Building Inspection Report: Sample
Building Inspection Report: Sample
136 236
www.qbpr.com.au This Report is produced for the clients use only. QBPR and the consultant are not liable for any reliance placed on the report by any third party. The Report is not to be reproduced for any third party under any circumstances.
No
RESULTS OF INSPECTION
IMPORTANT NOTE: The Client acknowledges that, unless stated otherwise, the Client as a matter of urgency should implement any recommendation or advice given in this Report. The Summary is not the Report. The following Report must be read in full in conjunction with this Summary. If there is a discrepancy between the information provided in this Summary and that contained within the body of the Report, the information in the body of the Report shall override this Summary.
SUMMARY OF FINDINGS
1. ON THE DAY OF INSPECTION THE PROPERTY WAS FOUND TO BE IN AN AVERAGE CONDITION FOR A PROPERTY OF ITS AGE & TYPE. SIGNIFICANT DEFECTS WERE DETECTED TO THE PROPERTY, PLEASE READ THIS SUMMARY IN CONJUNCTION WITH THE BODY OF THE REPORT.
2.
STRUCTURAL DEFECTS WERE DETECTED ON THE DAY OF INSPECTION. SEE ITEM 3.1 -STRUCTURAL DAMAGE IN THE DEFECTS ASSESSMENT FOR FURTHER DETAILS.
3.
CONDITIONS CONDUCIVE TO STRUCTURAL DAMAGE WERE DETECTED ON THE DAY OF INSPECTION. SEE ITEM 3.2 -CONDITIONS CONDUCIVE TO STRUCTURAL DAMAGEIN THE DEFECTS ASSESSMENT FOR FURTHER DETAILS.
4.
DEFECTS TO THE SECONDARY & FINISHING ELEMENTS OF THE PROPERTY WERE DETECTED ON THE DAY OF INSPECTION. SEE ITEM 3.3 -SIGNIFICANT DEFECTS / SECONDARY & FINISHING ELEMENTS- IN THE DEFECTS ASSESSMENT FOR FURTHER DETAILS.
5.
BRICK WEEP HOLES SHOULD ALWAYS BE KEPT CLEAR OF EARTH, CONCRETE AND VEGETATION AS THIS PROVIDES AN ENTRY POINT FOR MOISTURE TO ENTER STRUCTURAL WALL FRAMES AND UNDETECTED TERMITE ENTRY, RECOMMEND 75MM CLEARENCE. REFER TO TIMBER PEST INSPECTION REPORT.
6.
RECOMMEND THE INSTALLATION OF A SURFACE DRAINAGE SYSTEM TO AID IN THE REMOVAL OF EXCESS SURFACE WATER AWAY FROM THE BUILDING FOOTINGS / FOUNDATIONS. RECOMMEND SEEKING FURTHER ADVICE FROM A LICENSED & PRACTICING PLUMBER. ALL SURFACE WATER SHOULD BE DIVERTED AWAY FROM HOUSE FOOTINGS / FOUNDATIONS. REFER TO ATTACHED CSIRO INFORMATION SHEET.
Copyright
Page 2
7.
CRACKING WAS DETECTED TO SECTIONS OF CONCRETE PATHWAYS & OR DRIVEWAY. THIS IS A COMMON ISSUE WITH A LARGE PERCENTAGE OF HOMES AND CAN BE CAUSED BY MANY DIFFERING FACTORS INCLUDING POOR GROUND PREPARATION, INADEQUATE STEEL REINFORCING ETC. REPAIRS ARE NOT CONSIDERED ESSENTIAL, MONITOR FOR FURTHER CHANGES.
8.
EXTERNAL OF THE HOUSE REQUIRES AN OVERALL MAINTENANCE PROGRAM. STRONGLY RECOMMEND THE IMPLEMENTATION OF AN ONGOING MAINTENANCE PROGRAM FOR THE PROPERTY. REFER TO THE GENERAL MAINTENANCE TIP SHEET ATTACHED TO THIS REPORT.
9.
