Data
WEATHERMASTER
48/50P2,P3,P4,P5030-100
Single-Package Gas Heating/Electric
Cooling Rooftop Units
and Electric Cooling Rooftop Units
with Optional Electric Heat
with ComfortLink Controls
and PURON Refrigerant (R-410A)
30 to 100 Nominal Tons
Features/Benefits
Carriers 48/50P commercial
packaged unit offers design
flexibility, quality, reliability,
interoperability and
ComfortLink controls.
ComfortLink controls
a48-8424
Features/Benefits (cont)
ComfortLink controls also have the
capability to communicate with the
Carrier Comfort Network (CCN) system. This communication flexibility allows simple system integration as well
as data collection, trending, monitoring
and alarm displays.
The 48/50P Series may also be configured to communicate via MODBUS or LonWorks** protocols if required by the application.
The ComfortLink controls can also
interface directly with BACnet or CCN
controls on 35 and 45 Series VAV terminals to form a system for optimal efficiency and tenant comfort.
All units may also be applied to noncommunicating building control systems via switch and/or 4 to 20 mA signal to provide remote occupancy control, fire shutdown and smoke control
modes, IAQ (indoor air quality) modes,
and demand limit sequences.
In addition, VAV units can interface
with other control systems via a 4 to
20 mA signal capability which permits
control of supply-air temperature reset.
Standard ComfortLink controls
functions include:
easy to use plain English display
supply-fan control based on occupancy schedule
up to 6 steps of capacity control
with standard scroll compressors
digital scroll compressor option
allows variable control of compressor capacity to match load requirement of the space
lead-lag circuit control to equalize
the operating hours between the
dual refrigeration circuits
2-stage heat control
adaptive optimal start/morning
warm-up
Environmentally sound
Carriers Puron refrigerant (R-410A)
enables you to make an environmentally responsible decision. Puron
refrigerant (R-410A) is an HFC refrigerant that does not contain chlorine
that is damaging to the stratospheric
ozone layer. Puron refrigerant
(R-410A) is unaffected by the Montreal
Protocol. Puron refrigerant (R-410A) is
a safe, efficient and environmentally
sound refrigerant for the future.
Unique design
Table of contents
Page
Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Ratings and Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-28
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32
Base Unit Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-38
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-43
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-126
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127,128
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129-137
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138,139
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Typical Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141-147
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148-165
Additionally, when the space requires dehumidification only, the Humidi-Mizer system can increase hot discharge gas bypass to the Humidi-MiZer
coil in order to heat the air to the exact
neutral state required no overcooling
or overheating with similar latent capacity as that provided in the full subcooling mode.
TUBES
FINS
MANIFOLD
MICROCHANNELS
SPRING ISOLATION
Features/Benefits (cont)
Design flexibility
The P Series rooftop units with
ComfortLink controls are designed to
meet all customer requirements for new
construction, replacement jobs, or special applications.
The customer can choose from the
following:
CV, SAV or VAV applications
digital scoll compressors
4 or more supply-fan motor sizes
2 sizes of natural gas heat (48 Series
units)
electric heat (50 Series units)
hydronic heat (50 Series units)
Novation microchannel (MCHX)
condenser coils or e-coated MCHX
condenser coils
integrated economizer with low-leak
dampers, barometric relief, or
power exhaust
ultra low leak economizer
return fan, economizer, and high
capacity power exhaust can be
added to size 075-100 units.
extended chassis units are provided
with space and mounting tracks for
a factory or field-installed heating
coil.
standard 2-in. filter tracks are provided but can be field-modified to
accept 4-in. panel filters
Humidi-Mizer adaptive humidification system
Discharge options The units can
be used for vertical discharge, discharge plenum vertical discharge, or
special horizontal applications, such as
replacement or sound-sensitive applications. The horizontal installation allows sound to be attenuated before the
duct penetrates the roof.
Exhaust and return options For
applications requiring higher space exhaust requirements on size 075-100
units, select vertical return and supply
or horizontal return and supply models
with optional high-capacity modulating
power exhaust and integrated economizer features.
For applications requiring high return duct static pressures on sizes 075100, select units with optional return
fan and building pressure control exhaust system. The return fan provides
a separate fan system dedicated to
overcoming flow losses in the return
duct, thus reducing the total selection
load on the units supply fan. The return fan option includes a variable frequency drive (VFD) which modulates
Fan modulation
Supply fan duct pressure control on
VAV models is accomplished via a variable frequency (inverter) drive (VFD).
The VFD controls supply fan airflow to
maintain a user-established duct pressure set point in the units supply duct.
process. The heat exchanger operates under a negative pressure, preventing flue gas leakage into the indoor
supply air.
Flue outlet hoods with wind baffles
are located on the side of the unit, to
minimize the effects of wind on heating operations.
Standard units use 2-stage control,
for unoccupied, morning warm-up and
occupied space heating.
Additional control stages for heating
operation are available by specifying
the staged gas control option.
Modulating control option is available by specifying the modulating gas
control option.
A single hinged panel gains access
to the complete heat exchanger
assembly and controls, for improved
serviceability.
A single point gas connection provides for easy installation.
An LP (liquid propane) conversion
accessory can be field-installed on gas
units without staged or modulating gas
control option (sizes 030-070 for vertical low heat units and sizes 030-050
for vertical high heat units).
Optional modulating gas heat
The modulating gas heat option monitors unit supply-air temperature and
controls the unit heat exchanger to
provide first-stage demand heating
control, with modulation to maintain
user-configured heating supply air temperature set point.
The option also provides full-fire demand heating on heating control command and tempering heat control,
based on user-configured ventilation
supply air temperature set point, to
eliminate cold draft conditions with low
mixed-air temperatures.
The modulating gas control option
consists of a modulating controller capable of ensuring the proper fuel air
mixture at operating firing rates, supply air temperature thermistors with
duct-mounting base, a limit switch temperature thermistor, and stainless steel
heat exchanger tubes.
a48-8637
48 P2 D
030
Option Code
Factory Options
See note below
Voltage Options
1 575-3-60
5 208/230-3-60
6 460-3-60
LEGEND
CV
Constant Volume
SAV Staged Air Volume
VAV
Variable Air Volume
NOTE: Because of the large number of options and the many resulting combinations, the Applied Rooftop Builder software must be
used to generate the 8-digit option code for the unit model number.
Refer to the software for the different choices for unit factoryinstalled options. Once all of the options have been selected, the
software will generate the correct code. Unit options and accessories are listed in the Options and Accessories section on page 29.
50P2,P3,P4,P5 UNITS
a50-8722
50 P2 D 030
6 1 Option Code
Factory Options
See note below
Quality Assurance
Certified to ISO 9001
6
CV
SAV
SCR
VAV
LEGEND
Constant Volume
Staged Air Volume
Electronic Fan Speed Controller
Variable Air Volume
NOTE: Because of the large number of options and the many resulting combinations, the Applied Rooftop Builder software must be
used to generate the 8-digit option code for the unit model number.
Refer to the software for the different choices for unit factoryinstalled options. Once all of the options have been selected, the
software will generate the correct code. Unit options and accessories are listed in the Options and Accessories section on page 29.
UNIT TYPE
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
48P2,P3,P4,P5 Low Heat
48P2,P3,P4,P5 High Heat
50P2,P3,P4,P5
030
035
040
050
055
060
070
075
090
100
MAXIMUM CFM
15,000
15,000
15,000
15,000
15,000
15,000
20,000
20,000
20,000
20,000
19,500
20,000
25,000
25,000
25,000
30,000
30,000
30,000
30,000
30,000
30,000
30,000
30,000
30,000
40,000
37,000
40,000
44,000
37,000
44,000
NOTE: Refer to Application Data section for more information concerning minimum operating airflow in Cooling mode.
EFFICIENCY
(%)
81.0%
81.0%
80.7%
80.7%
80.9%
80.4%
LEGEND
LP Liquid Propane
NOTES:
1. Ratings are approved for altitudes to 2000 ft. At altitudes over
2000 ft, ratings are 4% less for each 1000 ft above sea level.
2. At altitudes up to 2000 ft, the following formula may be used to calculate air temperature rise:
t =
TEMP RISE
(F)
10-40
25-55
10-40
20-50
10-40
20-50
AIRFLOW (Cfm)
Min
Max
6,094
20,000
8,864
19,259
12,142
30,000
14,571
30,000
12,172
44,000
14,517
36,292
EFFICIENCY
(%)
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
LEGEND
TEMP RISE
(F)
10-40
25-55
10-40
20-50
10-40
20-50
AIRFLOW (Cfm)
Min
Max
6,019
20,000
8,754
19,259
12,037
30,000
14,444
30,000
12,037
44,000
14,444
36,111
LP Liquid Propane
NOTES:
1. Ratings are approved for altitudes to 2000 ft. At altitudes over
2000 ft, ratings are 4% less for each 1000 ft above sea level.
2. At altitudes up to 2000 ft, the following formula may be used to calculate air temperature rise:
maximum output capacity
1.10 x air quantity
t =
t =
INPUT
CAPACITY
(1000 Btuh)
244
325
% FULL FIRE
THERMAL
EFFICIENCY %
75%
100%
81.0%
81.0%
OUTPUT
CAPACITY
(1000 Btuh)
197.4
263.3
SECTION 2
SECTION 3
197.4
263.3
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
% FULL FIRE
THERMAL
EFFICIENCY %
75%
100%
80.0%
80.0%
OUTPUT
CAPACITY
(1000 Btuh)
195.0
260.0
SECTION 2
SECTION 3
195.0
260.0
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
% FULL FIRE
THERMAL
EFFICIENCY %
38%
50%
75%
88%
100%
81.0%
81.0%
81.0%
81.0%
81.0%
OUTPUT
CAPACITY
(1000 Btuh)
197.4
263.3
394.9
460.7
526.5
SECTION 2
SECTION 3
197.4
263.3
197.4
263.3
263.3
0.0
0.0
197.4
197.4
263.3
N/A
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
% FULL FIRE
THERMAL
EFFICIENCY %
38%
50%
75%
88%
100%
80.0%
80.0%
80.0%
80.0%
80.0%
OUTPUT
CAPACITY
(1000 Btuh)
195.0
260.0
390.0
455.0
520.0
SECTION 2
SECTION 3
195.0
260.0
195.0
260.0
260.0
0.0
0.0
195.0
195.0
260.0
N/A
N/A
N/A
N/A
N/A
GAS HEATING CAPACITIES UNITS WITH STAGED GAS CONTROL OPTION (cont)
48P2,P3 055-070 LOW HEAT
HEATING
STAGES
1
2
3
4
5
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
% FULL FIRE
THERMAL
EFFICIENCY %
38%
50%
75%
88%
100%
80.7%
80.7%
80.7%
80.7%
80.7%
OUTPUT
CAPACITY
(1000 Btuh)
196.7
262.3
393.4
459.0
524.6
SECTION 2
SECTION 3
196.7
262.3
196.7
262.3
262.3
0.0
0.0
196.7
196.7
262.3
N/A
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
% FULL FIRE
THERMAL
EFFICIENCY %
38%
50%
75%
88%
100%
80.0%
80.0%
80.0%
80.0%
80.0%
OUTPUT
CAPACITY
(1000 Btuh)
195.0
260.0
390.0
455.0
520.0
SECTION 2
SECTION 3
195.0
260.0
195.0
260.0
260.0
0.0
0.0
195.0
195.0
260.0
N/A
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
731
813
894
975
% FULL FIRE
THERMAL
EFFICIENCY %
25%
33%
50%
58%
67%
75%
83%
92%
100%
80.7%
80.7%
80.7%
80.7%
80.7%
80.7%
80.7%
80.7%
80.7%
OUTPUT
CAPACITY
(1000 Btuh)
196.7
262.3
393.4
459.0
524.6
590.1
655.7
721.3
786.8
SECTION 2
SECTION 3
196.7
262.3
196.7
262.3
262.3
196.7
196.7
262.3
262.3
0.0
0.0
196.7
196.7
262.3
196.7
262.3
262.3
262.3
0.0
0.0
0.0
0.0
0.0
196.7
196.7
196.7
262.3
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
731
813
894
975
% FULL FIRE
THERMAL
EFFICIENCY %
25%
33%
50%
58%
67%
75%
83%
92%
100%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
OUTPUT
CAPACITY
(1000 Btuh)
195.0
260.0
390.0
455.0
520.0
585.0
650.0
715.0
780.0
SECTION 2
SECTION 3
195.0
260.0
195.0
260.0
260.0
195.0
195.0
260.0
260.0
0.0
0.0
195.0
195.0
260.0
195.0
260.0
260.0
260.0
0.0
0.0
0.0
0.0
0.0
195.0
195.0
195.0
260.0
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
% FULL FIRE
THERMAL
EFFICIENCY %
38%
50%
75%
88%
100%
80.9%
80.9%
80.9%
80.9%
80.9%
OUTPUT
CAPACITY
(1000 Btuh)
197.2
262.9
394.4
460.1
525.9
SECTION 2
SECTION 3
197.2
262.9
197.2
262.9
262.9
0.0
0.0
197.2
197.2
262.9
N/A
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
% FULL FIRE
THERMAL
EFFICIENCY %
38%
50%
75%
88%
100%
80.0%
80.0%
80.0%
80.0%
80.0%
OUTPUT
CAPACITY
(1000 Btuh)
195.0
260.0
390.0
455.0
520.0
SECTION 2
SECTION 3
195.0
260.0
195.0
260.0
260.0
0.0
0.0
195.0
195.0
260.0
N/A
N/A
N/A
N/A
N/A
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
731
813
894
975
% FULL FIRE
THERMAL
EFFICIENCY %
25%
33%
50%
58%
67%
75%
83%
92%
100%
80.4%
80.4%
80.4%
80.4%
80.4%
80.4%
80.4%
80.4%
80.4%
OUTPUT
CAPACITY
(1000 Btuh)
196.0
261.3
392.0
457.3
522.6
587.9
653.3
718.6
783.9
SECTION 2
SECTION 3
196.0
261.3
196.0
261.3
261.3
196.0
196.0
261.3
261.3
0.0
0.0
196.0
196.0
261.3
196.0
261.3
261.3
261.3
0.0
0.0
0.0
0.0
0.0
196.0
196.0
196.0
261.3
INPUT
CAPACITY
(1000 Btuh)
244
325
488
569
650
731
813
894
975
% FULL FIRE
THERMAL
EFFICIENCY %
25%
33%
50%
58%
67%
75%
83%
92%
100%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
80.0%
OUTPUT
CAPACITY
(1000 Btuh)
195.0
260.0
390.0
455.0
520.0
585.0
650.0
715.0
780.0
SECTION 2
SECTION 3
195.0
260.0
195.0
260.0
260.0
195.0
195.0
260.0
260.0
0.0
0.0
195.0
195.0
260.0
195.0
260.0
260.0
260.0
0.0
0.0
0.0
0.0
0.0
195.0
195.0
195.0
260.0
PERCENT
FULL FIRE
92 - 325
28 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 263
FIRING STAGE
1
Modulating
PERCENT
FULL FIRE
92 - 325
28 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 260
FIRING STAGE
1
Modulating
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
14 - 50%
52 - 88%
64 - 100%
LEGEND
HF High Fire
LF Low Fire
10
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 527
FIRING STAGE
1
Modulating
Modulating
Modulating
0
LF
HF
GAS HEATING CAPACITIES UNITS WITH MODULATING GAS CONTROL OPTION (cont)
48P4,P5 030-050 HIGH HEAT
GAS INPUT
(1000 Btuh)
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
14 - 50%
52 - 88%
64 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
FIRING STAGE
1
Modulating
Modulating
Modulating
0
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
14 - 50%
52 - 88%
64 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 525
FIRING STAGE
1
Modulating
Modulating
Modulating
0
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
14 - 50%
52 - 88%
64 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
FIRING STAGE
1
Modulating
Modulating
Modulating
0
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
579 - 813
660 - 894
741 - 975
9 - 33%
34 - 58%
43 - 67%
59 - 83%
68 - 92%
76 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
463 - 650
528 - 721
593 - 787
FIRING STAGE
1
Modulating
Modulating
Modulating
Modulating
Modulating
Modulating
0
LF
HF
LF
HF
HF
0
0
0
LF
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
579 - 813
660 - 894
741 - 975
9 - 33%
34 - 58%
43 - 67%
59 - 83%
68 - 92%
76 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
463 - 650
528 - 721
593 - 780
FIRING STAGE
1
Modulating
Modulating
Modulating
Modulating
Modulating
Modulating
0
LF
HF
LF
HF
HF
0
0
0
LF
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
14 - 50%
52 - 88%
64 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 526
FIRING STAGE
1
Modulating
Modulating
Modulating
0
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
14 - 50%
52 - 88%
64 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
FIRING STAGE
1
Modulating
Modulating
Modulating
0
LF
HF
LEGEND
HF High Fire
LF Low Fire
11
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
579 - 813
660 - 894
741 - 975
9 - 33%
34 - 58%
43 - 67%
59 - 83%
68 - 92%
76 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
463 - 650
528 - 719
593 - 784
FIRING STAGE
1
Modulating
Modulating
Modulating
Modulating
Modulating
Modulating
0
LF
HF
LF
HF
HF
0
0
0
LF
LF
HF
PERCENT
FULL FIRE
92 - 325
335 - 569
416 - 650
579 - 813
660 - 894
741 - 975
9 - 33%
34 - 58%
43 - 67%
59 - 83%
68 - 92%
76 - 100%
OUTPUT
CAPACITY
(1000 Btuh)
68 - 256
265 - 455
333 - 520
463 - 650
528 - 715
593 - 780
FIRING STAGE
1
Modulating
Modulating
Modulating
Modulating
Modulating
Modulating
0
LF
HF
LF
HF
HF
0
0
0
LF
LF
HF
LEGEND
HF High Fire
LF Low Fire
NO. STAGES
LOW
(kW)
CAPACITY
PER
STAGE (%)
MED
(kW)
CAPACITY
PER
STAGE (%)
HIGH
(kW)
CAPACITY
PER
STAGE (%)
MIN
CFM
MAX
CFM
2
2
2
2
2
29
36
25
36
36
50,100
50,100
50,100
50,100
50,100
59
72
51
72
72
50,100
50,100
50,100
50,100
50,100
88
108
76
108
108
67,100
67,100
67,100
67,100
67,100
9,000
9,000
9,000
9,000
9,000
20,000
20,000
20,000
20,000
20,000
2
2
2
2
2
29
36
25
36
36
50,100
50,100
50,100
50,100
50,100
59
72
51
72
72
50,100
50,100
50,100
50,100
50,100
88
108
76
108
108
67,100
67,100
67,100
67,100
67,100
15,000
15,000
15,000
15,000
15,000
30,000
30,000
30,000
30,000
30,000
108
67,100
216
50,100
15,000
44,000
NOTES:
1. Electric heat options are NOT AVAILABLE on discharge plenum units or size 030-070 horizontal units.
2. Electric heat is available on horizontal size 075-100 units with airfoil fan option only.
12
48P2,P3,P4,P5030
30
Standard Chassis
Extended Chassis
48P2,P3,P4,P5035
35
Standard Chassis
Extended Chassis
5310
5440
5810
5940
5410
5540
5910
6040
5610
5740
6110
6240
5710
5840
6210
6340
Scroll
1...ZP154/1...ZP154
110
2
1...ZP182/1...ZP182
110
2
R-410A
15.4/14.8
18.4/17.6
15.4/24.9
18.4/27.7
17.2/16.0
N/A
17.2/26.1
N/A
Aluminum Novation Heat Exchanger with Microchannel Coils
1
1
33.3
33.3
1
32.1
TXV...1
3...15.0
Double Wavy
Cross Hatched
4...15.0
Double Wavy
Cross Hatched
4...15.0
Double Wavy
Cross Hatched
N/A
N/A
N/A
Low Heat
7
325
263/260
10-40
81/80
High Heat
14
650
527/520
25-55
81/80
Low Heat
7
325
263/260
10-40
81/80
High Heat
14
650
527/520
25-55
81/80
7 (.1285...30)
3.5
5.0...13.0
2
1
14 (.1285...30)
3.5
5.0...13.0
2
2
7 (.1258...30)
3.5
5.0...13.0
2
1
14 (.1258...30)
3.5
5.0...13.0
2
2
Propeller Type
2...30
18,000
1.0...1140
2...30
19,500
1.0...1140
Centrifugal 25 x 25 in.
