ABB Selectivity Backup and Motors
ABB Selectivity Backup and Motors
L.V. Breakers
Via Baioni, 35
24123 Bergamo, Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com
Coordination tables
1SDC007004D0204 - 12/2004
Printed in Italy
Tipografia
1SDC007004D0204
Coordination tables
Index
Introduction ................................................................................................................... I
Back-up ....................................................................................................................1/1
Discrimination ...........................................................................................................2/1
Motor protection .......................................................................................................3/1
Switch-disconnectors ...............................................................................................4/1
ABB SACE
Coordination tables
Introduction
ABB SACE
Coordination tables
Discrimination and back-up
This collection of selectivity and back-up tables for ABB circuit-breakers has been
studied to help select the appropriate circuit-breaker, fulfilling the specific selectivity
and back-up requirements according to the different types of installation.
The tables are divided on the basis of the type of intervention (back-up or selective
protection), and are grouped according to types of circuit-breakers (air, moulded-case,
and miniature), covering all the possible combinations of ABB circuit-breakers.
The technical data, updated to the latest series of miniature, moulded-case and air
circuit breakers on the market, make this publication a comprehensive and simple tool:
once again, ABB SACE makes its consolidated experience in the Low Voltage sector
available to professionals.
II
ABB SACE
Coordination tables
Discrimination and back-up
Restricting the field to an analysis of the problem of how to harmonize the action of the
protection devices in the event of overcurrents (overloads and short-circuits) - a problem
covering 90% of the coordination requirements of protection devices in radial low voltage
installations - it is important to remember that:
overcurrent trip selectivity means coordination of the operating characteristics of
two or more overcurrent protection devices so that, on occurrence of overcurrents
within established limits, the device supposed to operate within these limits intervenes,
whereas the others do not1;
total discrimination means overcurrent selectivity so that when there are two
overcurrent protection devices in series, the protection device on the load side provides
protection without tripping the other protection device2;
partial discrimination means overcurrent selectivity so that when there are two
overcurrent protection devices in series, the protection device on the load side provides
protection up to a given overcurrent limit without tripping the other device3. This
overcurrent threshold is called the selectivity limit current Is4;
back-up protection means coordination for protection against overcurrents of two
protection devices in series, where the protection device generally (but not necessarily)
situated on the supply side provides overcurrent protection with or without the aid of
the other protection device and avoids excessive stress on the latter5. The current
value above which protection is ensured is called the switching current IB6.
Types of coordination
Influence of the electrical parameters of the installation (rated current and shortcircuit current)
If the analysis is restricted to the behaviour of the protection devices with tripping
based on overcurrent releases, the strategy used to coordinate the protection devices
mainly depends on the rated current (In) and short-circuit current (Ik) values in the part of
installation concerned.
Generally speaking, the following types of coordination can be classified:
current type selectivity;
time type selectivity;
zone selectivity;
energy selectivity;
back-up.
Now let us examine these various solutions in detail.
ABB SACE
III
Coordination tables
Discrimination and back-up
IV
ABB SACE
Coordination tables
Discrimination and back-up
time delay. Selective circuit-breakers, often of the open type, must be used for the
various levels (category B circuit-breakers according to the IEC 60947-2 Standard) to
guarantee a sufficiently high short-time withstand current;
the duration of the disturbance induced by the short-circuit current on the power
supply voltages in the zones unaffected by the fault can pose problems with
electromechanical (voltage below the electromagnetic release value) and electronic
devices;
the number of discrimination levels is limited by the maximum time which can be
withstood by the electrical system without loss of stability.
Zone (or logical) selectivity
This type of coordination is a further evolution of time coordination and can be direct or
indirect. Generally speaking, it is implemented by means of a dialogue between
currentmeasuring devices which, when they detect that the setting threshold has been
exceeded, enable correct identification and power supply disconnection of just the
zone affected by the fault.
It can be implemented in two ways:
the measuring devices send information to the supervision system about the fact
that the set current threshold has been exceeded and the latter decides which
protection device to trip;
when there are current values over the set threshold, each protection device sends a
blocking signal via a direct connection or a bus to the protection device higher in the
hierarchy (i.e. on the supply side in relation to the direction of the power flow) and,
before it trips, makes sure that a similar blocking signal has not arrived from the
protection device on the load side. This way, only the protection device immediately
to the supply side of the fault is tripped.
The first mode has trip times of around 0.5-5 s and is mainly used in the case of not
particularly high short-circuit currents with a power flow direction not unequivocally
defined (e.g. for lighting systems in long road and rail tunnels).
The second mode has distinctly shorter trip times: compared with time type coordination,
there is no longer any need to increase the intentional time delay progressively as you
move closer to the power supply source. The delay can be reduced to a waiting time
sufficient to rule out any presence of a block signal from the protection device on the
load side (time taken by the device to detect the anomalous situation and successfully
complete transmission of the signal).
Compared with time type coordination, zone selectivity implemented in this way:
reduces the trip times and increases the safety level. The trip times can be around a
hundred milliseconds;
reduces both the damage caused by the fault and the disturbance to the power
supply network;
reduces the thermal and dynamic stresses on the circuit-breakers;
allows a very high number of discrimination levels;
but it is more burdensome both in terms of costs and in the complexity of the installation.
This solution is therefore mainly used in systems with high rated current and shortcircuit
current values, with inescapable needs both in terms of safety and service continuity:
in particular, examples of logical discrimination are often found in primary distribution
switchgear, immediately to the load side of transformers and generators.
Another interesting application is the combined use of zone and time type selectivity, in
which the stretches of the coordination chain managed logically have protection device
trip times for short-circuits which decrease progressively moving up towards the power
supply sources. The zone selectivity function is available with:
Emax circuit-breakers equipped with PR122/P and PR123/P electronic releases
Tmax circuit-breakers equipped with PR223EF electronic releases.
For further information, please consult the specific technical catalogues.
ABB SACE
Coordination tables
Discrimination and back-up
Energy-based selectivity
Energy-based coordination is a particular type of selectivity which exploits the
currentlimiting characteristics of moulded-case circuit-breakers. It is important to
remember that a current-limiting circuit-breaker is a circuit-breaker with a trip time
short enough to prevent the short-circuit current reaching the peak value it would
otherwise reach7.
In practice, all the ABB SACE moulded-case circuit-breakers in the Isomax and Tmax
ranges have more or less accentuated current-limiting features, obtained by:
reaching a valid compromise between the capacity of the release to withstand current
values lower than the instantaneous trip thresholds and the repulsion of the main
contacts at short-circuit currents;
triggering rapid displacement of the arc inside the arcing chambers (magnetic blast)
suitably designed to generate a high arcing voltage;
placing several arcing chambers in series, with contacts optimised to carry out different
functions (main opening under short-circuit, backup opening with the principal function
of isolation and opposition to the recovery voltage, etc.).
Under short-circuit conditions, these circuit-breakers are extremely rapid (with trip times
of a few milliseconds) and open in the event of a strong asymmetric component. It is
therefore not possible to use the time-current trip curves (load side circuit-breaker) and
no trip limit curves (supply side circuit-breaker), obtained with symmetrical sine wave
forms, to study the coordination. The phenomena are mainly dynamic (and therefore
proportional to the square of the instantaneous current value) and can be described
using the specific let-through energy and no trip limit energy curves of the supply side
circuit-breaker.
What generally happens is that the energy associated with the load side circuit-breaker
trip is lower than the energy value needed to complete the opening of the supply side
circuit-breaker. To ensure a good level of reliability, avoiding any oversizing or transient
contact repulsion phenomena in the circuit-breaker on the supply side, this calculation
should be integrated with additional information, such as the current limiting curves
(peak Ip value - prospective value of the symmetrical component of the short-circuit
current) and the setting for contact repulsion.
This type of selectivity is certainly more difficult to consider than the previous ones
because it depends largely on the interaction between the two devices placed in series
(wave forms, etc.) and requires access to data often unavailable to the end user.
Manufacturers provide tables, slide rules and calculation programs in which the limit
selectivity current values Is under short-circuit conditions between different combinations
of circuit-breakers are given. These values are defined by theoretically integrating the
results of a large number of tests performed in compliance with the requirements of
appendix A of the IEC 60947-2 Standard.
The advantages of using this type of coordination include:
breaking is fast, with trip times which become shorter as the short-circuit current
increases. This consequently reduces the damage caused by the fault (thermal and
dynamic stresses), the disturbance to the power supply system, the sizing costs,
etc.;
the discrimination level is no longer limited by the value of the short-time current Icw
withstood by the devices;
a large number of hierarchically different levels can be coordinated;
VI
ABB SACE
Coordination tables
Discrimination and back-up
ABB SACE
VII
Coordination tables
General notes on motor protection and switching
Electromechanical starter
The starter is designed to:
start motors;
ensure continuous functioning of motors;
disconnect motors from the supply line;
guarantee protection of motors against working overloads.
The starter is typically made up of a switching device (contactor) and an overload
protection device (thermal release).
The two devices must be coordinated with equipment capable of providing protection
against short-circuit (typically a circuit breaker with magnetic release only), which is not
necessarily part of the starter.
The characteristics of the starter must comply with the international Standard
IEC 60947-4-1, which defines the above as follows:
Contactor: a mechanical switching device having only one position of rest, operated
otherwise than by hand, capable of making, carrying and breaking currents under normal
circuit conditions including operating overload conditions.
Thermal release: thermal overload relay or release which operates in the case of
overload and also in case of loss of phase.
Circuit-breaker: defined by IEC 60947-2 as a mechanical switching device, capable
of making, carrying and breaking currents under normal circuit conditions and also
making, carrying for a specified time and breaking currents under specified abnormal
circuit conditions.
The main types of motor which can be operated and which determine the characteristics
of the starter are defined by the following utilization categories:
(1)
Utilization
categories
AC-2
Typical applications
The choice of the starting method and also, if necessary, of the type of motor to be
used depends on the typical resistant torque of the load and on the short-circuit power
of the motor supplying network.
With alternating current, the most commonly used motor types are as follows:
asynchronous three-phase squirrel-cage motors (AC-3): the most widespread type
due to the fact that they are of simple construction, economical and sturdy; they
develop high torque with short acceleration times, but require elevated starting
currents;
slip-ring motors (AC-2): characterized by less demanding starting conditions, and
have quite a high starting torque, even with a supply network of low power.
VIII
ABB SACE
Coordination tables
General notes on motor protection and switching
Starting methods
The most common starting methods for asynchronous squirrel-cage motors are detailed
below.
Direct starting (DOL)
With direct starting, the DOL (Direct On Line) starter, with the closing of line contactor
KL, the line voltage is applied to the motor terminals in a single operation. Hence a
squirrel-cage motor develops a high starting torque with a
relatively reduced acceleration time. This method is generally
used with small and medium power motors which reach full
working speed in a short time.
These advantages are, however, accompanied by a series of
MCCB
drawbacks, including, for example:
high current consumption and associated voltage drop which
may cause damages to the other parts of the system
KL
connected to the network;
violent acceleration which has negative effects on mechanical
transmission components (belts, chains and mechanical
joints), reducing working life.
TOR
Other types of starting for squirrel-cage motors are
accomplished by reducing the supply voltage of the motor:
MOTOR
this leads to a reduction in the starting current and of the motor
torque, and an increase in the acceleration time.
Star-Delta starter (Y-)
The most common reduced voltage starter is the Star-Delta starter (Y-), in which:
on starting, the stator windings are star-connected, thus achieving the reduction of
peak inrush current;
once the normal speed of the motor is nearly reached, the switchover to delta is
carried out.
After the switchover, the current and the torque
follow the progress of the curves associated with
normal service connections (delta).
As can be easily checked, starting the motor
MCCB
with star-connection gives a voltage reduction
of 3, and the current absorbed from the line is
reduced by 1/3 compared with that absorbed
with delta-connection.
K
KL
The start-up torque, proportional to the square
KY
of the voltage, is reduced by 3 times, compared
with the torque that the same motor would
TOR
supply when delta-connected.
This method is generally applied to motors with
MOTOR
power from 15 to 355 kW, but intended to start
with a low initial resistant torque.
ABB SACE
IX
Coordination tables
General notes on motor protection and switching
Starting sequence
By pressing the start button, contactors KL and KY are closed. The timer starts to
measure the start time with the motor connected in star. Once the set time has elapsed,
the first contact of the timer opens the KY contactor and the second contact, delayed
by approximately 50-80 ms, closes the K contactor.
With this new configuration, contactors KL and K closed, the motor becomes
deltaconnected.
The thermal release TOR, inserted in the delta circuit, can detect any 3rd harmonic
currents, which may occur due to saturation of the magnetic pack and by adding to the
fundamental current, overload the motor without involving the line.
With reference to the connection diagram, the equipment used for a Star/Delta starter
must be able to carry the following currents:
Ie
3
Ie
3
Ie
3
KY star contactor
where Tp is the cold trip time of the thermal release at 7.2 times the set current value
(for example: a release in class 10 at 7.2 times the set current value must not trip within
4 s, but must trip within 10 s).
It is normal procedure to associate class 10 with a normal start-up type, and class 30
with a heavy duty start-up type.
ABB SACE
Coordination tables
General notes on motor protection and switching
Coordination type
Type 1
It is acceptable that in the case of short-circuit the contactor and the thermal release
may be damaged. The starter may still not be able to function and must be inspected;
if necessary, the contactor and/or the thermal release must be replaced, and the breaker
release reset.
Type 2
In the case of short-circuit, the thermal release must not be damaged, while the welding
of the contactor contacts is allowed, as they can easily be separated (with a screwdriver,
for example), without any significant deformation.
ABB SACE
XI
Coordination tables
Switch-disconnectors
Switch-disconnectors
Switch-disconnectors are mechanical switching devices, capable of closing, carrying
and interrupting currents under normal circuit conditions which can include specific
overload switching conditions and which, in the open position, satisfy the isolation
requirements specified for an isolator.
A switch-disconnector can be able to close and carry currents - for an established time
- under specific abnormal circuit conditions, such as those which occur in the case of
a short-circuit.
The Standard regarding switch-disconnectors is IEC 60947-3.
Each switch-disconnector must be protected by a coordinated device which safeguards
it against overcurrents - normally a circuit-breaker, and which is able to limit the peak
values of the short-circuit current and the specific let-through energy, to acceptable
levels for the switch-disconnector.
XII
ABB SACE
Tabelle di coordinamento
Coordination
tables
Introduzione
Back-up
ABB SACE
1/1
1/2
ABB SACE
Back-up
Notes for use
Back-up protection
The tables given provide the value (in kA, referring to the breaking capacity according
to the IEC 60947-2 Standard) for which the back-up protection among the combination
of selected circuit-breakers is verified. The tables cover the possible combinations
between ABB SACE Tmax and Isomax series of moulded-case circuit-breakers and
those between the above-mentioned circuit-breakers and the ABB series of miniature
circuit-breakers.
The values indicated in the tables refer to the voltage:
Vn of 230/240 V AC for coordination with miniature S9 circuit-breakers
Vn of 400/415 V AC for all the other coordinations.
Note
The following tables give the breaking capacities at 415 V AC for circuit-breakers SACE
Isomax and Tmax.