THIS REPORT IS LIMITED TO THE AGREED SERVICE REQUESTED. FOR ALL OTHER ASPECTS PERTAINING TO THE PROPERTY YOU WILL REQUIRE CONSULTATION WITH RELEVANT EXPERTS PRIOR TO SETTLEMENT. THESE ASPECTS MAY INCLUDE, BUT ARE NOT LIMITED TO, FIRE AND SEGREGATION, EGRESS, DISABLED ACCESS, PLUMBING, ELECTRICAL, STRUCTURAL DESIGN, LICENSING, TOWN PLANNING, OCCUPATIONAL HEALTH AND SAFETY, REGULATORY COMPLIANCE. NO INSPECTION TO SEPTIC, GREASE TRAPS, PUMP SYSTEMS, TANKS ETC. AS PER AUSTRALIAN STANDARDS.
10. RECOMMEND CLIENT OR CLIENTS SOLICITOR MAKE THE NECESSARY ENQUIRIES WITH THE LOCAL COUNCIL INTO THE LEGALITY OF ANY STRUCTURE OR ADDITIONS ON THE PROPERTY. THE BUILDING REPORT SHOULD BE READ IN CONJUNCTION WITH THE TIMBER PEST REPORT. ALL NOTES AND RECOMMENDATIONS BY BUILDING AND PEST REPORTS SHOULD BE ADDRESSED PRIOR TO THE CONTRACT BECOMING BINDING. In conclusion, following the inspection of the surface work in the Readily Accessible Areas of the property, the overall condition of the building on the day of the inspection in the context of the average condition of a similar building of approximately the same age was considered: Above Average Condition Average Condition Below Average Condition
Copyright
Page 3
1.0
Area/s*NOT Inspected and/or Area/s* to which REASONABLE ACCESS for Inspection was NOT AVAILABLE and the reason/s why. These include Area/s* in which Visual Inspection was Obstructed or Restricted: (See also Clause A.2) Roof void because
VISUAL INSPECTION TO SOME TIMBERS IN THE ROOF VOID WERE OBSTRUCTED DUE TO THE DESIGN OF THE ROOF. VEGETATION. FLOOR COVERINGS, FURNITURE AND STORED GOODS. VISUAL INSPECTION LIMITED DUE TO STORAGE. VEGETATION & FOLIAGE.
2.0 GENERAL
2.1 Brief description of the building and other structures on the property:
Type: Townhouse Height: Highset Building: Weather-board Metal Sheeting Piers: Steel Floor: Chipboard Roof: FC Sheeting Domestic
Other
Apartment/Unit/Flat Split Level Concrete Block Aluminium Timber Multistorey Stone Cladding Stone Timber Aluminium Yes Fine Yes No Raining No
Single Storey
Other
Timber with Concrete Areas Timber with Hardboard Areas Metal Iron
2.2 Was the property furnished at the time of inspection? 2.3 Weather on day of inspection? 2.4 Were Smoke Detectors fitted on the day of inspection?
2.5
Was a safety switch installed? Yes No Note: Only a licenced and practicing Electrical Contractor can verify the adequacy of the installation as a visual inspection can not assess this.
Was the inspection limited to assessing the interior and immediate exterior of a particular unit? Yes No
Note. NO INSPECTION TO COMMON PROPERTY AS PER AUSTRALIAN STANDARDS. MATTERS IN RELATION TO COMMON PROPERTY REQUIRE FURTHER INVESTIGATION THROUGH BODY CORPORATE. STRONGLY RECOMMEND CLIENTS SOLICITOR MAKE THE NECESSARY ENQUIRIES RELATING TO THE TYPE OF BODY CORPORATE TITLE WHICH PERTAINS TO THIS PROPERTY AS THIS WILL HAVE A BEARING ON REPAIRS/ MAINTENANCE RESPONSIBILITIES, BEFORE CONTRACT BECOMING BINDING
2.6
Copyright
Page 4
Structural Cracking and Movement: YES - SEE COMMENTS BELOW AND CLAUSE A.3
Details (for example) the location and any recommendations for further expert advice e.g. from a licenced specialist contractor:
1. CRACKING / MOVEMENT WAS DETECTED TO BRICKWORK / MASONRY WALLS TO THE REAR & RIGHT HAND SIDES. DUE TO THE SIZE OF THIS CRACKING / MOVEMENT, THE ISSUE REQUIRES A LICENSED AND SUITABLY EXPERIENCED STRUCTURAL ENGINEER TO FURTHER INVESTIGATE THIS MATTER. PLEASE READ THE ATTACHED INFORMATION FROM CSIRO THAT CLASSIFIES THESE CRACKS / MOVEMENT AS CATEGORY 3 & 4. THE ABOVE RECOMMENDATION(S) SHOULD BE IMPLEMENTED AS A MATTER OF IMPORTANCE
2.
