Process Values
XLReporter can take snapshots of the process values and add them to an existing report worksheet, periodically or on event. To prevent excessive build-up of information in a single worksheet, new workbooks and worksheets can be created automatically. XLReporter supports data retrieval from any RSLinx Classic version that provides the RSLinx OPC Server. This includes: RSLinx Classic Single Node RSLinx Classic OEM RSLinx Classic Gateway In order to access the RSLinx OPC Server from a remote machine, you must use RSLinx Classic Gateway.
Select New and enter a name for the topic and browse to the target device for this topic. Click Apply. On the Data Collection tab specify the Processor Type and the settings on the Advanced Communication tab.
Click Done when finished. If RSLinx Classic Gateway is being used, a remote computer that has no installed Rockwell Automation products will have access to the PLCs.
To connect ,select Server, Connect. This opens the Select an OPC Server window. Choose RSLinx OPC Server and click OK. Select Group, Add Group. Enter a Group Name and click OK. Select Item, Add Item to open the Add OPC Item window. Select a tag by navigating in the lower left list, selecting a tag on the lower right list and clicking Add. When finished, click Done to return to the OPC Test Client window.
Real Time System Check
To connect to RSLinx Classic, the Server should be set to RSLinx OPC Server or RSLinx Remote OPC Server depending on if the server is local or remote. Select one or more tags and verify that they update with the current value.
All of the selected tags appear along with their real time values, type, quality, and timestamp. If at any point you experience an issue with this client, it is an indication that there is something wrong with the RSLinx server, since now two OPC clients have demonstrated issues. At this point, contact Rockwell Software technical support to troubleshoot and correct these issues.
Rockwell Software, RSLinx are registered trademarks of Rockwell Automation, Inc.
Troubleshooting
If you are experiencing issues connecting to or retrieving data from RSLinx with XLReporter, you can use the OPC Test Client provided by Rockwell Software to test the OPC server. The OPC Test Client is opened from the Rockwell Software program group under RSLinx, Tools, OPC Test Client.