Isomax @ 415 V AC
Tmax @ 415 V AC
Version
Icu [kA]
Version
Icu [kA]
16
50
25
65
36
100
50
70
L (T2)
L (T4, T5)
L (T6)
85
120
100
200
Caption
MCB = miniature circuit-breakers (S9, S2, S500)
MCCB = moulded-case circuit-breakers (Tmax, Isomax)
For moulded-case or air circuit-breakers:
TM = thermomagnetic release
TMD (Tmax)
TMA (Tmax)
M = magnetic only release
MF (Tmax)
MA (Tmax)
EL = electronic release
PR211/P - PR212/P (Isomax)
PR221DS - PR222DS (Tmax)
Caption of symbols
MCB
Tmax
Isomax
Emax
For solutions not shown in these tables, please consult the website:
http://bol.it.abb.com
or contact ABB SACE
ABB SACE
1/3
Back-up
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - MCB @ 240 V (Two-pole circuit-breakers)
Supply s.
Char.
Load s.
Icu [kA]
In [A]
S931 N
4,5
2..40
S 200L
S200
S200M
S 280
S 290
B-C
B-C
B-C
S200P
B-C
B-C
S 500
B-C
10
6..40
10
20
0.5..63
20
25
0.5..63
25
40
0.5..25
40
25
32..63
25
20
80, 100
15
25
80..125
15
100
6..63
100
S941 N
B,C
2..40
10
20
25
40
25
15
15
100
S951 N
B,C
10
2..40
10
20
25
40
25
15
15
100
S971 N
B,C
10
2..40
10
20
25
40
25
15
15
100
S200L
10
6..40
20
25
40
25
15
15
S200
B,C,K,Z
20
0.5..63
25
40
25
S200M
B,C,D
25
0.5..63
B, C,
40
0.5..25
100
D, K, Z
25
32..63
100
B,C
20
80, 100
S200P
S280
S290
C,D
25
80..125
S500
B,C,D
100
6..63
1/4
40
100
100
100
ABB SACE
Back-up
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
MCCB @ 415 V - MCB @ 240 V
Load s.
Char.
S931 N
S941 N
B,C
S951 N
B,C
S971 N
B,C
In [A]
2..25
32, 40
2..25
32, 40
2..25
32, 40
2..25
32, 40
Supply s.*
T1
T1
Version
Icu [kA]
16
25
36
50
70
85
4,5
6
T1
T2
16
16
16
20
10
10
10
16
16
16
16
20
10
10
10
16
10
16
16
16
10
16
16
16
25
16
25
16
T3
10
10
16
16
T2
20
16
20
16
25
16
25
16
T3
10
10
16
16
T2
T2
20
20
16
16
20
20
16
16
25
25
16
16
25
25
16
16
* Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral)
ABB SACE
1/5
Back-up
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - MCB @ 415 V
Supply s.
Char.
Load s.
Icu [kA]
In [A]
S200L
6..40
S200
B,C,K,Z
10
0.5..63
S200M
B,C,D
15
0.5..63
B, C,
25
0.5..25
D, K, Z
15
32..63
B,C
80, 100
S290
C,D
15
80..125
S500
B,C,D
50
6..63
S200P
S280
1/6
S 200L
S200
S200M
S 280
S 290
S 500
B-C
B-C
B-C
S200P
B-C
B-C
B-C
6
6..40
10
0.5..63
10
15
0.5..63
15
25
0.5..25
25
15
32..63
15
6
80, 100
15
80..125
15
50
6..63
50
15
25
15
15
50
25
50
50
ABB SACE
Back-up
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
MCCB - MCB @ 415 V
Load s.
Char.
S200L
S200
B,C,K,Z
S200M
B,C,D
S200P
B, C,
D, K, Z
In [A]
6..10
13..40
0.5..10
13..63
0.5..10
13..63
0.5..10
13..25
Supply s.
T1
T1
T2
T4
Version
T1
Icu [kA]
16
25
36
50
70
85
120
200
16
25
30
T2
36
10
16
25
30
36
15
16
25
30
36
25
T3
36
16
36
16
36
25
T4
36
T2
36
36
36
36
50
T3
40
16
40
16
40
25
T4
T2
T4
T4
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
70
60
40
85
60
30
36
36
36
50
40
40
70
40
85
40
40
30
36
30
36
50
30
40
60
40
60
40
40
40
32..63
15
16
25
30
36
25
36
50
25
40
60
40
60
40
S280
B,C
80, 100
16
16
16
36
16
30
36
16
30
36
30
36
30
30
S290
C,D
80..125
15
16
25
30
36
30
30
50
30
30
70
30
85
30
30
S500
B,C,D
6..63
50
70
70
85
120
200
ABB SACE
1/7
Back-up
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - MCCB @ 415 V
Supply s. T1 T1 T2 T3 T4 T5 T6 T2 T3 T4 T5 T6 S7 T2 T4 T5 T6 S7 T2 T4 T5 T6 S7 T4 T5
Version
Char.
Icu [kA]
25
36
50
T1
16
25 36
36 36
30 30 30
50 50 36 36
36
T1
25
36
36 36
36 36 36
50 50 40 40
50 50 70 65 65 65 50 85
T1
50 50 50 50
T2
50 50 50 50
T3
50 50 50
50 50
65 65 65 50
50 50
50 50
65 65 65 50
50
50 50
65 65 50
100 85 65
65 40
70 50
Load s.
T4
36
T5
T6
50 40
T2
L
65 85
70 40 40 40
50
V
200
50 50 50
T2
200 150
100 85 85
150
85 85
85 120 120 85 85 200 150
70
T6
180
100 85
T2
1/8
120
70
T5
65
70 70 65
T4
85
85 85 70 50 130 100
70 70 70 65
T6
T5
L
100
70 70 70
T5
T4
85
L
120
T3
T4
H
70
85
L
120
120 120
200 180
200 200
200
ABB SACE
Tabelle di coordinamento
Coordination
tables
Introduzione
Discrimination
ABB SACE
2/1
Discrimination
Notes for use
Selective protection
The tables given provide the value (in kA, referring to the breaking capacity according
to the IEC 60947-2 Standard) for which the selective protection is verified among the
combination of selected circuit-breakers. The tables cover the possible combinations
between ABB SACE Emax series air circuit-breakers, ABB SACE Tmax and Isomax
series of moulded-case circuit-breakers, and the ABB series of miniature circuit-breakers.
The values in the table represent the maximum value obtainable of discrimination
between supply side circuit-breaker and load side circuit-breaker referring to the voltage:
Vn of 230/240 V AC for the S9 circuit-breakers and Vn of 400/415 V AC for the supply
side circuit-breakers in the coordination between MCB with the miniature S9 circuitbreakers.
Vn of 400/415 V AC for all the other coordinations.
These values are obtained following particular specifications which, when not respected,
could give discrimination values which are in some cases much lower than what is
indicated. Some of these are generally valid and are given below, others referring
exclusively to particular types of circuit-breakers will be the subject of a note under the
relative table.
General prescriptions
Function I of the electronic releases of the supply side circuit-breakers must be
excluded (I3 in OFF);
The magnetic trip of thermomagnetic (TM) or magnetic only (M) circuit-breakers placed
on the supply side must be 10 x In and regulated to the maximum threshold;
It is of prime importance to check that the settings made by the user for the electronic
and thermomagnetic relays of circuit-breakers placed both on the load and supply
side results in time-current curves properly spaced.
2/2
ABB SACE
Discrimination
Notes for use
Note
The letter T indicates total discrimination for the selected combination; the corresponding
value in kA is obtained by considering the lowest between the breaking capacities (Icu)
of the circuit-breaker on the load side and the circuit-breaker on the supply side.
The following tables give the breaking capacities at 415 V AC for SACE Emax, Isomax
and Tmax circuit-breakers.
Isomax @ 415 V AC
Tmax @ 415 V AC
Emax @ 415 V AC
Version
Icu [kA]
Version
Icu [kA]
16
50
Version
B
42
25
65
N (E1)
50
36
100
65
50
75
Icu [kA]
70
S (E2)
85
L (T2)
L (T4, T5)
L (T6)
85
120
100
100
130
V (E3)
130
200
150
Caption
MCB = miniature circuit-breakers (S9, S2, S500)
MCCB = moulded-case circuit-breakers (Tmax, Isomax)
ACB = air circuit-breakers (Emax)
For moulded-case or air circuit-breakers:
TM = thermomagnetic release
TMD (Tmax)
TMA (Tmax)
M = magnetic only release
MF (Tmax)
MA (Tmax)
EL = electronic release
PR121/P - PR122/P - PR123/P (Emax)
PR211/P - PR212/P (Isomax)
PR221DS - PR222DS (Tmax)
Caption of symbols
MCB
Tmax
Isomax
Emax
For solutions not shown in these tables, please consult the website:
http://bol.it.abb.com
or contact ABB SACE
ABB SACE
2/3
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S9 @ 230/240 V
Supply s.**
S290
Char.
Icu [kA]
Load s.*
S931N
S941N
S951N
S971N
B-C
B-C
B-C
B-C
S500
4.5
10
10
15
50
In [A]
80
100
125
80
100
16
20
25
32
40
50
63
0.1
0.15
0.2
0.3
0.4
0.5
0.6
0.15
0.25
0.3
0.4
0.5
0.075
0.2
0.25
0.3
0.4
0.15
0.2
0.25
0.06
10
16
2.5
3.5
3.5
0.3
20
1.5
2.5
2.5
0.3
25
0.5
0.5
1.5
0.3
32
0.5
0.5
0.5
1.5
3.5
40
0.5
0.5
0.5
1.5
3.5
4.5
5.5
10
4.5
16
2.5
3.5
3.5
20
1.5
2.5
2.5
0.2
0.3
0.4
0.5
0.15
0.25
0.3
0.4
0.5
0.2
0.25
0.3
0.4
0.15
0.2
0.25
0.3
4.5
0.3
4.5
0.3
0.3
25
0.5
0.5
1.5
32
0.5
0.5
0.5
1.5
3.5
40
0.5
0.5
0.5
1.5
3.5
7.5
4.5
5.5
10
4.5
16
2.5
3.5
3.5
20
1.5
2.5
2.5
25
0.5
0.5
1.5
32
0.5
0.5
40
0.5
4
6
0.1
0.1
0.15
0.3
0.2
0.3
0.4
0.5
0.15
0.25
0.3
0.4
0.5
0.2
0.25
0.3
0.4
0.15
0.2
0.25
4.5
0.3
4.5
0.3
0.3
0.5
1.5
3.5
0.5
0.5
1.5
3.5
7.5
4.5
5.5
10
4.5
16
2.5
3.5
3.5
20
1.5
2.5
2.5
25
0.5
0.5
1.5
32
0.5
0.5
40
0.5
0.5
0.1
0.15
0.6
0.15
0.6
0.3
0.2
0.3
0.4
0.5
0.15
0.25
0.3
0.4
0.6
0.5
0.2
0.25
0.3
0.4
0.15
0.2
0.25
4.5
0.3
4.5
0.3
0.3
0.5
1.5
3.5
0.5
1.5
3.5
0.3
2/4
ABB SACE
S500
S500
50
50
10
13
16
20
25
32
40
50
63
10
13
16
20
25
32
40
50
63
0.1
0.2
0.34
0.53
0.58
0.62
0.7
0.85
0.24
0.5
0.15
0.26
0.4
0.53
0.58
0.62
0.7
0.85
0.2
0.32
0.5
3.5
0.1
0.2
0.26
0.4
0.53
0.58
0.62
0.7
0.15
0.24
0.35
0.5
0.15
0.2
0.34
0.48
0.53
0.58
0.62
0.2
0.32
0.35
0.5
0.5
0.15
0.26
0.4
0.48
0.53
0.58
0.24
0.3
0.5
0.5
1.5
3.5
0.2
0.34
0.4
0.48
0.53
0.26
0.34
0.4
0.48
0.1
0.4
0.48
0.34
0.4
0.48
2.5
3.5
0.5
1.5
1.5
0.5
0.5
0.34
0.53
0.58
0.62
0.7
0.85
0.24
0.5
0.15
0.26
0.4
0.53
0.58
0.62
0.7
0.85
0.2
0.32
0.5
3.5
0.2
0.26
0.4
0.53
0.58
0.62
0.7
0.15
0.24
0.35
0.5
5.5
0.15
0.2
0.34
0.48
0.53
0.58
0.62
0.2
0.32
0.35
0.5
0.5
4.5
0.15
0.26
0.4
0.48
0.53
0.58
0.24
0.3
0.5
0.5
1.5
3.5
5.5
0.2
0.34
0.4
0.48
0.53
3.5
0.26
0.34
0.4
0.48
0.26
0.34
0.4
0.48
0.26
0.34
0.4
0.48
0.62
0.7
0.85
0.2
0.34
0.15
0.1
1.5
0.5
0.4
0.53
0.58
0.62
0.7
0.85
0.2
0.32
0.5
0.4
0.53
0.58
0.62
0.7
0.15
0.24
0.35
0.2
0.34
0.48
0.53
0.58
0.62
0.32
0.35
0.5
0.5
4.5
0.15
0.26
0.4
0.48
0.53
0.58
0.24
0.3
0.5
0.5
1.5
3.5
5.5
0.2
0.34
0.4
0.48
0.53
3.5
0.26
0.34
0.4
0.48
0.26
0.34
0.4
0.48
0.26
0.34
0.4
0.48
0.62
0.7
0.85
0.1
0.5
0.26
0.2
2.5
1.5
0.2
0.15
0.5
1
0.5
0.26
0.34
0.24
0.5
0.5
0.58
0.2
3.5
0.5
5.5
0.35
0.24
0.5
2.5
0.5
1.5
0.5
1.5
0.5
0.58
0.26
0.4
0.53
0.58
0.62
0.7
0.85
0.2
0.32
0.5
0.2
0.26
0.4
0.53
0.58
0.62
0.7
0.15
0.24
0.35
0.2
0.34
0.48
0.53
0.58
0.62
0.32
0.35
0.5
0.5
4.5
0.15
0.26
0.4
0.48
0.53
0.58
0.24
0.3
0.5
0.5
1.5
3.5
5.5
0.2
0.34
0.4
0.48
0.53
3.5
0.26
0.34
0.4
0.48
0.26
0.34
0.4
0.48
0.26
0.34
0.4
0.48
0.2
0.5
0.5
0.53
0.15
ABB SACE
0.35
0.53
0.15
0.1
0.34
0.26
0.5
0.5
0.2
0.1
0.1
0.26
0.35
3.5
0.5
5.5
0.35
0.5
2.5
0.5
0.5
1.5
0.5
1.5
0.5
2/5
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
MCCB @ 415 V 4p - S9 @ 240 V
Supply s.
Load s.
S931N
S941N
Char.
S971N
Release
TMD
Iu [A]
160
TMD, MA
In [A]
16
20
25
32
40
50
63
80
16
20
25
32
40
50
10
3*
16
3*
3*
4.5
20
3*
3*
25
32
40
B-C
B-C
B-C
10
4.5
3*
4.5
B-C
16
4.5
3*
4.5
3*
3*
3*
B-C
B-C
S951N
B, C, N
Icu [kA]
T1
Version
20
25
B-C
32
B-C
40
B-C
B-C
B-C
10
4.5
7.5
8.5
3*
4.5
B-C
16
4.5
7.5
3*
4.5
3*
3*
7.5
3*
7.5
B-C
10
20
B-C
25
B-C
32
B-C
40
B-C
B-C
12
B-C
10
4.5
7.5
8.5
3*
4.5
B-C
16
4.5
7.5
3*
4.5
3*
3*
7.5
3*
7.5
B-C
10
20
B-C
25
B-C
32
B-C
40
Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral)
Load side circuit-breaker 1P+N (230/240 V)
* Value valid only for magnetic only supply side circuit-breaker
** Neutral 50%
2/6
ABB SACE
T2
T3
N, S, H, L
N, S
EL
TMD, MA
160
250
63
80
T*
10
25
63
100
T*
7.5
8.5
160 63
80
T*
T*
7.5
8.5
7.5
7.5
7.5
7.5
7.5
6*
7.5
7.5
8.5
7.5
7.5
7.5
6*
7.5
ABB SACE
7.5
6*
7.5
7.5
8.5
7.5
7.5
7.5
6*
7.5
2/7
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S200L @ 400/415 V
Supply s.