3.2
Was evidence of building deficiencies or environmental factors that may contribute to the occurrence of Structural Damage observed, or revealed and/or confirmed under test conditions?
Defective Plumbing / Drainage: YES - SEE COMMENTS BELOW AND CLAUSE A.3 Roof Plumbing and Flashings: YES - SEE COMMENTS BELOW AND CLAUSE A.3 Tree Roots: YES - SEE COMMENTS BELOW AND CLAUSE A.3 Other: YES - SEE COMMENTS BELOW AND CLAUSE A.3
Details (for example) the location and any recommendations for further expert advice e.g. from a licenced specialist contractor:
1. EVIDENCE OF DAMPNESS / PONDING WATER TO REAR & RIGHT HAND SIDES. ALL SURFACE WATER SHOULD BE DIVERTED AWAY FROM HOUSE FOOTINGS / FOUNDATIONS. REFER TO ATTACHED CSIRO INFORMATION SHEET. RECOMMEND A SUITABLY LICENSED AND PRACTICING PLUMBER TO FURTHER INVESTIGATE THE MOST APPROPRIATE METHOD OF RECTIFICATION AND PROBABLE COSTS OF RECTIFICATION WORKS. STRONGLY RECOMMEND REFIXING LOOSE / BROKEN TILE PIECES TO THE ROOF VALLEY GUTTER AREA. THIS SHOULD BE REPAIRED AS A MATTER OF URGENCY AS WATER PENETRATION INTO THE ROOF VOID CAN CAUSE DAMAGE TO THE ROOF FRAMWORK AND INTERNAL CEILING LINING. RECOMMEND SEEKING FURTHER ADVICE FROM A LICENSED & PRACTICING ROOF TILER. MATURE TREES LOCATED IN CLOSE PROXIMITY TO THE BUILDING. HAVING TREES CLOSE TO THE BUILDING CAN LEAD TO PROBLEMS SUCH AS LEAVES BLOCKING GUTTERS AND DOWNPIPES, TREES FALLING ONTO THE HOUSE, AND TREE ROOTS UNDERMINING THE BUILDING FOOTINGS & PLUMBING SERVICES. RECOMMEND ENGAGING A SUITABLE QUALIFIED AND EXPERIENCED ARBORIST (TREE SPECIALIST) TO ADVISE ON THE MOST APPROPRIATE METHOD OF RECTIFICATION AND ASSOCIATED COSTS OF RECTIFICATION. RECOMMEND TO DIVERT HOT WATER SYSTEM / AIR CONDITIONER OVERFLOW AWAY FROM BUILDING FOUNDATIONS. REFER TO TIMBER PEST REPORT. THE ABOVE RECOMMENDATION(S) SHOULD BE IMPLEMENTED AS A MATTER OF IMPORTANCE
2.
3.
4.
5. 6.
