Increased Revenue
Supply can be quickly restored to unaffected areas, resulting in less outage time and therefore increased revenue.
RL-Series
Nu-Lec Industries
Modular design
Safe design
In the event of an internal arc fault, a vent on the side of the load break switch ruptures to vent the over-pressure. This eliminates the risk of explosion or detachment from the power pole and since the unit is not oil filled, a major fire hazard is eliminated.
Load Break Switch with optional motor
A low pressure locking device locks the manual operating handle if the pressure drops below a pre-set threshold.
Easy Installation
High voltage connections are made with insulated cable terminated on epoxy bushings. The cable and bushings are covered by a gripping elastomeric boot that is filled with silicone grease to form an insulated system on the 27kV model. The 15kV model is provided with bare terminals instead of the covered assemblies. The switch is installed using the standard cross arm mounting bracket.
SF6 switch Motor Control Cubicle Mechanism control Battery charging unit
Motor and Control is Optional
Motor Option
An optional motor pack can be purchased which then allows the switch to be interfaced to Nu-Lec Industries or third party control cubicles to provide local and/or remote control.
Nu-Lec Industries
RL-Series
Surge Arresters always earthed to tank, even if mounted separately Surge Arrester
Earth Stud
Two M20 bolts for timber pole mounting (not supplied) or Two clamp bands for concrete pole mounting (optional)
Motor
Control Cable
Tee Off
Earth stud
Pole mounted installation showing the load break swithc with motorised remote control
Note:
1. Details given in this illustration are subject to change without notice. For full details refer the separate Technical Manual.
RL-Series
Nu-Lec Industries
Cable Terminations
Standard Lug
Bushing
Clamp Ring
Boot
Bushing Clamp Ring Cable terminated with standard lug (250&400A) Boot
Nu-Lec Industries
RL-Series
RL-Series specifications
15kV 12.5kA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15kV .630A .12.5kA .31.5kA .3000 .600 .12.5kA
Ratings
Maximum System Voltage . . . Rated Continuous Current . . . Fault Make Capacity (RMS) . . Fault Make Capacity (Peak) . . Mechanical Operations . . . . . Rated Full Load Operations . . Short Time Current (4s RMS)
15kV 16kA
15kV 630A 16kA 40kA 3000 600 16kA
27kV 12.5kA
27kV 630A 12.5kA 31.5kA 3000 600 12.5kA
27kV 16kA
27kV 630A 16kA 40kA 3000 600 16kA
Breaking Capacity
Mainly Active (0.7pf) . . . . . . . . . . . . . . . . . . . .630A Cable Charging . . . . . . . . . . . . . . . . . . . . . . . .25A Transformer Magnetising . . . . . . . . . . . . . . . . .22A 630A 25A 22A 630A 25A 22A 630A 25A 22A
Environmental
Ambient Temperature Radiation (Max) . . . . . Humidity . . . . . . . . . . Altitude (Max) (1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-30 to +50C .1.1kW/m2 .0 to 100% .3000m -30 to +50C 1.1kW/m2 0 to 100% 3000m -30 to +50C 1.1kW/m2 0 to 100% 3000m -30 to +50C 1.1kW/m2 0 to 100% 3000m
Net Weights
Load break switch
(2)
. . . . . . . . . . . . . . . . . . . .95kg
95kg
95kg
95kg
Crate Dimensions
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W=1200mm D=1150mm H=755mm
1 2
For altitudes above 1000m, derate in accordance with ANSI C37.63 For Gross Weights add 75kg
RL-Series
Nu-Lec Industries
Ordering Information
The RL-Series LBS ordering information comprises one part number. The load break switch part number includes a Model Identifier and fields describing the Automation Status, Insulation Medium, System Voltage, Fault Make Capacity, Insulation Level and Cable Rating. The part number does not include measurement units and is constructed using only one option per field in the selection chart below. A part number example is shown below: Nu-Lec-RL27-LBS-RC-SF6-27-16-150-400 Nu-Lec RL27-LBS 2
- SF6 -
Field descriptions
1. Model: RL27 is the current model
RL-Series LBS
RL27-LBS
RL27-LBS
MR RC
MR RC
3. Insulation Medium: SF6 gas insulated load break switch 4. System Voltage: 15 = 15kV, 27 = 27kV
SF6
SF6
15 27
12 16
12 16
125 150
7. Cable Rating: 250 = 250A, 400 = 400A 630 = 630A 630-BT = 630A Bare Terminal (BT) (15kV max.)
Nu-Lec Industries
RL-Series
Distributor:
N00-598
CORPORATE OFFICE & FACTORY 35-37 South Street, Lytton, 4178 Queensland, Australia PO Box 761, Edith Street Wynnum, Queensland, 4178 Telephone (07) 3249 5444 Intl +61 7 3249 5444 Facsimile (07) 3249 5888 Intl +61 7 3249 5888 E-mail: [email protected] http://www.nulec.com.au
UK OFFICE Unit 9, Kings Meadow Ferry Hinksey Road Oxford OX2 0DP United Kingdom Telephone (01865) 209 999 Intl +44 1865 209 999 Facsimile (01865) 209 900 Intl +44 1865 209 900 E-mail: [email protected] http://www.nulec.co.uk
USA OFFICE 1252 Old Alpharetta Road Alpharetta, Georgia 30005-3986 United States of America Telephone (770) 521 2000 Intl +1770 521 2000 Facsimile (770) 521 2100 Intl +1770 521 2100 E-mail: [email protected] http://www.nulec.com
SOUTH AFRICA OFFICE Cnr. Bekker & Montrose Rds, Midrand, South Africa Postal address: Private Bag X139, Halfway House, 1685 Telephone (011) 254 6400 Intl +27 11 254 6400 Facsimile (011) 254 6925 Intl +27 11 254 6925 E-mail: [email protected] http://www.nulec.co.za
Copyright 2001 Nu-Lec Industries Pty Ltd. No responsibility for loss incurred by any person acting or refraining from action in reliance upon any material in this brochure can be accepted by Nu-Lec Industries Pty Ltd.