S290
Char.
Icu [kA]
Load s.
S200L
S500
15
50
In [A]
80
100
32
40
50
63
6..8
1.5
5.5
10
1.5
13
4.5
1.5
16
4.5
20
3.5
25
3.5
32
3
2.5
5
4.5
40
2/8
ABB SACE
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S200 @ 400/415 V
Supply s.
S290
Char.
Icu [kA]
Load s.
C
10
B-C
S500
15
50
In [A]
80
100
32
40
50
1.5
5.5
1.5
5.5
10
1.5
13
4.5
1.5
16
4.5
20
3.5
25
3.5
32
63
3
2.5
5
4.5
40
50
S200
63
10
1.5
5.5
5.5
1.5
10
1.5
13
1.5
1.5
16
20
25
32
40
50
63
ABB SACE
2/9
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S200 @ 400/415 V
Supply s.
S290
Char.
Icu [kA]
Load s.
2
K
10
S500
15
50
In [A]
80
100
32
40
50
63
1.5
5.5
1.5
5.5
10
1.5
16
20
25
32
40
50
63
S200
10
1.5
5.5
1.5
5.5
10
1.5
16
4.5
1.5
20
3.5
1.5
2.5
25
3.5
2.5
32
4.5
40
4.5
50
63
2/10
ABB SACE
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S200M @ 400/415 V
Supply s.
S290
Char.
Icu [kA]
Load s.
C
15
B-C
S500
15
50
In [A]
80
100
32
40
50
10.5
1.5
5.5
10.5
1.5
5.5
10
1.5
13
4.5
1.5
16
4.5
20
3.5
25
3.5
32
63
3
2.5
5
4.5
40
50
63
S200M
15
10.5
1.5
5.5
10.5
1.5
5.5
10
1.5
16
1.5
20
25
32
40
50
63
15
10.5
1.5
5.5
1.5
5.5
1.5
10.5
10
16
20
25
32
40
50
63
ABB SACE
2/11
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S200P @ 400/415 V
Supply s.
S290
Char.
Icu [kA]
Load s.
C
25
B-C
15
S200P
25
D
15
2/12
In [A]
2
3
4
6
8
10
13
16
20
25
32
40
50
63
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S500
15
50
80
T
T
T
10.5
10.5
5
4.5
4.5
3.5
3.5
100
T
T
T
T
T
8
7
7
5
5
4.5
32
T
3
2
1.5
1.5
1
40
T
6
3
2
2
1.5
1.5
50
T
15
6
3
3
2
2
2
63
T
15
15
5.5
5.5
3
3
3
2.5
T
T
T
10.5
10.5
5
3
3
3
T
T
T
T
T
8
5
5
5
4
T
3
2
1.5
1.5
1
T
6
3
2
2
1.5
T
15
6
3
3
2
1.5
1.5
T
15
15
5.5
5.5
3
2
2
2
ABB SACE
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S200P @ 400/415 V
Supply s.
S290
Char.
Icu [kA]
Load s.
25
K
15
S200P
25
Z
15
ABB SACE
In [A]
2
3
4
6
8
10
13
16
20
25
32
40
50
63
2
3
4
6
8
10
16
20
25
32
40
50
63
S500
15
50
80
T
T
T
10.5
10.5
5
3
3
3
100
T
T
T
T
T
8
5
5
5
4
32
T
3
2
1.5
1.5
40
T
6
3
2
2
1.5
50
T
15
6
3
3
2
1.5
63
T
15
15
5.5
5.5
3
2
2
T
T
T
10.5
10.5
5
4.5
3.5
3.5
3
3
T
T
T
T
T
8
7
5
5
4.5
4.5
3
T
3
2
1.5
1.5
1
1
T
6
3
2
2
1.5
1.5
1.5
T
15
6
3
3
2
2
2
2
T
15
15
5.5
5.5
3
3
2.5
2.5
2
2/13
Discrimination
Supply side circuit-breaker: MCB
Load side circuit-breaker: MCB
MCB - S500 @ 400/415 V
Supply s.
S290
Char.
D
Icu [kA]
Load s.
B-C-D
50
15
In [A]
80
10
10
10
13
10
16
10
20
7.5
25
4.5
32
100
40
50
63
S500
50
5.8
5.3..8
10
7.3..11
7.5
10..15
4.5
10
14..20
4.5
18..26
30
6
4.5
23..32
29..37
34..41
38..45
2/14
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S200L @ 400/415 V
Load s.
Char.
Icu [kA]
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
160
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.5
4.5
4.5
8
10
13
S200L
16
20
25
32
40
ABB SACE
2/15
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S200 @ 400/415 V
Load s.
Char.
Icu [kA]
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
160
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.5
7.5
8.5
4.5
7.5
7.5
4.5
7.5
7.5
7.5
8
10
10
B-C
13
16
20
25
32
40
7.5
50
63
S200
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
8.5
13
16
4.5
6.5
2.5
9.5
9.5
9.5
8
10
D
10
20
25
32
40
50
63
2/16
9.5
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S200 @ 400/415 V
Load s.
Char.
Icu [kA]
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
160
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
8.5
4.5
7.5
3.5
5.5
6.5
3.5
5.5
9.5
4.5
9.5
9.5
8
10
K
10
16
20
25
32
40
50
63
S200
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.5
8.5
4.5
7.5
7.5
7.5
8
Z
10
16
20
25
32
40
50
63
ABB SACE
9.5
10
7.5
2/17
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S200M @ 400/415 V
Load s.
Char.
Icu [kA]
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
160
5.5
5.5
5.5
5.5
5.5
5.5
10.5
5.5
5.5
5.5
5.5
5.5
10.5
4.5
7.5
8.5
4.5
7.5
7.5
12
4.5
7.5
12
10
10
7.5
12
8
10
15
B-C
13
16
20
25
32
40
7.5
50
12
7.5
10.5
63
10.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
5.5
5.5
5.5
5.5
5.5
10.5
12
8.5
13.5
4.5
6.5
11
2.5
9.5
9.5
9.5
8
S200M
15
10
16
20
25
32
40
50
63
T
5.5
5.5
5.5
5.5
5.5
5.5
10.5
5.5
5.5
5.5
5.5
5.5
10.5
12
8.5
4.5
7.5
10
13.5
3.5
5.5
6.5
11
3.5
5.5
9.5
9.5
9.5
8
10
K
15
16
20
25
32
40
50
63
2/18
9.5
4.5
9.5
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S200P @ 400/415 V
Load s.
Char.
Icu [kA]
25
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
15
15
15
15
15
15
15
15
17*
15
15
15
15
15
15
15
15
17*
5.5
5.5
5.5
5.5
5.5
5.5
10.5
15
17*
5.5
5.5
5.5
5.5
5.5
10.5
15
17*
4.5
7.5
8.5
17*
4.5
7.5
7.5
12
20*
4.5
7.5
12
20*
10
15
10
15
7.5
12
8
10
13
16
B-C
20
25
32
15
40
7.5
50
12
7.5
10.5
63
S200P
25
D
15
15
15
15
15
15
15
15
17*
15
15
15
15
15
15
15
15
17*
5.5
5.5
5.5
5.5
5.5
5.5
10.5
15
17*
5.5
5.5
5.5
5.5
5.5
10.5
12
17*
8.5
17*
13
13.5
16
13.5
4.5
6.5
11
2.5
9.5
9.5
9.5
8
10
25
32
40
50
63
10.5
20
15
160
9.5
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
ABB SACE
2/19
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S200P @ 400/415 V
Load s.
Char.
Icu [kA]
25
K
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
160
15
15
15
15
15
15
15
15
17*
15
15
15
15
15
15
15
15
17*
5.5
5.5
5.5
5.5
5.5
5.5
10.5
15
17*
5.5
5.5
5.5
5.5
5.5
10.5
12
17*
8
10
8.5
17*
13
7.5
10
13.5
16
4.5
7.5
10
13.5
3.5
5.5
6.5
11
3.5
5.5
9.5
4.5
9.5
9.5
20
25
32
15
40
50
63
S200P
25
15
15
15
15
15
15
15
15
17*
15
15
15
15
15
15
15
15
17*
5.5
5.5
5.5
5.5
5.5
5.5
10.5
15
17*
5.5
5.5
5.5
5.5
5.5
10.5
12
17*
4.5
8.5
17*
4.5
7.5
12
20*
10
15
10
15
7.5
12
8
10
16
20
25
32
15
9.5
40
50
63
7.5
12
7.5
10.5
10.5
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
2/20
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T1 - S500 @ 400/415 V
Load s.
Char.
Icu [kA]
Supply s.
T1
Version
B, C, N
Release
TM
Iu [A]
160
In [A]
16
20
25
32
40
50
63
80
100
125
5.5
5.5
5.5
5.5
5.5
5.5
10.5
15
20*
25*
4.5
4.5
4.5
4.5
10
20*
25*
4.5
4.5
4.5
7.5
10
15
25*
4.5
4.5
7.5
10
15
25*
4.5
7.5
10
15
25*
10
15
20*
7.5
10
20*
10
20*
15
10
13
16
B-C-D
50
20
25
32
40
50
160
63
S500
50
36
36
5.3..8
5.5
5.5
5.5
5.5
5.5
5.5
10.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
7.5
10
15
4.5
4.5
7.5
10
15
4.5
7.5
10
15
10
15
20*
7.5
10
20*
10
20*
15
10..15
14..20
18..26
30
5.8
7.3..11
23..32
29..37
34..41
38..45
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
ABB SACE
2/21
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S200L @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
S200L
Char.
Icu [kA]
160
In [A]
12.5
16
20
25
32
40
50
63
80
25
63
5.5*
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10
3*
4.5
13
3*
4.5
16
3*
4.5
20
3*
25
3*
32
3*
5.5*
40
10
100 160
2/22
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S200 @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
Char.
Icu [kA]
10
B-C
160
In [A]
12.5
16
20
25
32
40
50
63
80
10
25
63
5.5*
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10
3*
4.5
7.5
8.5
13
10
100 160
3*
4.5
7.5
7.5
16
3*
4.5
7.5
20
3*
25
3*
32
3*
7.5
40
5.5*
7.5
50
3*
5*
7.5
63
S200
5*
5.5*
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10
3*
8.5
13
2*
16
2*
20
2*
4.5
6.5
2*
2.5
25
9.5
32
9.5
40
3*
50
2*
3*
9.5
9.5
9.5
63
3*
9.5
9.5
ABB SACE
2/23
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S200 @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
Char.
Icu [kA]
2
K
10
160
In [A]
12.5
16
20
25
32
40
50
63
80
10
25
63
5.5*
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10
3*
8.5
2*
4.5
7.5
20
2*
3.5
5.5
6.5
2*
3.5
5.5
9.5
32
4.5
9.5
40
3*
50
2*
3*
9.5
9.5
9.5
63
10
100 160
16
25
S200
3*
9.5
9.5
5.5*
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10
3*
4.5
8.5
16
3*
4.5
7.5
20
3*
25
3*
32
3*
7.5
40
5.5*
7.5
50
4*
5*
7.5
63
5*
2/24
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S200M @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
Char.
Icu [kA]
15
B-C
160
In [A]
12.5
16
20
25
32
40
50
63
80
10
25
63
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
5.5 10.5
5.5
5.5
5.5
5.5
10
3*
13
3*
15
7.5
8.5
4.5
7.5
7.5
12
16
3*
4.5
7.5
12
20
3*
10
25
3*
10
32
3*
7.5
12
40
5.5*
7.5
12
50
3*
5*
7.5 10.5
5*
10.5
10.5
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
5.5
5.5
5.5
5.5
5.5 10.5
12
10
3*
8.5
16
2*
13.5
20
2*
4.5
6.5
11
2*
2.5
9.5
32
9.5
40
3*
50
2*
3*
9.5
9.5
9.5
63
15
10.5 10.5
25
100 160
4.5
63
S200M
3*
9.5
9.5
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
5.5
5.5
5.5
5.5
5.5 10.5
12
10
3*
8.5
16
2*
4.5
7.5
10
13.5
20
2*
3.5
5.5
6.5
11
2*
3.5
5.5
9.5
25
32
4.5
9.5
40
3*
50
2*
3*
9.5
9.5
9.5
63
3*
9.5
9.5
ABB SACE
2/25
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S200P @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
Char.
Icu [kA]
25
B-C
15
160
In [A]
12.5
16
20
25
32
40
50
63
80
10
25
63
15
15
15
15
15
15
15
15
15
17
15
15
15
15
15
15
15
15
15
17
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
15
17
5.5 10.5
15
17
4.5
7.5
8.5
17
5.5
5.5
5.5
5.5
10
3*
13
3*
25
D
4.5
7.5
7.5
12
20
3*
4.5
7.5
12
20
20
3*
10
15
25
3*
10
15
32
3*
7.5
12
40
5.5*
7.5
12
50
3*
5*
7.5 10.5
5*
10.5 10.5
10.5
10.5
15
15
15
15
15
15
15
15
15
17
15
15
15
15
15
15
15
15
15
17
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
15
17
5.5
5.5
5.5
5.5
5.5 10.5
12
17
10
3*
8.5
17
13
2*
13.5
16
2*
13.5
20
2*
4.5
6.5
11
2*
2.5
25
15
100 160
16
63
S200P
9.5
32
9.5
40
3*
50
2*
3*
9.5
9.5
9.5
63
3*
9.5
9.5
2/26
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S200P @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
Char.
Icu [kA]
25
K
160
In [A]
12.5
16
20
25
32
40
50
63
80
10
25
63
15
15
15
15
15
15
15
15
15
17
15
15
15
15
15
15
15
15
15
17
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
15
17
5.5
5.5
5.5
5.5
5.5 10.5
12
17
10
3*
8.5
17
13
2*
7.5
10
13.5
16
2*
4.5
7.5
10
13.5
20
2*
3.5
5.5
6.5
11
2*
3.5
25
15
25
Z
15
100 160
5.5
9.5
32
4.5
9.5
40
3*
50
2*
3*
9.5
9.5
9.5
63
S200P
3*
9.5
9.5
15
15
15
15
15
15
15
15
15
17
15
15
15
15
15
15
15
15
15
17
5.5*
5.5
5.5
5.5
5.5
5.5
5.5 10.5
15
17
5.5
5.5
5.5
5.5
5.5 10.5
15
17
10
3*
4.5
8.5
17
16
3*
4.5
7.5
12
20
20
3*
10
15
25
3*
10
15
32
3*
7.5
12
40
5.5*
7.5
12
50
4*
5*
7.5 10.5
10.5 10.5
5*
10.5
10.5
63
ABB SACE
2/27
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T2 - S290 @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
S290
Char.
C-D-K
Icu [kA]
15
160
In [A]
160
160
80
100
125
2
Tmax T2 - S500 @ 400/415 V
Supply s.