Copyright
Page 5
3.3 Defects in the Condition of the Secondary and Finishing Elements of the Construction (See also Clause A.3)
Was evidence of any Defect (i.e. a matter, in view of the age and type of the building being inspected, requires substantial repairs or urgent attention and rectification) in the general condition of Secondary Elements and Finishing Elements observed, or revealed an/or confirmed under test conditions? Yes No Details (for example) the location and any recommendations for further expert advice e.g. from a licenced specialist contractor:
1. DRUMMY TILE SECTIONS TO LOUNGE & HALLWAY, THIS MAY BE THE RESULT OF POOR GLUE COVERAGE OR SEPARATION OF THE TILE FROM THE CEMENT BED. EXTENSIVE EVIDENCE OF CRACKING AND LIFTING OF TILES WAS DETECTED AND REPAIRS ARE RECOMMENDED. RECOMMEND SEEKING FURTHER ADVICE FROM A LICENSED & PRACTICING WALL & FLOOR TILER. POPPING NAILS TO FIXING POINTS IN CEILING LININGS WERE DETECTED. MOVEMENT CRACKING DETECTED TO CEILING SHEETING IN HALLWAY. RECOMMEND TO INSTALL EXPANSION JOINT. REFIXING, PATCHING & PAINTING WILL IMPROVE DEFECT NOTED. RECOMMEND SEEKING FURTHER ADVICE FROM A LICENSED & PRACTICING PLASTERER / GYPROCKER. FRONT / ENTRY DOOR IS BINDING ON TOP / SIDE JAMB AND REQUIRES EASING. EXTERNAL FACE OF DOOR IS DELAMINATING / LIFTING OFF. REPAIRS REQUIRED, RECOMMEND SEEKING FURTHER ADVICE FROM A LICENSED & PRACTICING CARPENTER. ALUMINIUM SLIDING DOOR ROLLERS (THROUGHOUT) REQUIRE MAINTENANCE, HEAVY TO SLIDE. REFER TO GENERAL MAINTENANCE TIP SHEET. TIMBER DECKING REQUIRES GENERAL MAINTANENCE / REPAIRS. LOOSE BOARDS REQUIRE REFIXING AND RAISED NAIL HEADS REQUIRE PUNCHING BELOW THE SURFACE. TIMBER TREATMENT RECOMMENDED TO PREVENT DECAY. RECOMMEND SEEKING FURTHER ADVICE FROM A LICENSED & PRACTICING CARPENTER.
2.
3.
4.
5.
In conclusion, following the inspection of the surface work in the Readily Accessible Areas of the property, the overall condition of the building on the day of the inspection in the context of the average condition of a similar building of approximately the same age was considered: Above Average Condition Average Condition Below Average Condition
For further important information including advice on the implementation of a preventative maintenance programme see: (Clause A.3 Important Note).
Copyright
Page 6
5.0 CERTIFICATION
This document certifies that the property described in this Report has been inspected by the Building Consultant in accordance with the level of service requested by the Client and the Terms and Conditions set out in Clause A.1 of this Report, and in strict accordance with the current edition of the Report Systems Australia (RSA) Handbook Standard Property Inspection Reports Residential Buildings Uniform Inspection Guidelines for Building Consultants. COMPANY NAME: NAME OF CONSULTANT: STREET ADDRESS: SUBURB: POST CODE: PHONE: FAX: AUTHORISED SIGNATORY: DATE OF ISSUE: P O BOX 118 HELENSVALE PLAZA QLD 4212 136 236 (Freecall) 1300 135 356 QUEENSLAND BUILDING & PEST REPORTS
DON JURY
05/03/2007
Copyright
Page 7
If the Client has any doubt about the Scope of this Report please discuss your concerns with the Consultant on receipt of the Report. The Client acknowledges that, unless stated otherwise, the Client as a matter of urgency should implement any recommendation or advice given in this Report.
LIMITATIONS
The Client acknowledges: 1. 2. 3. 4. Visual only inspections are not recommended. A visual only inspection may be of limited use to the Client. In addition to a visual inspection, to thoroughly inspect the Readily Accessible Areas of the property requires the Consultant to carry out when ever necessary appropriate Tests. This Report does not include the inspection and assessment of items or matters outside the scope of the requested inspection and report. Other items or matters may be the subject of a Special-Purpose Inspection Report, which is adequately specified (see Exclusions below). This Report does not include the inspection and assessment of items or matters that do not fall within the Consultants direct expertise. The inspection only covered the Readily Accessible Areas of the property. The inspection did not include areas, which were inaccessible, not readily accessible or obstructed at the time of inspection. Obstructions are defined as any condition or physical limitation which inhibits or prevents inspection and may include but are not limited to roofing, fixed ceilings, wall linings, floor coverings, fixtures, fittings, furniture, clothes, stored articles/materials, thermal insulation, sarking, pipe/duct work, builders debris, vegetation, pavements or earth. Australian Standard Inspection of Buildings. Part 1: Property Inspections Residential Buildings recognises that a standard property inspection report is not a warranty or an insurance policy against problems developing with the building in the future. This Report was produced for the use of the Client. The Consultant is not liable for any reliance placed on this report by any third party.
