Pulsatron Installation and Operating Manual (A+, C, C+, E, E-DC, E+ and HV)
Pulsatron Installation and Operating Manual (A+, C, C+, E, E-DC, E+ and HV)
TABLE OF CONTENTS
1.0 SAFETY INSTRUCTIONS ................................................................................................................. 3 1.1 1.2 2.0 3.0 General Safety Considerations ........................................................................................... 3 Safety Operating Procedures.............................................................................................. 3
UNPACKING THE PUMP ................................................................................................................... 4 INTRODUCTION ................................................................................................................................. 5 3.1 3.2 Principle of Operation.......................................................................................................... 5 Materials of Construction .................................................................................................... 5
4.0
INSTALLATION .................................................................................................................................. 5 4.1 4.2 4.3 4.4 Mounting ............................................................................................................................. 5 Piping .................................................................................................................................. 6 Wiring .................................................................................................................................. 7 Well Pump System Installation ........................................................................................... 7
5.0
START UP AND OPERATION ........................................................................................................... 8 5.1 5.2 5.3 5.3.1 5.3.2 5.3.3 5.4 5.5 5.5.1 5.5.2 5.5.3 Power .................................................................................................................................. 8 Priming ................................................................................................................................ 8 Capacity Control.................................................................................................................. 8 Stroke Frequency Adjustment............................................................................................. 8 Stroke Length Adjustment ................................................................................................... 9 Controlling Procedure ......................................................................................................... 9 Control Panel Symbols ....................................................................................................... 9 Operation By External Input Signals ................................................................................... 9 Stop Functions .................................................................................................................... 9 External Pacing Function .................................................................................................. 10 4-20mA DC Input Function ............................................................................................... 10
6.0
MAINTENANCE ................................................................................................................................ 11 6.1 6.2 6.3 6.4 Routine Maintenance ........................................................................................................ 11 Disassembly and Assembly Diaphragm Removal ............................................................ 11 Diaphragm Replacement .................................................................................................. 11 Valve Replacement ........................................................................................................... 12
7.0
8.0
POLICIES AND PROCEDURES ...................................................................................................... 16 8.1 8.2 8.3 Manufacturer's Product Warranty ..................................................................................... 16 Returns .............................................................................................................................. 16 Credits ............................................................................................................................... 16
1.0
SAFETY INSTRUCTIONS
When using chemical feed pumps, basic safety precautions should always be followed to reduce risk of fire, electric shock, and personal injury. Failure to follow these instructions could result in death or serious injury.
An air bleed valve is available for most models with tubing connections. Air purges should be performed when the pumpchamber contains no fluid at the time of start-up. As a safety measure, connect the return tubing to the air bleed valve and bypass fluid back to storage tank or a suitable drain. For accurate volume output, the pump must be calibrated under typical operating conditions. Chemicals used may be dangerous and should be used carefully and according to warnings on the label. Follow the directions given with each type of chemical. Do not assume chemicals are the same because they look alike. Always store chemicals in a safe location away from children and others. We cannot be responsible for the misuse of chemicals being fed by the pump. Always have the material safety data sheet (MSDS) available for any fluid being pumped. All pumps are pretested with water before shipment. Remove head and dry thoroughly if you are pumping a material that will react with water, (i.e. sulfuric acid, polymers). Valve seats, ball checks, gaskets, and diaphragm should also be dried. Before placing pump into service, extreme care should be taken to follow this procedure. Valve cartridges are stamped to indicate fluid flow direction. Always install so that markings read from top to bottom, with the arrow pointing in the direction of flow. When metering hazardous material DO NOT use plastic tubing, strictly use proper rigid pipe. Consult supplier for special adapters or valve assemblies. Pump is NOT to be used to handle or meter flammable liquids or materials. Standard white discharge tubing is not recommended for installations exposed to direct sunlight. Consult supplier for special black tubing. Factory will not be held responsible for improper installation of pump, or plumbing. All cautions are to be read thoroughly prior to hookup and plumbing. For all installations a professional plumber should be consulted. Always adhere to local plumbing codes and requirements. When using pump with pressurized systems, make sure the pressure of the system does not exceed the maximum pressure rating on the pump data label. Be sure to depressurize system prior to hook up or disconnecting a metering pump. Electronic power modules are equipped with automatic reset thermal overload devices and may reset unexpectedly.
