Analog Module Simatic S7-400
Analog Module Simatic S7-400
Analog modules
Overview
SIMATIC S7-400
Analog inputs for the SIMATIC S7-400 For connection of voltage and current sensors, thermocouples, resistors and resistance thermometers Resolution from 13 to 16 bit
5
Technical specifications
6ES7 431-0HH00-0AB0 Supply voltages Load voltage L+ Rated value (DC) 24 V; only required for supplying 2-wire transmitters Yes 24 V; only required for supplying 2-wire transmitters Yes not necessary 24 V; only required for supplying 2-wire transmitters Yes 200 mA 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0
reverse polarity protection Current consumption from load voltage L+ (without load), max. from backplane bus DC 5 V, max. Current consumption/ power loss Power loss, typ. Analog inputs Number of analog inputs Number of analog inputs for voltage/current measurement Number of analog inputs for resistance measurement cable length, shielded, max.
400 mA; for 16 connected, 200 mA; for 8 connected, fully controlled 2-wire trans- fully controlled 2-wire transmitters mitters 100 mA 1 000 mA 350 mA
600 mA
2W 16 16
4.9 W 8 8 4
1.8 W 8 8 4 200 m
200 m
200 m
Input ranges (rated values), voltages 1 to 5 V -1 V to +1 V -10 V to +10 V -2.5 V to +2.5 V -250 mV to +250 mV -5 V to +5 V -500 mV to +500 mV -80 mV to +80 mV Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
5/70
Siemens ST 70 2009
Siemens AG 2008
SIMATIC S7-400
Technical specifications (continued)
6ES7 431-0HH00-0AB0 Input ranges (rated values), currents 0 to 20 mA -20 to +20 mA 4 to 20 mA Input ranges (rated values), thermoelements Type B Type E Type J Type K Type L Type N Type R Type S Type T Type U Input ranges (rated values), resistance thermometers Ni 100 Ni 1000 Pt 100 Pt 1000 Pt 10000 Pt 200 Pt 500 Input ranges (rated values), resistors 0 to 150 Ohm 0 to 300 Ohm 0 to 48 Ohm 0 to 600 Ohm 0 to 6000 Ohm permissible input frequency for voltage input (destruction limit), max. 20 V; 20 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) 40 mA; Permanent 50 V Yes Yes Yes Yes Yes Yes Yes; usable up to 5000 ohms Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0
Analog modules
6ES7 431-1KF10-0AB0
permissible input current for 40 mA current input (destruction limit), max. Characteristic curve linearization programmable - for thermoelements - for thermoresistor Temperature compensation internal temperature compensation external temperature compensation with compensations socket external temperature compensation with Pt100 dynamic reference temperature value
50 mA; 40 mA continuous
Yes Type B, E, J, K, L, N, R, S, T, U Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 Yes Yes
No Yes
Siemens ST 70 2009
5/71
Siemens AG 2008
Analog modules
SIMATIC S7-400
additional conversiontime for resistance measurement additional conversiontime for wire break monitoring and resistance measurement Interference voltage suppression for interference frequency f1 in Hz Encoder Connection of signal encoders for current measurement as 2-wire transducer for current measurement as 4-wire transducer for resistance measurement with 2-conductor connection for resistance measurement with 3-conductor connection for resistance measurement with 4-conductor connection Errors/accuracies Operational limit in overall temperature range Voltage, relative to input area +/- 0,65 %; 1.0% at 1 to 5 V; 0.65% at +/-1 V, +/-10 V +/- 0,7 %; +/- 1 %; +/-0.7% at +/-1 V; +/-1.0% at +/-1 V; +/-0.9% at +/-10 V, 1 to 5 V +/-0.6% at +/-10 V; +/-0.7% at 1 to 5 V +/- 0,8 %; at +/-20 mA, 4 to 20 mA +/- 1 % +/- 1 %; at +/-20 mA, 4 to 20 mA Yes Yes Yes Yes; Line resistances are also measured Yes; Line resistances are also measured Yes Yes; with external transmitter supply Yes Yes; Line resistances are also measured Yes; Line resistances are also measured Yes 60 / 50 Hz none / 400 / 60 / 50 Hz 60 / 50 Hz
60 / 50 Hz
Yes Yes Yes; Line resistances are also measured Yes Yes
+/- 0,38 %; +/-0.38% at +/-80 mV; +/-0.35% at +/-250 mV, +/-500mV, +/-1 V, +/-2,5 V, +/-5 V, 1 to 5 V, +/-10 V +/- 0,35 %; 0 to 20 mA, +/-20 mA, 4 to 20 mA