5. 6.
EXCLUSIONS
The Client acknowledges that this Report does not cover or deal with: any minor fault or defect, i.e. a matter, in view of the age, type and condition of the building being inspected, does not require substantial repairs or urgent attention and rectification; (ii) solving or providing costs for any rectification or repair work; (iii) the structural design or adequacy of any element of construction; (iv) detection of wood destroying insects such as termites and wood borers; (v) the operation of fireplaces and chimneys; (vi) any services including building, engineering (electronic), fire and smoke detection or mechanical; (vii) any swimming pools and associated pool equipment or spa baths and spa equipment or the like; (viii) any appliances such as dishwashers, insinkerators, ovens, stoves and ducted vacuum systems; (ix) a review of occupational, health or safety issues such as asbestos content, or the provision of safety glass or swimming pool fencing; (x) a review of environmental or health or biological risks such as toxic mould; (xi) whether the building complies with the provision of any building act, code regulation(s) or by-laws; and (xii) whether the ground on which the building rests has been filled, is liable to subside, swell or shrink, is subject to landslip or tidal inundation, or if it is flood prone. Any of the above matters may be the subject of a special-purpose inspection report, which is adequately specified and undertaken by an appropriately qualified inspector. (i)
DEFINITIONS
Primary Elements means those parts of the building providing the basic loadbearing capacity to the Structure, such as foundations, footings, floor framing, loadbearing walls, beams or columns. The term Primary Elements also includes other structural building elements including: those that provide a level of personal protection such as handrails; floor-to-floor access such as stairways; and the structural flooring of the building such as floorboards. Secondary Elements means those parts of the building not providing loadbearing capacity to the Structure, or those non-essential elements which, in the main, perform a completion role around openings in Primary Elements and the building in general such as nonloadbearing walls, partitions, wall linings, ceilings, chimneys, flashings, windows, glazing or doors. Finishing Elements means the fixtures, fittings and finishes applied or affixed to Primary Elements and Secondary Elements such as baths, water closets, vanity basins, kitchen cupboards, door furniture, window hardware, render, floor and wall tiles, trim or paint. The term Finishing Elements does not include furniture or soft floor coverings such as carpet and lino. Structure means the loadbearing part of the building, comprising the Primary Elements.
Copyright
Page 8
Structural Damage means a significant impairment to the integrity of the whole or part of the Structure falling into one or more of the following categories: (a) Structural Cracking and Movement major (full depth) cracking forming in Primary Elements resulting from differential movement between or within the elements of construction, such as foundations, footings, floors, walls and roofs. (b) Deformation an abnormal change of shape of Primary Elements resulting from the application of load(s). (c) Dampness the presence of moisture within the building, which is causing consequential damage to Primary Elements. (d) Structural Timber Pest Damage structural failure, i.e. an obvious weak spot, deformation or even collapse of timber Primary Elements resulting from attack by one or more of the following wood destroying agents: chemical delignification; fungal decay; wood borers; and termites. Conditions Conducive to Structural Damage means noticeable building deficiencies or environmental factors that may contribute to the occurrence of Structural Damage. Significant Defect means a matter, in view of the age and type of the building being inspected, requires substantial repairs or urgent attention and rectification. Client means the person or persons, for whom the Inspection Report was carried out or their Principal (i.e. the person or persons for whom the report is being obtained). Building Consultant means a person, business or company who is qualified and experienced to undertake a Standard Property Inspection Report in accordance with Australian Standard AS 4349. Inspection of Buildings. Part 1: Property Inspections Residential Buildings. The consultant must also meet any Government licensing requirement, where applicable. Readily Accessible Areas means areas which can be easily and safely inspected without injury to person or property, are up to 3.6 metres above ground or floor levels, in roof spaces where the minimum area of accessibility is not less than 600 mm high by 600 mm wide and subfloor spaces where the minimum area of accessibility is not less than 400 mm high by 600 mm wide, providing the spaces or areas permit entry. Or where these clearances are not available, areas within the consultants unobstructed line of sight and within arms length. Tests means where appropriate the carrying out of tests using the following procedures and instruments: (a) (b) Dampness Tests means additional attention to the visual examination was given to those accessible areas which the consultants experience has shown to be particularly susceptible to damp problems. Instrument testing using an electronic moisture detecting meter of those areas and other visible accessible elements of construction showing evidence of dampness was performed. Physical Tests means the following physical actions undertaken by the consultant: opening and shutting of doors, windows and draws; operation of taps; water testing of shower recesses; and the tapping of tiles and wall plaster.