10,500
15,000
900
111/16
10,500
15,000
900
111/16
7.5
213T
91.7
13.7
3.4
438
2...BX60
17.74-14.30
2...3.0
182T
88.5
11.0
4.1-3.1
4.1
17/16
500-656
656
1000
25
284T
93.6
13.7
6.5
830
2...5VX650
16.63...12.87
2...10
215T
91.7
12
7.0-5.8
6.4
17/16
854-1000
927
1000
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
None
None
Aluminum Frame, Permanent
5...20 x 20 x 2
2...20 x 25 x 1
5...20 x 20 x 1
2...20 x 25 x 1
LEGEND
MBtuh Btuh in Thousands
TXV
Thermostatic Expansion Valve
* 460-3-60 only.
See Power Exhaust Fan Drive Data table on page 28 for more information.
13
14
48P2,P3,P4,P5040
40
Standard Chassis
Extended Chassis
48P2,P3,P4,P5050
50
Standard Chassis
Extended Chassis
5810
5940
6310
6440
6025
6155
6525
6655
6110
6240
6610
6740
6325
6455
6825
6955
Scroll
2...ZP103/1...ZP182
110
2
2...ZP120/2...ZP137
110
2
R-410A
21.6/26.7
29.4/29.0
21.6/39.1
29.4/41.4
31.1/37.2
35.2/36.5
31.1/49.6
35.2/48.9
Aluminum Novation Heat Exchanger with Microchannel Coils
2
2
66.7
66.7
1
45.5
TXV...2
3...15.0
Double Wavy
Cross Hatched
4...15.0
Double Wavy
Cross Hatched
6...16.0
Double Wavy
Cross Hatched
6...16.0
Double Wavy
Cross Hatched
Low Heat
7
325
263/260
10-40
81/80
High Heat
14
650
527/520
25-55
81/80
Low Heat
7
325
263/260
10-40
81/80
High Heat
14
650
527/520
25-55
81/80
7 (.1285...30)
3.5
5.0...13.0
2
1
14 (.1285...30)
3.5
5.0...13.0
2
2
7 (.1285...30)
3.5
5.0...13.0
2
1
14 (.1285...30)
3.5
5.0...13.0
2
2
Propeller Type
3...30
30,000
1.0...1140
4...30
38,000
1.0...1140
Centrifugal 25 x 25 in.
14,000
20,000
900
111/16
7.5
213T
91.7
13.7
3.4
438
2...BX60
17.74-14.30
2...3.0
182T
88.5
11.0
4.1-3.1
4.1
17/16
500-656
656
1000
14,000
20,000
900
111/16
30*
286T
93.6
12.5
6.5
910
3...5VX630
16.63...12.87
2...10
215T
91.7
12
7.0-5.8
6.4
17/16
854-1000
927
1000
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
None
None
Aluminum Frame, Permanent
5...20 x 20 x 2
2...20 x 25 x 1
5...20 x 20 x 1
2...20 x 25 x 1
48P2,P3,P4,P5055-070
BASE UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Base Unit
Low Heat
High Heat
With Economizer
Low Heat
High Heat
COMPRESSORS
Quantity...Type
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
REFRIGERANT
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
Standard Evaporator with Humidi-MiZer System
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with
Humidi-MiZer
CONDENSER COILS
Quantity
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
Fin Type
Tube Type
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
Fin Type
Tube Type
HEATING SECTION
Number of Heat Exchangers
Input (MBtuh)
Output (MBtuh) (Vertical/Horizontal)
Temperature Rise Range (F)
Efficiency (%) (Vertical/Horizontal)
Burner Orifice Diameter
Quantity (in. ...drill no.)
Manifold Pressure (in. wg)
Line Pressure (in. wg) (min...max)
Firing Stages
Number of Gas Valves
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
SUPPLY FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Speed (rpm)
Belts Quantity...Type
Center Distance Range (in.)
OPTIONAL POWER EXHAUST*
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Resulting Fan Rpm
Maximum Allowable Rpm
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Optional)
Quantity...Size (in.)
Bag Filter
Prefilter
Cartridge Filters with
High Velocity Prefilters (Optional)
Quantity...Size (in.)
Cartridge Filter
Prefilter
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
48P2,P3,P4,P5055
55
Standard Chassis
Extended Chassis
48P2,P3,P4,P5060
60
Standard Chassis
Extended Chassis
48P2,P3,P4,P5070
70
Standard Chassis
Extended Chassis
7810
7940
8360
8490
7865
7995
8415
8545
8205
8335
8755
8885
8340
8470
8890
9020
8395
8525
8945
9075
8735
8865
9285
9415
2...ZP137/2...ZP137
110
2
Scroll
2...ZP154/2...ZP154
110
2
R-410A
1...ZP154,1...ZP182/1...ZP154,1...ZP182
110
2
37.6/37.9
37.6/50.3
43.5/42.8
43.5/55.2
37.6/37.9
37.6/50.3
44.6/43.5
44.6/55.9
39.5/42.0
39.5/54.4
49.0/50.0
49.0/62.4
2
66.7
4
106.7
2
61.5
TXV...2
4...15
Double Wavy
Cross Hatched
4...15
Double Wavy
Cross Hatched
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
Low Heat
High Heat
14
21
650
975
525/520
787/780
10-40
20-50
81/80
81/80
6...16
Double Wavy
Cross Hatched
Low Heat
High Heat
14
21
650
975
525/520
787/780
10-40
20-50
81/80
81/80
6...16
Double Wavy
Cross Hatched
Low Heat
High Heat
14
21
650
975
525/520
787/780
10-40
20-50
81/80
81/80
14 (.1285...30)
3.5
5.0...13.0
2
2
21 (.1285...30)
3.5
5.0...13.0
2
3
4...30
36,000
1.0...1140
17,500
25,000
800
111/16
15
254T
93.0
13.7
4.5
575
2...5VX1230
48.25-44.00
2...5
184T
89.5
740
1000
14 (.1285...30)
21 (.1285...30)
14 (.1285...30)
21 (.1285...30)
3.5
3.5
3.5
3.5
5.0...13.0
5.0...13.0
5.0...13.0
5.0...13.0
2
2
2
2
2
3
2
3
Propeller Type
4...30
4...30
36,600
39,000
1.0...1140
1.0...1140
Centrifugal 30 x 27.5 in.
21,000
24,500
30,000
30,000
800
800
111/16
111/16
(Any motor available on any unit)
20
25
30
40
256T
284T
286T
S324T
93.6
93.6
93.6
94.5
13.7
13.7
15.5
16.1
5.1
5.5
5.9
6.7
651
703
711
740
2...5VX1230
2...5VX1230
2...5VX1230
3...5VX1250
48.25-44.00
48.50-44.25
48.50-44.25
48.25-44.00
Centrifugal, 18 x 15 in. (Any motor available on any unit)
2...7.5
2...10
213T
215T
91.7
91.7
820
920
1000
1000
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
4...25 x 16 x 1, 2...20 x 16 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
Aluminum Frame, Permanent
12...16 x 25 x 1, 2...16 x 20 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
LEGEND
MBtuh Btuh in Thousands
TXV
Thermostatic Expansion Valve
*See Power Exhaust Fan Drive Data table on page 28 for more information.
15
48P2,P3,P4,P5075
75
Standard
Extended
Chassis
Chassis
48P2,P3,P4,P5100
100
Standard
Extended
Chassis
Chassis
9065
9195
9615
9745
9665
9795
10,215
10,345
9685
9815
10,235
10,365
9595
9725
10,145
10,275
10,195
10,325
10,745
10,875
10,215
10,345
10,765
10,895
2...ZP182/2...ZP182
110
2
Scroll
3...ZP154,3...ZP154
110
2
R-410A
3...ZP154,3...ZP182
110
2
39.5/42.0
39.5/54.4
49.0/50.0
49.0/62.4
50.4/51.3
50.4/69.1
61.5/62.9
61.5/80.7
50.8/52.8
50.8/70.6
59.3/62.8
59.3/80.6
4
106.7
6
160.0
2
61.5
TXV...2
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
Low Heat
High Heat
2
3
650
975
526/520
784/780
10-40
20-50
81/80
81/80
7 (.1285...30)
3.5
5.0...13.0
2
7 (.1285...30)
3.5
5.0...13.0
3
4...30
39,000
1.0...1140
24,500
30,000
680
111/16
30
S268T
93.6
18.5
5.3
501
3...5VX1320
47.88-45.01
24,500
30,000
1846
211/16
30
S268T
93.6
9.7
7.5
1353
2...5VX1150
42.96...45.82
LEGEND
MBtuh Btuh in Thousands
TXV Thermostatic Expansion Valve
*See page 22 for high-capacity power exhaust information. See Power Exhaust
Fan Drive Data table on page 28 for more information.
16
48P2,P3,P4,P5090
90
Standard
Extended
Chassis
Chassis
4...15
Double Wavy
Cross Hatched
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
Low Heat
High Heat
2
3
650
975
526/520
784/780
10-40
20-50
81/80
81/80
6...16
Double Wavy
Cross Hatched
Low Heat
High Heat
2
3
650
975
526/520
784/780
10-40
20-50
81/80
81/80
7 (.1285...30)
7 (.1285...30)
3.5
3.5
5.0...13.0
5.0...13.0
2
3
Propeller Type
6...30
58,000
1.0...1140
Forward Curved Centrifugal 36 x 30 in.
29,750
34,000
680
111/16
(Any motor available on any unit)
40
50
S324T
S36T
94.5
94.5
18.5
18.5
5.7
6.5
539
615
4...5VX1320
4...5VX1320
47.64-44.76
47.42-44.52
Airfoil
29,750
34,000
1846
211/16
7 (.1285...30)
3.5
5.0...13.0
2
7 (.1285...30)
3.5
5.0...13.0
3
6...30
58,000
1.0...1140
35,000
40,000
680
111/16
60
S364T
95.4
18.5
7.1
672
4...5VX1320
47.42-44.52
35,000
40,000
1846
211/16
75
365T
95.4
10.8
11.1
1799
3...5VX1230
42.45...45.35
48P2,P3,P4,P5075-100 (cont)
BASE UNIT
OPTIONAL POWER EXHAUST*
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
30% and 65% Pleated (Optional)
Quantity...Size (in.)
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
48P2,P3,P4,P5075
48P2,P3,P4,P5090
Centrifugal, 18 x 15 in. (Any motor available on any unit.)
2...7.5
213T
91.7
10.6
5.0
17/16
820
1000
48P2,P3,P4,P5100
2...5
184T
89.5
10.6
4.5
17/16
740
1000
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
4...25 x 16 x 1, 2...20 x 16 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
Aluminum Frame, Permanent
12...16 x 25 x 1, 2...16 x 20 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
2...10
215T
91.7
10.6
5.6
17/16
920
1000
12...16 x 25 x 1, 2...16 x 20 x 1
LEGEND
MBtuh Btuh in Thousands
TXV Thermostatic Expansion Valve
*See page 22 for high-capacity power exhaust information. See Power Exhaust
Fan Drive Data table on page 28 for more information.
17
TXV
50P2,P3,P4,P5030
30
Standard Chassis
Extended Chassis
4810
5310
4910
5410
5110
5610
5210
5710
5110
5410
5610
5910
5210
5510
5710
6010
Scroll
1...ZP154/1...ZP154
110
2
1...ZP182/1...ZP182
110
2
R-410A
15.4/14.8
18.4/17.6
15.4/24.9
18.4/27.7
17.2/16.0
N/A
17.2/26.1
N/A
Aluminum Novation Heat Exchanger with Microchannel Coils
1
33.3
1
33.3
1
32.1
TXV...1
3...15.0
Double Wavy
Cross Hatched
4...15.0
Double Wavy
Cross Hatched
4...15.0
Double Wavy
Cross Hatched
N/A
N/A
N/A
Propeller Type
2...30
18,000
1.0...1140
2...30
19,500
1.0...1140
Centrifugal 25 x 25 in.
10,500
15,000
900
111/16
7.5
213T
91.7
13.7
3.4
438
2...BX60
17.74-14.30
2...3.0
182T
88.5
11.0
4.1-3.1
4.1
17/16
500-656
656
1000
LEGEND
Thermostatic Expansion Valve
* 460-3-60 only.
See Power Exhaust Fan Drive Data table on page 28 for more information.
18
50P2,P3,P4,P5035
35
Standard Chassis
Extended Chassis
10,500
15,000
900
111/16
25
284T
93.6
13.7
6.5
830
2...5VX650
16.63...12.87
2...10
215T
91.7
12
7.0-5.8
6.4
17/16
854-1000
927
1000
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
None
None
Aluminum Frame, Permanent
5...20 x 20 x 2, 2...20 x 25 x 1
5...20 x 20 x 1, 2...20 x 25 x 1
50P2,P3,P4,P5030-050 (cont)
BASE UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Base Unit
Vertical Discharge
Horizontal Discharge and Vertical Discharge
with Discharge Plenum
With Economizer
Vertical Discharge
Horizontal Discharge and Vertical Discharge
with Discharge Plenum
COMPRESSORS
Quantity...Type
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
REFRIGERANT
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
Standard Evaporator with Humidi-MiZer System
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with Humidi-MiZer
CONDENSER COILS
Quantity
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
Fin Type
Tube Type
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
Fin Type
Tube Type
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
SUPPLY FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Speed (rpm)
Belts Quantity...Type
Center Distance Range (in.)
OPTIONAL POWER EXHAUST
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter Range (in.)
Motor Pulley Pitch Diameter Factory Setup (in.)
Blower Shaft Diameter at Pulley (in.)
Fan Rpm Range
Factory Setup Fan Rpm
Maximum Allowable Rpm
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
High Efficiency (90%) Bag Filters with High Velocity
Prefilters (Optional)
Quantity...Size (in.)
Bag Filter
Prefilter
Cartridge Filters with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Cartridge Filter
Prefilter
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
TXV
50P2,P3,P4,P5040
40
Standard Chassis
Extended Chassis
50P2,P3,P4,P5050
50
Standard Chassis
Extended Chassis
5310
5810
5525
6025
5610
6110
5825
6325
5610
6110
5825
6325
5910
6410
6125
6625
Scroll
2...ZP103/1...ZP182
110
2
2...ZP120/2...ZP137
110
2
R-410A
21.6/26.7
29.4/29.0
21.6/39.1
29.4/41.4
31.1/37.2
35.2/36.5
31.1/49.6
35.2/48.9
Aluminum Novation Heat Exchanger with Microchannel Coils
2
2
66.7
66.7
1
45.5
TXV...2
3...15.0
Double Wavy
Cross Hatched
4...15.0
Double Wavy
Cross Hatched
6...16.0
Double Wavy
Cross Hatched
6...16.0
Double Wavy
Cross Hatched
Propeller Type
3...30
30,000
1.0...1140
4...30
38,000
1.0...1140
Centrifugal 25 x 25 in.
14,000
20,000
900
111/16
7.5
213T
91.7
13.7
3.4
438
2...BX60
17.74-14.30
2...3.0
182T
88.5
11.0
4.1-3.1
4.1
17/16
500-656
656
1000
14,000
20,000
900
111/16
30*
286T
93.6
12.5
6.5
910
3...5VX630
16.63...12.87
2...10
215T
91.7
12
7.0-5.8
6.4
17/16
854-1000
927
1000
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
None
None
Aluminum Frame, Permanent
5...20 x 20 x 2, 2...20 x 25 x 1
5...20 x 20 x 1, 2...20 x 25 x 1
LEGEND
Thermostatic Expansion Valve
* 460-3-60 only.
See Power Exhaust Fan Drive Data table on page 28 for more information.
19
50P2,P3,P4,P5055
55
Standard Chassis Extended Chassis
TXV
7370
6875
7425
7215
7765
7370
7920
7425
7975
7765
8315
7350
7900
7900
8450
7405
7955
7955
8505
7745
8295
8295
8845
2...ZP137/2...ZP137
110
2
Scroll
2...ZP154/2...ZP154
110
2
R-410A
1...ZP154,1...ZP182/1...ZP154,1...ZP182
110
2
37.6/37.9
37.6/37.9
39.5/42.0
37.6/50.3
37.6/50.3
39.5/54.4
43.5/42.8
43.5/55.2
44.6/43.5
44.6/55.9
49.0/50.0
49.0/62.4
2
66.7
4
106.7
2
61.5
TXV...2
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
4...30
36,000
1.0...1140
17,500
25,000
800
111/16
15
254T
93.0
13.7
4.5
575
2...5VX1230
48.25-44.00
2...5
184T
89.5
740
1000
4...15
Double Wavy
Cross Hatched
4...15
Double Wavy
Cross Hatched
6...16
6...16
Double Wavy
Double Wavy
Cross Hatched
Cross Hatched
Propeller Type
4...30
4...30
36,600
39,000
1.0...1140
1.0...1140
Centrifugal 30 x 27.5 in.
21,000
24,500
30,000
30,000
800
800
111/16
111/16
(Any motor available on any unit)
20
25
30
40*
256T
284T
286T
S324T
93.6
93.6
93.6
94.5
13.7
13.7
15.5
16.1
5.1
5.5
5.9
6.7
651
703
711
740
2...5VX1230
2...5VX1230
2...5VX1230
3...5VX1250
48.25-44.00
48.50-44.25
48.50-44.25
48.25-44.00
Centrifugal, 18 x 15 in. (Any motor available on any unit)
2...7.5
2...10
213T
215T
91.7
91.7
820
920
1000
1000
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
4...25 x 16 x 1
2...20 x 16 x 1
4...25 x 16 x 1
2...20 x 16 x 1
Aluminum Frame, Permanent
12...16 x 25 x 1
2...16 x 20 x 1
4...25 x 16 x 1
2...20 x 16 x 1
12...16 x 25 x 1
2...16 x 20 x 1
LEGEND
Thermostatic Expansion Valve
20
50P2,P3,P4,P5070
70
Standard Chassis Extended Chassis
6820
50P2,P3,P4,P5060
60
Standard Chassis Extended Chassis
12...16 x 25 x 1
2...16 x 20 x 1
50P2,P3,P4,P5075-100
BASE UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Base Unit
Vertical Discharge
Horizontal Discharge and Vertical Discharge
with Discharge Plenum
With Economizer
Vertical Discharge
Horizontal Discharge and Vertical Discharge
with Discharge Plenum
COMPRESSORS
Quantity...Type
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
REFRIGERANT
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
Standard Evaporator with Humidi-MiZer System
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with
Humidi-MiZer
CONDENSER COILS
Quantity
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
Fin Type
Tube Type
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
Fin Type
Tube Type
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp (ea)...rpm
STANDARD SUPPLY FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
STANDARD SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Belts Quantity...Type
Center Distance Range (in.)