The carton should Contain: 9 9 9 9 9 9 9 9 Metering Pump Clear Flexible Suction Tubing* Stiff White Discharge Tubing* Foot valve/Strainer Assembly Backpressure Injection Valve Assembly Manual Bleed Valve Assembly* Strainer Weight*
Figure 1
Make sure that all items have been removed from the shipping carton before it is discarded.
3.0 INTRODUCTION
These installation, operation and maintenance instructions cover your electronic metering pump. Refer to the pump data label to determine the actual model.
4.0 INSTALLATION
The metering pump should be located in an area that allows convenient connections to both the chemical storage tank and the point of injection. The pump is water resistant and dust proof by construction and can be used outdoors, however, do not operate submerged. Avoid continuous temperatures in excess of 104F (40C). To do otherwise could result in damage to the pump.
4.1 Mounting
Typical mounting arrangements are shown in Figures 3, 4, and 5. Important: Injection point must be higher than the top of the solution supply tank to prohibit gravity feeding, unless suitable backpressure is always present at the injection point. Installation of an anti-siphon valve will prohibit gravity feeding. For wall or shelf mounting refer to Figure 3. Connect suction tubing to suction valve of chemical pump. Suction valve is the lower valve. Tubing should be long enough so that the foot valve/strainer assembly hangs about 1-2 inches (2-5 cm) above the bottom of chemical tank. To keep chemical from being contaminated, the tank should have a cover. Flooded suction mounting (installing the pump at the base of the chemical storage tank, Figure 4) is the most trouble free type of installation and is recommended for very low output requirements. Since the suction tubing is filled with chemical, priming is accomplished quickly and the chance of losing prime is reduced. To mount pump, drill four holes of .25 (6 mm) diameter in the shelf as shown in the dimension drawing (figure 2). Attach pump securely using four #10 (M5) bolts and nuts. The pump can be mounted on top of a solution tank as shown in Figure 5. Install chemical pump on the cover. Insert suction tubing through the center hole and cut tubing so foot valve/strainer hangs about 1 or 2 inches (2-5 cm) above the bottom of the tank. Mount the chemical pump rigidly by drilling four .25 (6 mm) holes and using four (4) #10 (M5) screws and nuts.
USE AN ANTI-SIPHON VALVE IN THE DISCHARGE LINE whenever the fluid pressure in the discharge line is below atmospheric pressure. This can occur if the injection point is on the suction side of a water pump or against a "negative" head such as when feeding down into a well.
4.2 Piping
Use provided tubing of specified size for connection. Connect tubing securely to prevent leakage of chemical and the entrance of air. Since plastic nuts are used for fittings, they should not be tightened excessively (i.e. hand tighten only). NPT suction and discharge valves must NOT be over tightened. Hold fitting in place while adding piping and fittings. NPT suction and discharge valves should only be tightened 25 to 35 in. lbs. (4.5-6.3 kg/cm). If the air bleed valve assembly is being used, a return line (tubing) should be securely connected and routed back to the storage tank. To avoid possible injury from chemicals do not attempt to prime using a bleed valve without installing a return line. When pump is shelf mounted or top mounted on tank, suction tubing should be kept as short as possible. To maintain metering performance, a backpressure/injection valve is provided. The spring in the standard injection valve typically adds 17 - 20 PSI (1.17 - 1.38 BAR) to the line pressure, with the exception of the H8 pump, which adds 8 - 10 PSI (.55 - .69 BAR). The injection valve must be installed in the discharge line. Best practice is to install the injection valve at the point of chemical injection. If the discharge tubing is going to be exposed to direct sunlight, black tubing should be used instead of the standard white translucent tubing supplied with each pump. To obtain, contact supplier. To prevent clogging or check valve malfunction always install a strainer assembly to the end of the suction tubing (Figure 5). This foot valve/strainer assembly should always be installed 1 to 2 inches (2-5 cm) above the bottom of the chemical tank. This will help prevent clogging the strainer with any solids that may settle on the tank bottom. The chemical tank and foot valve/strainer should be cleaned regularly, to ensure continuous trouble free operation. If the chemical being pumped regularly precipitates out of solution or does not dissolve easily or completely (e.g. calcium hydroxide), a mixer should be used in the chemical tank. These are readily available in many motor configurations and mounting. To obtain, contact supplier.