A.2 ACCESSIBILITY
Unless specified in writing, the inspection only covered the Readily Accessible Areas of the property. The inspection did not include areas, which were inaccessible, not readily accessible or obstructed at the time of inspection. Areas, which are not normally accessible, were not inspected and include - but not limited to - the interior of a flat roof or beneath a suspended floor filled with earth. Building Interior The consultant did not move or remove any ceilings, wall coverings, floor coverings (including carpeting and wooden floorboards), furnishing, equipment, appliances, pictures or other household goods. In an occupied property, furnishings or household items may be concealing evidence of defects, which may only be revealed when the items are moved or removed. NOTE. In the case of strata and company title properties or other Class 2 buildings or equivalent, if the inspection was limited to assessing the interior of a particular unit or lot, the Client may have additional liability for defects in the common property. This additional liability can only be addressed through the undertaking of a special-purpose inspection report, which is adequately specified. Building Exterior, Roof Exterior and Site The consultant did not move or remove any obstructions such as wall cladding, awnings, trellis, earth, plants, bushes, foliage, stored materials, debris or rubbish, etc. Such items may be concealing defects, which may only be revealed when the items are moved or removed. Roof Space Obstructions such as roofing, stored articles, thermal insulation, sarking and pipe/duct work may be concealing evidence of defects, which may only be revealed when the obstructions are moved or removed. Also, bodily access should be provided to the interior of all accessible roof spaces. In accordance with Australian Standard As 4349 the minimum requirement is a 450 mm by 400 mm access manhole. Subfloor Space Storage of materials in subfloor areas is not recommended as it reduces ventilation and makes inspection difficult. Obstructions may be concealing evidence of defects, which may only be revealed when the obstructions are moved or removed. Bodily access should be provided to all accessible subfloor areas. In accordance with Australian Standard AS 4349 the minimum requirement is a 500 mm x 400 mm access manhole. In the case of suspended floors, if the clearance between the ground and structural components is less than 400 mm, then the ground should be excavated to provide the required clearance, subject to maintaining adequate drainage and support to footings. If the subfloor has been sprayed for subterranean termites or if the area is susceptible to mould growth, appropriate health precautions must be followed before entering the area. Also, special care should be taken not to disturb the treated soil. For further advice consult the person who carried out this report.
Copyright
Page 9
This additional information or advice may be the subject of a special-purpose inspection report, which is adequately specified and undertaken by an appropriately qualified inspector. In addition, this inspection and report does not include the inspection and assessment of items or areas that do not fall within the consultants expertise. Accordingly, consideration should be given to other specialist inspections and services such as: hydraulics; geotechnics; or building, engineering (electronic), fire and smoke detection or mechanical services. As a matter of course, in the interests of safety, an inspection and assessment of the electrical and plumbing/gas installations should be carried out by a suitably qualified person. Also, in all parts of mainland Australia, termites are a known problem to timber in service. Therefore, it is recommended that a timber pest inspection and report be carried out in accordance with the Report Systems Australia handbook Timber Pest Detection Reports. Where possible, the records of the appropriate local authority should be checked to determine or confirm: whether the ground on which the building rests has been filled, is liable to subside, is subject to landslip or tidal inundation, or if it is flood prone; the status of the property and services (e.g. compliance of the building with the provisions of any building Act, code, regulation or by-laws); and whether council has issued a building certificate or other notice for the dwelling.
Where appropriate, legal advice (e.g. from a solicitor) should be sought to explain title and ownership matters and to deal with matters concerning easements, covenants, restrictions, zoning certificates and all other law-related matters. This inspection report was produced for the use of the client. The building consultant is not liable for any reliance placed on the report by any third party. If you have any queries with this report or require further information, please do not hesitate to contact the consultant who carried out the inspection.
Copyright
Page 10
(2)
(3) (4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)