ALTERNATE, AIRFOIL FAN
Nominal Airflow (cfm)
Maximum Allowable Airflow (cfm)
Maximum Allowable Wheel Speed (rpm)
Shaft Diameter at Pulley (in.)
ALTERNATE SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Belts Quantity...Type
Center Distance Range (in.)
OPTIONAL POWER EXHAUST*
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
30% and 65% Pleated (Optional)
Quantity...Size (in.)
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
TXV
50P2,P3,P4,P5075
75
50P2,P3,P4,P5090
90
50P2,P3,P4,P5100
100
Standard
Chassis
Extended
Chassis
Standard
Chassis
Extended
Chassis
Standard
Chassis
Extended
Chassis
8665
9215
9265
9815
9285
9835
9195
9745
9795
10,345
9815
10,365
2...ZP182/2...ZP182
110
2
Scroll
3...ZP154,3...ZP154
110
2
R-410A
3...ZP154,3...ZP182
110
2
39.5/42.0
39.5/54.4
49.0/50.0
49.0/62.4
50.4/51.3
50.4/69.1
61.5/62.9
61.5/80.7
50.8/52.8
50.8/70.6
59.3/62.8
59.3/80.6
4
106.7
6
160.0
2
61.5
TXV...2
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
4...30
39,000
1.0...1140
24,500
30,000
680
111/16
30
S268T
93.6
18.5
5.3
501
3...5VX1320
47.88-45.01
24,500
30,000
1846
211/16
30
S268T
93.6
9.7
7.5
1353
2...5VX1150
42.96...45.82
2...5
184T
89.5
10.6
4.5
17/16
740
1000
12...20 x 25 x 2
12...20 x 20 x 2
12...20 x 25 x 2
12...20 x 20 x 2
4...25 x 16 x 1
2...20 x 16 x 1
12...16 x 25 x 1
2...16 x 20 x 1
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
Propeller Type
6...30
58,000
1.0...1140
Forward Curved Centrifugal 36 x 30 in.
29,750
34,000
680
111/16
(Any motor available on any unit)
40
50
S324T
S36T
94.5
94.5
18.5
18.5
5.7
6.5
539
615
4...5VX1320
4...5VX1320
47.64-44.76
47.42-44.52
Airfoil
29,750
34,000
1846
211/16
(Any motor available on any unit)
40
50
60
S324T
S36T
S364T
94.5
94.5
95.4
10.2
8.9
8.9
8.7
8.1
8.7
1493
1593
1711
2...5VX1180
3...5VX1150
3...5VX1150
42.96...45.57
42.96...45.57
42.45...45.35
Centrifugal, 18 x 15 in. (Any motor available on any unit.)
2...7.5
213T
91.7
10.6
5.0
17/16
820
1000
12...20 x 25 x 2
12...20 x 20 x 2
12...20 x 25 x 2
12...20 x 20 x 2
4...25 x 16 x 1
2...20 x 16 x 1
Aluminum Frame, Permanent
12...16 x 25 x 1
2...16 x 20 x 1
4...15
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
6...30
58,000
1.0...1140
35,000
40,000
680
111/16
60
S364T
95.4
18.5
7.1
672
4...5VX1320
47.42-44.52
35,000
40,000
1846
211/16
75
365T
95.4
10.8
11.1
1799
3...5VX1230
42.45...45.35
2...10
215T
91.7
10.6
5.6
17/16
920
1000
12...20 x 25 x 2
12...20 x 20 x 2
12...20 x 25 x 2
12...20 x 20 x 2
4...25 x 16 x 1
2...20 x 16 x 1
12...16 x 25 x 1
2...16 x 20 x 1
LEGEND
Thermostatic Expansion Valve
* See page 22 for high-capacity power exhaust information. See Power Exhaust
Fan Drive Data table on page 28 for more information.
21
030-050
055-100
-in. OD copper tubes, aluminum plate fins, galvanized steel frame
22.6
(2) sections: total 27.1
28
211
Half
Half
(1) 21/2 NPT
(1) 21/2 NPT
Steel
0.5272
Steel
0.6327
HEADER MATERIAL
INTERNAL VOLUME (cu ft)
1...20
256T
93.6
8.5
5.3
215/16
1104
1447
1...40
324T
93.8
8.5
6.7
215/16
1396
1447
POWER EXHAUST
Total Hp
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
Fan Sheave Pitch Diameter (in.)
Motor Sheave Pitch Diameter (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
Belts Quantity...Type
030-075
090,100
Aluminum Novation Heat Exchanger with Microchannel Coil Technology
1
1
26.7
33.3
STAGING SEQUENCES
SIZES 030,035
STAGE
COMP
A1
B1
UNIT
030
035
SEQUENCE
1*
1
Compressor Status
ON
ON
OFF
OFF
Capacity 48/50P
36%
50%
38%
50%
0
OFF
OFF
0%
0%
COMP
A1*
B1
UNIT
030
035
0
OFF
OFF
0%
0%
SEQUENCE
1
2
Compressor Status
ON
ON
OFF
ON
Capacity 48/50P
25% to 50%
75% to 100%
25% to 50%
75% to 100%
*On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.
22
COMP
A1
B1
B2
UNIT
040
1*
OFF
OFF
OFF
ON
OFF
OFF
0%
36%
SEQUENCE
1
2
Compressor Status
ON
ON
OFF
ON
OFF
OFF
Capacity 48/50P
47%
73%
3
ON
ON
ON
100%
STAGE
0
OFF
OFF
OFF
0%
SEQUENCE
1
2
Compressor Status
ON
ON
OFF
ON
OFF
OFF
Capacity 48/50P
23% to 47% 50% to 73%
3
ON
ON
ON
77% to 100%
*On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.
OFF
OFF
OFF
OFF
ON
OFF
0%
27%
SEQUENCE
2
3
Compressor Status
ON
ON
OFF
ON
OFF
OFF
Capacity 48/50P
47%
73%
SIZES 050-075
4
ON
ON
ON
100%
STAGE
COMP
A1
A2
B1
B2
UNIT
050
055
060
070
075
1*
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
0%
0%
0%
0%
0%
15%
17%
18%
16%
19%
SEQUENCE
1
2
Compressor Status
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
Capacity 48/50P
23%
50%
25%
50%
25%
50%
23%
46%
25%
50%
ON
ON
ON
OFF
ON
ON
ON
ON
73%
75%
75%
73%
75%
100%
100%
100%
100%
100%
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
0%
0%
0%
0%
0%
12% to 23%
13% to 25%
13% to 25%
11% to 23%
13% to 25%
SEQUENCE
2
Compressor Status
ON
OFF
ON
OFF
Capacity 48/50P
38% to 50%
38% to 50%
38% to 50%
34% to 46%
38% to 50%
ON
ON
ON
OFF
ON
ON
ON
ON
62% to 73%
63% to 75%
63% to 75%
61% to 73%
63% to 75%
88% to 100%
88% to 100%
88% to 100%
89% to 100%
88% to 100%
*On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.
SIZES 090-100
STAGE
COMP
A1
A2
A3
B1
B2
B3
UNIT
090
100
1*
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
0%
0%
12%
11%
17%
15%
SEQUENCE
2
3
Compressor Status
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
Capacity 48/50P
33%
50%
33%
49%
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
67%
67%
83%
82%
100%
100%
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
0%
0%
8% to 17%
8% to 15%
25% to 33%
26% to 33%
SEQUENCE
3
4
Compressor Status
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
Capacity 48/50P
42% to 50%
58% to 67%
41% to 49%
59% to 67%
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
75% to 83%
74% to 82%
92% to 100%
92% to 100%
*On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.
23
B
2
1
A
48P2,P3,P4,P5 UNITS
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
No Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
High Heat
No Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
with Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
High Heat
with Extended Chassis
SIZE
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
SIZE
075
090
100
075
090
100
075
090
100
075
090
100
1
2002
2056
1983
2079
2408
2417
2950
3385
3255
3248
2034
2088
2013
2108
2443
2452
2991
3444
3307
3303
2166
2223
2148
2244
2558
2567
3117
3551
3419
3409
2197
2253
2177
2272
2592
2602
3158
3610
3471
3463
1
4171
4004
4002
4230
4058
4054
6905
6484
6620
6969
6541
6679
4
2000
2053
1981
2076
2404
2414
2303
2643
2691
2686
2032
2085
2010
2105
2439
2449
2335
2689
2734
2731
2163
2220
2145
2241
2554
2563
2434
2773
2827
2819
2194
2250
2174
2269
2589
2598
2466
2818
2870
2864
TOTAL
(lb)
6,019
6,169
6,710
6,925
9,220
9,275
9,615
10,665
11,265
11,285
6,149
6,299
6,840
7,055
9,350
9,405
9,745
10,795
11,395
11,415
6,519
6,669
7,210
7,425
9,770
9,825
10,165
11,215
11,815
11,835
6,649
6,799
7,340
7,555
9,900
9,955
10,295
11,345
11,945
11,965
A
in.
170 5/8
170 7/8
198 1/4
201 1/4
228 7/8
228 1/2
244 5/8
253 1/8
261
260
169 3/4
170
197 3/8
200 3/8
229
228 1/2
244 3/4
254 3/8
262 1/8
261 1/4
187 1/8
187 3/4
214 3/4
217 7/8
242 5/8
242 1/8
258 7/8
266 3/4
274 5/8
273 3/8
186 1/8
186 5/8
213 3/4
216 7/8
242 3/4
242 1/4
258 1/2
268
275 3/4
274 3/4
B
in.
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
4
3256
3311
3309
3302
3356
3352
5391
5362
5474
5441
5409
5523
TOTAL
(lb)
13,499
14,097
14,119
13,629
14,227
14,249
14,049
14,647
14,669
14,179
14,777
14,799
A
in.
290
297 5/8
297 1/8
291 3/8
299
298 1/4
483 1/2
484 3/8
493 3/4
483 1/2
484 1/4
493 3/4
B
in.
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
24
B
2
1
A
48P2,P3,P4,P5 UNITS
WITH OPTIONAL RETURN/EXHAUST FAN
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
Vertical Supply/Return
Horizontal Supply/Return
High Heat
Vertical Supply/Return
Horizontal Supply/Return
Low Heat with Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
High Heat with Extended Chassis
SIZE
075
090
100
075
090
100
075
090
100
075
090
100
1
3470
3327
3302
3543
3377
3370
3609
3467
3437
3681
3517
3505
4
2709
2751
2730
2766
2793
2787
2818
2867
2842
2874
2908
2898
TOTAL
(lb)
12,321
12,921
12,941
12,451
13,051
13,071
12,871
13,471
13,491
13,001
13,601
13,621
A
in.
224 5/8
232 5/8
230 3/8
226 7/8
233 3/4
232 7/8
236 1/4
244 1/4
241 3/4
238 1/2
245 3/8
244 1/4
B
in.
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
B
2
1
A
50P2,P3,P4,P5 UNITS
50P2,P3 Vertical Supply/Return
No Discharge Plenum
No Extended Chassis
SIZE
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
1
1848
1901
1826
1921
2204
2215
2984
3219
3108
3101
1727
1770
1749
1842
2321
2331
2847
4
1845
1898
1824
1919
2201
2212
2329
2514
2570
2564
1725
1768
1746
1839
2318
2328
2223
TOTAL
(lb)
5,519
5,669
6,210
6,425
8,230
8,285
8,625
10,265
10,865
10,885
5,819
5,969
6,510
6,725
8,780
8,835
9,175
A
in.
159 1/8
159 3/8
186 1/8
189 1/4
212 5/8
212 1/4
250 1/2
250 1/8
258 3/8
257 1/4
152 1/4
152 1/8
180 1/8
183 5/8
231 3/4
231 1/4
247 1/2
B
in.
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
25
B
2
1
A
50P2,P3,P4,P5 UNITS
50P2,P3 Vertical Supply/Return
with Extended Chassis
SIZE
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
SIZE
075
090
100
075
090
100
SIZE
075
090
100
075
090
100
1
2009
2067
1992
2086
2350
2361
3159
3398
3282
3272
1872
1919
1899
1992
2467
2476
2683
4
2006
2064
1989
2084
2347
2357
2467
2653
2714
2706
1869
1916
1896
1990
2464
2473
2679
1
3290
3166
3163
3430
3306
3299
4
2568
2618
2615
2678
2734
2728
1
4006
3857
3854
6709
6308
6441
4
3128
3189
3187
5238
5216
5326
TOTAL
(lb)
6,019
6,169
6,710
6,925
8,780
8,835
9,175
10,815
11,415
11,435
6,319
6,469
7,010
7,225
9,330
9,385
9,725
TOTAL
(lb)
11,921
12,521
12,541
12,471
13,071
13,091
TOTAL
(lb)
13,099
13,697
13,719
13,649
14,247
14,269
A
in.
175 1/2
176 1/8
202 3/4
205 7/8
226
225 5/8
264 3/4
264 5/8
272 7/8
271 5/8
166 7/8
167 1/8
195 1/4
198 7/8
245 1/8
244 5/8
260 3/4
B
in.
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
A
in.
220 1/8
228 3/8
227 3/4
231 3/4
240 1/8
239 1/8
B
in.
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
A
in.
287 1/8
295 1/8
294 3/8
483 1/2
484 3/8
493 7/8
B
in.
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
LEGEND
PE Power Exhaust
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
26
030,035
140
300
710
200
700
040,050
140
300
710
200
800
455
545
390
455
545
545
20
35
120
495
545
480
495
545
545
20
35
150
20
20
35
35
53
53
53
53
53
152
150
72
150
20
20
35
35
53
53
53
53
53
152
300
72
150
075
250
625
530
710
200
900
090
250
625
530
710
200
900
100
250
625
530
710
200
900
605
1200
560
605
545
1200
20
40
145
605
1200
560
605
545
1200
20
40
145
605
560
605
545
20
40
210
605
700
605
605
700
20
210
605
700
605
605
700
20
210
605
700
605
605
700
20
210
20
20
35
35
53
53
53
53
53
152
300
72
180
20
20
35
35
53
53
53
53
53
152
300
72
180
20
20
35
35
53
53
53
53
53
152
300
72
180
20
20
35
35
53
53
53
53
53
152
300
350
72
180
20
20
35
35
53
53
53
53
53
152
300
350
92
180
20
20
35
35
53
53
53
53
53
152
300
350
92
180
055
140
540
530
710
200
900
SHAFT
DIA (in.)
SPEED
(rpm)
MOTOR
SHEAVE
MOTOR
PITCH DIA. (in.)
WHEEL
SHEAVE
WHEEL
PITCH DIA. (in.)
QUANTITY
...BELT
13/8
438
2BK36
3.4
2B5V136
13.7
2...BX60
10
13/8
549
2B5V42
4.3
2B5V136
13.7
2...5VX630
15
15/8
626
2B5V48
4.9
2B5V136
13.7
2...5VX630
20
15/8
703
2B5V54
5.5
2B5V136
13.7
2...5VX630
25
17/8
830
2B5V64
6.5
2B5V136
13.7
2...5VX650
30*
17/8
910
3B5V64
6.5
3B5V124
12.5
3...5VX630
15
15/8
575
2B5V44
4.5
2B5V136
13.7
20
15/8
651
2B5V50
5.1
2B5V136
13.7
25
17/8
703
2B5V54
5.5
2B5V136
13.7
30
17/8
711
2B5V62
5.9
2B5V154
15.5
40
21/8
740
3B5V66
6.7
3B5V160
16.1
2...5VX1230
2...5VX1120**
2...5VX1230
2...5XV1150**
2...5VX1230
2...5VX1150**
2...5VX1230
2...5VX1180**
3...5VX1250
3...5VX1180**
Sizes 055-070
501
3B5V52
5.33
B5V184
18.5
3...5VX1320
40
21/8
539
4B5V56
5.74
B5V184
18.5
4...5VX1320
50
21/8
615
4B5V64
6.54
B5V184
18.5
4...5VX1320
60
23/8
672
4B5V70
7.14
B5V184
18.5
4...5VX1320
1353
2B5V74
7.5
2Q5V97
9.7
2...5VX1150
40
21/8
1493
2B5V86
8.7
2Q5V103
10.2
2...5VX1180
50
21/8
1593
3B5V80
8.1
3R5V90
8.9
3...5VX1150
60
23/8
1711
3B5V86
8.7
3R5V90
8.9
3...5VX1150
75
23/8
1799
3B5V110
11.1
3R5V109
10.8
3...5VX1230
27
FAN
SPEED
RPM
MOTOR SHEAVE
Pitch
Part
Diameter
Number
(in.)
BLOWER SHEAVE
Pitch
Part
Diameter
Number
(in.)
48/50P2,P3 UNITS
CENTER
BELTS
DISTANCE
QTY...P/N
RANGE (in.)
48/50P4,P5 UNITS
CENTER
BELTS
DISTANCE
QTY...P/N
RANGE (in.)
1 1 /8
1 1 /8
13/8
13/8
656/500
785/621
882/717
1000/854
1VP44L
1VP50L
1VP65
1VP75
4.1-3.1
4.7-3.7
6.0-4.8
7.0-5.8
BK115
BK110
BK130
BK130
11
10.4
12
12
1...BX71
1...BX71
1...BX77
1...BX79
23.62-26.50
23.62-26.50
23.62-26.50
23.62-26.50
1...BX46
1...BX46
1...BX53
1...BX53
11.40-13.26
11.16-13.05
11.40-13.26
11.04-12.95
1 1 /8
13/8
13/8
740
820
920
2P3V45
2P3V50
2P3V56
4.5
5.0
5.6
2Q3V106
2Q3V106
2Q3V106
10.6
10.6
10.6
2...3VX71
2...3VX71
2...3VX75
22.71-26.38
22.71-26.38
22.71-26.38
2...3VX50
2...3VX50
2...3VX50
10.91-13.30
10.78-13.20
10.78-13.20
HIGH-CAPACITY POWER EXHAUST FAN DRIVE DATA (Two Drive Sets Per Unit)
(Size 075-100 Units Only)
TOTAL
HP
MOTOR
QTY...HP
MOTOR
SHAFT
DIAMETER
(in.)
FAN
SPEED
RPM
20
30
40
50
60
2...10
2...15
2...20
2...25
2...30
1.375
1.625
1.625
1.875
1.875
714
841
928
1020
1094
MOTOR SHEAVE
Pitch
Part
Diameter
Number
(in.)
2B5V48
4.8
2B5V58
5.8
2B5V58
5.9
2B5V64
6.5
2B5V68
6.9
BLOWER SHEAVE
Pitch
Part
Diameter
Number
(in.)
2B5V124
12.4
2B5V124
12.4
2B5V110
11.1
2B5V110
11.1
2B5V110
11.1
BELTS
QTY...P/N
CENTER
DISTANCE
RANGE (in.)
2...BX93
2...BX93
2...5VX950
2...5VX950
2...5VX950
32.8 to 36.7
32.6 to 36.5
32.6 to 36.5
32.5 to 36.3
32.5 to 36.3
OPTIONAL RETURN/EXHAUST FAN DRIVE DATA (One Drive Set Per Unit)
(Size 075-100 Units Only)
TOTAL
HP
MOTOR
QTY...HP
MOTOR
SHAFT
DIAMETER
(in.)