A flooded suction (tank liquid level always at a higher elevation than the pump) is recommended when pumping solutions such as sodium hypochlorite (NaOCl), hydrogen peroxide (H 2O2), etc., which are likely to produce air bubbles. Maintaining a low liquid temperature will also help eliminate this problem. Pipe corrosion can result if dilution at the injection point does not occur rapidly. This problem is easily prevented by observing this simple rule: install injection fitting so that the end is in the center of the flow stream of the line being treated. Trim injector tip as required. See Figure 6. Note: Extended injection assemblies are available for large water lines. Consult your supplier for more information.
4.3 Wiring
Risk of electrical shock. This pump is supplied with a three-prong grounding type power plug. To reduce risk of electric shock, connect only to a properly grounded, grounding type receptacle.
Figure 6
The metering pump should be wired to an electrical source, which conforms to those on the pump data label. Applying higher voltage than the pump is rated for will damage the internal circuit. In the electronic circuit of the control unit, measures for surge voltage are made by means of surge absorbing elements and high voltage semiconductors. Nevertheless, excessive surge voltage may cause failure in some areas. Therefore, the receptacle should not be used in common with heavy electrical equipment, which generates high voltage. If this is unavoidable however, measures should be taken by (a) the installation of a surge-absorbing element (varistor of min. surge resistance 2000A) to the power supply connection of the pump, or (b) the installation of a noise suppression transformer.
Signal input to the external pulse signal input terminals ([EXTERNAL], [STOP]) must be a no-voltage signal from relaycontacts etc. and the input of other signals is prohibited. In the case of relay contacts, 100 ohms or below when ON and 1-meg ohms or above when OFF. The pulse duration of the input signal must be 10 milliseconds or over and the frequency of the input signal must not exceed 125 times per minute. Signal cord is provided with the pump.
5.2 Priming
When working on or around a chemical metering pump installation, protective clothing and gloves and safety glasses should be worn at all times. All pumps are tested with water. If the chemical to be pumped reacts when mixed with water (e.g. sulfuric acid, polymer) the pump head should be removed and dried thoroughly along with the diaphragm and valve seats. Turn on the power to the pump. The green LED (not available on all models) will light up and flash off each time the pump strokes. Adjust the stroke rate knob to the 100% setting mark (for more information see Section 5.3, Capacity Control). Adjust the stroke length knob to the 100% setting mark if applicable (for more information see Section 5.3, Capacity Controls). If the discharge line is connected directly to a pressurized system it should be temporarily bypassed during priming of the pump. A bleed valve will simplify this operation by allowing easy bypass of the discharge fluid. Air must be purged from the pump-head before the pump will operate against pressure. (See Figure 9) Air Bleed Operation: While pump is running, turn adjustment knob counterclockwise. Run with valve open until a solid stream of fluid comes out of the bypass tubing with no air bubbles. Close air bleed valve by turning adjustment screw clockwise. Chemical should reach the pump head after a few minutes of operation. If not, remove the discharge fitting and moisten the discharge valve area (ball check and valve seats) with a few drops of chemical being fed to the metering pump. For safety, always use protective clothing and gloves, wear safety glasses and use a proper container to hold the chemical. If the pump continues not to prime, refer to Section 7.0, Troubleshooting, of these instructions. Once the pump has been primed and is pumping the chemical through the head, turn off the power, reconnect the discharge tubing (if it had been removed) and immediately clean any spilled chemical that is on the pump housing or head. Turn the power on once more and adjust the pump flow to the desired rate (see Section 5.3.3, Controlling Procedure). Always check the calibration of the pump after start-up. Its best to calibrate the pump under your typical use conditions.