+/- 0.65 %
Impedance, relative to input area Resistance-type thermometer, relative to input area Basic error limit (operational limit at 25 C) Voltage, relative to input area +/- 0,25 %; 0.5% at 1 to 5 V; 0.25% at +/-1 V, +/-10 V
+/- 1,25 %; 0 to 500 ohms +/- 0.5 % (4-conductor measurement, in range of 600 ohms) +/- 0.5 %
+/- 0,7 %; 0.7% at +/-1 V; 0.4% at +/-10 V; 0.5% at 1 to 5 V +/- 0,7 %; at +/- 20 mA, 4...20 mA
+/- 0,15 %; +/-0.15% (+/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V); +/-0.17% (+/- 80 mV); +/- 0,15 %; 0 to 20 mA, +/- 20 mA, 4 to 20 mA
5/72
Siemens ST 70 2009
Siemens AG 2008
SIMATIC S7-400
Technical specifications (continued)
6ES7 431-0HH00-0AB0 Basic error limit (operational limit at 25 C) Impedance, relative to input area +/- 0,7 %; 0 to 600 ohms +/- 0,8 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms) 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0
Analog modules
6ES7 431-1KF10-0AB0
+/- 0,15 %; +/-0.15% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 600 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.3% at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms) +/- 0.3 %
Resistance-type thermometer, relative to input area Isolation Isolation checked with 500 V DC between bus and 2120 V DC between bus local ground and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 2120 V DC between analog part and local ground
2120 V DC between bus and L+/M; 2120 V D between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground
Isolation Isolation, analog inputs Isolation, analog inputs between the channels Permissible potential difference between the inputs (UCM) Dimensions Required slots Dimensions Dimensions Width Height Depth Weights Weight, approx. 500 g 500 g 500 g 500 g 25 mm 290 mm 210 mm 25 mm 290 mm 210 mm 25 mm 290 mm 210 mm 25 mm 290 mm 210 mm 1 1 1 1 2 V DC / 2 Vpp AC 8 V AC 30 V AC 120 V AC No No Yes; internal/external No Yes; internal/external No Yes; internal/external No
Siemens ST 70 2009
5/73
Siemens AG 2008
Analog modules
SIMATIC S7-400
Power loss, typ. Analog inputs Number of analog inputs Number of analog inputs for voltage/current measurement Number of analog inputs for resistance measurement cable length, shielded, max. Input ranges (rated values), voltages 1 to 5 V -1 V to +1 V -10 V to +10 V -100 mV to +100 mV -2.5 V to +2.5 V -20 mV to +20 mV -25 mV to +25 mV -250 mV to +250 mV -5 V to +5 V -50 mV to +50 mV -500 mV to +500 mV -80 mV to +80 mV Input ranges (rated values), currents 0 to 20 mA -10 to +10 mA -20 to +20 mA -3.2 to +3.2 mA 4 to 20 mA -5 to +5 mA Input ranges (rated values), thermoelements Type B Type E Type J Type K Type L Type N Type R Type S Type T Type U
4.5 W 16 16 8
4.6 W 8 8
3.3 W 8
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Siemens ST 70 2009
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
5/74
Siemens AG 2008
SIMATIC S7-400
Technical specifications (continued)
6ES7 431-7QH00-0AB0 Input ranges (rated values), resistance thermometers Ni 100 Ni 1000 Pt 100 Pt 1000 Pt 200 Pt 500 Input ranges (rated values), resistors 0 to 150 Ohm 0 to 300 Ohm 0 to 48 Ohm 0 to 600 Ohm 0 to 6000 Ohm Yes Yes Yes Yes Yes; usable up to 5000 ohms 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) 32 mA 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) Yes Yes Yes Yes Yes Yes Yes Yes; Different characteristics selectable: Europe/U.S Yes Yes Yes Yes 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Analog modules
permissible input frequency for 18 V; 18 V continuous, voltage input (destruction 75 V for 1 ms limit), max. (mark to space ratio 1:20) permissible input current for 40 mA current input (destruction limit), max. Characteristic curve linearization programmable - for thermoelements - for thermoresistor Yes Type B, E, J, K, L, N, R, S, T, U Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000
Yes Type B, E, J, K, L, N, R, S, T, U
Yes Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000; different characteristics selectable (Europe/U.S.)
