0% found this document useful (0 votes)
91 views

CoolFlex Application Report - KW Per Rack

The document describes tests conducted on a cold aisle containment system in a data center to improve energy efficiency. The system isolated cold and hot air zones within server racks using infill panels and enclosed cold aisles. Tests showed that at a heat load of 14kW per rack, the cold aisle temperature was maintained at 23°C. When computer room air conditioning units were switched off to simulate emergencies, the cold aisle temperature only slightly exceeded 23°C. The system was able to maintain suitable temperatures even with very high heat loads, demonstrating its effectiveness in improving energy efficiency.

Uploaded by

majortay
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
91 views

CoolFlex Application Report - KW Per Rack

The document describes tests conducted on a cold aisle containment system in a data center to improve energy efficiency. The system isolated cold and hot air zones within server racks using infill panels and enclosed cold aisles. Tests showed that at a heat load of 14kW per rack, the cold aisle temperature was maintained at 23°C. When computer room air conditioning units were switched off to simulate emergencies, the cold aisle temperature only slightly exceeded 23°C. The system was able to maintain suitable temperatures even with very high heat loads, demonstrating its effectiveness in improving energy efficiency.

Uploaded by

majortay
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

COLD-AISLE CONTAINMENT IN DATA CENTRES

the smart concept for optimal energy use

www.knuerr.com

Application Report
Cold-Aisle Containment in Data Centres
The smart concept for optimal energy use

Cooling requirements in data centres are continually rising, causing conventional climate control systems to be overloaded. Switching to a water cooled systems is an option, but structurally and financially this is not always possible. Cold-Aisle Containment (CoolFlex) is another option. This option consistently separates cold and warm areas without requiring structurally changes to the data centre. Over several weeks the efficiency of CoolFlex was tested and proved. The test was conducted using fan heaters to simulate the heat load generated by servers. The result: At a thermal load of ca. 14kW per rack, the required temperature of 23C in the cold aisle was reached. During further tests, several computer room air conditioning units (CRAC) were switched off to simulate an emergency. During these tests the cold aisle temperature of 23C was only marginally exceeded.

COLD-AISLE CONTAINMENT IN DATA CENTRES


the smart concept for optimal energy use

www.knuerr.com

Description of application:
Test conditions
The raised floor provided greater energy efficiency by directing cool air through perforated plates in the cold aisle and by sealing the cable entry in to the racks. Knrr isolated the cold and hot zones within the server racks using infill panels. All 4 cold aisles were then enclosed using cold aisle containment. The 342 KW heat capacity was simulated via fan heaters (38 x 9kW = 342 kW). 288 kW heat capacity was simulated within aisle 2. Aisle 1, 3 and 4 were not in use and therefore produced no heat. The remaining 54 kW were distributed throughout the room, simulating the heat capacity in the network and free standing racks. To minimise the loss of circulation and pressure caused by the raised floor, Knrr used special grate catch instead of perforated raised floor plates. All holes for cables through the floor were sealed to prevent hot air shortcuts.

The CRAC units used were designed to use 250 kW in their energy-efficient, normal mode and 500 kW at high power mode. The capacity of the fans is proportional to the third power of the circulatory. Therefore it is more energy-efficient to run all CRAC units at lower speed, instead of using less CRAC units at their maximal speed. By consistently isolating cold and warm air, the nominal capacity of the CRAC units is increased, therefore the same number of CRAC units can run at a high power mode, without reducing redundancy.

COLD-AISLE CONTAINMENT IN DATA CENTRES


the smart concept for optimal energy use

www.knuerr.com

Test areas
Test 1: Energy-efficiency in normal mode 6 CRAC units in normal mode (speed ca. 30%) Pressure test with a rising thermal load

Results during full load(ca. 288 kW in aisle + 54 kW) Temperature of cold aisle: 23,0 C Temperature of warm aisle: 37,0 C

Test 2: Emergency (Breakdown of 2 CACUs) 3 CRAC units in emergency mode (speed ca. 80%)

Results during full load(ca. 288 kW in aisle + 54 kW Temperature of cold aisle: 23,1 C Temperature of warm aisle: 42,9 C 3

COLD-AISLE CONTAINMENT IN DATA CENTRES


the smart concept for optimal energy use

www.knuerr.com

Test 3: Extreme emergency (Breakdown of 4 CACUs) 2 CRAC units in emergency mode (speed 100%)

Results during full load(ca. 288 kW in aisle + 54 kW) Temperature of cold aisle: 23,5 C Temperature of warm aisle: 47,0 C With only 2 CRAC units the temperature in the cold aisle did not exceed the required 24C. After a time the fan heaters simulating server heat load failed due to a fail safe switch.

Results and Conclusions


To discover the maximum capacity of cold aisle containment by increasing the heat capacity in the data centre. - Load per Rack 3.6kW (Face: 3.5 m = ca. 1000 W/m) = possible! - Load per Rack 7.6kW (Face: 3.5 m = ca. 2000 W/m) = possible! - Load per Rack 10.8kW (Face: 3.5 m = ca. 3000 W/m) = possible! - Load per Rack 14.4kW (Face: 3.5 m = ca. 4000 W/m) = possible! The cold aisle containment could possibly discharge a higher heat load however the fan heater fail safe thermostat caused at collapsed after 4'000W/m. Also the test equipment was not calibrated for higher heat load. Therefore we could not demonstrate the limits of the cold aisle containment. Note: It is important to note that during this pilot project, fan heaters were used to demonstrate the cooling capacity. Fan heaters can only simulate the heat generated by servers, as they have a lower flow volume across the server. We are positive, that in a real situation, 10 to 12 KW per rack should be possible (various other experts do not differentiate between the use of fan heater and real servers)

COLD-AISLE CONTAINMENT IN DATA CENTRES


the smart concept for optimal energy use

www.knuerr.com Pictures of test site

COLD-AISLE CONTAINMENT IN DATA CENTRES


the smart concept for optimal energy use

www.knuerr.com

Services provided
Using trained personnel, Knrr is able to provide the following services: Consulting, calculation, and simulation of a solution. Simple installation into existing racks (dependent of make of rack). Integration and installation without the need for down time. Data Centres Thermal Assessment - Review of thermal demands and air flow within the data centre - Thermal imaging of the computer centre, several aisles and/or racks - Proposal of cost effective measures - Complete report, with achievable improvements Cold Aisle Containment implementation of the solution - Site visit (inclusive demarcation of project specific items, especially competitor racks) - Creation of project plan - Detailed pricing offer

Knrr AG Mariakirchener Strae 38 94424 Arnstorf


Telefon +49 (0) 87 23-27-0 Telefax +49 (0) 87 23-27-154 E-Mail: [email protected]

www.knuerr.com

You might also like