5.3.2 Stroke Length Adjustment Stroke length can be controlled within 0 to 100% of the diaphragm displacement. It should be controlled within 20 to 100% for practical use. Stroke length can be set by means of the stroke length adjusting knob while the pump is in operation. Do not turn the knob while the pump is stopped. 5.3.3 Controlling Procedure Proper set points for stoke length and stroke frequency should be determined after consideration of the pump and characteristics of the fluid. The following procedure is recommended from the viewpoint of pump performance. Note: The closer the stroke length is to 100%, the better the pump performance will be. Set the stroke length to 100% then adjust the stroke frequency for coarse capacity control. Measure the capacity. When the measured capacity is less than the required value, increase the stroke frequency and measure the capacity again. Then, adjust the stroke length for fine capacity control. Finally, measure the capacity and make sure that the required value is obtained. Example Selected Model = Set Stroke Length = Set Stroke Rate = Output Capacity = (Rated Pressure) Desired Flow = Adjust Stroke Rate to 80% Output Capacity = Stroke Length Setting = LPD4 100% 100% 21 gallons per day (GPD)* 15 GPD
0.80 x 21 = 16.8 GPD* 15 x 100 = 90% approximate 16.8 Thus to obtain the desired flow, stroke length is set at 90% and stroke rate is set at 80% i.e. output capacity = 0.90 x 0.80 x 21 = 15.12 GPD* *IMPORTANT! Check these values by measurement. Output capacity is higher when feeding against less than rated pressure
5.5.2 External Pacing Function (E+, A+, C+ and C only) The pump's stroke rate can be controlled by an external signal input. When the input signal line is connected and the EXTERNAL /OFF /MANUAL switch is in the external position and a contact signal is input to the terminal marked , the pump makes one discharge stroke. Operation of more than one pump from the same contact closure will damage the pump circuits. When such operation is required, the pump circuits must be electrically isolated from one another by means of a multi-contact control relay or similar means. When the ON signal pulse is input, the pump operates one stroke and the fluid is discharged. In addition, the pump can be operated continuously to its maximum strokes/min. by repeated input of ON and OFF signals. After receiving an input signal, the pump generates the necessary power pulse to actuate the solenoid. The external signal input is debounced by the pump circuit. The pump will not stroke in response to a spurious or erratic input signal that follows at a rate greater than its maximum strokes/minute. If the external signal rate exceeds its maximum stokes/minute, the pump will stroke at half the external signal rate to prevent overdosing and to protect the pump from overheating. The input signal must be in the form of closure of a mechanical relay, other mechanical switching device, or of a solidstate switching device. Voltage signals are prohibited. The switching resistance of either mechanical or solid-state devices must be 100 ohms or below when ON and 1 megohm or above when OFF. If any type of solid-state device is employed, it must be installed with proper polarity, if required for the device; and leakage current must not exceed 200 microamperes to prevent false triggering in the OFF state.
Cycle rate of the input signal should not exceed the maximum stroke/minute speed of the pump. Typical wiring is shown at right for use with switch closure flow-meters. (Figure 12) 10 millisecond contact time required for each ON input signal. 5.5.3 4-20mA DC Input Function (E+ only) The pumps stroke rate can also be controlled by a 4-20 mA DC signal to the terminal marked [4-20 mA]. For the 4-20 mA input to have any effect on the pump output rate, the AUTO/OFF/MANUAL switch must be in the AUTO position. The 4-20 mA input signal affects the pumps outputs as per the graph below:
10
The signal cord polarity is: Black = Common White = Positive Wrong polarity can result in excess flow. Signal input impedance is 124 ohms. Remove cap from pump socket labeled 4-20 mA, use polarized cord supplied with pump to connect control circuit to pump. Plug cord into pump socket labeled 4-20 mA.
6.0 MAINTENANCE
Before performing any maintenance or repairs on chemical metering pumps, be sure to disconnect all electrical connections, insure that all pressure valves are shut off and pressure in the pump and lines has been bled off. Always wear protective clothing, gloves and safety glasses when performing any maintenance or repairs on chemical metering pumps.
11
Apply grease to areas of the diaphragm that contact the deflection plate. Slide the diaphragm deflection plate onto the back of the diaphragm stud, radius side towards the diaphragm. Next slide two shims onto the diaphragm threaded stud and screw the diaphragm into the EPM unit. Refer to Figure 14. Turn diaphragm clockwise until deflection plate and shims are tight against solenoid shaft and the diaphragm stops turning. If there is a gap between the adaptor and diaphragm, repeat the procedure removing one shim each time until the diaphragm just touches the adaptor or is slightly recessed. If not already done, adjust stroke length to 50%. Place the pump head onto the adaptor with valve flow arrows pointing up and install and tighten pump head screws. Tighten screws until pump head pulls up against adaptor. NOTE: Adjust stroke length only when pump is running! Adjust stroke length back to 100% for easier priming and place pump back into service.