external temperature compen- Yes sation with compensations socket external temperature compensation with Pt100 dynamic reference temperature value Analog value creation Integration and conversion time/resolution per channel Resolution with overload area (bit including sign), max. Integration time, parameterizable Basic conversion time, ms 16 Bit; 16 / 16 / 16 Yes 2.5 / 16.7 / 20 ms 16 Bit Yes 2.5 / 16.7 / 20 / 100 16 Bit Yes 8 / 23 / 25 ms Yes Yes Yes
Siemens ST 70 2009
5/75
Siemens AG 2008
Analog modules
SIMATIC S7-400
400 / 60 / 50 Hz
400 / 60 / 50 / 10 Hz
none/ 60 / 50 Hz
Encoder Connection of signal encoders for current measurement as 2-wire transducer for current measurement as 4-wire transducer for resistance measurement with 2-conductor connection for resistance measurement with 3-conductor connection for resistance measurement with 4-conductor connection Errors/accuracies Operational limit in overall temperature range Voltage, relative to input area +/- 0,3 %; +/-0.3% at +/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V; +/-0.31% at +/-80 mV; +/-0.32% at +/-50 mV; +/-0.35% at +/-25 mV; +/- 0,3 %; at 0 to 20 mA, +/-5 mA, +/-10 mA, +/- 20 mA, 4 to 20 mA +/- 0,3 %; +/-0.3% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 600 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.4% at 0 to300 ohms (3conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms); +/- 0.4 % +/-1 C +/- 0.3 % Yes Yes Yes; Line resistances are also measured Yes Yes Yes Yes Yes Yes
+/- 0.5 %
Resistance-type thermometer, relative to input area Basic error limit (operational limit at 25 C) Voltage, relative to input area
+/- 0,15 %; +/-0.15% at +/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/-10 V; +/-0.17% at +/-80 mV; +/-0.19% at +/-50 mV; +/-0.23% at +/-25 mV; +/- 0,15 %; at 0 to 20 mA, +/-5 mA, +/-10 mA, +/- 20 mA, 4 to 20 mA
+/- 0.1 %
+/- 0.17 %
5/76
Siemens ST 70 2009
Siemens AG 2008
SIMATIC S7-400
Technical specifications (continued)
6ES7 431-7QH00-0AB0 Basic error limit (operational limit at 25 C) Impedance, relative to input area +/- 0,15 %; +/-0.15% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.3% at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms) +/- 0.3 % +/-0.2 C 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Analog modules
Resistance-type thermometer, relative to input area Status information/alarms/ diagnostics Alarms Diagnostic alarm Limit value alarm Diagnoses Diagnostics Isolation Isolation checked with
2120 V DC between bus and L+/M; 1500 V DC 2120 V D between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground
Isolation Isolation, analog inputs Isolation, analog inputs between the channels Permissible potential difference between the inputs (UCM) Dimensions Required slots Dimensions Dimensions Width Height Depth Weights Weight, approx. 500 g 650 g 650 g 25 mm 290 mm 210 mm 25 mm 290 mm 210 mm 25 mm 290 mm 210 mm 1 1 1 120 V AC 120 V AC none Yes; internal/external No Yes; internal/external Yes Yes; internal/external No
Siemens ST 70 2009
5/77
Siemens AG 2008
Analog modules
Ordering data
SIMATIC S7-400
Order No.