FAN
SPEED
RPM
20
25
30
40
1...20
1...25
1...30
1...40
1.625
1.875
1.875
2.125
1104
1209
1271
1396
28
MOTOR SHEAVE
Pitch
Diameter
(in.)
3B5V52
5.3
3B5V66
6.7
3B5V60
6.1
3B5V66
6.7
Part
Number
BLOWER SHEAVE
Pitch
Part
Diameter
Number
(in.)
3R5V85
8.5
3R5V97
9.8
3R5V85
8.5
3R5V85
8.5
BELTS
QTY...P/N
CENTER
DISTANCE
RANGE (in.)
3...5VX1000
3...5VX1060
3...5VX1030
3...5VX1060
38.1 to 41.0
38.9 to 41.8
38.9 to 41.8
39.9 to 42.8
LEGEND
Aluminum
Copper
Engineered-To-Order
Ground Fault Interrrupt
Indoor Fan Motor
Microchannel Heat Exchanger
Silicon Controlled Rectifier
Ultraviolet
Variable Frequency Drive
OPTION*
ACCESSORY
SPECIAL ORDER**
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
*Factory installed.
Field installed.
**A special order is offered to meet specific customer requirements. Quotations
for special order options can be requested via the Carrier ETO process. Lead
times and prices vary with the option.
Standard 2-in. filter track may be field converted to accept 4-in. filters.
29
OPTION*
ACCESSORY
X
X
SPECIAL ORDER**
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
STANDARD CHASSIS
a48-8427
a48-8426
30
COIL
COMPARTMENT
a48-8428
Vertical discharge with optional high-capacity modulating power exhaust system This vertical discharge arrangement adds a factory-installed extended rear
plenum to house the integrated economizer and highcapacity modulating power exhaust systems (standard features on these models). Return air enters unit through bottom opening upstream of the power exhaust system and
follows a straight-through path to the supply fan and into
the heating section, where it exits unit through bottom supply air outlet. Ductwork is attached to accessory roof curb.
OPTIONAL HIGH-CAPACITY POWER EXHAUST
31
COIL
COMPARTMENT
COIL
COMPARTMENT
32
48P4,P5030,035 UNIT
a48-8444
33
34
This section details six examples of the P Series
large rooftop unit. To determine dimensions for the
appropriate unit for your application, refer to the
Applied Rooftop Builder software.
a50-8376
a48-8635
35
48P2,P3055,060 UNITS
50P2,P3055,060 UNITS
a50-8714
36
a48-8636
37
48P4,P5075-100 UNITS
38
This section details six examples of the P Series
large rooftop unit. To determine dimensions for the
appropriate unit for your application, refer to the
Applied Rooftop Builder software.
a48-8432
Accessory dimensions
a48-8433
39
a48-8434
40
a48-8435
41
42
a48-8437
43
Selection procedure
I Determine cooling and heating loads at design
conditions.
Given:
Required Gross Cooling
Capacity (TC). . . . . . . . . . . . . . . . .950,000 Btuh
Sensible Gross Heat Capacity (SHC) . .775,000 Btuh
Required Heating Capacity . . . . . . . . .500,000 Btuh
Condenser Entering-Air Temperature db . . . . . .95 F
Indoor Air Temperature . . . . . . . 82 F edb, 67 F ewb
Evaporator Air Quantity . . . . . . . . . . . . 31,500 Cfm
External Static Pressure . . . . . . . . . . . . . .3.0 in. wg
Electrical Characteristics (V-Ph-Hz) . . . . . . 460-3-60
Integrated economizer required.
Options: VFD on supply fan, 65% filters, premium
efficiency motor, integrated economizer, power
exhaust, airfoil fan, vertical duct configuration.
II Select the rooftop unit based on required
cooling capacity.
Enter cooling capacity table on page 91 for size 090
(standard capacity coil) at condenser entering temperature 95 F, evaporator air quantity of 31,500 cfm,
and an indoor wet bulb temperature of 67 F.
The unit will provide a total gross cooling capacity of
1,011,000 Btuh and an SHC of 750,000 Btuh.
Since these values were not at 80 F edb, calculate an
SHC correction (at 82 F edb) based on the notes following the Cooling Capacity tables. Calculate a corrected SHC of 812,400 Btuh.
Unit meets design conditions for TC and SHC.
NOTE: Unit ratings are gross capacities and do not
include the effect of supply-fan motor heat. To calculate net capacities see Step V.
III Select net heating capacity of unit to meet
design condition requirements.
Enter the Gas Heating Capacities table on page 7.
The 48P2090 unit (low heat) will provide 526,000
Btuh of heating with an input of 650,000 Btuh.
IV Determine fan speed and power requirements at
design conditions.
Before entering the Fan Performance tables, calculate
the selection static pressure required based on unit
44
Performance data
Humidi-MiZer performance data
The following pages of Performance Data include performance tables for Humidi-MiZer equipped units. The tables
include capacity in normal cooling, subcooling mode and
hot gas reheat mode.
For hot gas reheat performance, the ambient outdoor air
and return air temperature ranges are different from the
ranges listed for normal design cooling and subcooling
rooftop operation. This is to provide appropriate performance data for those conditions when the rooftop unit
would most likely respond to provide all latent capacity removal from the space.
All performance data are provided in terms of gross capacities. Combined, the subcooling and reheat tables provide the endpoints of performance potential for each unit
60.0
50.0
0.66 SHR
0.60 SHR
Ca
apacity (Tons)
40.0
Sensible
30.0
Latent
20.0
10.0
0.00 SHR
0.0
100% Reheat
100% Subcool
Normal
45
62
336
285
21.4
0.18
327
281
23.9
0.18
315
275
26.9
0.17
301
269
30.2
0.17
285
261
34.4
0.17
57
312
312
21.0
0.26
305
305
23.6
0.27
295
295
26.6
0.30
284
284
30.1
0.32
272
272
34.5
0.35
62
360
354
22.0
0.28
349
348
24.4
0.29
339
334
27.3
0.32
326
321
30.7
0.35
311
310
34.5
0.36
57
357
357
22.0
0.49
348
348
24.4
0.50
338
338
27.3
0.52
325
325
30.7
0.54
310
310
34.5
0.56
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
tldb = tedb
1.10 x cfm
tlwb =
hlwb =
46
10,500
75
421
175
23.6
0.00
404
170
25.8
0.36
391
166
28.4
0.31
377
162
31.5
0.28
360
156
35.1
0.26
72
401
206
23.1
0.25
389
202
25.3
0.24
376
198
28.0
0.23
361
193
31.2
0.22
344
187
34.8
0.21
67
372
256
22.3
0.21
361
252
24.7
0.21
349
248
27.5
0.21
334
242
30.7
0.20
317
235
34.4
0.20
62
345
307
21.6
0.19
335
303
24.1
0.19
322
296
27.1
0.20
308
288
30.5
0.20
291
279
34.5
0.21
57
327
327
21.3
0.33
319
319
23.8
0.35
309
309
26.8
0.37
297
297
30.2
0.39
285
285
34.4
0.42
BF
79
81
.05
.10
.20
1.04
0.99
0.88
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for indoor
fan motor heat.
62
293
231
22.5
0.12
271
213
24.6
0.12
250
195
27.0
0.12
229
177
29.7
0.13
207
159
32.7
0.13
57
273
266
21.9
0.21
256
249
24.1
0.22
238
231
26.6
0.23
220
214
29.3
0.24
201
196
32.4
0.25
62
348
246
24.1
0.19
296
276
25.3
0.26
272
253
27.6
0.27
249
230
30.2
0.28
224
207
33.1
0.29
57
319
299
23.2
0.25
290
290
25.1
0.45
267
267
27.5
0.45
244
244
30.1
0.46
221
221
33.0
0.48
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. The SHC is based on 80 F edb temperature of air entering evaporator coil. For edb temperatures other than 80 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
10,500
75
385
118
25.1
0.10
355
94
27.1
0.10
326
70
29.4
0.10
296
46
31.8
0.10
266
21
34.6
0.10
72
363
149
24.5
0.13
335
125
26.5
0.13
308
102
28.7
0.13
280
80
31.3
0.13
251
56
34.0
0.13
67
330
200
23.5
0.14
305
179
25.6
0.14
280
158
27.9
0.14
254
137
30.4
0.14
228
116
33.3
0.14
62
301
252
22.7
0.15
279
232
24.8
0.15
257
213
27.1
0.15
234
194
29.8
0.16
213
176
32.8
0.17
57
283
283
22.2
0.26
264
264
24.3
0.28
245
245
26.8
0.29
225
225
29.5
0.30
205
205
32.6
0.32
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
47
13,500
143
5
23.8
0.17
146
6
23.2
0.17
149
7
22.7
0.17
145
6
23.6
0.17
150
9
22.6
0.17
157
12
21.7
0.17
15,000
145
12
23.9
0.19
148
14
23.3
0.19
151
15
22.8
0.19
146
14
23.7
0.19
152
17
22.7
0.19
159
20
21.8
0.19
48/50P2,P3,P4,P5030 (30 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
6000
7500
9000
10,500
12,000
13,500
15,000
6000
7500
9000
10,500
12,000
TC
127
135
141
144
147
149
151
133
141
146
150
152
SHC
-52
-52
-50
-48
-44
-40
-36
-77
-81
-83
-83
-83
80
kW
24.3
24.2
24.2
24.3
24.4
24.5
24.5
24.9
24.9
24.9
25.0
25.0
BF
0.03
0.07
0.10
0.13
0.15
0.17
0.18
0.00
0.02
0.05
0.10
0.12
TC
130
138
143
147
150
152
154
135
143
149
153
156
SHC
-50
-50
-49
-46
-43
-39
-34
-76
-80
-81
-82
-81
75
kW
23.6
23.6
23.7
23.7
23.8
23.9
24.0
24.3
24.3
24.3
24.4
24.5
BF
0.03
0.07
0.10
0.13
0.15
0.17
0.18
0.00
0.02
0.05
0.09
0.12
TC
132
140
146
150
153
156
158
137
146
152
156
160
SHC
-49
-49
-48
-45
-41
-37
-32
-75
-78
-80
-80
-79
70
kW
23.0
23.0
23.1
23.2
23.3
23.4
23.4
23.8
23.7
23.8
23.8
23.9
BF
0.03
0.07
0.10
0.12
0.15
0.16
0.18
0.00
0.01
0.05
0.09
0.12
TC
130
137
142
146
148
150
152
135
142
147
151
154
SHC
-50
-50
-49
-46
-42
-38
-34
-76
-79
-81
-81
-81
60
kW
23.8
23.9
24.0
24.1
24.3
24.4
24.4
24.6
24.7
24.8
24.9
25.0
BF
0.03
0.07
0.10
0.13
0.15
0.17
0.18
0.00
0.02
0.05
0.10
0.13
TC
134
142
147
151
154
157
159
139
147
153
157
160
SHC
-47
-48
-46
-43
-40
-35
-30
-73
-77
-78
-78
-77
50
kW
22.7
22.8
22.9
23.1
23.2
23.3
23.4
23.5
23.5
23.7
23.8
23.9
BF
0.02
0.07
0.10
0.13
0.15
0.16
0.18
0.00
0.01
0.05
0.09
0.12
TC
138
147
153
158
161
164
166
144
153
159
164
168
SHC
-45
-45
-43
-40
-36
-31
-27
-71
-74
-75
-75
-74
40
kW
21.7
21.8
22.0
22.1
22.3
22.4
22.5
22.5
22.6
22.7
22.9
23.0
BF
0.02
0.07
0.10
0.12
0.15
0.16
0.18
0.00
0.01
0.05
0.09
0.12
13,500
155
-82
25.1
0.15
159
-80
24.5
0.15
163
-78
24.0
0.15
156
-80
25.0
0.15
163
-76
24.0
0.15
171
-72
23.1
0.15
15,000
157
-80
25.1
0.17
161
-78
24.6
0.17
165
-76
24.1
0.17
157
-78
25.1
0.17
165
-74
24.1
0.17
173
-70
23.2
0.17
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
48
10,500
62
341
300
21.5
0.09
333
296
23.9
0.09
323
292
26.7
0.09
310
285
30.3
0.09
294
278
34.5
0.10
57
323
323
21.1
0.23
317
317
23.5
0.24
309
309
26.5
0.26
298
298
30.0
0.29
285
285
34.4
0.32
75
429
183
23.9
0.20
414
179
26.1
0.18
399
174
28.7
0.16
386
170
31.7
0.15
370
164
35.3
0.14
72
410
217
23.4
0.14
395
212
25.6
0.13
383
208
28.2
0.13
370
203
31.3
0.12
353
197
35.0
0.12
67
378
271
22.5
0.12
367
267
24.8
0.11
356
263
27.5
0.11
343
257
30.7
0.11
326
251
34.5
0.11
62
351
325
21.8
0.11
342
321
24.1
0.11
331
315
27.0
0.12
317
307
30.5
0.12
302
295
34.5
0.15
57
338
338
21.5
0.31
331
331
23.9
0.32
323
323
26.8
0.34
312
312
30.3
0.36
299
299
34.5
0.39
49
62
300
239
22.7
0.06
277
219
24.8
0.06
254
199
27.2
0.07
231
180
29.9
0.07
208
162
32.9
0.08
57
282
275
22.2
0.16
263
257
24.3
0.17
244
238
26.8
0.18
225
219
29.6
0.19
205
200
32.8
0.21
62
331
314
23.7
0.19
306
289
25.7
0.20
279
263
27.9
0.21
253
238
30.5
0.22
227
212
33.4
0.24
57
326
326
23.5
0.41
300
300
25.5
0.41
275
275
27.8
0.42
249
249
30.4
0.43
223
223
33.3
0.44
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. The SHC is based on 80 F edb temperature of air entering evaporator coil. For edb temperatures other than 80 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
50
10,500
75
398
121
25.6
0.04
369
97
27.6
0.04
337
70
29.8
0.04
305
44
32.3
0.04
271
17
34.9
0.04
72
377
155
25.0
0.06
346
129
26.9
0.06
317
104
29.1
0.06
286
79
31.6
0.06
254
53
34.3
0.06
67
340
208
23.9
0.07
313
185
25.9
0.07
286
162
28.1
0.07
257
138
30.7
0.07
229
115
33.6
0.07
62
309
262
23.0
0.08
285
241
25.0
0.09
261
220
27.4
0.09
239
200
30.1
0.11
216
177
33.1
0.13
57
292
292
22.5
0.22
272
272
24.6
0.23
251
251
27.1
0.25
229
229
29.8
0.26
207
207
32.9
0.28
15,000
72
401
192
25.8
0.10
365
162
27.6
0.10
331
133
29.7
0.10
297
105
32.1
0.10
261
75
34.7
0.10
67
361
263
24.6
0.11
329
235
26.5
0.11
298
208
28.6
0.11
267
181
31.1
0.11
235
156
33.8
0.12
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
13,500
157
17
24.1
0.09
159
19
23.5
0.09
163
20
23.0
0.09
158
19
24.0
0.09
164
22
22.9
0.09
171
26
22.0
0.09
15,000
158
27
24.2
0.10
161
28
23.6
0.10
165
30
23.1
0.10
160
29
24.1
0.10
166
32
23.0
0.10
173
36
22.2
0.10
48/50P2,P3,P4,P5030 (30 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
6000
7500
9000
10,500
12,000
13,500
15,000
6000
7500
9000
10,500
12,000
TC
139
148
154
158
161
163
165
145
154
160
164
167
SHC
-48
-47
-44
-41
-36
-31
-25
-74
-77
-79
-79
-77
80
kW
24.7
24.6
24.6
24.6
24.7
24.8
24.9
25.4
25.3
25.3
25.4
25.4
BF
0.01
0.03
0.04
0.06
0.07
0.09
0.10
0.00
0.00
0.02
0.04
0.06
TC
142
151
156
160
164
167
169
148
157
163
167
171
SHC
-46
-45
-43
-39
-34
-29
-23
-73
-76
-77
-77
-75
75
kW
24.0
23.9
24.0
24.1
24.2
24.2
24.3
24.8
24.7
24.7
24.8
24.9
BF
0.01
0.03
0.04
0.06
0.07
0.09
0.10
0.00
0.00
0.02
0.04
0.06
TC
144
153
159
164
168
171
173
150
159
166
171
175
SHC
-45
-44
-42
-38
-33
-27
-21
-71
-74
-76
-75
-73
70
kW
23.4
23.4
23.4
23.5
23.6
23.7
23.8
24.1
24.1
24.2
24.3
24.3
BF
0.01
0.02
0.04
0.06
0.07
0.09
0.10
0.00
0.00
0.02
0.04
0.06
TC
142
150
155
159
162
164
166
147
155
161
165
167
SHC
-45
-45
-43
-39
-34
-29
-23
-72
-76
-77
-77
-75
60
kW
24.2
24.3
24.4
24.6
24.7
24.8
24.9
25.1
25.1
25.2
25.3
25.4
BF
0.01
0.03
0.04
0.06
0.07
0.09
0.10
0.00
0.00
0.02
0.04
0.06
TC
146
155
160
165
168
171
173
152
160
167
172
175
SHC
-43
-43
-40
-36
-31
-25
-19
-69
-73
-74
-73
-72
50
kW
23.0
23.2
23.3
23.5
23.6
23.7
23.8
23.9
24.0
24.1
24.3
24.4
BF
0.01
0.03
0.04
0.06
0.07
0.09
0.10
0.00
0.00
0.02
0.04
0.06
TC
150
160
167
172
176
179
181
157
167
174
179
183
SHC
-41
-40
-37
-32
-27
-21
-15
-67
-70
-70
-70
-68
40
kW
22.0
22.2
22.4
22.6
22.7
22.8
22.9
22.9
23.0
23.2
23.3
23.5
BF
0.01
0.02
0.04
0.06
0.07
0.09