12
7.0 TROUBLESHOOTING
Problem Probable Cause 1. Leak in suction side of pump Remedy 1. Examine suction tubing. If worn at the end, cut approximately one inch (2.5cm) off and reconnect 2. Clean valve seats if dirty or replace with alternate material if deterioration is noted 3. When pumping against pressure, the dial should be set above 20% capacity for a reliable feed rate 4. Solution must be above foot valve strainer 5. Replace diaphragm as shown in 6.0 Maintenance Section. Check for pressure above rated maximum at the injection point. NOTE Chemical incompatibility with diaphragm material can cause diaphragm rupture and leakage around the pump head 6. Replace pump head as shown in 6.0 Maintenance Section. Make sure fitting are hand tight only. Using pliers and wrench can crack pump head. Also, chemical incompatibility can cause cracking and subsequent leakage. 7. Bleed pump head, see 5.0 Start-up and Operation section 8. Connect wiring properly. Check fuse or circuit breaker 9. Take measures after investigation of cause 10. Contact supplier 1. Adjust to higher setting (pump must be operating to adjust stroke length knob) 2. Clean injection parts with 8% muriatic acid or undiluted vinegar (also, see Maintenance Section) 3. Refill the tank with solution and prime (see Startup and Operation Section) 1. Lower pump setting (pump must be operating to adjust stroke length knob) 2. Dilute chemical solution. NOTE: For chemical that reacts with water, it may be necessary to purchase a more dilute grade of chemical direct from chemical supplier 3. Test for suction or vacuum at the injection point. If suction exists, install an anti-siphon valve 1. Cut off end of tubing approximately one inch (2.5cm) and reconnect 2. Consult your seller for alternate material
9. Voltage drop 10. Malfunction of electronic control board 1. Pump setting to low Loss of Chemical Residual
3. Siphoning of chemical into well or main line Leakage at Tubing Connections 1. Worn tube ends
2. Chemical attack
13
1. Tighten hand tight. Replace gasket if hand tightening does not stop leakage 2. Check gaskets and replace if broken or damaged 3. Consult your pump supplier for alternate material 1. Remove and replace or clean off any scale or sediment 2. Check seat and ball checks for chips, clean gently. If deformity or deterioration is noted, replace part with proper material. Resulting crystals can hold check valves open, therefore, the valves must be disassembled and cleaned 3. Refill the tank with solution and prime. See 5.0 Start-up and Operation Section 4. Bleed gas, use flooded suction and maintain chemical at room temperature (approximately 20F) to minimize out gassing 1. Turn off all pressure valves, relieve system pressure then loosen outlet tubing connection at discharge point. Remove discharge valve cartridge. Dampen ball check and valve seats with a few drops of solution. Set pump dial to maximum rate. When pump is primed, reconnect all tubing connections 2. Disassemble, clean and check for deterioration, damage or swelling. Reassemble and wet the valve assembly, then prime. See 5.0 Start-Up and Operation Section. 3. Always prime pump with output dial set at maximum rated capacity. 4. Decrease suction lift or pull vacuum on pump discharge until pump is primed 5. Loosen discharge valve to aid in priming, take necessary safety precautions for spills or apply vacuum to pump discharge
2. Ball checks not seating or not sealing properly Pump Loses Prime 3. Solution container allowed to run dry
2. Check valves not sealing Pump will not Prime 3. Output dials not set at maximum
4. Suction lift height too much. Maximum 5ft (1.5m) 5. Pump equipped with spring loaded high viscosity valves
14
Appendix A
15
8.2 Returns
The Customer Service Department will issue a Return Authorization (RA) number for all returns. The following information will be required: 1. Billing and a ship-to address. 2. Model and serial number. 3. Contact name and phone number. 4. Reason for return. 5. Purchase order (where applicable). 6. RA number on outside of the carton. All material must be returned freight prepaid. All merchandise must be properly packaged and free of any corrosive, toxic or otherwise hazardous chemical. All items returned must reference Return Authorization.
8.3 Credits
No equipment will be accepted beyond six months after date of shipment from the factory. Only unused and undamaged equipment will be accepted for return to stock. All credits are based on acceptance of materials as new and unused by our inspection personnel. A restocking fee will apply. All equipment returned for credit must have a RA number and be returned freight prepaid.
L9408900-000 Rev B
16