) 27.9 27 27.7 Measured slope 0.24 0.24 0.23
I1= Kvg *M* I nsec W1 = 0.586 M where M constant , Kvg = (1.0) Ph-N I2= Kvg *M* I nsec W2 = 1.62 M where M constant , Kvg = (1.73) Ph-N The calculated slope 1 should be with in +-10% of setting
Inject same phase (L1) to High side & low side by stable current in table with phase shift 180 and increase the angle of HS till Trip then calculate the slop by this angle
Name: Eng.
Mohamed
Witnessed By
II: slope 2 : Slope2 0.50 M 1 1.5 2 I1 (source1) I2 (source2) 0.586 0.879 1.172 1.62 2.43 3.24 Operating angle (Either one source) 59 58 51.1 Measured slope 0.49 0.48 0.34
I1= Kvg* M* In sec W1 = 0.586 M where M constant , Kvg = (1.0) Ph-N I2= Kvg* M* In sec W2 =1.62 M where M constant , Kvg = (1.73) Ph-N The calculated slope 2 should be with in +-10% of setting
Inject same phase(L1) to High side & low side by stable current in table with phase shift 180 and increase the angle of HS till Trip then calculate the slop by this angle
Name: Eng.
Mohamed
Witnessed By
10- HARMONICS CHECK: I 2nd HARMONICS : SETTING % 15 INJECTED CURRENT (A) 1 HV TRIP
<16%
LV TRIP
<16%
BLOCK
>16%
BLOCK
>16%
REMARKS -
By Freja Remote mode (Edit curve) Inject 1A Have fundamental + 10 % of 2nd Harmonic and increase the value of harmonic in curve till Block II 5TH HARMONICS : SETTING % 30 INJECTED CURRENT (A) 0.4 HV TRIP
<30%
LV TRIP
<30%
BLOCK
>30%
BLOCK
>30%
REMARKS -
By Freja Remote mode Inject 0.4A Have fundamental + 10 % of 5nd Harmonic and increase the value of harmonic in curve till Block (Injection current must not excised the( limit IDIFF max of n-th harm-Restrain) setting Remarks Test Inst. Used Tested By Shokry
Date: 20/07/09 Signature:
FREJA300
Name: Eng.
Mohamed
Witnessed By
11-Cross Blocking 2nd Harmonics adress1612: Procedure: 1. Inject two different phase at same time at one side 2. Phase A>Id with fundamental harmonics 3. Phase B>Id with 2nd harmonics 4. 1 Cycle=60HZ=1/60 =0.01666 sec Time set in (Cycles) 0.0 125 250 500 1000 Time set in (s) 2.075 4.15 8.3 16.6 Time measured (s) 126.3
Name: Eng.
Mohamed
Witnessed By
Notes: 1. For this table, 0 is considered even. 2. Use this row if the I0Process setting for the tested winding is I0 Elimination. The settings are Address 1106 for Winding 1, Address 1126 for Winding 2, and Address 1146 for Winding 3. 3. Use this row if the I0Process setting for the tested winding is either without or I0 CORRECTION. The settings are Address 1106 for Winding 1, Address 1126 for Winding 2, and Address 1146 for Winding 3.In tests 1-3 current is injected in one phase at any time; therefore, use the rows for 1-phase faults. The other fault types are given if the user wishes to expand the tests.
Name: Eng.
Mohamed
Witnessed By