SM 431 analog output module 16 inputs, non-floating, 13 bit 8 inputs, floating, 13 bit 8 inputs, floating, 14 bit, with linearization 8 inputs, floating, 14 bit 16 inputs, floating, 16 bit, process interrupt capability 8 inputs, floating, 16 bit, process interrupt capability, for thermocouples (I, U) 8 inputs, floating, 16 bit, process interrupt capability, for temperature sensors Front connectors 48-pin with screw contacts, 1 item with screw contacts, 84 items with spring-loaded terminals, 1 item with crimp contacts, 1 item with crimp contacts, 84 items 1 unit; for 6ES7 431-7KF00-0AB0; spare part, included in scope of delivery SIMATIC TOP connect
B7
6ES7 492-2AX00-0AA0 6ES7 492-2BX00-0AA0 6ES7 492-2CX00-0AA0 6ES7 492-2DX00-0AA0 6ES7 998-8XC01-8YE0
6ES7 492-1AL00-0AA0 6ES7 492-1AL00-1AB0 6ES7 492-1BL00-0AA0 6ES7 492-1CL00-0AA0 6ES7 492-1CL00-1AB0 6ES7431-7KF00-6AA0
Electronic manuals on DVD, five languages: S7-200/300/400, C7, LOGO!, SIMATIC DP, PC, PG, STEP 7, engineering software, runtime software, PCS 7, SIMATIC HMI, SIMATIC NET
B3 SIMATIC Manual Collection maintenance service for 1 year
6ES7 998-8XC01-8YE2
Current "Manual Collection" DVD and the three subsequent updates Manual "SIMATIC S7-400 programmable controller" incl. instruction list German English French Spanish 6ES7 498-8AA05-8AA0 6ES7 498-8AA05-8BA0 6ES7 498-8AA05-8CA0 6ES7 498-8AA05-8DA0 6ES7 498-8AA05-8EA0
see page 5/131; Information about which components can be used for the respective module, see DT&IAMall or Catalog KT 10.2 6ES7 974-0AA00-0AA0
Measuring range module for analog inputs 1 module for 2 inputs (spare part) Cover film for labeling strips Spare part
6ES7 492-2XX00-0AA0
Italian
B3: Subject to export regulations: AL: N and ECCN: 5D992B1 B6: Subject to export regulations: AL: N and ECCN: EAR99 B7: Subject to export regulations: AL: N and ECCN: EAR99H B8: Subject to export regulations: AL: N and ECCN: EAR99S
5/78
Siemens ST 70 2009
Siemens AG 2008
SIMATIC S7-400
Overview
Analog outputs for the SIMATIC S7-400 For the connection of analog actuators
Analog modules
5
Technical specifications
6ES7 432-1HF00-0AB0 Supply voltages Load voltage L+ Rated value (DC) Current consumption from backplane bus DC 5 V, max. from supply voltage L+, max. Current consumption/ power loss Power loss, max. Analog outputs Number of analg outputs cable length, shielded, max. Voltage output, Short-circuit protection Voltage output, short-circuit current, max.. 8 200 m Yes 30 mA 9W 150 mA 400 mA 24 V Analog value creation Integration and conversion time/resolution per channel Resolution with overload area (bit including sign), max. 13 Bit 6ES7 432-1HF00-0AB0
Conversion time (per channel) 420 s; 420 s in the ranges 1 to 5 V and 4 to 20 mA; 300 s in all ranges Settling time for resistive load for capacitive load for inductive load Errors/accuracies Operational limit in overall temperature range Voltage, relative to output area +/- 0,5 %; +/-10 V, 0 to 10 V, 1 to 5 V Current, relative to output area +/- 1 %; +/-20 mA, 4 to 20 mV Basic error limit (operational limit at 25 C) Voltage, relative to output area +/- 0,5 %; +/- 10 V, 0 to 10 V, 1 to 5 V Current, relative to output area +/- 0,5 %; +/-20 mA, 0 to 20 mA Status information/alarms/ diagnostics Substitute values connectable Isolation Isolation checked with No 2120 V DC between bus and L+/M; 2120 V D between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground 0.1 ms 3.5 ms 0.5 ms