0.10
0.00
0.00
0.02
0.04
0.06
13,500
170
-75
25.5
0.07
174
-73
24.9
0.07
178
-71
24.4
0.07
170
-73
25.5
0.08
178
-69
24.5
0.07
186
-65
23.6
0.07
15,000
172
-72
25.5
0.09
176
-70
25.0
0.09
180
-68
24.5
0.09
172
-71
25.6
0.09
180
-66
24.6
0.09
188
-62
23.7
0.09
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
51
10,500
62
384
328
25.1
0.10
375
325
27.7
0.10
363
319
30.9
0.10
349
313
34.8
0.10
332
304
39.5
0.10
57
361
361
24.5
0.20
353
353
27.2
0.21
344
344
30.6
0.23
332
332
34.6
0.26
318
318
39.6
0.29
75
472
195
28.1
0.14
456
190
30.6
0.25
438
184
33.4
0.21
425
180
36.7
0.19
408
175
40.7
0.17
72
453
231
27.4
0.16
438
225
29.9
0.15
423
220
32.7
0.14
410
216
36.2
0.13
393
210
40.3
0.13
67
420
288
26.3
0.12
408
283
28.8
0.12
397
278
31.8
0.12
382
272
35.4
0.12
364
265
39.7
0.11
62
389
343
25.3
0.11
380
339
27.9
0.11
369
334
31.1
0.11
354
326
35.1
0.11
336
318
39.8
0.11
57
370
370
24.7
0.24
363
363
27.4
0.26
353
353
30.8
0.28
341
341
34.8
0.30
327
327
39.7
0.33
52
62
319
255
24.3
0.07
294
234
26.5
0.07
269
212
28.9
0.07
244
190
31.7
0.07
207
160
34.7
0.08
57
297
294
23.7
0.15
276
273
25.9
0.16
255
253
28.4
0.17
225
223
31.2
0.19
199
199
34.4
0.20
62
349
331
25.3
0.16
320
302
27.3
0.17
292
275
29.7
0.18
264
248
32.4
0.20
224
209
35.3
0.21
57
342
342
25.1
0.38
314
314
27.1
0.39
287
287
29.5
0.40
259
259
32.2
0.41
219
219
35.2
0.42
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. The SHC is based on 80 F edb temperature of air entering evaporator coil. For edb temperatures other than 80 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
10,500
75
419
127
27.3
0.03
392
106
29.6
0.04
357
78
31.9
0.04
322
49
34.4
0.04
287
20
37.2
0.04
72
401
165
26.8
0.06
368
138
28.8
0.06
335
111
31.1
0.06
301
83
33.7
0.06
269
56
36.5
0.06
67
360
217
25.6
0.07
330
192
27.6
0.07
302
167
30.0
0.07
272
142
32.6
0.07
237
112
35.5
0.07
62
325
270
24.5
0.08
299
247
26.6
0.08
273
224
29.1
0.08
247
202
31.8
0.08
210
169
34.8
0.09
57
304
304
23.9
0.19
282
282
26.1
0.20
259
259
28.6
0.22
236
236
31.5
0.23
200
200
34.5
0.25
15,000
67
381
269
26.2
0.10
350
244
28.3
0.10
316
216
30.6
0.11
283
187
33.1
0.11
245
155
35.9
0.11
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
53
14,000
178
29
25.9
0.10
182
31
25.3
0.10
185
33
24.7
0.10
178
31
25.9
0.10
186
37
24.8
0.10
193
43
23.8
0.10
15,000
179
36
26.0
0.10
183
38
25.4
0.10
187
40
24.8
0.10
180
38
26.0
0.10
187
45
24.9
0.10
194
49
23.9
0.10
48/50P2,P3,P4,P5035 (35 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
7000
8750
9625
10,500
12,250
14,000
15,000
7000
8750
9625
10,500
12,250
TC
163
171
174
177
182
185
187
169
178
182
185
189
SHC
-39
-37
-34
-32
-26
-19
-15
-69
-70
-70
-69
-68
80
kW
26.0
26.2
26.3
26.4
26.5
26.7
26.7
26.8
27.0
27.1
27.1
27.3
BF
0.01
0.04
0.05
0.06
0.08
0.09
0.10
0.00
0.01
0.02
0.03
0.06
TC
165
175
178
181
186
189
191
172
182
186
189
193
SHC
-37
-35
-33
-30
-24
-17
-13
-67
-68
-68
-67
-66
75
kW
25.4
25.6
25.7
25.8
25.9
26.1
26.1
26.2
26.3
26.4
26.5
26.7
BF
0.01
0.04
0.05
0.06
0.08
0.09
0.10
0.00
0.01
0.02
0.03
0.06
TC
168
178
182
185
190
193
195
176
186
189
193
197
SHC
-36
-33
-31
-28
-22
-15
-11
-64
-66
-66
-66
-64
70
kW
24.8
25.0
25.1
25.2
25.3
25.5
25.6
25.5
25.8
25.9
25.9
26.1
BF
0.01
0.04
0.05
0.06
0.07
0.09
0.10
0.00
0.01
0.02
0.03
0.06
TC
164
172
175
178
182
185
187
170
179
182
185
189
SHC
-37
-35
-33
-30
-24
-17
-13
-66
-68
-68
-68
-66
60
kW
25.8
26.1
26.2
26.4
26.6
26.8
26.9
26.7
27.0
27.1
27.2
27.4
BF
0.01
0.04
0.05
0.06
0.08
0.09
0.10
0.00
0.01
0.02
0.03
0.06
TC
170
179
183
185
190
193
195
177
186
190
192
197
SHC
-33
-31
-29
-26
-20
-10
-5
-61
-64
-64
-64
-62
50
kW
24.5
24.9
25.1
25.2
25.4
25.7
25.8
25.4
25.8
25.9
26.1
26.3
BF
0.01
0.04
0.05
0.06
0.08
0.09
0.10
0.00
0.01
0.02
0.03
0.06
TC
175
185
189
192
197
200
202
183
193
196
199
204
SHC
-30
-28
-25
-22
-16
-9
-4
-58
-61
-61
-60
-58
40
kW
23.5
23.9
24.0
24.2
24.4
24.6
24.8
24.4
24.8
24.9
25.0
25.3
BF
0.01
0.04
0.05
0.06
0.07
0.09
0.10
0.00
0.00
0.01
0.03
0.06
14,000
193
-65
27.4
0.08
197
-63
26.8
0.08
201
-61
26.2
0.08
192
-63
27.6
0.08
200
-54
26.5
0.08
208
-55
25.5
0.07
15,000
194
-63
27.5
0.09
199
-61
26.9
0.09
203
-59
26.3
0.09
194
-61
27.7
0.09
202
-56
26.6
0.09
209
-50
25.6
0.09
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
54
14,000
62
420
339
24.1
0.32
407
334
27.0
0.31
393
328
30.4
0.31
377
321
34.3
0.30
359
314
39.1
0.29
57
383
371
23.5
0.37
370
367
26.6
0.35
360
356
30.0
0.37
347
347
34.4
0.38
334
334
39.6
0.40
75
533
210
26.0
0.00
520
205
28.6
0.00
504
203
31.7
0.00
486
199
35.3
0.00
466
193
39.5
0.00
72
508
249
25.5
0.22
497
246
28.2
0.44
482
241
31.3
0.42
464
235
35.1
0.39
443
229
39.4
0.37
67
469
307
24.8
0.36
457
302
27.6
0.36
441
296
30.9
0.35
424
289
34.8
0.35
404
282
39.1
0.34
62
431
364
24.2
0.33
419
358
27.1
0.33
404
352
30.5
0.32
387
345
34.3
0.32
368
336
39.2
0.32
57
397
397
23.9
0.39
388
387
26.8
0.41
377
377
30.3
0.42
364
364
34.4
0.44
350
350
39.4
0.46
55
62
393
300
23.5
0.36
377
288
26.1
0.36
373
289
30.0
0.35
353
273
34.0
0.36
320
245
36.2
0.35
57
363
342
23.1
0.37
349
329
25.6
0.38
332
312
28.6
0.40
316
296
32.0
0.41
299
280
35.9
0.42
62
427
376
24.2
0.44
419
377
27.4
0.43
390
348
29.6
0.44
369
323
32.9
0.44
351
310
36.8
0.46
57
404
385
23.8
0.57
388
388
26.3
0.51
373
373
29.3
0.54
356
356
32.7
0.55
336
336
36.5
0.56
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. The SHC is based on 80 F edb temperature of air entering evaporator coil. For edb temperatures other than 80 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
56
14,000
75
513
183
25.8
0.00
490
167
28.2
0.00
467
151
31.0
0.00
444
134
34.3
0.00
418
117
37.9
0.20
72
486
212
25.3
0.18
465
197
27.7
0.17
459
197
31.5
0.17
422
166
33.8
0.16
398
149
37.5
0.15
67
455
281
25.6
0.43
426
255
26.9
0.42
406
241
29.8
0.42
385
225
33.1
0.41
362
209
36.9
0.41
62
406
326
23.8
0.36
388
311
26.3
0.37
360
287
29.0
0.37
345
277
33.1
0.36
329
266
36.4
0.37
57
377
362
23.3
0.42
361
347
25.8
0.43
345
330
28.8
0.44
328
314
32.2
0.45
309
296
36.1
0.46
20,000
67
466
316
24.9
0.42
434
288
27.2
0.42
441
300
31.6
0.42
395
260
33.4
0.42
380
252
37.3
0.42
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
18,000
184
-2
26.5
0.46
187
-1
25.7
0.46
184
-2
26.5
0.46
190
1
25.1
0.46
195
4
24.0
0.46
201
6
23.3
0.47
20,000
187
6
26.5
0.45
190
7
25.8
0.45
186
6
26.6
0.45
193
9
25.2
0.45
198
12
24.1
0.45
204
14
23.3
0.46
48/50P2,P3,P4,P5040 (40 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
8000 10,000 12,000
14,000
16,000
18,000
20,000
8000 10,000 12,000
14,000
16,000
TC
160
172
180
186
191
194
197
169
180
189
196
200
SHC
-58
-65
-66
-63
-56
-50
-45
-84
-85
-87
-97
-93
80
kW
27.1
27.1
27.0
26.9
26.9
27.0
27.0
27.5
27.3
27.2
27.4
27.3
BF
0.00
0.00
0.00
0.21
0.19
0.18
0.18
0.00
0.00
0.00
0.00
0.00
TC
163
175
183
189
194
198
200
172
183
193
200
204
SHC
-56
-63
-64
-61
-54
-48
-43
-82
-83
-85
-95
-91
75
kW
26.3
26.3
26.2
26.2
26.2
26.2
26.3
26.7
26.5
26.5
26.7
26.6
BF
0.00
0.00
0.00
0.22
0.19
0.19
0.19
0.00
0.00
0.00
0.00
0.00
TC
162
172
180
185
190
193
196
170
180
189
195
199
SHC
-56
-64
-64
-62
-56
-49
-44
-83
-84
-86
-95
-92
70
kW
26.9
27.0
27.0
27.0
27.0
27.1
27.1
27.4
27.3
27.4
27.5
27.5
BF
0.00
0.00
0.00
0.21
0.19
0.18
0.18
0.00
0.00
0.00
0.00
0.00
TC
166
178
185
191
196
200
202
175
186
195
201
206
SHC
-54
-61
-62
-62
-52
-47
-41
-80
-80
-84
-93
-90
60
kW
25.5
25.6
25.6
25.7
25.7
25.7
25.8
26.0
26.0
26.1
26.3
26.4
BF
0.00
0.00
0.00
0.22
0.19
0.19
0.19
0.00
0.00
0.00
0.00
0.00
TC
171
184
191
197
202
206
209
178
191
201
208
213
SHC
-51
-59
-59
-59
-50
-44
-38
-76
-77
-81
-89
-87
50
kW
24.3
24.5
24.6
24.7
24.7
24.8
24.9
25.0
25.0
25.2
25.4
25.4
BF
0.00
0.00
0.00
0.00
0.20
0.19
0.19
0.00
0.00
0.00
0.00
0.00
TC
174
189
197
203
208
213
216
182
197
207
214
220
SHC
-44
-55
-57
-56
-47
-41
-36
-72
-75
-78
-86
-85
40
kW
23.3
23.7
23.8
23.9
23.9
24.0
24.1
24.1
24.2
24.4
24.6
24.7
BF
0.00
0.00
0.00
0.00
0.22
0.20
0.19
0.00
0.00
0.00
0.00
0.00
18,000
204
-96
27.4
0.00
208
-94
26.7
0.00
203
-95
27.6
0.26
209
-92
26.5
0.00
217
-89
25.5
0.00
224
-86
24.8
0.00
20,000
207
-92
27.4
0.23
211
-90
26.7
0.24
205
-92
27.7
0.22
212
-89
26.5
0.24
220
-86
25.6
0.00
227
-86
24.8
0.00
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
57
14,000
62
443
387
24.2
0.13
435
383
27.0
0.13
423
377
30.6
0.13
406
369
35.0
0.13
386
358
41.8
0.14
57
417
417
23.8
0.25
410
410
26.7
0.27
400
400
30.3
0.28
387
387
35.0
0.31
372
372
41.8
0.34
75
565
239
26.7
0.12
551
235
29.3
0.26
539
231
32.4
0.24
524
226
36.4
0.22
502
219
41.3
0.21
72
537
282
26.1
0.18
523
277
28.6
0.17
514
273
31.9
0.18
498
267
36.0
0.18
476
260
41.0
0.17
67
493
349
25.2
0.16
484
346
27.9
0.16
472
341
31.2
0.16
455
336
35.2
0.15
433
328
40.5
0.14
62
456
417
24.5
0.16
447
412
27.3
0.16
434
404
30.8
0.16
416
393
35.2
0.17
397
378
41.7
0.20
57
436
436
24.2
0.33
429
429
27.0
0.34
419
419
30.6
0.36
406
406
35.1
0.38
390
390
40.9
0.40
58
62
385
314
23.7
0.14
362
293
26.0
0.14
338
273
28.9
0.14
312
251
32.2
0.14
284
229
36.3
0.15
57
358
352
23.2
0.24
339
332
25.6
0.25
318
311
28.5
0.26
300
293
31.9
0.25
276
269
36.1
0.27
62
428
406
24.5
0.26
419
400
27.1
0.28
398
380
29.9
0.28
377
360
33.4
0.29
347
327
37.2
0.29
57
419
419
24.3
0.46
405
405
26.8
0.45
382
382
29.6
0.46
361
361
33.0
0.48
334
334
36.9
0.49
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. The SHC is based on 80 F edb temperature of air entering evaporator coil. For edb temperatures other than 80 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
14,000
75
518
170
26.4
0.10
482
139
28.5
0.10
449
111
31.1
0.09
416
84
34.1
0.09
381
56
37.7
0.08
72
486
211
25.7
0.22
453
183
27.9
0.22
424
158
30.5
0.22
393
132
33.6
0.21
358
105
37.3
0.21
67
440
279
24.7
0.17
414
256
27.0
0.17
388
234
29.8
0.17
358
210
33.0
0.17
329
187
36.8
0.17
62
401
348
23.9
0.16
378
328
26.3
0.16
354
307
29.1
0.17
331
284
32.4
0.18
300
255
36.4
0.18
57
382
381
23.6
0.30
362
361
26.0
0.31
339
339
28.8
0.30
318
317
32.2
0.31
295
295
36.3
0.34
20,000
72
516
257
26.3
0.22
485
232
28.5
0.22
454
205
31.2
0.22
422
179
34.3
0.22
390
155
38.1
0.22
67
471
350
25.3
0.20
444
327
27.6
0.20
417
305
30.4
0.20
388
281
33.6
0.20
354
255
37.5
0.20
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
59
18,000
199
28
26.1
0.20
201
30
25.5
0.20
198
29
26.6
0.20
202
32
25.5
0.20
207
36
24.6
0.20
211
38
23.9
0.20
20,000
202
40
26.1
0.21
204
42
25.6
0.21
200
42
26.7
0.21
204
44
25.6
0.21
210
48
24.7
0.21
214
51
24.0
0.21
48/50P2,P3,P4,P5040 (40 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
8000 10,000 12,000
14,000
16,000
18,000
20,000
8000 10,000 12,000
14,000
16,000
TC
174
186
195
201
206
209
212
182
195
204
210
215
SHC
-55
-56
-50
-43
-36
-29
-21
-83
-89
-92
-92
-86
80
kW
26.4
26.5
26.6
26.7
26.8
26.9
27.0
27.2
27.4
27.5
27.6
27.6
BF
0.00
0.09
0.08
0.24
0.22
0.23
0.23
0.00
0.00
0.00
0.12
0.10
TC
176
188
197
203
208
211
215
185
198
207
213
218
SHC
-54
-55
-48
-41
-34
-27
-19
-81
-88
-90
-90
-84
75
kW
25.8
26.0
26.1
26.2
26.3
26.4
26.4
26.6
26.8
27.0
27.1
27.1
BF
0.00
0.10
0.08
0.24
0.22
0.23
0.23
0.00
0.00
0.00
0.12
0.11
TC
173
185
193
200
204
208
211
180
193
202
208
213
SHC
-54
-55
-48
-42
-35
-28
-20
-82
-88
-90
-91
-85
70
kW
26.7
26.9
27.1
27.2
27.4
27.5
27.6
27.6
27.8
28.0
28.2
28.3
BF
0.00
0.09
0.08
0.23
0.22
0.23
0.23
0.00
0.00
0.00
0.12
0.10
TC
177
189
197
204
208
212
215
186
199
207
213
218
SHC
-52
-52
-45
-39
-31
-25
-17
-78
-85
-87
-86
-82
60
kW
25.6
25.9
26.0
26.2
26.3
26.4
26.5
26.5
26.8
27.0
27.1
27.2
BF
0.00
0.10
0.08
0.23
0.22
0.22
0.23
0.00
0.00
0.00
0.12
0.11
TC
181
194
202
209
214
218
221
188
203
212
219
224
SHC
-52
-49
-42
-36
-29
-21
-13
-76
-82
-84
-83
-78
50
kW
24.8
25.0
25.1
25.3
25.4
25.5
25.6
25.6
25.9
26.1
26.2
26.3
BF
0.00
0.11
0.09
0.23
0.22
0.23
0.23
0.00
0.00
0.00
0.13
0.11
TC
183
197
206
213
218
222
225
192
206
216
223
228
SHC
-52
-47
-40
-33
-26
-18
-10
-73
-80
-81
-80
-75
40
kW
24.1
24.3
24.4
24.6
24.7
24.8
24.9
24.8
25.2
25.4
25.5
25.6
BF
0.00
0.12
0.09
0.23
0.22
0.23
0.23
0.00
0.00
0.00
0.14
0.12
18,000
219
-82
27.7
0.31
222
-80
27.2
0.31
218
-81
28.4
0.29
222
-78
27.3
0.29
228
-74
26.4
0.29
233
-71
25.7
0.29
20,000
223
-78
27.8
0.28
225
-76
27.3
0.27
222
-77
28.5
0.27
225
-73
27.4
0.27
231
-70
26.5
0.27
236
-67
25.8
0.27
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
60
17,500
62
561
470
32.8
0.20
542
461
36.7
0.20
520
452
41.6
0.19
495
441
47.3
0.19
467
428
55.3
0.19
57
520
518
32.4
0.28
501
500
36.5
0.29
484
484
41.4
0.31
465
465
47.8
0.33
443
443
56.0
0.36
75
707
288
35.0
0.00
681
282
38.7
0.20
658
275
43.0
0.17
635
268
48.1
0.14
607
259
54.1
0.33
72
672
341
34.4
0.30
650
333
38.1
0.28
632
327
42.6
0.27
608
319
47.9
0.26
578
309
54.1
0.24
67
622
423
33.6
0.24
605
417
37.4
0.23
583
408
42.1
0.23
557
398
47.7
0.22
528
387
54.1
0.22
62
576
506
33.0
0.21
557
497
36.9
0.21
534
487
41.8
0.21
508
474
47.5
0.22
479
455
55.0
0.23
57
541
541
32.6
0.33
526
526
36.7
0.35
508
508
41.7
0.38
488
488
47.6
0.40
466
466
55.5
0.43
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
tldb = tedb
1.10 x cfm
tlwb =
hlwb =
hewb
BF
79
81
.05
.10
.20
1.04
0.99
0.88
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for indoor fan motor heat.