T2
Version
N, S, H, L
Release
TM, M
EL
Iu [A]
Load s.
Char.
B-C-D
Icu [kA]
50
160
In [A]
12.5
16
20
25
32
40
50
80
25
63
100 160
4.5
5.5
5.5
5.5
5.5
5.5
5.5 10.5
63
15
20
25
36
36
36
36
10
4.5*
4.5
4.5
4.5
4.5
10
20
25
36
36
36
36
36
13
4.5*
4.5
4.5
4.5
7.5
10
15
25
36
36
36
36
36
16
4.5*
4.5
4.5
7.5
10
15
25
36
36
36
36
20
4.5*
4.5
7.5
10
15
25
36
36
36
36
25
4.5*
32
4.5*
50
K
30
36
10
15
20
36
36
36
36
7.5
10
20
36
36
36
36
40
5*
10
20
36
36
36
50
5*
7.5*
15
36
36
36
36
36
36
63
S500
10
5*
5.8
36
36
5.3..8
4.5*
5.5
36
36
36
36
36
36
36
36
5.5
5.5
5.5
5.5
5.5 10.5
36
36
36
50**
7.3..11
4.5*
4.5
4.5
4.5
4.5
36
36
36
50**
10..15
4.5*
4.5
4.5
4.5
7.5
10
15
14..20
4.5*
4.5
4.5
7.5
10
15
18..26
4.5*
4.5
7.5
10
15
23..32
4.5*
29..37
4.5*
10
15
20
7.5
10
20
34..41
5*
10
20
38..45
5*
7.5*
15
2/28
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S200L@ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
S200L
ABB SACE
Char.
Icu [kA]
250
In [A]
63
80
100
125
160
200
250
10
13
16
20
25
32
40
2/29
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S200 @ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
2
10
B-C
250
In [A]
63
80
100
125
160
200
250
10
7.5
8.5
13
7.5
7.5
16
7.5
20
25
7.5
40
7.5
50
5*
7.5
32
63
S200
10
5*
6*
10
8.5
13
16
20
4.5
6.5
25
2.5
9.5
T
T
32
9.5
40
50
3*
9.5
63
3*
5*
9.5
2/30
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S200 @ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
10
250
In [A]
63
80
100
125
160
200
250
10
8.5
16
4.5
7.5
20
3.5
5.5
6.5
25
3.5
5.5
9.5
T
T
32
9.5
40
4.5
50
3*
9.5
63
S200
10
3*
5.5*
9.5
10
8.5
16
7.5
20
25
7.5
40
7.5
50
5*
7.5
63
5*
6*
32
ABB SACE
2/31
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S200M @ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
2
15
B-C
250
In [A]
63
80
100
125
160
200
250
10.5
10.5
10
7.5
8.5
13
7.5
7.5
12
16
7.5
12
20
10
25
10
7.5
12
32
S200M
D
15
40
7.5
12
50
5*
7.5
10.5
63
5*
6*
10.5
10.5
10.5
12
10
8.5
16
13.5
20
4.5
6.5
11
25
2.5
9.5
9.5
40
50
3*
9.5
32
63
15
3*
5*
9.5
10.5
10.5
12
10
8.5
T
T
16
4.5
7.5
10
13.5
20
3.5
5.5
6.5
11
25
3.5
5.5
9.5
T
T
32
9.5
40
4.5
50
3*
9.5
63
3*
5.5*
9.5
2/32
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S200P @ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
25
B-C
250
In [A]
63
80
100
125
160
200
250
15
15
17
15
15
17
10.5
15
17
10.5
15
17
10
7.5
8.5
17
13
7.5
7.5
12
20
16
7.5
12
20
20
10
15
25
10
15
7.5
12
32
15
S200P
25
D
40
7.5
12
50
5*
7.5
10.5
63
5*
6*
10.5
15
15
15
15
10.5
15
10.5
12
10
8.5
13
13.5
16
13.5
20
4.5
6.5
11
25
2.5
9.5
9.5
40
50
3*
9.5
63
3*
5*
9.5
32
15
ABB SACE
2/33
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S200P @ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
25
K
250
In [A]
63
80
100
125
160
200
250
15
15
17
15
15
17
10.5
15
17
T
T
10.5
12
17
10
8.5
17
13
7.5
10
13.5
16
4.5
7.5
10
13.5
20
3.5
5.5
6.5
11
25
3.5
5.5
9.5
4.5
9.5
40
50
3*
9.5
32
15
63
S200P
25
Z
3*
5.5*
9.5
15
15
17
15
15
17
10.5
15
17
10.5
15
17
10
8.5
17
16
7.5
12
20
20
10
15
25
10
15
7.5
12
32
15
40
7.5
12
50
5*
7.5
10.5
63
5*
6*
10.5
2/34
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T3 - S290 @ 400/415 V
Supply s.
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
S290
Char.
C-D-K
Icu [kA]
15
250
In [A]
160
200
80
4*
10
15
100
4*
7.5*
15
125
250
7.5*
T3
Version
N, S
Release
TM, M
Iu [A]
Load s.
Char.
B-C-D
Icu [kA]
50
250
In [A]
63
80
100
125
160
200
250
10.5
15
20
25
36
36
36
10
10
20
25
36
36
36
13
7.5
10
15
25
36
36
36
16
7.5
10
15
25
36
36
36
20
7.5
10
15
25
36
36
36
25
10
15
20
36
36
36
7.5
10
20
36
36
36
32
40
10
20
36
36
36
50
7.5*
15
36
36
36
36
63
S500
50
K
30
5*
6*
36
36
5.8
36
36
36
36
5.3..8
10.5
36
36
36
7.3..11
36
36
36
10..15
7.5
10
15
14..20
7.5
10
15
18..26
7.5
10
15
23..32
10
15
20
7.5
10
20
34..41
10
20
38..45
7.5*
15
29..37
ABB SACE
2/35
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S200L @ 400/415 V
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
Load s.
S200L
Char.
Icu [kA]
EL
250
250
20
25
32
50
80
100
125
160
200
T*
T*
10
5*
13
5*
16
3*
25
32
5**
20
40
250 100
320
In [A]
160
250
320
2/36
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S200 @ 400/415 V
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
10
B-C
10
320
20
25
32
50
80
100
125
160
200
250
100
160
250
320
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
6.5
13
5*
6.5
16
3*
6.5
7.5
25
7.5
32
5**
7.5
40
6.5
50
5*
63
250
In [A]
20
S200
EL
250
T*
T*
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
5.5
16
13
5*
5.5
20
4**
25
4**
4.5
32
4.5*
40
4.5*
T*
T*
T*
T*
T*
50
63
ABB SACE
2/37
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S200 @ 400/415 V
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
2
K
10
10
250
320
In [A]
20
25
32
50
80
100
125
160
200
250
100
160
250
320
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
16
5*
20
25
5**
6*
32
5**
6*
T*
40
5.5*
T*
T*
50
5*
T*
T*
T*
T*
T*
T*
T*
63
S200
EL
250
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
6.5
5*
4.5
6.5
20
7.5
25
7.5
32
5**
7.5
40
6.5
50
5*
T*
16
63
* Value valid with supply side magnetic only circuit-breaker
** Value valid with supply side magnetic only MA 52 circuit-breaker
2/38
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S200M @ 400/415 V
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
15
B-C
15
25
32
50
80
100
125
160
200
250
100
160
250
320
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
6.5
13
5*
6.5
16
3*
6.5
7.5
25
7.5
32
5**
7.5
40
6.5
50
5*
T*
T*
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
16
5.5
20
4**
25
4**
4.5
32
4.5*
40
4.5*
T*
50
T*
63
15
320
20
63
250
In [A]
20
S200M
EL
250
T*
T*
T*
T*
T*
T*
7.5
7.5*
7.5
7.5
7.5
7.5*
7.5
7.5
10
5*
16
5*
20
25
5**
6*
32
5**
6*
T*
40
5.5*
T*
T*
50
5*
T*
T*
T*
T*
T*
T*
T*
63
ABB SACE
2/39
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S200P @ 400/415 V
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
25
B-C
In [A]
20
25
32
50
25
100
125
160
200
250
100
160
250
320
T*
15
15*
15
15
15
15
15*
15
15
15
7.5
7.5*
7.5
7.5
15
7.5
7.5*
7.5
7.5
15
10
5*
6.5
13
5*
6.5
16
3*
6.5
7.5
25
7.5
32
5**
7.5
40
6.5
50
5*
15
T*
T*
T*
15
15*
15
15
15
15
15*
15
15
15
7.5
7.5*
7.5
7.5
15
7.5
7.5*
7.5
7.5
15
10
5*
5.5
16
5.5
20
4**
25
4**
4.5
13
320
80
63
S200P
250
20
15
EL
250
5*
32
4.5*
40
4.5*
T*
50
63
T*
T*
T*
T*
2/40
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S200P @ 400/415 V
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
Load s.
Char.
Icu [kA]
25
K
15
In [A]
20
25
32
50
25
Z
320
100
125
160
200
250
100
160
250
320
T*
15
15*
15
15
15
15
15*
15
15
15
7.5
7.5*
7.5
7.5
15
7.5
7.5*
7.5
7.5
15
10
5*
13
5*
16
5*
20
25
5**
6*
32
5**
6*
T*
40
5.5*
T*
T*
50
5*
T*
T*
T*
T*
T*
T*
T*
T*
15
15*
15
15
15
15
15*
15
15
15
7.5
7.5*
7.5
7.5
15
7.5
7.5*
7.5
7.5
15
10
5*
6.5
5*
4.5
6.5
20
7.5
25
7.5
32
5**
7.5
40
6.5
50
5*
T*
16
15
250
80
63
S200P
EL
250
63
ABB SACE
2/41
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S290 @ 400/415 V
Load s.
Char.
Icu [kA]
C-K
S290
C
D
15
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
250
In [A]
EL
250
200
80
11
100
5*
12
8*
12
11
12
125
80
100
250
160
320
160
250
320
2/42
ABB SACE
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCB
Tmax T4 - S500 @ 400/415 V
Load s.
Char.
B-C
Icu [kA]
50
Supply s.
T4
Version
N, S, H, L, V
Release
TM, M
Iu [A]
250
In [A]
20
25
32
50
80
160
320
250
320
7.5
7.5
16
6.5*
6.5
6.5
11
13
6.5
5*
6.5
6.5
11
16
5*
6.5
6.5
11
20
4*
6.5
6.5
11
25
6.5
11
32
6.5
40
5*
6.5
5*
7.5
5*
7.5
7.5*
7.5
7.5
16
10
6.5
6.5*
6.5
6.5
11
6.5
11
16
6.5
11
20
6.5*
11
25
6.5*
11
5*
32
8*
40
6.5*
T*
7.5*
T*
7*
T*
5.8
30
250 100
7.5*
63
200
6.5
50
50
160
7.5
13
50
125
63
100
10
50
S500
EL
250
5.3..8
6*
40**
7.3..11
5*
40**
10..15
5*
12
14..20
12
18..26
5*
12*
23..32
5*
12*
T*
29..37
5*
8*
T*
T*
34..41
6*
T*
T*
38..45
6*
8*
T*
T*
* Value valid with supply side magnetic only circuit-breaker (with In = 50 A please refer to MA52 circuit-breakers)
** Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
ABB SACE
2/43
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T1 @ 400/415 V
Supply s. T1
Version
B,
C,
N
Release
Iu [A]
Load s.
In [A]
2
B
T2
T3
T4
N,S,H,L
N,S
N,S,H,L,V
TM,M
TM TM,M
EL
TM,M
160
160
250
160 160 25
250
25
32
50
16
10** 10
10
10
10
10
10
20
10** 10
10
10
10
10
10
25
10** 10
10
10
10
10
10
32
10*
10
10
10
10
10
40
10*
10
10
10
10
10
50
10* 10
10
10
10
63
10* 10
10
10
10
10
10
10* 10
10
10*
10
80
100
125
160
T1
TM
C
160
25
32
10** 10
10
10
10
10
10
10*
10
10
10
10
10
10*
10
10
10
10
10
10* 10
10
10
10
40
50
63
80
10* 10
10
10
10
10
10
10* 10
10
10*
10
10
100
125
160
32
10*
10
10
10
10
40
10*
10
10
10
10
10
50
10* 10
10
10
10
63
10* 10
10
10
10
10
10
10* 10
10
10*
10
80
100
125
160
* Value valid with supply side magnetic only circuit-breaker
** Value valid with supply side magnetic only MA 52 circuit-breaker
2/44
ABB SACE
T4
T5
T6
S7
N,S,H,L,V
N,S,H,L,V
N,S,H,L
S,H,L
EL
250
TM
320
400
EL
630
400
TM,M
EL
EL
1250
1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 100010001250 1600
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
ABB SACE
10
10
10
10
10
10
2/45
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T2 @ 400/415 V
Supply s. T1
Version
B,
C,
N
Release
Load s.
T4
N,S,H,L
N,S
N,S,H,L,V
TM,M
TM,M
In [A]
160
EL
160
160
160 160 25
25
32
50
1.6-2.5 T
T2
T3
TM TM,M
Iu [A]
TM
T2
250
250
T*
3.2
T*
4-5
T*
6.3
10
10
10
10
10
10 10
15 40** T
T*
10
10
10
10
10
10 10
15 40**
T*
10
10
10
10
10
10
10 10
15 40**
T*
12.5
16
20
T*
25
T*
32
T*
40
30* 30* 30
30
30
30
50
30* 30* 30
30
30
30
63
80
100
30
30
3*
25
4*
25
125
25* 25*
160
EL
160
25*
10
25
63
100
160
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
2/46
ABB SACE
T4
T5
T6
S7
N,S,H,L,V
N,S,H,L,V
N,S,H,L
S,H,L
EL
TM
250
320
400
EL
630
400
TM,M
EL
EL
1250
1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 10001000 1250 1600
T
30
30
30
30
30
30
30
30
30
30
30
30
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
ABB SACE
2/47
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T2 @ 400/415 V
Supply s. T1
Version
B,
C,
N
Release
Load s.
T4
N,S,H,L
N,S
N,S,H,L,V
TM,M
TM,M
In [A]
160
EL
160
160
160 160 25
25
32
50
1.6-2.5 T
T2
T3
TM TM,M
Iu [A]
TM
T2
250
250
T*
3.2
T*
4-5
T*
6.3
10
10
10
10
10
10 10
15 40** T
T*
10
10
10
10
10
10 10
15 40**
T*
10
10
10
10
10
10
10 10
15 40**
T*
12.5
16
20
T*
25
32
40
30* 30* 30
30
30
30
50
30* 30* 30
30
30
30
63
80
100
30
30
3*
25
25
125
25* 25*
160
EL
160
25*
10
25
63
100
160
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
2/48
ABB SACE
T4
T5
T6
S7
N,S,H,L,V
N,S,H,L,V
N,S,H,L
S,H,L
EL
TM
250
320
400
EL
630
400
TM,M
EL
EL
1250
1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 10001250 1600
T
30
30
30
30
30
30
30
30
30
30
30
30
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
ABB SACE
2/49
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T2 @ 400/415 V
Supply s. T1
Version
B,
C,
N
Release
Iu [A]
Load s.
