Halton FDB2 fire dampers are type-approved class A0(A60) fire and gas dampers for use in offshore, marine and navy ventilation systems. The FDB2 can be installed in rectangular or circular ducts. All fire dampers have a fusible link and they prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. Fire dampers are set from outside and can be installed in any position. An open-closed indicator is visible on the outside of the damper. Fire dampers with non-standard dimensions can be supplied on request. Type-approved by most recoganized classification societies, class A0 - A60 fire and gas damper when suitably insulated ATEX approved. Shock tested.
PART Frame Frame Blades Blades Maintenance-free bearings Shafts MATERIAL Carbon steel Stainless steel Steel Stainless steel Stainless steel Stainless steel
Blades contain silicone (effective up to 300 C) for low leakage in normal conditions and thermal expansion graphite seals (effective from 150 C) to increase tightness even up to 50% in a case of fire. Tightness substantially better than NORSOK requirements. (tested size 1000x1000 mm, VTT test report no. RTE4424/04) Nominal fuse release temperature 50 C, 74 C or 100 C. Other temperatures available Low weight due to patented double skin blade structure Automatic electrical, pneumatic or spring operation system available Maximum duct pressure for damper construction 5000 Pa and maximum air velocity 15 m/s. In case of high duct pressure, contact Halton Marine for finding the most suitable solution.
FINISHING Painted or galvanised Galvanized NOTE Bronze bearings optional -
FDB2 DIMENSIONS AND MATERIAL THICKNESS FDB2 fire dampers meet international standards for both rectangular (width B 100-1200 mm and height H 100-1600 mm, 1 mm division) and circular ducts (100-1250 mm). Non-standard dimensions and flange drilling available on request. Standard flange width 27 mm. Flanges and drilling also available according to ISO 15138 standards. Modular construction sizes up to 2400x3200 mm are available. Standard frame material thickness 3 mm. Frame thickness 3-5 mm according to SOLAS available on request. Frame thickness according to SOLAS
DIMENSIONS If B or H > 100, but < 449 If B or H > 450, but < 649 If B or H > 650 S 3 4 5 L 210 212 215
The above table contains only some examples of actuators and their effect on dimensions.
150 n*150
150 n*150 18 30 R
MIN. 50
MIN. 50
10
10
S, ACCORDING TO SOLAS
S, ACCORDING TO SOLAS
160
S, ACCORDING TO SOLAS
ACTUATOR
H+58
H+4
150 n*150
B+58 FDB2 B+56 FDL max. FDL 1300 max. FDB2 1200 12.0
FLAT BARS TO BE SEALED WITH PYROCRYL SEALANT
DETAIL I
ACTUATOR
ACTUATOR
H+58 FDB2
H+56 FDL
ACTUATOR
10.0 FDB2
ACTUATOR
M10*20 8.8
FDB2 PRODUCT OPTIONS Halton FDB2 is available with following actuators: FDB2-EL: Electrical spring return motor; standard actuators being 24 V or 230 V or 120 V. The motor contains built-in open-closed limit switches. Separate junction box included in the EL -model. A wide range of eex-proof actuators available, including a one second closing time function as an option. FDB2-PNL: Pneumatic linear actuator, material AISI 316 FDB2-PNR: Pneumatic rotating actuator FDB2-SP: Manual spring-actuated damper with fusible link. DOT: manual override function available for PNL, PNR and EL models. A wide range of accessories available.
OPERATION PRINCIPLE In the event of a temperature rise in ductwork: FDB2-EL: fusible link releases and cuts off operating voltage to the spring return motor, allowing the spring to close the damper blades. The fire damper opens automatically when the fuse has been changed and the operating voltage to the motor is re-established. FDB2-PNL, FDB2-PNR: fusible link releases and cuts off operating pressure to the spring return actuator, allowing springs to close the damper blades. The fire damper opens automatically when the fuse has been changed and the pneumatic air supply is re-established. FDB2-SP: fusible link releases allowing the spring to close the damper blades. When the fuse has been changed, the fire damper must be reset into open position manually.
1000
1100
100 125 160 200 250 315 400 500 630 800 1000 1250
Examples of actuator weights: FDB2-EL GGA 326.1E 2,3 kg, GNA 326.1E 1,3 kg, BF230 +3,2 kg, BLF230 +1,7 kg, ExMax /Redmax +3,5 kg, FDB2-PNL Roder +4 kg, FDB2-PNR AT100 +2,1 kg, AT100 as AISI316 4,4 kg, AT200 +3,2kg, AT200 as AISI316 +6,2 kg, FDB2-SP +1 kg.
9.0 FDL
2.0
CLOSED 21 13
21 13 OPEN
1. SPRING RETURN ACTUATOR 2. QUICK EXHAUST VALVE 3. SILENCER 4. FUSIBLE LINK VALVE
12 13
9
22 14 22 14
1 3 7 2 3 6
1 2 3 4 5 6 7 8 9 10 11
THERMAL FUSE SM-072-A0-2A (72C)
5. OPTION: SOLENOID VALVE 6. MALE CONNECTOR 7. DOUBLE NIPPLE 8. PLASTIC TUBE 9. OPTION: OPEN/CLOSED SWITCHES 10. OPTION: MANUAL VALVE 11. PRESSURE REGULATOR
3 6 6
8 4
8
10
3 6
8
5
S2
S3
S4
S5
S1
S6
87
IP 54
NOTICE! ADDITIONAL SOLENOID VALVE MAX 10 METER FROM FIRE DAMPER PNEU. INLET (5-10 BAR) FOR A PLASTIC TUBE 6 MM