Module SEPAM Generalities
Module SEPAM Generalities
67 : Directional phase overcurrent 67N : Directional earth fault 64REF : Restrictive earth fault 87T : transformer differential 87 M : Machine differential 87B : Busbar differential 87L : Line differential (46 : Negative sequence / unbalance) (37 : Phase undercurrent)
Schneider Electric - Division - Name Date
25 : Synchro-check
- 25 = Module MCS025 for SEPAM (only on SEPAM 60 or 80) - Voltage Reference = 1 single Voltage or 1 composed voltage - VT healthy circuit is needed (to be sure when the busbar is dead
MCB 25 VT VT MCB
Source 1
Source 2
Fuse
Fuse
MCB close
Transformer protection
38 / 49T : Temperature monitoring
8 sensors (PT100 or Ni100) per module (MET-148) for SEPAM
Motor protection
32P : Directional active overpower (32Q : Directional reactive overpower) (37P : Directional active underpower) Others ansi codes : - 64G (100% stator) 79 (recloser) 24 (overfluxing) 67NC (for compensed neutral)
SEPAM Range
SEPAM series 100
SEPAM series 10
SEPAM 100 LA =
For back-up protection : Phase overcurrent (50/51) & earth fault (50N/51N) :
SEPAM 100 LD =
High impedance differential relay. It provides restricted earth fault, busbar and machine protection.
SEPAM 100 MI =
High impedance differential relay. It provides restricted earth fault, busbar and machine protection.
SEPAM series 10
10
11
12
13
14
15
16
17
Series 20 & 40
Series 80 & 60
18
19
20
I/O modules
FOR SEPAM Series 20 & 40 : MES114, MES114E, MES114F 10 inputs / 4 output modules 1 module by SEPAM
FOR SEPAM Series 60 & 80 : MES120, MES120G, MES120H 14 inputs / 6 outputs modules Up to 3 modules for SEPAM 80 Up to 2 modules for SEPAM 60
21
CT + CSH30
connection of CT with secondary 1A: 2 turns 5A: 4 turns Or direct on CCA634
23
CCA630/CCA634 connector The CCA630 connector is used to connect 3 phase current transformers to Sepam The CCA634 adds an input for a residual current transformer : do not connect a core balance ct With CCA634 Io input on A or E connector must not be used. Both contain interposing ring CTs with through primaries and be disconnected with the power on since disconnection does not open the CT secondary circuit.
24
CT 1 or 5A
Characteristics comparison
Series 20 Power supply User / Machine Interface Basic I/O Maximum I/O Sensors 24 / 250 V DC 110 / 240 V AC No UMI or remote advanced UMI 0 inputs / 4 outputs 10 inputs / 8 outputs 3 CTs + 1 core balance CT Or 4 VTs 1 3 CTs + 3 VTs + 1 core balance CT 1 Yes Series 40 Series 80 24 / 250 V DC No UMI Or advanced UMI Or mimic-based UMI 0 inputs / 5 outputs 42 inputs / 23 outputs 3 CTs + 4 VTs + 2 core bal. CTs 6 CTs + 4 VTs + 2 core bal. CTs Or 3 CTs + 8 VTs + 1 cor. bal. CT 2 Yes Yes (optional) Yes Yes
25
26
27
28
29
30
31
32
33
The availability of some protection functions depend on VTs wiring ACExxx communication modules need to be powered with 12 or 24 V DC Synchro check option only work with series 60 or 80 and need specific cable CCA 785
34