In [A]
TM
T2
160
T3
T4
N,S,H,L
N,S
N,S,H,L,V
TM,M
TM TM,M
EL
TM,M
160
160
250
160 160 25
25
32
50
1.6-2.5 T
T2
250
T*
3.2
T*
4-5
T*
6.3
10
10
10
10
10
10 10
15 40** T
T*
10
10
10
10
10
10 10
15 40**
T*
10
10
10
10
10
10
10 10
15 40**
T*
12.5
16
20
25
32
40
30* 30* 30
30
30
30
50
30* 30* 30
30
30
30
63
80
100
30
30
3*
25
25
125
25* 25*
160
EL
160
25*
10
25
63
100
160
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
2/50
ABB SACE
T4
T5
T6
S7
N,S,H,L,V
N,S,H,L,V
N,S,H,L
S,H,L
EL
TM
250
320
400
EL
630
400
TM,M
EL
EL
1250
1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 10001250 1600
T
30
30
30
30
30
30
30
30
30
30
30
30
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
ABB SACE
2/51
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T2 @ 400/415 V
Supply s. T1
Version
B,
C,
N
Release
Load s.
T4
N,S,H,L
N,S
N,S,H,L,V
TM,M
TM,M
In [A]
160
EL
160
160
160 160 25
25
32
50
1.6-2.5 T
T2
T3
TM TM,M
Iu [A]
TM
T2
250
250
T*
3.2
T*
4-5
T*
6.3
10
10
10
10
10
10 10
15 40** T
T*
10
10
10
10
10
10 10
15 40**
T*
10
T*
10
10
10
10
10
10 10
15 40**
12.5
16
20
25
32
40
30* 30* 30
30
30
30
50
30* 30* 30
30
30
30
63
80
100
30
30
3*
25
25
125
25* 25*
160
EL
160
25*
10
25
63
100
160
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
2/52
ABB SACE
T4
T5
T6
S7
N,S,H,L,V
N,S,H,L,V
N,S,H,L
S,H,L
EL
TM
250
320
400
EL
630
400
TM,M
EL
EL
1250
1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 10001250 1600
T
30
30
30
30
30
30
30
30
30
30
30
30
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
ABB SACE
2/53
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T3 @ 400/415 V
Supply s. T1
Version
B,
C,
N
Release
T3
T4
N,S,H,L
N,S
N,S,H,L,V
TM,M
TM,M
TM TM,M
Iu [A]
Load s.
T2
In [A]
EL
160
160
250
160 160 25
32
50
63
80
3*
7*
4*
7*
7*
100
N
250
25
7*
125
7*
160
200
T3
TM
250
250
63
80
3*
7*
4*
7*
7*
100
S
7*
125
7*
160
200
250
* Value valid with supply side magnetic only circuit-breaker
** Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
T5
T6
S7
N,S,H,L,V
N,S,H,L
S,H,L
Version
Release
TM
Iu [A]
Load s.
In [A]
EL
630
400
TM,M
EL
EL
1250
1600
320 400 500 320 400 630 630 800 630 800 1000100012501600
20
32
50
80
100
S,
125
H,
160
L,
200
250
50* 50* T
100
160
N,
T4
400
TM
EL
250
250
250
320
320
50*
50* 50* T
50* T
* Select the lowest value among what is indicated, the breaking capacity of the supply side
circuit-breaker and the breaking capacity of the load side circuit-breaker
2/54
ABB SACE
T4
T5
T6
S7
N,S,H,L,V
N,S,H,L,V
N,S,H,L
S,H,L
EL
TM
250
320
400
EL
630
400
TM,M
EL
EL
1250
1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 100012501600
7
25
25
25
25
25 25
25
25
25
25
25
25
25
25
25
25
25
25
20
20
20
20
20
20
20
20
20
20
20
20
20
30
30
20
20
30
30
7
7
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25 40**
T 40** T
20
20
20
20
20
20
36
36
20
20
20
20
36
36
20
20
20
30
30
20
20
ABB SACE
2/55
Discrimination
Supply side circuit-breaker: MCCB
Load side circuit-breaker: MCCB
MCCB - Tmax T5 @ 400/415 V
Supply s.
T6
S7
N,S,H,L
S,H,L
Version
Release
TM,M
Iu [A]
Load s.
T5
N,
S,
H,
L,
V
400
TM
EL
630
400
630
EL
EL
1250
1600
In [A]
320
30 30
400
30
30
500
30 30
30
30
30
30
320
30
30
30
30
30
400
30
30
30
30
30
30
630
S7
Version
S,H,L
Release
EL
Iu [A]
Load s.
1600
TM
S
EL
T6
TM
H
EL
TM
L
EL
2/56
1250
630
630
800
800
T
T
630
630
800
800
1000
1000
630
630
40
40
800
800
40
40
630
630
40
40
40
800
800
40
40
40
1000
1000
40
40
630
630
40
40
40
40
800
800
630
630
40
40
40
800
800
40
40
40
1000
1000
40
40
630
630
40
40
800
800
40
40
630
630
40
40
40
800
800
40
40
40
1000
1000
40
40
ABB SACE
Discrimination
Supply side circuit-breaker: ACB
Load side circuit-breaker: MCCB
ACB - MCCB @ 400/415 V
Supply s.
Version
E1
B
Release
Load s.
T2
Iu[A]
T4
EL
800 800
1000 1000
1250 1250
1600 1600
E4
V
L*
EL
1250
1600
E6
V
EL
800
1000
1250
1600
2000
2500
3200
V
EL
4000 3200
5000 4000
6300 5000
6300
TM,EL
N
S
TM
160
250
55
65
55
65
75
55
65
55
65
100
75
85
100
100
100
55
65
100
75
85
100
100
100
TM,EL
250
320
55
65
55
65
100
75
85
100
100
100
55
65
100
75
85
100
100
100
TM,EL
S
H
TM,EL
L
S
S7
L*
160
T6
E3
S
T
TM
T5
L
T3
EL
B
T1
E2
N
H
L
EL
400
630
630
800
1000
1250
1600
55
65
55
65
75
85
55
55
65
75
85
Table valid for Emax circuit-breakers only with PR121/P, PR122/P and PR123/P releases
* Emax L circuit-breakers only with PR122/P and PR123/P releases
ABB SACE
2/57
Tabelle di coordinamento
Coordination
tables
Introduzione
Motor
protection
ABB SACE
3/1
Motor protection
Notes for use
ABB SACE proposes a vast range of coordination solutions for the power supply of any
motor for which protection against short-circuit and overload are of fundamental
importance.
Standard used
IEC 60947 - 4 1
Rated power of the motor
The tables are based on the current consumed by electric, three-phase squirrel cage
ABB induction motors with four poles.
The rated power of the motor is expressed in kiloWatt
Protection device
As protection device, the following tables use the moulded-case circuit-breakers (MCCB)
with the following types of releases:
MF fixed magnetic only release (for Tmax T2 circuit-breakers)
MA magnetic only release adjustable (for Tmax T2e T3 circuit-breakers)
PR221/I electronic release (for Tmax T4 and T5 circuit-breakers)
PR222MP electronic release (for Tmax T4 and T5 circuit-breakers).
The solutions proposed refer to an ambient temperature of 40 C and to fixed version
apparatus. For higher temperatures, please contact ABB SACE.
Type of starting
By normal starting, a starting time up to 2 s is intended in accordance with the trip
time of the thermal relays in class 10 A (see table 2).
By heavy duty, a starting time up to 9 s is intended in accordance with the trip time of
the thermal relays in class 30 (see table 2).
Two factors must be considered for normal star-delta starting: the speed the motor
has reached at the end of the starting period is 85% higher than the rated one; the
transition time between the star delta connection is 80 ms shorter.
Short-circuit current
The valid selection for a certain value also covers lower levels of short-circuit. For
example, by selecting 80 kA, protection which is also valid for lower values is obtained
(70, 60..kA, at the same voltage). This means a starter with higher performances at
the required breaking capacity. For more economical solutions, verifying some specific
solutions for lower short-circuit levels is recommended.
3/2
ABB SACE
Motor protection
Notes for use
Notes
To determine a type of coordination univocally, and therefore the apparatus needed to
carry it out, the following must be known:
motor power in kW and the type;
rated installation voltage;
rated current of the motor;
short-circuit current at the point of installation;
type of starting: DOL or Y/ - Normal or Heavy - Type 1 o Type 2.
Example for using the tables
You want to realize Y/ Normal Type 2 starting of a three-phase asynchronous
squirrelcage motor with the following data:
rated voltage
short-circuit current
rated motor power
Ur = 400 V
Ik = 50 kA
Pe = 200 kW
The following information is read from the table (stardelta 400 V 50 kA), in
correspondence with the relative line:
Ie (rated current):
349 A
protection device against short-circuit:
T5S630 PR221-I In630 circuit-breaker
magnetic trip threshold:
I3 = 4410 A
line contactor:
A210
delta contactor:
A210
star contactor:
A185
thermal relay:
E320DU320 adjustable 105-320 A
Ie
(to adjusted to
= 202 A).
3
Caption of symbols
MCB
Tmax
Isomax
Emax
For solutions not shown in these tables, please consult the website:
http://bol.it.abb.com
or contact ABB SACE
ABB SACE
3/3
Motor protection
DOL Type 2 - Normal starting
3/4
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
min
[A]
Group
Current
setting
I max
max
[kW]
[A]
[A]
[A]
[A]
0.37
1.1
T2N160 MF1.6
21
A9
TA25DU1.4
1.4
1.4
0.55
1.5
T2N160 MF1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
0.75
1.9
T2N160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.8
T2N160 MF 3.2
42
A9
TA25DU4
2.8
3.2
1.5
3.5
T2N160 MF 4
52
A16
TA25DU5
3.5
2.2
T2N160 MF 5
65
A26
TA25DU6.5
4.5
6.5
6.6
T2N160 MF 8.5
110
A26
TA25DU8.5
8.5
8.5
8.6
T2N160 MF 11
145
A30
TA25DU11
7.5
11
11
5.5
11.5
T2N160 MF 12.5
163
A30
TA25DU14
10
14
12.5
7.5
15.2
T2N160 MA 20
210
A30
TA25DU19
13
19
19
11
22
T2N160 MA 32
288
A30
TA42DU25
18
25
25
15
28.5
T2N160 MA 52
392
A50
TA75DU42
29
42
42
18.5
36
T2N160 MA 52
469
A50
TA75DU52
36
52
50
22
42
T2N160 MA 52
547
A50
TA75DU52
36
52
50
30
56
T2N160 MA 80
840
A63
TA75DU80
60
80
65
37
68
T2N160 MA 80
960
A75
TA75DU80
60
80
75
45
83
T2N160 MA 100
1200
A95
TA110DU110
80
110
96
55
98
T3N250 MA 160
1440
A110
TA110DU110
80
110
110
75
135
T3N250 MA 200
1800
A145
TA200DU175
130
175
145
90
158
T3N250 MA 200
2400
A185
TA200DU200
150
200
185
110
193
2720
A210
E320DU320
100
320
210
132
232
3200
A260
E320DU320
100
320
260
160
282
4000
A300
E320DU320
100
320
300
200
349
5040
AF400
E500DU500
150
500
400
250
430
6300
AF460
E500DU500
150
500
430
290
520
7200
AF580
E800DU800
250
800
580
315
545
8000
AF580
E800DU800
250
800
580
355
610
8000
AF750
E800DU800
250
800
750
ABB SACE
Motor protection
DOL Type 2 - Normal starting
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
min
[A]
Group
Current
setting
I max
max
[kW]
[A]
[A]
[A]
[A]
0.37
1.1
T2S160 MF 1.6
21
A9
TA25DU1.4
1.4
1.4
0.55
1.5
T2S160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
0.75
1.9
T2S160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.8
T2S160 MF 3.2
42
A9
TA25DU4
2.8
3.2
1.5
3.5
T2S160 MF 4
52
A16
TA25DU5
3.5
2.2
T2S160 MF 5
65
A26
TA25DU6.5
4.5
6.5
6.6
T2S160 MF 8.5
110
A26
TA25DU8.5
8.5
8.5
8.6
T2S160 MF 11
145
A30
TA25DU11
7.5
11
11
5.5
11.5
T2S160 MF 12.5
163
A30
TA25DU14
10
14
12.5
7.5
15.2
T2S160 MA 20
210
A30
TA25DU19
13
19
19
11
22
T2S160 MA 32
288
A30
TA42DU25
18
25
25
15