61
17,500
62
524
406
32.3
0.28
500
388
35.9
0.28
473
369
40.3
0.27
445
350
45.5
0.27
424
357
52.1
0.18
57
491
480
31.6
0.25
467
467
35.4
0.26
444
444
39.9
0.27
420
420
45.5
0.29
394
394
52.3
0.31
75
671
235
34.5
0.00
638
212
38.0
0.00
607
189
42.2
0.00
572
164
46.9
0.17
534
138
52.4
0.15
72
638
281
34.0
0.14
610
260
37.5
0.13
581
238
41.7
0.13
547
215
46.6
0.12
510
191
52.2
0.12
67
588
362
33.2
0.33
562
343
36.8
0.32
533
322
41.1
0.32
502
301
46.1
0.31
483
305
52.0
0.21
62
551
473
32.5
0.20
513
420
36.2
0.29
487
402
40.5
0.29
458
382
45.8
0.29
434
388
52.1
0.21
57
513
513
32.0
0.32
492
492
35.8
0.34
467
467
40.1
0.35
442
442
45.6
0.36
415
415
52.2
0.38
62
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
48/50P2,P3,P4,P5050 (50 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
Air Ent
62.5 Wet Bulb (50% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
10,000
12,500
15,000
17,500
20,000
10,000
TC
218
233
244
252
258
227
SHC
-72
-79
-77
-71
-62
-102
80
kW
37.2
37.3
37.2
37.3
37.3
37.7
BF
0.00
0.00
0.00
0.16
0.14
0.00
TC
222
237
248
256
262
231
SHC
-70
-77
-75
-69
-61
-100
75
kW
36.1
36.2
36.2
36.2
36.2
36.7
BF
0.00
0.00
0.00
0.16
0.15
0.00
TC
220
236
247
254
260
229
SHC
-70
-76
-78
-69
-61
-100
70
kW
36.7
36.6
36.8
37.0
37.1
37.3
BF
0.00
0.00
0.00
0.16
0.15
0.03
TC
225
241
253
261
267
235
SHC
-62
-73
-75
-66
-58
-96
60
kW
34.7
35.0
35.1
35.2
35.3
35.5
BF
0.00
0.00
0.00
0.17
0.15
0.02
TC
230
248
259
267
273
241
SHC
-59
-71
-70
-63
-54
-93
50
kW
33.3
33.7
33.8
33.9
34.0
34.2
BF
0.00
0.00
0.00
0.18
0.16
0.01
TC
235
254
264
273
279
246
SHC
-56
-68
-68
-60
-51
-91
40
kW
32.5
32.8
33.0
33.0
33.0
33.4
BF
0.00
0.00
0.00
0.20
0.16
0.00
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
75 Dry Bulb
65.3 Wet Bulb (60% RH)
12,500
220
-38
36.8
0.15
225
-35
35.5
0.16
223
-36
36.2
0.16
230
-32
34.2
0.00
235
-29
32.8
0.00
240
-26
32.0
0.00
15,000
231
-25
36.6
0.13
235
-23
35.5
0.13
234
-23
36.1
0.13
241
-19
34.2
0.13
245
-17
32.9
0.14
251
-14
32.0
0.14
17,500
239
-13
36.6
0.12
243
-11
35.5
0.12
242
-11
36.2
0.12
249
-7
34.3
0.13
253
-5
33.0
0.13
259
-2
32.1
0.13
20,000
245
-1
36.7
0.37
250
1
35.6
0.37
248
1
36.3
0.37
255
5
34.4
0.37
260
7
33.1
0.37
266
10
32.2
0.37
17,500
264
-119
37.9
0.00
268
-118
36.9
0.00
265
-118
37.8
0.00
272
-115
36.1
0.00
281
-112
34.8
0.00
286
-108
33.8
0.00
20,000
270
-116
37.8
0.00
274
-114
36.9
0.00
271
-114
37.9
0.00
278
-111
36.1
0.00
287
-107
34.8
0.00
293
-109
33.9
0.00
75 Dry Bulb
65.3 Wet Bulb (60% RH)
12,500
244
-108
37.7
0.00
247
-106
36.7
0.00
246
-106
37.4
0.00
251
-103
35.7
0.00
258
-99
34.4
0.00
264
-96
33.5
0.00
15,000
256
-111
37.7
0.00
260
-109
36.7
0.00
257
-109
37.6
0.00
264
-106
35.8
0.00
272
-103
34.6
0.00
277
-100
33.6
0.00
63
17,500
62
566
481
32.5
0.17
552
475
36.3
0.16
534
466
41.3
0.16
510
455
47.2
0.16
479
442
55.7
0.16
57
527
526
31.9
0.25
515
515
35.9
0.26
500
500
41.0
0.28
481
481
47.3
0.31
459
459
56.4
0.34
75
715
298
35.1
0.16
695
292
38.8
0.14
677
287
43.2
0.31
656
280
48.7
0.28
627
271
55.4
0.25
72
677
351
34.5
0.22
661
345
38.1
0.22
646
339
42.7
0.21
625
331
48.3
0.21
595
321
55.1
0.21
67
627
434
33.5
0.20
613
428
37.2
0.20
596
421
41.9
0.19
573
412
47.7
0.19
542
402
54.6
0.18
62
581
518
32.8
0.18
567
511
36.6
0.19
548
502
41.6
0.19
523
488
47.5
0.19
493
470
55.8
0.20
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
tldb = tedb
1.10 x cfm
tlwb =
hlwb =
hewb
BF
79
81
.05
.10
.20
1.04
0.99
0.88
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for indoor fan motor heat.
64
57
552
552
32.3
0.32
540
540
36.2
0.34
525
525
41.2
0.36
505
505
47.3
0.38
483
483
56.0
0.41
17,500
62
515
411
32.1
0.18
488
390
35.5
0.10
457
365
39.7
0.10
423
339
44.7
0.10
387
312
51.0
0.11
57
482
468
31.5
0.24
460
460
35.0
0.20
435
435
39.2
0.22
405
405
44.2
0.24
381
381
50.7
0.26
75
697
251
35.4
0.14
640
201
38.3
0.13
597
166
42.2
0.12
555
133
46.7
0.11
511
99
52.0
0.10
72
653
297
34.6
0.30
601
252
37.6
0.29
564
221
41.5
0.28
525
191
46.2
0.27
482
159
51.5
0.26
67
583
367
33.3
0.21
550
340
36.6
0.21
518
314
40.7
0.21
482
286
45.5
0.20
441
256
51.1
0.20
62
534
452
32.4
0.19
502
432
35.8
0.12
470
405
39.9
0.13
436
378
44.8
0.13
400
345
50.2
0.15
57
509
509
32.0
0.28
483
483
35.4
0.29
453
453
39.5
0.30
425
425
44.5
0.31
398
398
50.7
0.33
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
65
48/50P2,P3,P4,P5050 (50 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
10,000
12,500
15,000
17,500
20,000
10,000
TC
223
238
249
257
263
233
SHC
-72
-75
-68
-60
-51
-104
80
kW
36.4
36.8
36.9
37.0
37.1
37.4
BF
0.00
0.15
0.11
0.11
0.28
0.00
TC
227
242
253
261
267
237
SHC
-70
-73
-66
-57
-50
-102
75
kW
35.6
35.9
36.0
36.1
36.3
36.6
BF
0.00
0.00
0.11
0.11
0.29
0.00
TC
225
239
249
257
263
234
SHC
-71
-73
-66
-58
-49
-103
70
kW
36.3
36.8
36.9
37.1
37.2
37.3
BF
0.00
0.16
0.11
0.11
0.27
0.00
TC
232
246
257
265
271
241
SHC
-68
-69
-62
-53
-45
-98
60
kW
34.8
35.2
35.3
35.5
35.6
35.8
BF
0.00
0.00
0.12
0.11
0.28
0.00
TC
236
251
263
271
278
246
SHC
-62
-68
-58
-50
-42
-94
50
kW
33.6
34.1
34.2
34.3
34.4
34.6
BF
0.00
0.00
0.12
0.11
0.28
0.00
TC
238
254
266
274
280
248
SHC
-61
-65
-57
-47
-39
-92
40
kW
32.9
33.3
33.3
33.4
33.5
33.8
BF
0.00
0.00
0.13
0.31
0.28
0.00
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
66
75 Dry Bulb
65.3 Wet Bulb (60% RH)
12,500
228
-24
35.6
0.09
230
-22
34.8
0.09
229
-22
35.5
0.09
234
-19
33.9
0.10
240
-15
32.8
0.10
244
-12
32.1
0.10
15,000
238
-12
35.8
0.26
240
-11
34.9
0.26
239
-11
35.7
0.26
245
-7
34.2
0.26
251
-3
33.0
0.25
254
-1
32.2
0.25
17,500
245
1
35.9
0.24
248
2
35.1
0.24
246
2
36.0
0.24
252
6
34.4
0.24
259
9
33.2
0.24
262
12
32.4
0.24
20,000
249
15
36.0
0.24
254
15
35.2
0.24
252
15
36.1
0.24
258
19
34.6
0.24
265
23
33.4
0.24
268
26
32.5
0.24
17,500
270
-116
38.0
0.18
274
-113
37.1
0.00
269
-117
38.3
0.18
277
-113
36.6
0.00
283
-110
35.3
0.00
286
-107
34.4
0.00
20,000
276
-113
38.1
0.13
280
-112
37.3
0.14
275
-112
38.3
0.14
283
-108
36.8
0.14
292
-105
35.3
0.15
292
-103
34.4
0.16
75 Dry Bulb
70.5 Wet Bulb (80% RH)
12,500
250
-113
37.7
0.00
254
-111
36.8
0.00
250
-111
37.8
0.00
257
-105
36.1
0.00
262
-101
34.9
0.00
264
-99
34.1
0.00
15,000
262
-113
37.8
0.00
266
-111
37.0
0.00
261
-111
38.0
0.00
270
-107
36.4
0.00
275
-111
35.2
0.00
277
-109
34.3
0.00
TC
643 612 561
602 570 519 468
626 595 544 492
SHC
19,250
62
609
531
35.7
0.13
589
522
40.1
0.13
566
505
45.5
0.13
539
497
52.5
0.14
508
481
62.2
0.14
57
572
572
35.2
0.25
556
556
39.7
0.28
537
537
45.2
0.30
516
516
52.5
0.33
494
494
61.0
0.36
75
761
322
38.8
0.29
732
313
42.6
0.26
708
306
47.1
0.23
686
299
52.8
0.22
657
289
59.5
0.20
72
726
381
38.0
0.19
702
373
41.9
0.18
681
366
46.7
0.18
655
357
52.5
0.17
625
347
59.3
0.16
67
672
477
36.9
0.16
653
470
41.0
0.16
631
461
46.1
0.16
604
451
52.2
0.15
573
439
59.9
0.15
62
625
572
36.1
0.15
604
562
40.5
0.16
580
549
45.9
0.16
552
533
52.5
0.17
521
513
61.3
0.19
57
598
598
35.6
0.33
582
582
40.0
0.35
563
563
45.4
0.37
542
542
51.9
0.39
517
517
61.1
0.42
67
19,250
62
561
471
40.5
0.11
537
453
44.3
0.12
509
433
48.7
0.12
479
411
53.7
0.12
448
389
59.8
0.12
57
523
523
40.0
0.23
500
500
43.8
0.24
476
476
48.2
0.26
451
451
53.5
0.27
424
424
59.7
0.29
75
719
248
43.3
0.16
687
225
46.9
0.16
652
200
51.1
0.16
623
183
56.2
0.16
584
157
61.7
0.16
72
684
310
42.6
0.15
654
289
46.3
0.15
623
267
50.6
0.15
589
243
55.5
0.15
552
219
61.0
0.15
67
630
415
41.6
0.14
602
394
45.3
0.14
572
373
49.7
0.14
539
351
54.6
0.14
505
328
60.2
0.14
62
578
515
40.8
0.14
551
495
44.5
0.14
522
473
48.9
0.14
491
450
53.8
0.15
460
422
59.7
0.17
57
549
549
40.3
0.31
525
525
44.2
0.32
500
500
48.6
0.33
474
474
53.6
0.35
457
457
60.4
0.37
68
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
24,750
285
54
42.7
0.17
291
56
41.4
0.17
287
55
42.4
0.17
297
60
40.1
0.17
307
60
38.4
0.17
319
69
37.0
0.17
48/50P2,P3,P4,P5055 (55 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
11,000
13,750
16,500
19,250
22,000
24,750
11,000
13,750
16,500
19,250
22,000
TC
252
270
281
289
295
300
265
283
294
302
309
SHC
-72
-67
-59
-49
-39
-29
-117
-119
-117
-114
-110
80
kW
44.1
43.6
43.4
43.3
43.3
43.3
44.8
44.3
44.2
44.0
44.0
BF
0.07
0.10
0.12
0.15
0.16
0.18
0.00
0.11
0.14
0.16
0.18
TC
258
275
286
295
301
305
270
288
300
308
314
SHC
-70
-64
-56
-47
-37
-26
-115
-116
-115
-111
-107
75
kW
42.7
42.3
42.1
42.0
42.1
42.0
43.5
43.1
42.9
42.8
42.8
BF
0.07
0.10
0.12
0.15
0.16
0.18
0.00
0.11
0.14
0.16
0.18
TC
256
272
283
291
296
301
268
285
296
303
309
SHC
-70
-64
-57
-48
-38
-27
-115
-117
-115
-112
-108
70
kW
43.6
43.2
43.2
43.2
43.2
43.2
44.4
44.1
44.1
44.0
44.0
BF
0.07
0.10
0.12
0.15
0.16
0.18
0.00
0.11
0.14
0.16
0.18
TC
265
282
293
301
307
311
277
295
306
314
320
SHC
-65
-59
-52
-43
-33
-23
-110
-112
-110
-108
-103
60
kW
41.1
40.9
40.9
40.9
40.9
41.0
42.0
41.8
41.8
41.7
41.8
BF
0.07
0.10
0.12
0.15
0.16
0.18
0.00
0.12
0.14
0.16
0.18
TC
274
291
302
310
317
322
286
303
315
324
331
SHC
-60
-55
-47
-39
-29
-22
-106
-107
-106
-103
-99
50
kW
39.1
39.0
39.0
39.1
39.2
39.3
40.0
39.9
40.0
40.0
40.1
BF
0.07
0.10
0.12
0.14
0.16
0.18
0.00
0.11
0.14
0.16
0.18
TC
281
300
312
322
329
335
294
313
327
337
344
SHC
-56
-51
-43
-33
-23
-13
-102
-103
-101
-98
-94
40
kW
37.4
37.4
37.6
37.7
37.7
37.8
38.3
38.4
38.5
38.5
38.6
BF
0.07
0.10
0.12
0.14
0.16
0.18
0.00
0.12
0.14
0.16
0.18
24,750
313
-105
44.0
0.20
319
-102
42.8
0.20
314
-103
44.0
0.20
324
-99
41.8
0.20
336
-94
40.1
0.20
350
-89
38.7
0.20
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
69
19,250
62
609
539
35.5
0.11
596
532
39.6
0.11
576
525
44.5
0.10
555
509
51.2
0.12
519
494
61.3
0.12
57
575
575
34.9
0.25
565
565
38.9
0.27
551
551
44.1
0.28
533
533
50.7
0.31
505
505
60.6
0.34
75
776
334
38.8
0.18
757
327
42.9
0.17
737
321
48.0
0.17
711
312
54.8
0.15
72
737
390
38.1
0.16
717
383
42.0
0.15
699
376
47.0
0.15
674
367
53.5
0.15
641
356
63.6
0.14
67
678
488
36.9
0.13
661
481
40.9
0.13
644
474
45.9
0.13
619
464
52.3
0.13
585
451
61.9
0.13
62
625
581
35.8
0.13
609
575
39.8
0.13
592
561
44.9
0.15
568
548
51.4
0.15
537
523
60.8
0.18
57
602
602
35.4
0.33
591
591
39.5
0.34
577
577
44.6
0.36
558
558
51.1
0.38
529
529
61.1
0.41
TC
652 595 551 550
70
19,250
62
535
448
40.3
0.04
491
410
43.7
0.04
452
378
47.7
0.04
413
346
52.5
0.04
374
316
58.4
0.05
57
500
500
39.7
0.17
467
467
43.2
0.18
433
433
47.4
0.20
399
399
52.3
0.21
363
363
58.5
0.23
75
721
227
43.6
0.08
676
192
47.0
0.07
621
144
50.9
0.07
572
106
55.6
0.07
520
68
61.2
0.07
72
671
282
42.7
0.06
629
251
46.2
0.06
568
197
49.9
0.05
529
167
54.6
0.05
477
128
59.9
0.05
67
618
403
41.7
0.05
566
358
45.0
0.05
523
323
48.9
0.05
468
276
53.4
0.05
420
240
58.7
0.05
62
550
496
40.6
0.06
502
453
43.9
0.06
467
424
47.9
0.06
433
388
52.7
0.09
393
351
58.3
0.11
57
524
524
40.2
0.26
490
490
43.6
0.27
455
455
47.7
0.28
417
417
52.5
0.29
378
378
58.3
0.31
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
71
24,750
302
74
41.9
0.07
307
77
40.9
0.07
301
76
42.3
0.07
311
80
40.3
0.07
327
83
38.8
0.07
337
95
37.9
0.07
48/50P2,P3,P4,P5055 (55 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
11,000
13,750
16,500
19,250
22,000
24,750
11,000
13,750
16,500
19,250
22,000
TC
271
289
299
307
313
317
286
301
314
322
329
SHC
-67
-61
-52
-41
-29
-16
-114
-117
-115
-111
-106
80
kW
43.3
42.6
42.7
42.8
42.8
42.9
43.6
44.3
43.7
43.7
43.8
BF
0.02
0.03
0.04
0.05
0.07
0.08
0.00
0.05
0.06
0.07
0.08
TC
277
296
304
312
318
323
290
306
318
327
333
SHC
-65
-56
-50
-38
-26
-13
-112
-114
-113
-108
-103
75
kW
41.6
41.5
41.7
41.7
41.8
41.9
42.6
42.6
42.6
42.7
42.8
BF
0.01
0.03
0.04
0.05
0.07
0.08
0.00
0.05
0.06
0.07
0.08
TC
274
291
299
307
312
319
286
302
313
321
328
SHC
-65
-56
-50
-39
-27
-9
-113
-115
-113
-109
-104
70
kW
42.7
43.2
43.0
43.1
43.2
43.7
43.8
43.9
44.1
44.2
44.3
BF
0.02
0.03
0.04
0.05
0.07
0.08
0.00
0.05
0.06
0.07
0.08
TC
280
296
308
319
325
330
293
310
322
334
340
SHC
-62
-54
-45
-33
-21
-8
-109
-110
-108
-104
-99
60
kW
41.1
41.3
41.0
41.1
41.3
41.4
41.7
41.9
42.1
42.2
42.3
BF
0.01
0.03
0.04
0.06
0.07
0.08
0.00
0.05
0.06
0.07
0.09
TC
290
308
320
333
338
344
303
322
338
347
354
SHC
-56
-49
-39
-33
-14
-6
-103
-104
-102
-98
-93
50
kW
38.9
39.2
39.5
39.0
39.7
39.7
40.1
40.3
40.4
40.6
40.7
BF
0.01
0.03
0.04
0.05
0.07
0.08
0.00
0.05
0.06
0.07
0.09
TC
300
319
335
340
349
354
314
337
346
357
364
SHC
-51
-43
-37
-22
-13
0
-98
-103
-97
-96
-90
40
kW
37.5
37.7
37.6
38.3
38.7
38.8
38.6
38.3
39.1
39.6
39.9
BF
0.01
0.03
0.04
0.05
0.08
0.09
0.00
0.05
0.06
0.08
0.10
24,750
334
-100
43.8
0.10
339
-97
42.8
0.10
333
-98
44.3
0.10
345
-93
42.4
0.10
359
-87
40.9
0.10
372
-81
39.3
0.10
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
72
TC
700 668 612
657 624 569
682 650 594
SHC
115
kW
68.1 68.7 70.2
68.8 69.1 70.3
67.5 68.0 69.8
BF
0.00 0.25 0.12
0.00 0.18 0.14
0.24 0.17 0.15
21,000
62
667
577
41.9