Current output, no-load voltage, 19 V max. Output ranges, voltage 0 to 10 V 1 to 5 V -10 to +10 V Output ranges, current 0 to 20 mA -20 to +20 mA 4 to 20 mA Load impedance (in rated range of output) with voltage outputs, min. with voltage outputs, capacitive load, max. with current outputs, max. 1 k 1 F 500 ; 600 ohms if common-modevoltage reduced to <1 V Yes Yes Yes Yes Yes Yes
Siemens ST 70 2009
5/79
Siemens AG 2008
Analog modules
SIMATIC S7-400
Ordering data
SM 432 analog output module 8 outputs, floating, 13 bit Front connectors 48-pin with screw contacts, 1 item with screw contacts, 84 items 1 with spring-loaded terminals, 1 item with crimp contacts, 1 item 25 mm 290 mm 210 mm 650 g with crimp contacts, 84 items SIMATIC TOP connect
B7 B7 B6
6ES7 492-1AL00-0AA0 6ES7 492-1AL00-1AB0 6ES7 492-1BL00-0AA0 6ES7 492-1CL00-0AA0 6ES7 492-1CL00-1AB0 see page 5/131; Information about which components can be used for the respective module, see A&D Mall or Catalog KT 10.2 6ES7 492-2XX00-0AA0
Weights Weight, approx. Cover film for labeling strips Spare part S7 SmartLabel V3.0 Software for automatic labeling of modules direct from the STEP 7 project Single license Upgrade single license Labeling sheets for machine inscription DIN A4, for printing using laser printer; pack of 10 petrol light-beige yellow red SIMATIC Manual Collection Electronic manuals on DVD, five languages: S7-200/300/400, C7, LOGO!, SIMATIC DP, PC, PG, STEP 7, engineering software, runtime software, PCS 7, SIMATIC HMI, SIMATIC NET
B3 SIMATIC Manual Collection maintenance service for 1 year B3 B8 B8
6ES7 492-2AX00-0AA0 6ES7 492-2BX00-0AA0 6ES7 492-2CX00-0AA0 6ES7 492-2DX00-0AA0 6ES7 998-8XC01-8YE0
6ES7 998-8XC01-8YE2
Current "Manual Collection" DVD and the three subsequent updates Manual "SIMATIC S7-400 programmable controller" incl. instruction list German English French Spanish Italian 6ES7 498-8AA05-8AA0 6ES7 498-8AA05-8BA0 6ES7 498-8AA05-8CA0 6ES7 498-8AA05-8DA0 6ES7 498-8AA05-8EA0
B3: Subject to export regulations: AL: N and ECCN: 5D992B1 B6: Subject to export regulations: AL: N and ECCN: EAR99 B7: Subject to export regulations: AL: N and ECCN: EAR99H B8: Subject to export regulations: AL: N and ECCN: EAR99S
5/80
Siemens ST 70 2009
Siemens AG 2008
SIMATIC S7-400
5
Analog inputs for SIMATIC S7-400 Connecting voltage sensors and current sensors, thermo elements, resistors and resistance thermometers Resolution 13 to 16 bit
Analog input module SIPLUS SM 431 Order No. Order No. based on Ambient conditions 6AG1 431-0HH00-4AB0 6ES7 431-0HH00-0AB0 Suited for exceptional medial exposure (e. g. by chlorine sulfur atmosphere). The technical data are identical with those of the based-on modules.
Analog output module SIPLUS SM 432 Order No. Order No. based on Ambient conditions 6AG1 432-1HF00-4AB0 6ES7 432-0HF00-0AB0 Suited for exceptional medial exposure (e. g. by chlorine sulfur atmosphere). The technical data are identical with those of the based-on modules.
Technical data
Technical data
Ordering data
SIPLUS SM 431 analog input module (medial exposure) 16 inputs, non-floating, 13 bit Accessories
Ordering data
SIPLUS SM 432 analog output module (medium exposure) 8 outputs, floating, 13 bit
Accessories
Siemens ST 70 2009
5/81