28.5
T2S160 MA 52
392
A50
TA75DU42
29
42
42
18.5
36
T2S160 MA 52
469
A50
TA75DU52
36
52
50
22
42
T2S160 MA 52
547
A50
TA75DU52
36
52
50
30
56
T2S160 MA 80
840
A63
TA75DU80
60
80
65
37
68
T2S160 MA 80
960
A75
TA75DU80
60
80
75
45
83
T2S160 MA 100
1200
A95
TA110DU110
80
110
96
55
98
T3S250 MA 160
1440
A110
TA110DU110
80
110
110
75
135
T3S250 MA 200
1800
A145
TA200DU175
130
175
145
90
158
T3S250 MA 200
2400
A185
TA200DU200
150
200
185
110
193
2720
A210
E320DU320
100
320
210
132
232
3200
A260
E320DU320
100
320
260
160
282
4000
A300
E320DU320
100
320
300
200
349
5040
AF400
E500DU500
150
500
400
250
430
6300
AF460
E500DU500
150
500
430
290
520
7200
AF580
E800DU800
250
800
580
315
545
8000
AF580
E800DU800
250
800
580
355
610
8000
AF750
E800DU800
250
800
750
ABB SACE
3/5
Motor protection
DOL Type 2 - Normal starting
3/6
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
min
[A]
Group
Current
setting
I max
max
[kW]
[A]
[A]
[A]
[A]
0.37
1.1
T2H160 MF 1.6
21
A9
TA25DU1.4
1.4
1.4
0.55
1.5
T2H160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
0.75
1.9
T2H160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.8
T2H160 MF 3.2
42
A16
TA25DU4
2.8
3.2
1.5
3.5
T2H160 MF 4
52
A26
TA25DU5
3.5
2.2
T2H160 MF 5
65
A26
TA25DU6.5
4.5
6.5
6.6
T2H160 MF 8.5
110
A26
TA25DU8.5
8.5
8.5
8.6
T2H160 MF 11
145
A30
TA25DU11
7.5
11
11
5.5
11.5
T2H160 MF 12.5
163
A50
TA25DU14
10
14
12.5
7.5
15.2
T2H160 MA 20
210
A50
TA25DU19
13
19
19
11
22
T2H160 MA 32
288
A50
TA42DU25
18
25
25
15
28.5
T2H160 MA 52
392
A50
TA75DU42
29
42
42
18.5
36
T2H160 MA 52
469
A50
TA75DU52
36
52
50
22
42
T2H160 MA 52
547
A50
TA75DU52
36
52
50
30
56
T2H160 MA 80
840
A63
TA75DU80
60
80
65
37
68
T2H160 MA 80
960
A75
TA75DU80
60
80
75
45
83
T2H160 MA 100
1200
A95
TA110DU110
80
110
96
55
98
1360
A110
TA110DU110
80
110
110
75
135
1875
A145
E200DU200
60
200
145
90
158
2500
A185
E200DU200
60
200
185
110
193
2720
A210
E320DU320
100
320
210
132
232
3200
A260
E320DU320
100
320
260
160
282
4000
A300
E320DU320
100
320
300
200
349
5040
AF400
E500DU500
150
500
400
250
430
6300
AF460
E500DU500
150
500
430
290
520
7200
AF580
E800DU800
250
800
580
315
545
8000
AF580
E800DU800
250
800
580
355
610
8000
AF750
E800DU800
250
800
650
ABB SACE
Motor protection
DOL Type 2 - Normal starting
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
min
I max
max
[kW]
[A]
[A]
[A]
[A]
0.37
1.1
T2L160 MF 1.6
21
A9
TA25DU1.4
1.4
1.4
0.55
1.5
T2L160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
0.75
1.9
T2L160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.8
T2L160 MF 3.2
42
A16
TA25DU4
2.8
3.2
1.5
3.5
T2L160 MF 4
52
A26
TA25DU5
3.5
2.2
T2L160 MF 5
65
A26
TA25DU6.5
4.5
6.5
6.6
T2L160 MF 8.5
110
A26
TA25DU8.5
8.5
8.5
8.6
T2L160 MF 11
145
A30
TA25DU11
7.5
11
11
5.5
11.5
T2L160 MF 12.5
163
A50
TA25DU14
10
14
12.5
7.5
15.2
T2L160 MA 20
210
A50
TA25DU19
13
19
19
11
22
T2L160 MA 32
288
A50
TA42DU25
18
25
25
15
28.5
T2L160 MA 52
392
A50
TA75DU42
29
42
42
18.5
36
T2L160 MA 52
469
A50
TA75DU52
36
52
50
22
42
T2L160 MA 52
547
A50
TA75DU52
36
52
50
30
56
T2L160 MA 80
840
A63
TA75DU80
60
80
65
37
68
T2L160 MA 80
960
A75
TA75DU80
60
80
75
45
83
T2L160 MA 100
1200
A95
TA110DU110
80
110
96
55
98
1360
A110
TA110DU110
80
110
110
75
135
1875
A145
E200DU200
60
200
145
90
158
2500
A185
E200DU200
60
200
185
110
193
2720
A210
E320DU320
100
320
210
132
232
3200
A260
E320DU320
100
320
260
160
282
4000
A300
E320DU320
100
320
300
200
349
5040
AF400
E500DU500
150
500
400
250
430
6300
AF460
E500DU500
150
500
430
290
520
7200
AF580
E800DU800
250
800
580
315
545
8000
AF580
E800DU800
250
800
580
355
610
8000
AF750
E800DU800
250
800
750
ABB SACE
[A]
Group
Current
setting
3/7
Motor protection
DOL Type 2 - Normal starting
MCCB
Rated
Power
Rated
current
Pe
Ie
[kW]
[A]
0.37
0.55
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
min
[A]
Group
Current
setting
I max
max
[A]
[A]
T2H160 MF 1
13
A9
TA25DU1.4
1.4
[A]
1
1.4
T2H160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
0.75
1.7
T2H160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.2
T2H160 MF 2.5
33
A9
TA25DU3.1
2.2
3.1
2.5
1.5
T2H160 MF 3.2
42
A16
TA25DU4
2.8
3.2
2.2
4.4
T2H160 MF 5
65
A26
TA25DU5
3.5
5.7
T2H160 MF 6.5
84
A26
TA25DU6.5
4.5
6.5
6.5
7.8
T2H160 MF 8.5
110
A30
TA25DU11
7.5
11
8.5
5.5
10.5
T2H160 MF 11
145
A30
TA25DU14
10
14
11
7.5
13.5
T2H160 MA 20
180
A30
TA25DU19
13
19
19
11
19
T2H160 MA 32
240
A30
TA42DU25
18
25
25
15
26
T2H160 MA 32
336
A50
TA75DU32
22
32
32
18.5
32
T2H160 MA 52
469
A50
TA75DU42
29
42
42
22
38
T2H160 MA 52
547
A50
TA75DU52
36
52
45
30
52
T2H160 MA 80
720
A63
TA75DU63
45
63
63
37
63
T2H160 MA 80
840
A75
TA75DU80
60
80
70
45
75
T2H160 MA 100
1050
A95
TA110DU90
65
90
90
55
90
1200
A110
TA110DU110
80
110
100
75
120
1750
A145
E200DU200
60
200
145
90
147
2000
A185
E200DU200
60
200
185
110
177
2500
A210
E320DU320
100
320
210
132
212
3200
A260
E320DU320
100
320
220
160
260
3600
A300
E320DU320
100
320
280
200
320
4410
AF400
E500DU500
150
500
400
250
410
5355
AF460
E500DU500
150
500
430
290
448
6300
AF580
E500DU500*
150
500
500
315
500
7200
AF580
E800DU800
250
800
580
355
549
8000
AF580
E800DU800
250
800
580
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3/8
ABB SACE
Motor protection
DOL Type 2 - Normal starting
MCCB
Rated
Power
Rated
current
Pe
Ie
[kW]
[A]
0.37
0.55
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
min
[A]
Group
Current
setting
I max
max
[A]
[A]
T2L160 MF 1
13
A9
TA25DU1.4
1.4
[A]
1
1.4
T2L160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
0.75
1.7
T2L160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.2
T2L160 MF 2.5
33
A9
TA25DU3.1
2.2
3.1
2.5
1.5
T2L160 MF 3.2
42
A16
TA25DU4
2.8
3.2
2.2
4.4
T2L160 MF 5
65
A26
TA25DU5
3.5
5.7
T2L160 MF 6.5
84
A26
TA25DU6.5
4.5
6.5
6.5
7.8
T2L160 MF 8.5
110
A30
TA25DU11
7.5
11
8.5
5.5
10.5
T2L160 MF 11
145
A30
TA25DU14
10
14
11
7.5
13.5
T2L160 MA 20
180
A30
TA25DU19
13
19
19
11
19
T2L160 MA 32
240
A30
TA42DU25
18
25
25
15
26
T2L160 MA 32
336
A50
TA75DU32
22
32
32
18.5
32
T2L160 MA 52
469
A50
TA75DU42
29
42
42
22
38
T2L160 MA 52
547
A50
TA75DU52
36
52
45
30
52
T2L160 MA 80
720
A63
TA75DU63
45
63
63
37
63
T2L160 MA 80
840
A75
TA75DU80
60
80
70
45
75
T2L160 MA 100
1050
A95
TA110DU90
65
90
90
55
90
1200
A110
TA110DU110
80
110
100
75
120
1750
A145
E200DU200
60
200
145
90
147
2000
A185
E200DU200
60
200
185
110
177
2500
A210
E320DU320
100
320
210
132
212
3200
A260
E320DU320
100
320
220
160
260
3600
A300
E320DU320
100
320
280
200
320
4410
AF400
E500DU500
150
500
400
250
410
5355
AF460
E500DU500
150
500
430
290
448
6300
AF580
E500DU500*
150
500
500
315
500
7200
AF580
E800DU800
250
800
580
355
549
8000
AF580
E800DU800
250
800
580
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
ABB SACE
3/9
Motor protection
DOL Type 2 - Normal starting
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type
[A]
Group
Current
setting
I max
min
max
[kW]
[A]
[A]
[A]
0.37
0.88
T2L160 MF 1
13
A9
TA25DU1.0
0.63
[A]
1
0.55
1.2
T2L160 MF 1.6
21
A9
TA25DU1.4
1.4
1.4
0.75
1.5
T2L160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
1.1
2.2
T2L160 MF 2.5
33
A9
TA25DU3.1
2.2
3.1
2.5
1.5
2.8
T2L160 MF 3.2
42
A16
TA25DU4
2.8
3.2
2.2
T2L160 MF 4
52
A26
TA25DU5
3.5
5.2
T2L160 MF 6.5
84
A26
TA25DU6.5
4.5
6.5
6.5
6.9
T2L160 MF 8.5
110
A30
TA25DU8.5
8.5
8.5
5.5
9.1
T2L160 MF 11
145
A30
TA25DU11
7.5
11
11
7.5
12.2
T2L160 MF 12.5
163
A30
TA25DU14
10
14
12.5
11
17.5
T2L160 MA 20
240
A30
TA25DU19
13
19
19
15
23
T2L160 MA 32
336
A50
TA75DU25
18
25
25
18.5
29
T2L160 MA 52
392
A50
TA75DU32
22
32
32
22
34
T2L160 MA 52
469
A50
TA75DU42
29
42
42
30
45
T2L160 MA 52
624
A63
TA75DU52
36
52
52
37
56
T2L160 MA 80
840
A75
TA75DU63
45
63
63
45
67
T2L160 MA 80
960
A95
TA80DU80
60
80
80
55
82
T2L160 MA 100
1200
A110
TA110DU90
65
90
90
75
110
1440
A145
E200DU200
60
200
145
145
90
132
1875
A145
E200DU200
60
200
110
158
2250
A185
E200DU200
60
200
170
132
192
2720
A210
E320DU320
100
320
210
160
230
3600
A260
E320DU320
100
320
240
200
279
4000
A300
E320DU320
100
320
280
250
335
4725
AF400
E500DU500
150
500
400
290
394
5040
AF460
E500DU500
150
500
430
315
440
6300
AF580
E500DU500*
150
500
500
355
483
6300
AF580
E800DU800
250
800
500
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3/10
ABB SACE
Motor protection
DOL Type 2 - Normal starting
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
TC
KORC
No. of
turns of
the CT
primary
coil
Thermal release
Group
Type
I max
Current
setting
min max
[kW]
[A]
0.37
0.6
T2L160 MF1
13
[A]
A9
TA25DU0.63
0.4 0.63
[A]
[A]
[A]
0.55
0.9
T2L160 MF1
13
A9
TA25DU1
0.63
0.75
1.1
T2L160 MF1.6
21
A9
TA25DU1.4
1.4
1.4
1.1
1.6
T2L160 MF1.6
21
A9
TA25DU1.8
1.3
1.8
1.6
1.5
T2L160 MF2.5
33
A9
TA25DU2.4
1.7
2.4
2.4
2.2
2.9
T2L160 MF3.2
42
A9
TA25DU3.1 *
2.2
3.1
3.1
3.8
T2L160 MF4
52
A9
TA25DU4 *
2.8
T2L160 MF5
65
A9
TA25DU5 *
3.5
5.5
6.5
T2L160 MF6.5
84
A9
TA25DU6.5 *
4.5
6.5
6.5
150
A95
4L185R/4
13**
TA25DU2.4
8.5
8.5
7.5
8.8
150
A95
4L185R/4
10**
TA25DU2.4
7.9 11.1
11.1
11
13
200
A95
4L185R/4
7**
TA25DU2.4
11.2 15.9
15.9
15
18
250
A95
4L185R/4
7**
TA25DU3.1
15.2 20.5
20.5
18.5
21
300
A95
4L185R/4
TA25DU3.1
17.7 23.9
23.9
22
25
350
A95
4L185R/4
TA25DU4
21.6 30.8
30.8
30
33
450
A145
4L185R/4
TA25DU5
27 38.5
38.5
37
41
550
A145
4L185R/4
TA25DU4
32.4 46.3
46.3
45
49
700
A145
4L185R/4
TA25DU5
40.5 57.8
57.8
55
60
800
A145
4L185R/4
TA25DU5
54 77.1
77.1
75
80
1120
A145
E200DU200
65
200
120
90
95
1280
A145
E200DU200
65
200
120
110
115
1625
A145
E200DU200
65
200
120
132
139
2000
A185
E200DU200
65
200
170
160
167
2250
A185
E200DU200
65
200
170
200
202
2720
A210
E320DU320
105 320
210
250
242
3400
A300
E320DU320
105 320
280
290
301
4410
AF400
E500DU500
150 500
350
315
313
4410
AF400
E500DU500
150 500
350
355
370
5355
AF580
430
0.63
For further information about the KORC, please see the Brochure KORC 1 GB 00-04 catalogue.