0.14
647
568
47.0
0.14
622
556
53.3
0.14
591
541
62.3
0.15
554
522
73.7
0.15
57
624
624
41.2
0.26
607
607
46.6
0.27
587
587
53.2
0.30
564
564
62.4
0.33
75
834
351
45.9
0.12
803
341
50.1
0.29
779
334
55.4
0.26
748
324
61.6
0.23
714
313
69.4
0.22
72
796
415
44.8
0.21
773
407
49.3
0.20
748
399
54.8
0.19
717
388
61.4
0.19
681
376
69.5
0.18
67
739
520
43.4
0.17
718
511
48.2
0.17
692
501
54.1
0.17
661
489
61.1
0.17
625
476
70.4
0.16
62
684
621
42.4
0.17
663
611
47.5
0.17
636
598
53.6
0.17
605
576
62.2
0.17
570
556
72.7
0.20
57
653
653
41.7
0.33
636
636
47.0
0.35
616
616
53.1
0.37
591
591
61.8
0.39
562
562
72.3
0.42
73
21,000
62
626
522
47.1
0.12
589
492
51.0
0.12
560
470
55.9
0.13
528
447
61.7
0.13
494
422
68.5
0.13
57
570
570
45.8
0.23
546
546
50.2
0.24
521
521
55.2
0.25
495
495
61.3
0.27
465
465
68.4
0.29
75
789
269
50.3
0.17
755
244
54.4
0.17
727
227
59.6
0.17
679
192
64.7
0.17
644
173
71.2
0.17
72
758
344
49.7
0.16
717
311
53.5
0.16
684
288
58.4
0.16
646
262
64.0
0.16
605
235
70.1
0.16
67
692
450
48.1
0.15
661
427
52.4
0.15
629
404
57.3
0.15
593
379
62.8
0.15
555
353
69.2
0.15
62
634
559
47.0
0.15
605
537
51.3
0.15
575
513
56.2
0.15
542
489
61.8
0.16
506
462
68.5
0.16
57
599
599
46.3
0.31
586
586
51.6
0.32
548
548
55.7
0.33
519
519
61.5
0.34
489
489
68.4
0.36
74
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
27,000
294
34
49.3
0.19
300
37
47.8
0.19
295
35
49.4
0.19
306
40
46.7
0.19
316
45
44.6
0.19
327
50
42.9
0.19
48/50P2,P3,P4,P5060 (60 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
12,000
15,000
18,000
21,000
24,000
27,000
12,000
15,000
18,000
21,000
24,000
TC
259
277
289
298
304
309
272
291
303
312
318
SHC
-99
-94
-86
-77
-67
-56
-149
-151
-150
-148
-144
80
kW
50.7
50.3
50.1
50.1
50.1
50.1
51.6
51.1
51.0
50.9
51.0
BF
0.08
0.11
0.13
0.16
0.18
0.19
0.00
0.12
0.15
0.17
0.19
TC
264
282
295
304
310
315
278
296
309
318
325
SHC
-96
-91
-83
-74
-64
-53
-146
-148
-148
-145
-141
75
kW
49.1
48.8
48.7
48.6
48.7
48.7
50.0
49.7
49.6
49.6
49.6
BF
0.07
0.11
0.13
0.16
0.18
0.19
0.00
0.12
0.15
0.17
0.19
TC
262
279
291
299
305
310
275
292
304
312
318
SHC
-96
-92
-84
-75
-65
-55
-147
-149
-149
-146
-143
70
kW
50.5
50.3
50.2
50.3
50.3
50.4
51.5
51.3
51.3
51.3
51.3
BF
0.08
0.11
0.13
0.16
0.18
0.19
0.00
0.12
0.15
0.17
0.19
TC
272
289
301
309
315
320
285
302
314
323
329
SHC
-91
-87
-79
-70
-60
-50
-142
-144
-144
-142
-138
60
kW
47.6
47.5
47.5
47.6
47.7
47.7
48.7
48.5
48.6
48.7
48.7
BF
0.07
0.11
0.13
0.16
0.18
0.19
0.00
0.12
0.15
0.17
0.19
TC
280
298
310
319
325
330
293
311
324
332
339
SHC
-86
-82
-74
-66
-56
-46
-137
-139
-139
-137
-133
50
kW
45.2
45.1
45.3
45.4
45.6
45.7
46.3
46.3
46.4
46.6
46.7
BF
0.07
0.11
0.13
0.16
0.18
0.19
0.00
0.12
0.15
0.17
0.19
TC
288
306
319
329
337
344
301
320
334
345
353
SHC
-82
-78
-70
-61
-51
-40
-133
-135
-134
-132
-128
40
kW
43.2
43.3
43.5
43.7
43.9
44.0
44.4
44.5
44.7
44.9
45.0
BF
0.07
0.11
0.13
0.16
0.17
0.19
0.00
0.13
0.15
0.17
0.19
27,000
324
-139
51.0
0.21
330
-137
49.6
0.21
323
-138
51.4
0.21
334
-133
48.8
0.21
345
-129
46.8
0.21
359
-123
45.1
0.21
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
75
TC
688 630
675 639 582 527 482 706 668 610 554 523
SHC
366 456
276 316 378 440 476 296 343 419 493 523
115
kW
70.1 69.7 69.6 68.0 71.2 72.8 70.9 70.6 71.2 70.6 72.6 71.6
BF
0.00 0.15 0.10 0.07 0.16 0.07 0.13 0.11 0.10 0.25 0.15 0.12
21,000
62
666
588
41.4
0.11
656
580
46.3
0.12
637
571
52.3
0.12
610
556
60.2
0.13
574
540
71.7
0.13
57
628
628
40.7
0.25
619
619
45.3
0.26
605
605
51.3
0.28
584
584
59.0
0.30
555
555
70.8
0.34
75
851
364
46.0
0.21
831
358
50.5
0.19
808
350
56.4
0.18
775
339
64.1
0.17
72
809
426
45.0
0.17
788
418
49.4
0.17
766
410
55.1
0.16
736
400
62.4
0.16
67
744
531
43.4
0.14
727
524
48.0
0.14
707
516
53.7
0.14
679
505
61.0
0.14
644
491
72.2
0.14
62
685
629
42.0
0.15
672
625
46.7
0.14
652
613
52.7
0.15
624
598
60.2
0.16
590
573
71.6
0.18
57
659
659
41.3
0.33
647
647
46.0
0.34
633
633
52.0
0.35
611
611
59.6
0.38
582
582
71.3
0.41
TC
76
21,000
62
588
486
46.4
0.04
555
458
50.4
0.04
516
426
55.2
0.04
474
393
60.6
0.05
432
361
67.7
0.05
57
558
558
45.7
0.16
526
526
49.8
0.17
492
492
54.7
0.19
457
457
60.5
0.20
420
420
67.8
0.22
75
829
285
51.3
0.09
759
221
54.9
0.08
689
159
59.2
0.08
644
127
64.7
0.08
587
86
71.2
0.08
72
752
318
49.9
0.06
710
286
53.8
0.06
668
254
58.4
0.06
597
193
63.4
0.06
544
155
69.6
0.06
67
683
439
48.5
0.05
639
402
52.2
0.05
581
352
56.6
0.05
534
315
61.8
0.05
482
276
68.1
0.05
62
620
554
47.0
0.06
568
507
50.8
0.06
546
490
55.6
0.07
493
440
60.9
0.09
451
400
67.5
0.11
57
588
588
46.4
0.25
553
553
50.4
0.26
516
516
55.1
0.27
478
478
60.6
0.28
438
438
67.6
0.30
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
77
27,000
332
73
48.7
0.08
337
77
47.5
0.08
331
76
49.4
0.08
340
78
47.1
0.08
353
83
45.3
0.08
365
91
44.2
0.08
48/50P2,P3,P4,P5060 (60 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
12,000
15,000
18,000
21,000
24,000
27,000
12,000
15,000
18,000
21,000
24,000
TC
300
317
329
338
344
350
314
332
345
354
361
SHC
-77
-72
-63
-51
-39
-25
-130
-133
-132
-128
-123
80
kW
49.2
49.3
49.5
49.6
49.8
49.8
50.5
50.6
50.7
50.8
50.9
BF
0.02
0.03
0.05
0.06
0.07
0.09
0.00
0.05
0.06
0.08
0.09
TC
304
322
334
342
349
354
318
337
349
359
366
SHC
-75
-69
-60
-49
-35
-22
-128
-131
-129
-126
-120
75
kW
47.9
48.1
48.3
48.5
48.6
48.7
49.2
49.4
49.5
49.7
49.8
BF
0.01
0.03
0.05
0.06
0.07
0.09
0.00
0.05
0.06
0.08
0.09
TC
300
317
328
336
343
347
313
331
343
352
359
SHC
-76
-70
-61
-50
-37
-25
-129
-132
-130
-127
-121
70
kW
49.6
49.9
50.2
50.4
50.6
50.8
51.0
51.3
51.5
51.8
51.9
BF
0.02
0.03
0.05
0.06
0.07
0.09
0.00
0.05
0.06
0.08
0.09
TC
307
325
336
345
351
357
321
339
352
361
368
SHC
-72
-66
-56
-48
-35
-22
-124
-127
-126
-125
-120
60
kW
47.2
47.5
47.9
48.2
48.4
48.5
48.6
48.9
49.2
49.6
49.8
BF
0.01
0.03
0.05
0.06
0.08
0.09
0.00
0.05
0.06
0.08
0.10
TC
315
334
348
357
364
370
330
350
364
374
381
SHC
-67
-60
-54
-38
-30
-17
-120
-121
-123
-120
-115
50
kW
45.2
45.6
46.0
46.3
46.5
46.7
46.6
47.0
47.4
47.6
47.8
BF
0.01
0.03
0.05
0.06
0.08
0.09
0.00
0.05
0.07
0.08
0.10
TC
325
346
360
370
378
384
340
362
376
387
395
SHC
-62
-54
-47
-36
-23
-10
-117
-119
-118
-114
-109
40
kW
43.5
44.1
44.4
44.6
44.8
45.0
45.0
45.4
45.7
45.9
46.1
BF
0.01
0.03
0.05
0.06
0.08
0.09
0.00
0.05
0.07
0.08
0.10
27,000
367
-116
51.0
0.10
372
-114
49.9
0.10
364
-115
52.1
0.10
373
-114
50.0
0.11
387
-108
47.9
0.11
402
-102
46.3
0.11
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
78
24,500
62
744
672
44.3
0.10
722
660
49.1
0.11
695
647
54.8
0.11
664
631
62.0
0.11
629
602
71.1
0.14
57
710
710
43.5
0.27
694
694
48.3
0.29
673
673
54.1
0.31
648
648
61.4
0.34
620
620
71.0
0.37
75
924
402
48.9
0.17
900
394
53.4
0.16
871
385
58.9
0.16
836
374
65.3
0.15
796
361
73.0
0.14
72
882
479
47.7
0.13
860
471
52.3
0.13
832
461
57.9
0.13
798
449
64.4
0.13
760
435
72.4
0.13
67
820
606
46.1
0.12
798
597
50.8
0.12
771
586
56.4
0.12
737
573
62.9
0.11
700
559
71.7
0.11
62
761
722
44.7
0.13
739
709
49.5
0.14
711
688
55.1
0.15
679
672
62.0
0.16
650
641
70.8
0.20
57
741
741
44.2
0.35
724
724
49.0
0.36
702
702
54.8
0.38
676
676
61.8
0.41
646
646
71.1
0.43
79
24,500
62
671
580
49.6
0.11
668
584
54.3
0.11
646
571
60.7
0.11
613
547
66.7
0.12
576
522
73.5
0.12
57
663
663
49.3
0.26
623
623
53.3
0.27
616
616
60.4
0.28
586
586
66.6
0.30
555
555
73.5
0.32
75
875
308
54.8
0.16
833
279
59.0
0.15
791
250
63.8
0.15
747
221
69.3
0.15
718
209
76.3
0.15
72
813
369
53.1
0.14
793
361
57.8
0.14
753
333
62.7
0.14
713
305
68.2
0.14
668
275
74.5
0.14
67
767
525
51.7
0.13
731
497
56.1
0.13
696
472
61.1
0.13
657
444
66.7
0.13
615
416
73.0
0.13
62
703
648
50.4
0.14
672
624
54.7
0.14
639
597
59.6
0.15
604
560
65.3
0.17
567
526
71.7
0.19
57
681
681
49.6
0.34
675
675
55.7
0.35
621
621
59.2
0.36
589
589
64.9
0.37
554
554
71.4
0.39
80
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
30,000
320
51
54.7
0.16
327
54
53.0
0.16
334
57
51.6
0.16
324
55
53.5
0.16
336
61
50.8
0.16
349
67
48.8
0.16
48/50P2,P3,P4,P5070 (70 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
14,000
17,500
21,000
24,500
28,000
30,000
14,000
17,500
21,000
24,500
28,000
TC
289
307
319
327
333
336
303
321
333
342
348
SHC
-105
-97
-86
-73
-59
-51
-162
-163
-160
-156
-149
80
kW
55.8
55.6
55.5
55.5
55.5
55.5
56.8
56.6
56.4
56.5
56.6
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.02
0.12
0.14
0.15
0.17
TC
296
314
326
334
340
344
310
328
340
350
357
SHC
-101
-93
-82
-70
-56
-48
-159
-159
-157
-152
-145
75
kW
54.1
53.9
53.9
54.0
54.0
54.0
55.2
54.9
54.9
55.0
55.0
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.02
0.12
0.14
0.15
0.17
TC
302
320
332
341
349
352
316
334
348
358
366
SHC
-98
-90
-79
-66
-52
-44
-155
-156
-153
-148
-142
70
kW
52.6
52.5
52.4
52.5
52.6
52.6
53.7
53.5
53.5
53.6
53.6
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.02
0.12
0.14
0.15
0.17
TC
296
312
322
330
335
338
308
325
335
343
349
SHC
-99
-91
-80
-68
-55
-47
-156
-158
-156
-151
-145
60
kW
54.2
54.2
54.3
54.5
54.7
54.7
55.5
55.5
55.7
55.8
55.9
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.02
0.12
0.14
0.15
0.17
TC
306
323
334
342
348
351
319
337
348
356
363
SHC
-92
-84
-74
-62
-48
-40
-150
-151
-149
-144
-138
50
kW
51.3
51.4
51.6
51.8
52.0
52.1
52.6
52.7
52.9
53.1
53.4
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.02
0.12
0.14
0.15
0.17
TC
315
333
345
355
362
366
329
348
361
371
379
SHC
-87
-79
-68
-55
-42
-34
-144
-145
-142
-137
-131
40
kW
48.9
49.1
49.5
49.8
50.0
50.1
50.3
50.6
50.9
51.2
51.4
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.03
0.12
0.14
0.16
0.17
30,000
351
-145
56.6
0.18
361
-141
55.1
0.18
370
-137
53.7
0.18
351
-141
56.0
0.18
367
-134
53.4
0.18
382
-127
51.5
0.18
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
81
24,500
62
753
700
44.7
0.04
734
692
49.2
0.04
718
683
54.8
0.04
691
668
61.3
0.05
659
646
69.6
0.07
57
729
729
44.2
0.25
714
714
48.7
0.27
699
699
54.2
0.29
680
680
60.8
0.31
654
654
69.2
0.33
75
956
423
50.2
0.07
926
413
54.5
0.07
902
405
60.0
0.07
871
395
66.6
0.06
834
382
75.0
0.06
72
911
504
48.9
0.05
882
494
53.3
0.05
860
486
58.7
0.05
831
476
65.4
0.05
795
463
73.8
0.05
67
839
639
46.9
0.04
817
630
51.4
0.04
795
621
56.9
0.04
766
610
63.5
0.04
731
595
72.0
0.04
62
771
757
45.3
0.06
753
742
49.7
0.08
734
730
55.2
0.09
711
702
61.6
0.13
682
682
69.2
0.14
57
764
764
45.1
0.33
746
746
49.6
0.35
730
730
55.1
0.36
709
709
61.6
0.38
682
682
70.0
0.40
82
24,500
62
698
607
50.3
0.05
664
579
54.5
0.05
631
553
59.6
0.06
592
523
65.6
0.06
559
494
73.1
0.08
57
669
669
49.6
0.21
638
638
53.9
0.22
607
607
59.0
0.23
569
569
65.2
0.25
536
536
72.9
0.27
75
879
288
55.3
0.08
833
253
59.3
0.08
787
218
64.0
0.08
737
181
69.5
0.08
683
143
75.9
0.08
72
836
375
54.1
0.06
793
342
58.1
0.06
749
308
62.9
0.06
701
273
68.4
0.06
649
236
74.9
0.06
67
769
522
52.2
0.06
733
493
56.4
0.06
693
462
61.3
0.06
648
429
66.9
0.06
601
396
73.7
0.06
62
716
664
50.8
0.08
683
636
55.0
0.08
649
600
60.0
0.10
610
563
65.8
0.12
572
527
73.1
0.13
57
700
700
50.3
0.29
667
667
54.6
0.30
634
634
59.7
0.31
598
598
65.7
0.33
556
556
73.0
0.34
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
83
30,000
347
75
53.1
0.08
353
78
51.9
0.08
357
81
50.8
0.08
346
80
53.8
0.08
356
81
51.4
0.09
367
87
49.4
0.09
48/50P2,P3,P4,P5070 (70 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
14,000
17,500
21,000
24,500
28,000
30,000
14,000
17,500
21,000
24,500
28,000
TC
316
335
347
355
361
364
332
350
362
370
377
SHC
-96
-86
-73
-59
-44
-34
-154
-155
-153
-148
-141
80
kW
54.4
53.8
54.0
54.2
54.4
54.4
55.0
55.1
55.4
55.5
55.7
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.06
0.07
0.09
0.10
TC
323
341
352
360
366
369
336
355
367
376
382
SHC
-91
-82
-71
-57
-41
-31
-154
-153
-150
-145
-138
75
kW
52.3
52.5
52.8
53.0
53.1
53.2
54.4
53.9
54.1
54.3
54.5
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.06
0.07
0.09
0.10
TC
326
345
357
365
372
375
342
360
372
382
390
SHC
-90
-80
-68
-54
-37
-28
-148
-150
-147
-142
-134
70
kW
51.5
51.4
51.7
51.9
52.1
52.2
52.4
52.8
53.0
53.3
53.4
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.06
0.07
0.09
0.10
TC
320
336
346
353
359
361
333
349
360
368
373
SHC
-89
-81
-69
-55
-39
-34
-149
-151
-148
-143
-136
60
kW
53.6
54.1
54.6
54.9
55.2
55.5
55.2
55.7
56.1
56.5
56.7
BF
0.02
0.04
0.05
0.07
0.08
0.10
0.00
0.06
0.07
0.09
0.10
TC
329
345
356
363
369
371
342
359
369
378
383
SHC
-83
-75
-62
-53
-38
-29
-143
-145
-147
-136
-135
50
kW
51.1
51.7
52.2
52.6
52.8
52.9
52.7
53.3
53.9
54.1
54.5
BF
0.02
0.04
0.05
0.08
0.09
0.10
0.00
0.06
0.08
0.09
0.11
TC
335
352
365
374
381
385
349
368
383
390
398
SHC
-78
-74
-62
-40
-32
-23
-138
-138
-150
-129
-129
40
kW
49.1
49.7
50.2
50.7
50.8
51.0
50.7
51.3
50.8
52.2
52.4
BF
0.02
0.04
0.06
0.07
0.09
0.10
0.00
0.06
0.08
0.09
0.11
30,000
380