* Type 1 coordination
** Cable cross section= 4 mm2
*** No mounting kit to contactor is available; to use mounting kit provide E800DU
ABB SACE
3/11
Motor protection
DOL Type 2 - Heavy duty
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type**
[A]
Group
No. of
Current
turns of
setting
the CT
primary min max
coil
[A]
[A]
I max
[kW]
[A]
0.37
1.1
T2N160 MF1.6
21
A9
TA25DU1.4*
1.4
1.4
[A]
0.55
1.5
T2N160 MF1.6
21
A9
TA25DU1.8*
1.3
1.8
1.6
0.75
1.9
T2N160 MF 2
26
A9
TA25DU2.4*
1.7
2.4
1.1
2.8
T2N160 MF 3.2
42
A9
TA25DU4*
2.8
3.2
1.5
3.5
T2N160 MF 4
52
A16
TA25DU5*
3.5
2.2
T2N160 MF 5
65
A26
TA25DU6.5*
4.5
6.5
6.6
T2N160 MF 8.5
110
A26
TA25DU8.5*
8.5
8.5
8.6
T2N160 MF 11
145
A30
TA25DU11*
7.5
11
11
5.5
11.5
T2N160 MF 12.5
163
A30
TA450SU60
10
15
12.5
7.5
15.2
T2N160 MA 20
210
A30
TA450SU60
13
20
20
11
22
T2N160 MA 32
288
A30
TA450SU60
20
30
32
15
28.5
T2N160 MA 52
392
A50
TA450SU80
23
40
40
18.5
36
T2N160 MA 52
469
A50
TA450SU80
23
40
40
22
42
T2N160 MA 52
547
A50
TA450SU60
40
60
50
30
56
T2N160 MA 80
840
A63
TA450SU80
55
80
65
37
68
T2N160 MA 80
960
A95
TA450SU80
55
80
80
45
83
T2N160 MA 100
1200
A110
TA450SU105
70
105
100
55
98
T3N250 MA 160
1440
A145
TA450SU140
95
140
140
75
135
T3N250 MA 200
1800
A185
TA450SU185
130
185
185
90
158
T3N250 MA 200
2400
A210
TA450SU185
130
185
185
110
193
2720
A260
E320DU320
100
320
220
132
232
3200
A300
E320DU320
100
320
300
160
282
4000
AF400
E500DU500
150
500
400
200
349
5040
AF460
E500DU500
150
500
430
250
430
6300
AF580
E500DU500***
150
500
430
290
520
7200
AF750
E800DU800
250
800
750
315
545
8000
AF750
E800DU800
250
800
750
355
610
8000
AF750
E800DU800
250
800
750
3/12
ABB SACE
Motor protection
DOL Type 2 - Heavy duty
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type**
[A]
Group
No. of
Current
turns of
setting
the CT
primary min max
coil
[A]
[A]
I max
[kW]
[A]
0.37
1.1
T2S160 MF 1.6
21
A9
TA25DU1.4*
1.4
1.4
[A]
0.55
1.5
T2S160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
1.6
0.75
1.9
T2S160 MF 2
26
A9
TA25DU2.4*
1.7
2.4
1.1
2.8
T2S160 MF 3.2
42
A9
TA25DU4*
2.8
3.2
1.5
3.5
T2S160 MF 4
52
A16
TA25DU5*
3.5
2.2
T2S160 MF 5
65
A26
TA25DU6.5*
4.5
6.5
6.6
T2S160 MF 8.5
110
A26
TA25DU8.5*
8.5
8.5
8.6
T2S160 MF 11
145
A30
TA25DU11*
7.5
11
11
5.5
11.5
T2S160 MF 12.5
163
A30
TA450SU60
10
15
12.5
7.5
15.2
T2S160 MA 20
210
A30
TA450SU60
13
20
20
11
22
T2S160 MA 32
288
A30
TA450SU60
20
30
32
15
28.5
T2S160 MA 52
392
A50
TA450SU80
23
40
40
18.5
36
T2S160 MA 52
469
A50
TA450SU80
23
40
40
22
42
T2S160 MA 52
547
A50
TA450SU60
40
60
50
30
56
T2S160 MA 80
840
A63
TA450SU80
55
80
65
37
68
T2S160 MA 80
960
A95
TA450SU80
55
80
80
45
83
T2S160 MA 100
1200
A110
TA450SU105
70
105
100
55
98
T3S250 MA 160
1440
A145
TA450SU140
95
140
140
75
135
T3S250 MA 200
1800
A185
TA450SU185
130
185
185
90
158
T3S250 MA 200
2400
A210
TA450SU185
130
185
185
110
193
2720
A260
E320DU320
100
320
220
132
232
3200
A300
E320DU320
100
320
300
160
282
4000
AF400
E500DU500
150
500
400
200
349
5040
AF460
E500DU500
150
500
430
250
430
6300
AF580
E500DU500***
150
500
430
290
520
7200
AF750
E800DU800
250
800
750
315
545
8000
AF750
E800DU800
250
800
750
355
610
8000
AF750
E800DU800
250
800
750
ABB SACE
3/13
Motor protection
DOL Type 2 - Heavy duty
MCCB
Rated
Power
Rated
current
Pe
Ie
[kW]
[A]
0.37
0.55
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type**
[A]
Group
No. of
Current
turns of
setting
the CT
primary min max
coil
[A]
[A]
I max
[A]
T2H160 MF 1
13
A9
TA25DU1.4*
1.4
1.4
T2H160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
1.6
0.75
1.7
T2H160 MF 2
26
A9
TA25DU2.4*
1.7
2.4
1.1
2.2
T2H160 MF 2.5
33
A9
TA25DU3.1*
2.2
3.1
2.5
1.5
T2H160 MF 3.2
42
A16
TA25DU4*
2.8
3.2
2.2
4.4
T2H160 MF 5
65
A26
TA25DU5*
3.5
5.7
T2H160 MF 6.5
84
A26
TA25DU6.5*
4.5
6.5
6.5
7.8
T2H160 MF 8.5
110
A30
TA25DU11*
7.5
11
8.5
5.5
10.5
T2H160 MF 11
145
A30
TA25DU14*
10
14
11
7.5
13.5
T2H160 MA 20
180
A30
TA450SU60
10
15
15
11
19
T2H160 MA 32
240
A30
TA450SU80
18
27
27
15
26
T2H160 MA 32
336
A50
TA450SU60
20
30
32
18.5
32
T2H160 MA 52
469
A50
TA450SU80
28
40
40
22
38
T2H160 MA 52
547
A50
TA450SU80
28
40
40
30
52
T2H160 MA 80
720
A63
TA450SU60
40
60
60
37
63
T2H160 MA 80
840
A95
TA450SU80
55
80
80
45
75
T2H160 MA 100
1050
A110
TA450SU105
70
105
100
55
90
1200
A145
E200DU200
60
200
145
75
120
1750
A185
E200DU200
60
200
185
90
147
2000
A210
E320DU320
100
320
210
110
177
2500
A260
E320DU320
100
320
220
132
212
3200
A300
E320DU320
100
320
220
160
260
3600
AF400
E500DU500
150
500
400
200
320
4410
AF460
E500DU500
150
500
430
250
410
5355
AF580
E500DU500***
150
500
430
290
448
6300
AF750
E500DU500***
150
500
500
315
500
7200
AF 750
E800DU800
250
800
750
355
549
8000
AF 750
E800DU800
250
800
750
3/14
ABB SACE
Motor protection
DOL Type 2 - Heavy duty
MCCB
Rated
Power
Rated
current
Pe
Ie
[kW]
[A]
0.37
0.55
1.4
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type**
[A]
Group
No. of
Current
turns of
setting
the CT
primary min max
coil
[A]
[A]
I max
[A]
T2L160 MF 1
13
A9
TA25DU1.4*
1.4
T2L160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
1.6
0.75
1.7
T2L160 MF 2
26
A9
TA25DU2.4*
1.7
2.4
1.1
2.2
T2L160 MF 2.5
33
A9
TA25DU3.1*
2.2
3.1
2.5
1.5
T2L160 MF 3.2
42
A16
TA25DU4*
2.8
3.2
2.2
4.4
T2L160 MF 5
65
A26
TA25DU5*
3.5
5.7
T2L160 MF 6.5
84
A26
TA25DU6.5*
4.5
6.5
6.5
7.8
T2L160 MF 8.5
110
A30
TA25DU11*
7.5
11
8.5
5.5
10.5
T2L160 MF 11
145
A30
TA25DU14*
10
14
11
7.5
13.5
T2L160 MA 20
180
A30
TA450SU60
10
15
15
11
19
T2L160 MA 32
240
A30
TA450SU80
18
27
27
15
26
T2L160 MA 32
336
A50
TA450SU60
20
30
32
18.5
32
T2L160 MA 52
469
A50
TA450SU80
28
40
40
22
38
T2L160 MA 52
547
A50
TA450SU80
28
40
40
30
52
T2L160 MA 80
720
A63
TA450SU60
40
60
60
37
63
T2L160 MA 80
840
A95
TA450SU80
55
80
80
45
75
T2L160 MA 100
1050
A110
TA450SU105
70
105
100
55
90
1200
A145
E200DU200
60
200
145
75
120
1750
A185
E200DU200
60
200
185
90
147
2000
A210
E320DU320
100
320
210
110
177
2500
A260
E320DU320
100
320
220
132
212
3200
A300
E320DU320
100
320
220
160
260
3600
AF400
E500DU500
150
500
400
200
320
4410
AF460
E500DU500
150
500
430
250
410
5355
AF580
E500DU500***
150
500
430
290
448
6300
AF750
E500DU500***
150
500
500
315
500
7200
AF750
E800DU800
250
800
750
355
549
8000
AF750
E800DU800
250
800
750
ABB SACE
3/15
Motor protection
DOL Type 2 - Heavy duty
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Thermal release
Type
Type**
[A]
Group
No. of
Current
turns of
setting
the CT
primary min max
coil
[A]
[A]
I max
[kW]
[A]
0.37
0.88
T2L160 MF 1
13
A9
TA25DU1.0*
0.63
[A]
1
0.55
1.2
T2L160 MF 1.6
21
A9
TA25DU1.4*
1.4
1.4
0.75
1.5
T2L160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
1.6
1.1
2.2
T2L160 MF 2.5
33
A9
TA25DU3.1*
2.2
3.1
2.5
1.5
2.8
T2L160 MF 3.2
42
A16
TA25DU4*
2.8
3.2
2.2
T2L160 MF 4
52
A26
TA25DU5*
3.5
5.2
T2L160 MF 6.5
84
A26
TA25DU6.5*
4.5
6.5
6.5
6.9
T2L160 MF 8.5
110
A30
TA25DU8.5*
8.5
8.5
5.5
9.1
T2L160 MF 11
145
A30
TA25DU11*
7.5
11
11
7.5
12.2
T2L160 MF 12.5
163
A30
TA450SU60
10
15
12.5
11
17.5
T2L160 MA 20
240
A30
TA450SU60
13
20
20
15
23
T2L160 MA 32
336
A50
TA450SU60
20
30
30
18.5
29
T2L160 MA 52
392
A50
TA450SU80
27.5
40
40
22
34
T2L160 MA 52
469
A50
TA450SU80
27.5
40
40
30
45
T2L160 MA 52
624
A63
TA450SU60
40
60
52
37
56
T2L160 MA 80
840
A75
TA450SU60
40
60
60
45
67
T2L160 MA 80
960
A95
TA450SU80
55
80
80
55
82
T2L160 MA 100
1200
A145
TA450SU105
70
105
100
75
110
1440
A145
E200DU200
60
200
145
90
132
1875
A185
E200DU200
60
200
170
110
158
2125
A210
E320DU320
100
320
210
132
192
2720
A260
E320DU320
100
320
220
160
230
3200
A300
E320DU320
100
320
280
200
279
3600
AF400
E500DU500
150
500
400
250
335
4725
AF460
E500DU500
150
500
430
290
394
5040
AF580
E500DU500***
150
500
430
315
440
6300
AF750
E500DU500***
150
500
500
355
483
6300
AF750
E500DU500***
150
500
500
3/16
ABB SACE
Motor protection
DOL Type 2 - Heavy duty
MCCB
Rated
Power
Rated
current
Pe
Ie
Type
Contactor
Setting of
the magnetic
release
Type
Thermal release
Type**
Group
No. of
Current
turns of
setting
the CT
primary min max
coil
[A]
[A]
[A]
I max
[kW]
[A]
0.37
0.6
T2L160 MF1
13
A9
TA25DU0.63(X)
0.4
0.55
0.9
T2L160 MF1
13
A9
TA25DU1(X)
0.63
0.75
1.1
T2L160 MF1.6
21
A9
TA25DU1.4(X)
1.4
1.4
1.1
1.6
T2L160 MF1.6
21
A9
TA25DU1.8(X)
1.3
1.8
1.6
1.5
T2L160 MF2.5
33
A9
TA25DU2.4(X)
1.7
2.4
2.4
2.2
2.9
T2L160 MF3.2
42
A9
TA25DU3.1 *(X)
2.2
3.1
3.1
3.8
T2L160 MF4
52
A9
TA25DU4 *(X)
2.8
T2L160 MF5
65
A9
TA25DU5 *(X)
3.5
4.5
6.5
6.5
8.5
(X)
0.63
[A]
0.63
T2L160 MF6.5
84
A9
TA25DU6.5 *
150
A95
TA450SU60
7**
5.7
8.6
150
A95
TA450SU60
5**
12
12
13
200
A95
TA450SU60
4**
10
15
15
5.5
6.5
7.5
8.8
11
15
18
250
A95
TA450SU60
3**
13
20
20
18.5
21
300
A95
TA450SU80
18
27
27
22
25
350
A95
TA450SU60
20
30
30
30
33
450
A145
TA450SU80
27.5
40
40
37
41
550
A145
TA450SU60
40
60
60
45
49
700
A145
TA450SU60
40
60
60
55
60
800
A145
TA450SU80
55
80
80
75
80
1120
A145
TA450SU105
70
105
105
105
90
95
1280
A145
TA450SU105
70
105
110
115
1625
A185
TA450SU140
95
140
140
132
139
2000
A210
E320DU320
105
320
210
160
167
2250
A210
E320DU320
105
320
210
200
202
2720
A260
E320DU320
105
320
220
250
242
3400
AF400
E500DU500
150
500
350
290
301
4410
AF400
E500DU500
150
500
350
315
313
4410
AF460
E500DU500
150
500
400
355
370
5355
AF580
E500DU500***
150
500
430
* Type 1 coordination
** Cable cross section= 4 mm2
*** No mounting kit to contactor is available; to use mounting kit provide E800DU800
(X) Provide a by-pass contactor of the same size during motor start-up.
ABB SACE
3/17
Motor protection
Star-delta - Type 2
MCCB
Thermal release
Im [A]
delta
type
star
type
Pe [kW]
Ie [A]
18.5
36
T2N160 MA52
469
A50
A50
A26
TA75DU25
18-25
22
42
T2N160 MA52
547
A50
A50
A26
TA75DU32
22-32
30
56
T2N160 MA80
720
A63
A63
A30
TA75DU42
29-42
37
68
T2N160 MA80
840
A75
A75
A30
TA75DU52
36-52
45
83
T2N160 MA100
1050
A75
A75
A30
TA75DU63
45-63
Type
Contactor
line
type
type
[A]
55
98
T2N160 MA100
1200
A75
A75
A40
TA75DU63
45-63
75
135
T3N250 MA160
1700
A95
A95
A75
TA110DU90
66-90
90
158
T3N250 MA200
2000
A110
A110
A95
TA110DU110
80-110
110
193
T3N250 MA200
2400
A145
A145
A95
TA200DU135
100-135
132
232
2880
A145
A145
A110
E200DU200
60-200
160
282
3600
A185
A185
A145
E200DU200
60-200
200
349
4410
A210
A210
A185
E320DU320
100-320
250
430
5670
A260
A260
A210
E320DU320
100-320
290
520
6300
AF400
AF400
A260
E500DU500
150-500
315
545
7200
AF400
AF400
A260
E500DU500
150-500
355
610
8000
AF400
AF400
A260
E500DU500
150-500
MCCB
Thermal release
Im [A]
delta
type
star
type
Pe [kW]
Ie [A]
18.5
36
T2S160 MA52
469
A50
A50
A26
TA75DU25
18-25
22
42
T2S160 MA52
547
A50
A50
A26
TA75DU32
22-32
30
56
T2S160 MA80
720
A63
A63
A30
TA75DU42
29-42
37
68
T2S160 MA80
840
A75
A75
A30
TA75DU52
36-52
45
83
T2S160 MA100
1050
A75
A75
A30
TA75DU63
45-63
3/18
Type
Contactor
line
type
type
[A]
55
98
T2S160 MA100
1200
A75
A75
A40
TA75DU63
45-63
75
135
T3S250 MA160
1700
A95
A95
A75
TA110DU90
66-90
90
158
T3S250 MA200
2000
A110
A110
A95
TA110DU110
80-110
110
193
T3S250 MA200
2400
A145
A145
A95
TA200DU135
100-135
132
232
2880
A145
A145
A110
E200DU200
60-200
160
282
3600
A185
A185
A145
E200DU200
60-200
200
349
4410
A210
A210
A185
E320DU320
100-320
250
430
5670
A260
A260
A210
E320DU320
100-320
290
520
6300
AF400
AF400
A260
E500DU500
150-500
315
545
7200
AF400
AF400
A260
E500DU500
150-500
355
610
8000
AF400
AF400
A260
E500DU500
150-500
ABB SACE
Motor protection
Star-delta - Type 2
MCCB
Type
Contactor
Thermal release
Im [A]
line
type
delta
type
star
type
Pe [kW]
Ie [A]
type
[A]
18.5
32
T2H160 MA52
392
A50
A50
A16
TA75DU25
18-25
22
38
T2H160 MA52
469
A50
A50
A26
TA75DU25
18-25
30
52
T2H160 MA80
720
A63
A63
A26
TA75DU42
29-42
37
63
T2H160 MA80
840
A75
A75
A30
TA75DU42
29-42
45
75
T2H160 MA80
960
A75
A75
A30
TA75DU52
36-52
55
90
T2H160 MA100
1150
A75
A75
A40
TA75DU63
45-63
75
120
1625
A95
A95
A75
TA80DU80
60-80
90
147
1875
A95
A95
A75
TA110DU110
80-110
110
177
2250
A145
A145
A95
E200DU200
60-200
132
212
2720
A145
A145
A110
E200DU200
60-200
160
260
3200
A185
A185
A145
E200DU200
60-200
200
320
4095
A210
A210
A185
E320DU320
100-320
250
410
5040
A260
A260
A210
E320DU320
100-320
290
448
5670
AF400
AF400
A260
E500DU500
150-500
315
500
6300
AF400
AF400
A260
E500DU500
150-500
355
549
7200
AF400
AF400
A260
E500DU500
150-500
Im [A]
line
type
delta
type
star
type
MCCB
Thermal release
Pe [kW]
Ie [A]
18.5
32
T2L160 MA52
392
A50
A50
A16
TA75DU25
18-25
22
38
T2L160 MA52
469
A50
A50
A26
TA75DU25
18-25
30
52
T2L160 MA80
720
A63
A63
A26
TA75DU42
29-42
37
63
T2L160 MA80
840
A75
A75
A30
TA75DU42
29-42
45
75
T2L160 MA80
960
A75
A75
A30
TA75DU52
36-52
55
90
T2L160 MA100
1150
A75
A75
A40
TA75DU63
45-63
75
120
1625
A95
A95
A75
TA80DU80
60-80
90
147
1875
A95
A95
A75
TA110DU110
80-110
110
177
2250
A145
A145
A95
E200DU200
60-200
132
212
2720
A145
A145
A110
E200DU200
60-200
160
260
3200
A185
A185
A145
E200DU200
60-200
200
320
4095
A210
A210
A185
E320DU320
100-320
250
410
5040
A260
A260
A210
E320DU320
100-320
290
448
5670
AF400
AF400
A260
E500DU500
150-500
315
500
6300
AF400
AF400
A260
E500DU500
150-500
355
549
7200
AF400
AF400
A260
E500DU500
150-500
ABB SACE
Type
Contactor
type
[A]
3/19
Motor protection
Star-delta - Type 2
MCCB
Thermal release
Im [A]
delta
type
star
type
Pe [kW]
Ie [A]
22
34
T2L160 MA52
430
A50
A50
A16
TA75DU25
18-25
30
45
T2L160 MA52
547
A63
A63
A26
TA75DU32
22-32
37
56
T2L160 MA80
720
A75
A75
A30
TA75DU42
29-42
45
67
T2L160 MA80
840
A75
A75
A30
TA75DU52
36-52
55
82
T2L160 MA100
1050
A75
A75
A30
TA75DU52
36-52
75
110
1375
A95
A95
A50
TA80DU80
60-80
90
132
1750
A95
A95
A75
TA110DU90
65-90
110
158
2000
A110
A110
A95
TA110DU110
80-110
132
192
2560
A145
A145
A95
E200DU200
60-200
160
230
2880
A145
A145
A110
E200DU200
60-200
200
279
3400
A210
A210
A145
E320DU320
100-320
250
335
4410
A210
A210
A185
E320DU320
100-320
290
394
5040
A260
A260
A210
E320DU320
100-320
315
440
5760
AF400
AF400
A210
E500DU500
150-500
355
483
6300
AF400
AF400
A260
E500DU500
150-500
Type
Contactor
line
type
type
[A]
MCCB
Type
Contactor
TC
Thermal release
Im [A]
line
type
delta
type
star
type
KORC
Coils
type
[A]
5.5
6.5*
150
A95
A95
A26
4L185R/4**
13
TA25DU2.4**
6-8.5
7.5
8.8*
150
A95
A95
A26
4L185R/4**
10
TA25DU2.4**
7.9-11.1
11
13*
200
A95
A95
A26
4L185R/4**
TA25DU2.4**
11.2-15.9
15
18*
250
A95
A95
A26
4L185R/4**
TA25DU3.1**
15.2-20.5
18.5
21
300
A95
A95
A30
4L185R/4**
TA25DU3.1**
17.7-23.9
22
25
350
A95
A95
A30
4L185R/4**
TA25DU4**
21.6-30.8
30
33
450
A145
A145
A30
4L185R/4**
TA25DU5**
27-38.5
37
41
550
A145
A145
A30
TA75DU52**
36-52
45
49
650
A145
A145
A30
TA75DU52**
36-52
55
60
800
A145
A145
A40
TA75DU52**
36-52
75
80
1120
A145
A145
A50
TA75DU52
36-52
45-63
90
95
1280
A145
A145
A75
TA75DU63
110
115
1600
A145
A145
A75
TA75DU80
132
139
1875
A145
A145
A95
TA200DU110
160
167
2125
A145
A145
A110
TA200DU110
80-110
200
202
2720
A185
A185
A110
TA200DU135
100-135
250
242
3200
AF400
AF400
A145
E500DU500
150-500
290
301
4000
AF400
AF400
A145
E500DU500
150-500
315
313
4410
AF400
AF400
A185
E500DU500
150-500
355
370
5040
AF400
AF400
A210
E500DU500
150-500
400
420
5670
AF460
AF460
A210
E500DU500
150-500
450
470
6300
AF460
AF460
A260
E500DU500
150-500
60-80
80-110
For further information about the KORC, please see the Brochure KORC 1 GB 00-04 catalogue.
* Cable cross section = 4 mm2
** Connect the overload/relay upstream the line-delta mode.
3/20
ABB SACE
Motor protection
DOL Type 2 - Start-up with MP release
MCCB
Pe [kW]
Ie [A]
30
56
37
68
45
55
Type
Contactor
Group
I1* [A]
I3 [A]
type
I max [A]
40-100
600
A95
95
40-100
700
A95
95
83
40-100
800
A95
95
98
64-160
960
A145
145
75
135
64-160
1280
A145
145
90
158
80-200
1600
A185
185
110
193
128-320
1920
A210
210
132
232
128-320
2240
A260
260
160
282
128-320
2560
AF400**
320
200
349
160-400
3200
AF400
400
250
430
252-630
5040
AF460
460
290
520
252-630
5670
AF580
580
315
545
252-630
5670
AF580
580
355
610
252-630
5670
AF750
630
Contactor
Group
* For heavy-duty start set the electronic release tripping class to class 30
** In case of normal start use AF300
MCCB
Pe [kW]
Ie [A]
30
56
37
68
45
Type
I1* [A]
I3 [A]
type
I max [A]
40-100
600
A95
95
40-100
700
A95
95
83
40-100
800
A95
95
55
98
64-160
960
A145
145
75
135
64-160
1280
A145
145
90
158
80-200
1600
A185
185
110
193
128-320
1920
A210
210
132
232
128-320
2240
A260
260
160
282
128-320
2560
AF400**
320
200
349
160-400
3200
AF400
400
250
430
252-630
5040
AF460
460
290
520
252-630
5670
AF580
580
315
545
252-630
5670
AF580
580
355
610
252-630
5670
AF750
630
* For heavy-duty start set the electronic release tripping class to class 30
** In case of normal start use AF300
ABB SACE
3/21
Motor protection
DOL Type 2 - Start-up with MP release
MCCB
Pe [kW]
Ie [A]
30
52
37
63
45
Type
Contactor
Group
I1* [A]
I3 [A]
type
I max [A]
40-100
600
A95
93
40-100
700
A95
93
75
40-100
800
A95
93
55
90
64-160
960
A145
145
75
120
64-160
1120
A145
145
90
147
80-200
1400
A185
185
110
177
128-320
1920
A210
210
132
212
128-320
2240
A260
240
160
260
128-320
2560
AF400**
320
200
320
160-400
3200
AF400
400
250
370
252-630
4410
AF460
460
290
436
252-630
5040
AF460
460
315
500
252-630
5040
AF580
580
355
549
252-630
5670
AF580
580
Contactor
Group
* For heavy-duty start set the electronic release tripping class to class 30
** In case of normal start use AF300
MCCB
Pe [kW]
Ie [A]
30
45
37
56
45
67
Type
I1* [A]
I3 [A]
type
I max [A]
40-100
600
A95
80
40-100
600
A95
80
40-100
700
A145
100
55
82
40-100
800
A145
100
75
110
64-160
1120
A145
145
90
132
64-160
1280
A145
145
110
158
80-200
1600
A185
170
132
192
128-320
1920
A210
210
160
230
128-320
2240
A260
260
200
279
160-400
2800
AF400**
400
250
335
160-400
3200
AF400
400
290
395
252-630
5040
AF460
460
315
415
252-630
5040
AF460
460
355
451
252-630
5670
AF580
580
* For heavy-duty start set the electronic release tripping class to class 30
** In case of normal start use AF300
3/22
ABB SACE
Motor protection
DOL Type 2 - Start-up with MP release
MCCB
Pe [kW]
Ie [A]
45
49
55
60
75
90
Type
Contactor
Group
I1* [A]
I3 [A]
type
I max [A]
40-100
600
A145
100
40-100
600
A145
100
80
40-100
800
A145
100
95
64-160
960
A145
120
110
115
64-160
1120
A145
120
132
139
64-160
1440
A185
160
160
167
80-200
1600
A185
170
200
202
128-320
1920
A210
210
250
242
128-320
2240
A300
280
290
301
160-400
2800
AF400
350
315
313
160-400
3200
AF400
350
* For heavy-duty start set the electronic release tripping class to class 30
** In case of normal start use AF300
ABB SACE
3/23
Tabelle di coordinamento
Coordination
tables
Introduzione
Switch-disconnectors
ABB SACE
4/1
Switch-disconnectors
Notes for use
The following tables give the coordination between circuit-breakers and switchdisconnectors of the following series: Tmax, Isomax, OT and OTEL.
The tables give the value of the maximum short-circuit current in kA for which protection
between the combination of circuit-breaker - switch-disconnector is verified, for voltages
up to 415 V.
The MCCB-OT-OETL tables are also valid at a voltage of 440 V. It is important to check
that the breaking capacities at 440 V (present in the technical catalogues of the circuitbreakers) are compatible with the installation data.
With regard to the switch-disconnectors of the Emax series, on the other hand, it must
be checked that the short-circuit current value at the point of installation is lower than
the value of the short-time withstand current (Icw) of the switch-disconnector and that
the peak current value is lower than the making capacity current value (Icm).
The protection against overload of the Emax switch-disconnector must also be checked.
This can be carried out by means of an Emax series circuit-breaker of the same size.
Please consult the Emax Low Voltage air circuit-breakers technical catalogue for the
characteristics of Emax switch-disconnectors.
4/2
ABB SACE
Switch-disconnectors
Notes for use
Note
The letter T indicates the switch-disconnector protection up to the breaking-capacity
of the circuit-breaker.
The following tables give the breaking capacities at 415 V AC for Isomax and Tmax
circuit-breakers.
Isomax @ 415 V AC
Tmax @ 415 V AC
Version
Icu [kA]
Version
Icu [kA]
16
50
25
65
36
100
50
70
L (T2)
L (T4, T5)
85
120
L (T6)
100
200
Caption
MCS =
MCCB =
SD
=
OT
=
OETL =
Ith
=
Icw
=
switch-disconnectors derived from the moulded-case circuit-breakers (Tmax TD, Isomax SD)
moulded-case circuit-breakers (Tmax, Isomax)
switch-disconnectors
OT series switch-disconnectors
OETL series switch-disconnectors
traditional thermal current at 40 C in free air
short-time withstand current r.m.s. for 1 second
Caption of symbols
MCB
Tmax
Isomax
Emax
For solutions not shown in these tables, please consult the website:
http://bol.it.abb.com
or contact ABB SACE
ABB SACE
4/3
Switch-disconnectors
Supply side circuit-breaker: MCCB
Load side switch-disconnectors: MCS
MCCB - MCS @ 415 V
Supply s. Version
Load s.
T1D
T3D
T4D
T5D
T6D
S7D
Icw [kA]
3.6
3.6
15
25
160
250
320
400
630
630
800
1000
1250
1600
16
16
16
16
16
16
16
16
16
16
Ith[A]
Icu [kA]
Iu[A]
T1
T2
T3
T4
4
T5
T6
S7
16
25
25
25
25
25
25
25
25
25
25
25
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
50
50
50
50
50
50
50
50
50
50
50
70
70
70
70
70
70
70
70
70
70
70
85
85
85
85
85
85
85
85
85
85
85
36
36
36
36
36
36
36
36
36
36
50
50
50
50
50
50
50
50
50
50
36
36*
36
36
36
36
36
36
36
36
50
70
120
200
N
S
H
70
120
200
35
50
70
100
160
160
250
250
320
50*
50
50
50
50
50
50
50
50
70*
70
70
70
70
70
70
70
70
120*
120
120
120
120
120
120
120
120
200*
200
200
200
200
200
200
200
200
36
36*
36
36
36
36
36
36
50
50*
50
50
50
50
50
50
70*
70
70
70
70
70
70
120*
120
120
120
120
120
120
200*
200
200
200
200
200
200
35*
35*
35
35
35
50*
50*
50
50
50
70*
70*
70
70
70
100*
100*
100
100
100
50*
50*
50
65*
65*
65
100*
100*
100
50
65
100
400
630
630
800
1000
1250
1600
4/4
ABB SACE
Switch-disconnectors
Supply side circuit-breaker: MCCB
Load side switch-disconnectors: OT/OETL
MCCB - OT/OETL @ 415 V
Supply s. Release
T1
TM
Load s.
OT16
OT25
OT32
OT45
OT63
OT80
Icw[kA]
0.5
0.5
0.5
1.5
1.5
2.5
2.5
8 - 15
17 - 50
25
32
40
63
80
100
115
125
200
200-400
630 - 1600
16
20
20
20
20
20
25
18
18
32
18
18
40
4**
18
18
18
18
4**
18
18
6**
16
16
16**
In [A]
Ith [A]
50
4**
63
80
100
TM
16
160
16**
T**
16
20
20
20
50
20
14
14
14
36
25
12
12
12
25
70
70
32
12
12
12
25
70
70
40
12**
10
10
20
36
36
10**
10
20
36
36
10**
20
36
36
50
80
7**
16
16
50
50
16
50
50
125
16
50
50
160
16**
50**
50
T
T
25
10
10
10
16
50
50
63
8*
8*
8*
12
30
30
8*
8*
6*
16*
16
50
50
6*
16*
16*
50*
50
25
25
24
24
8**
21
21
8**
20
20
40
18
36
18**
36
36
100
63
3,5**
80
5**
100
TM
16**
160
T3
125
160
18**
200
250
20
32
6**
50
T4
TM
80
100
20
12
40
40
6**
12
40
40
8**
16
16
50
50
10
19
20
100
100
10**
19
20
100
100
20**
100
100
20*
100*
100*
10**
160
250
EL
OT200-400 OETL630-1600
16
100
EL
OT160
125
63
T2
OT100 OT125
100-320
10*
10*
19*
Select the lowest value between the Icu of the circuit-breaker and the value indicated
* Maximum setting of the overload threshold PR2xx = 1.28*Ith OTxx/OETLxx
** I1 = 0.7 x I
ABB SACE
4/5
Switch-disconnectors
Supply side circuit-breaker: MCCB
Load side circuit-breaker: OT/OETL
MCCB - OT/OETL @ 415 V
Load s.
OT
200
OT
250
OT
315
OT
400
OETL
630
OETL
800
OETL
1000
OETL
1250
OETL
1600
Icw[kA]
15
15
17
17
50
50
50
200
250
315
400
630
800
1000
1250
1600
Ith [A]
Supply s. Release Iu [A]
TM
T5
T6
EL
TM
EL
320
50
50
100
100
400
50**
50
100
100
320-630
50*
50*
100*
100
25
30
70
70
28**
60**
60
630
800
630-800-1000
22*
22*
28*
1000
S7
EL
1250
1600
20*
60
60
30*
30
50
50
50
30*
30*
50
50
50
30*
30*
50*
50*
50
Select the lowest value between the Icu of the circuit-breaker and the value indicated
* Maximum setting of the overload threshold PR2xx = 1.28*Ith OTxx/OETLxx
** I1 = 0.7 x I
4/6
ABB SACE
Coordination tables
L.V. Breakers
Via Baioni, 35
24123 Bergamo, Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com
Coordination tables
1SDC007004D0204 - 12/2004
Printed in Italy
Tipografia
1SDC007004D0204