-136
55.7
0.11
385
-133
54.5
0.11
393
-130
53.5
0.11
376
-132
56.8
0.11
386
-131
54.6
0.12
401
-124
52.5
0.12
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
84
24,500
62
789
693
48.3
0.10
765
682
53.8
0.10
735
667
60.2
0.10
701
650
69.2
0.11
664
631
79.9
0.11
57
745
745
47.3
0.24
726
726
52.9
0.26
704
704
59.1
0.28
678
678
68.0
0.31
647
647
79.4
0.34
75
981
420
53.3
0.20
957
413
58.4
0.18
925
403
64.6
0.17
886
390
71.8
0.16
845
377
81.0
0.15
72
937
499
52.0
0.14
910
490
57.1
0.13
884
480
63.5
0.13
846
467
70.7
0.13
806
452
80.3
0.13
67
874
627
50.3
0.12
848
617
55.6
0.12
817
605
61.9
0.12
781
591
69.6
0.12
742
574
79.6
0.12
62
809
747
48.8
0.12
783
734
54.2
0.13
752
716
60.5
0.13
717
693
69.1
0.15
683
669
78.5
0.17
57
780
780
48.0
0.32
760
760
53.5
0.33
735
735
60.1
0.36
708
708
68.7
0.38
677
677
79.4
0.41
85
24,500
62
725
610
53.7
0.11
681
576
58.3
0.11
682
585
66.0
0.11
645
559
72.6
0.11
607
533
80.3
0.12
57
674
674
52.5
0.22
670
670
59.6
0.24
641
641
65.6
0.25
610
610
72.3
0.27
576
576
80.2
0.29
75
914
310
58.7
0.16
878
287
63.4
0.16
859
282
69.9
0.16
789
226
74.9
0.15
764
219
83.1
0.15
72
868
391
57.4
0.14
838
371
62.2
0.14
797
341
67.6
0.14
752
311
73.7
0.13
704
279
80.6
0.13
67
809
530
55.8
0.12
773
508
60.4
0.13
734
480
65.9
0.13
692
451
72.1
0.13
647
421
79.0
0.13
62
743
665
54.1
0.13
710
639
58.8
0.13
674
611
64.3
0.14
634
582
70.5
0.14
622
570
80.7
0.17
57
709
709
53.3
0.31
680
680
58.1
0.32
648
648
63.7
0.33
613
613
70.0
0.34
577
577
77.3
0.36
86
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
30,000
339
38
59.0
0.16
347
42
57.2
0.16
355
46
55.5
0.16
341
42
58.2
0.16
355
49
55.1
0.16
367
56
52.6
0.16
48/50P2,P3,P4,P5075 (75 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
14,000
17,500
21,000
24,500
28,000
30,000
14,000
17,500
21,000
24,500
28,000
TC
301
322
336
345
353
356
317
337
351
361
369
SHC
-114
-107
-97
-86
-73
-65
-173
-175
-174
-170
-164
80
kW
60.5
60.1
59.9
59.9
59.9
59.9
61.5
61.1
60.9
61.0
61.0
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.00
0.13
0.14
0.15
0.17
TC
308
329
343
353
361
364
324
345
359
369
377
SHC
-110
-103
-94
-82
-69
-61
-169
-171
-170
-166
-161
75
kW
58.6
58.3
58.1
58.1
58.2
58.2
59.6
59.3
59.2
59.2
59.3
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.00
0.13
0.14
0.15
0.17
TC
315
336
351
360
368
372
330
352
366
376
385
SHC
-107
-100
-90
-78
-65
-58
-166
-168
-166
-162
-157
70
kW
56.8
56.5
56.4
56.6
56.6
56.7
58.0
57.7
57.6
57.7
57.7
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.00
0.06
0.14
0.15
0.17
TC
308
326
339
347
353
356
321
340
352
361
368
SHC
-108
-102
-92
-81
-68
-61
-167
-170
-169
-165
-160
60
kW
58.9
59.0
59.1
59.3
59.4
59.5
60.3
60.3
60.4
60.6
60.8
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.00
0.12
0.14
0.15
0.17
TC
320
339
352
361
367
371
334
353
366
375
382
SHC
-101
-95
-85
-74
-61
-54
-160
-162
-161
-158
-153
50
kW
55.6
55.7
55.9
56.2
56.4
56.5
57.0
57.1
57.4
57.6
57.7
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.00
0.14
0.14
0.15
0.17
TC
330
350
363
372
380
384
344
364
377
388
397
SHC
-95
-88
-79
-68
-55
-48
-154
-156
-155
-152
-146
40
kW
52.8
53.1
53.4
53.7
54.0
54.1
54.3
54.5
54.9
55.2
55.4
BF
0.07
0.10
0.12
0.14
0.16
0.17
0.00
0.06
0.14
0.16
0.17
30,000
372
-160
60.9
0.18
380
-157
59.3
0.18
390
-153
57.8
0.18
371
-157
60.9
0.18
385
-150
57.8
0.18
401
-143
55.6
0.18
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
87
24,500
62
803
724
48.5
0.04
786
716
53.6
0.04
763
705
59.7
0.04
733
690
67.0
0.04
699
673
76.7
0.04
57
767
767
47.7
0.22
752
752
52.7
0.23
735
735
58.8
0.25
714
714
66.1
0.27
687
687
75.8
0.30
75
1016
444
54.4
0.07
980
431
59.3
0.07
954
423
65.3
0.07
922
412
72.6
0.06
884
399
82.1
0.06
72
967
525
53.0
0.05
938
514
57.9
0.05
913
505
64.0
0.05
881
493
71.3
0.05
843
480
80.8
0.05
67
892
659
50.9
0.04
869
650
55.9
0.04
845
641
62.0
0.04
813
628
69.3
0.04
777
614
79.0
0.04
62
823
785
49.1
0.05
802
774
54.1
0.06
777
760
60.0
0.06
751
744
67.3
0.07
719
709
75.3
0.12
57
805
805
48.7
0.30
787
787
53.7
0.31
769
769
59.8
0.33
746
746
67.1
0.35
718
718
76.5
0.37
88
24,500
62
761
644
54.5
0.05
743
633
59.9
0.05
706
606
65.5
0.05
670
580
72.5
0.05
629
551
81.0
0.06
57
717
717
53.5
0.17
689
689
58.4
0.18
657
657
64.1
0.20
623
623
71.3
0.22
586
586
79.8
0.23
75
966
333
60.2
0.08
923
302
64.8
0.08
880
271
70.3
0.08
833
239
76.6
0.08
781
205
84.0
0.08
72
919
421
58.8
0.06
880
392
63.5
0.06
842
365
69.1
0.06
796
333
75.4
0.06
744
297
82.8
0.06
67
847
561
56.8
0.06
812
539
61.6
0.06
782
520
67.4
0.06
739
490
73.8
0.06
694
460
81.7
0.06
62
773
697
54.8
0.07
747
677
59.9
0.07
711
647
65.5
0.08
671
610
72.0
0.10
631
573
80.1
0.12
57
753
753
54.4
0.26
741
741
60.0
0.27
708
708
65.7
0.28
674
674
72.7
0.30
635
635
81.0
0.31
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
89
30,000
364
56
58.6
0.08
371
60
56.9
0.08
377
63
55.5
0.08
363
60
58.8
0.08
375
66
55.9
0.08
385
71
53.6
0.08
48/50P2,P3,P4,P5075 (75 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
70.5 Wet Bulb (80% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
14,000
17,500
21,000
24,500
28,000
30,000
14,000
17,500
21,000
24,500
28,000
TC
327
348
362
371
378
381
342
363
377
387
394
SHC
-111
-104
-93
-80
-65
-56
-174
-176
-175
-171
-165
80
kW
60.0
59.7
59.6
59.8
59.9
60.0
61.4
61.1
61.1
61.3
61.5
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.07
0.07
0.09
0.10
TC
333
354
368
377
385
388
348
370
384
393
401
SHC
-107
-100
-90
-77
-62
-52
-170
-173
-172
-168
-161
75
kW
58.2
57.9
58.1
58.2
58.3
58.4
59.6
59.4
59.6
59.7
59.8
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.07
0.07
0.09
0.10
TC
339
360
374
383
391
395
354
375
390
400
409
SHC
-104
-97
-87
-73
-58
-49
-167
-170
-168
-164
-158
70
kW
56.6
56.5
56.6
56.7
56.8
56.9
58.1
57.9
58.1
58.2
58.4
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.07
0.07
0.09
0.10
TC
330
349
361
370
376
379
344
363
376
384
391
SHC
-106
-99
-89
-76
-61
-52
-169
-172
-171
-167
-161
60
kW
59.4
59.6
59.9
60.2
60.4
60.5
61.2
61.4
61.6
61.9
62.2
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.06
0.07
0.09
0.10
TC
341
360
372
381
388
391
355
375
387
396
403
SHC
-99
-93
-83
-70
-55
-46
-162
-165
-165
-161
-155
50
kW
56.2
56.5
56.9
57.3
57.5
57.6
58.0
58.3
58.6
59.0
59.2
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.07
0.07
0.09
0.10
TC
349
369
382
392
400
404
364
384
398
409
417
SHC
-94
-88
-78
-64
-49
-40
-157
-160
-159
-155
-149
40
kW
53.6
54.0
54.5
54.9
55.2
55.3
55.3
55.8
56.2
56.6
56.9
BF
0.02
0.04
0.05
0.07
0.08
0.09
0.00
0.07
0.07
0.09
0.10
30,000
398
-160
61.5
0.11
405
-157
59.9
0.11
413
-153
58.5
0.11
394
-157
62.3
0.11
407
-151
59.3
0.11
421
-144
57.0
0.11
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
90
31,500
62
981
863
59.2
0.13
947
846
66.0
0.13
909
828
73.7
0.13
867
807
82.8
0.13
821
784
94.2
0.14
57
922
922
58.2
0.25
899
899
65.1
0.28
873
873
72.9
0.30
839
839
82.0
0.33
802
802
93.8
0.36
75
1231
525
63.9
0.25
1187
512
70.3
0.22
1144
498
77.9
0.21
1095
482
86.6
0.19
1039
465
96.5
0.18
72
1175
624
62.8
0.17
1137
609
69.3
0.17
1093
594
76.9
0.16
1046
578
85.7
0.16
992
560
95.6
0.15
67
1090
781
61.1
0.15
1052
766
67.7
0.15
1011
750
75.4
0.15
965
732
84.2
0.14
914
712
94.5
0.14
62
1005
928
59.6
0.15
970
911
66.4
0.16
930
888
74.1
0.16
886
859
82.9
0.18
839
833
94.1
0.19
57
970
970
58.9
0.34
942
942
65.8
0.36
910
910
73.7
0.38
874
874
82.6
0.40
837
837
94.0
0.43
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
tldb = tedb
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb).
hlwb =
hewb
BF
79
81
.05
.10
.20
1.04
0.99
0.88
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for indoor fan motor heat.
91
31,500
62
925
782
58.6
0.15
910
778
65.9
0.15
866
746
73.6
0.15
819
712
82.5
0.15
769
675
92.7
0.16
57
883
883
58.4
0.26
844
844
65.1
0.26
808
808
73.0
0.28
770
770
82.0
0.30
728
728
92.5
0.31
75
1201
475
63.6
0.12
1144
436
69.8
0.12
1086
396
77.0
0.12
1041
372
85.6
0.12
974
329
94.8
0.13
72
1142
563
62.4
0.15
1088
525
68.7
0.15
1053
508
76.5
0.15
993
468
84.6
0.15
930
426
94.2
0.15
67
1045
707
60.7
0.16
996
673
67.0
0.16
944
637
74.2
0.16
916
625
83.5
0.16
858
586
93.4
0.16
62
952
846
59.1
0.17
935
841
66.4
0.18
890
807
73.9
0.18
843
773
82.8
0.19
790
728
92.9
0.20
57
923
923
59.0
0.33
887
887
65.7
0.34
849
849
73.5
0.35
807
807
82.4
0.37
762
762
92.7
0.39
92
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
48/50P2,P3,P4,P5090 (90 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
18,000
22,500
27,000
31,500
36,000
18,000
TC
409
440
461
477
490
432
SHC
-76
-64
-51
-35
-15
-139
80
kW
66.7
66.2
66.2
66.2
66.3
68.2
BF
0.06
0.10
0.13
0.15
0.17
0.00
TC
418
450
472
488
501
441
SHC
-68
-55
-40
-23
-5
-130
75
kW
64.5
64.3
64.4
64.6
64.7
66.3
BF
0.06
0.10
0.13
0.15
0.17
0.00
TC
423
453
475
490
502
444
SHC
-63
-49
-34
-16
2
-124
70
kW
64.8
64.9
65.1
65.4
65.6
66.8
BF
0.06
0.10
0.13
0.15
0.17
0.00
TC
434
464
486
501
513
455
SHC
-50
-35
-17
2
23
-109
60
kW
63.4
63.8
64.2
64.5
64.8
65.6
BF
0.06
0.10
0.13
0.15
0.17
0.00
TC
440
470
491
505
516
461
SHC
-38
-20
0
21
43
-93
50
kW
63.1
63.6
64.2
64.6
65.0
65.4
BF
0.06
0.10
0.13
0.15
0.17
0.01
TC
456
487
509
525
537
477
SHC
-26
-9
11
31
52
-84
40
kW
59.7
60.3
60.8
61.3
61.7
61.9
BF
0.05
0.10
0.13
0.15
0.17
0.00
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
75 Dry Bulb
65.3 Wet Bulb (60% RH)
22,500
415
14
64.9
0.11
425
21
62.7
0.11
430
25
62.9
0.11
441
39
61.6
0.11
448
51
61.3
0.11
464
63
58.1
0.11
27,000
436
39
64.7
0.14
446
47
62.6
0.14
451
50
63.0
0.14
462
66
62.1
0.14
468
80
61.9
0.14
485
91
58.7
0.14
31,500
451
63
64.8
0.16
462
73
62.7
0.16
465
78
63.4
0.16
477
93
62.4
0.16
482
109
62.4
0.16
501
120
59.2
0.16
36,000
463
90
64.7
0.18
474
100
62.9
0.18
477
105
63.7
0.18
488
122
62.8
0.18
493
139
62.8
0.18
513
150
59.6
0.18
31,500
502
-121
67.9
0.12
513
-110
66.4
0.12
514
-102
67.3
0.12
524
-80
66.5
0.13
527
-57
66.8
0.13
547
-50
63.3
0.12
36,000
514
-112
68.0
0.15
526
-101
66.5
0.15
527
-94
67.4
0.15
536
-70
66.7
0.15
538
-47
67.1
0.15
559
-38
63.6
0.15
75 Dry Bulb
70.5 Wet Bulb (80% RH)
22,500
463
-134
67.8
0.04
473
-125
66.1
0.04
476
-119
66.9
0.04
487
-100
65.9
0.05
491
-82
65.9
0.05
509
-74
62.4
0.04
27,000
485
-129
67.8
0.09
496
-118
66.2
0.09
498
-111
67.1
0.09
508
-91
66.2
0.09
512
-70
66.4
0.10
531
-62
62.9
0.09
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
93
31,500
62
1036
927
60.2
0.05
1005
912
66.9
0.05
971
895
74.8
0.05
930
875
83.9
0.05
882
852
94.4
0.06
57
984
984
59.2
0.22
962
962
65.9
0.24
936
936
73.8
0.26
905
905
83.1
0.28
868
868
94.2
0.31
75
1309
569
66.1
0.10
1255
551
72.3
0.09
1208
535
79.8
0.09
1161
520
88.5
0.08
1108
502
98.8
0.08
72
1246
672
64.7
0.07
1198
655
71.0
0.07
1153
640
78.5
0.06
1104
623
87.1
0.06
1059
605
97.8
0.06
67
1147
842
62.6
0.06
1113
829
69.2
0.06
1075
813
76.9
0.05
1031
797
86.0
0.05
979
776
96.7
0.05
62
1061
1004
60.8
0.07
1028
986
67.4
0.07
994
968
75.2
0.08
952
941
84.2
0.09
910
899
95.0
0.13
57
1031
1031
60.2
0.30
1006
1006
66.9
0.31
979
979
74.8
0.33
946
946
83.9
0.36
906
906
94.8
0.38
LEGEND
48/50P3,P5 units only.
BF Bypass Factor
kW
Compressor Motor Power Input
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
tldb = tedb
1.10 x cfm
Wet-bulb temperature corresponding to enthalpy of air
tlwb = leaving evaporator coil (h ).
lwb
hlwb =
hewb
BF
79
81
.05
.10
.20
1.04
0.99
0.88
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for indoor fan motor heat.
94
31,500
62
985
837
59.9
0.06
937
800
66.2
0.06
887
762
74.2
0.06
834
722
83.7
0.06
777
680
94.8
0.07
57
932
932
58.9
0.18
886
886
65.6
0.19
843
843
73.8
0.20
798
798
83.5
0.22
748
748
94.9
0.24
75
1259
474
65.1
0.05
1196
429
71.3
0.05
1129
382
78.4
0.06
1058
332
86.5
0.06
984
282
96.3
0.06
72
1198
577
63.9
0.06
1138
533
70.1
0.06
1074
487
77.3
0.06
1006
440
85.5
0.06
935
391
95.6
0.06
67
1103
748
62.0
0.06
1046
706
68.3
0.06
988
664
75.5
0.06
926
620
84.5
0.06
860
575
95.0
0.07
62
1014
911
60.4
0.08
964
872
66.7
0.08
912
831
74.5
0.09
858
793
83.8
0.10
803
735
94.6
0.12
57
974
974
59.7
0.26
930
930
66.1
0.27
885
885
74.1
0.29
836
836
83.6
0.30
783
783
94.7
0.32
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
95
48/50P2,P3,P4,P5090 (90 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
18,000
22,500
27,000
31,500
36,000
18,000
TC
435
467
489
505
517
458
SHC
-89
-76
-61
-42
-19
-159
80
kW
68.8
68.3
68.3
68.3
68.4
70.5
BF
0.01
0.03
0.05
0.06
0.08
0.00
TC
445
478
500
516
529
468
SHC
-82
-68
-50
-31
-10
-151
75
kW
66.6
66.4
66.5
66.7
66.8
68.5
BF
0.01
0.03
0.05
0.06
0.08
0.00
TC
448
480
501
517
528
471
SHC
-78
-64
-46
-27
-5
-147
70
kW
66.9
67.1
67.3
67.5
67.7
69.1
BF
0.01
0.03
0.05
0.06
0.08
0.00
TC
459
490
511
526
537
481
SHC
-67
-53
-35
-14
8
-137
60
kW
65.6
65.9
66.3
66.6
66.8
67.9
BF
0.01
0.03
0.05
0.06
0.08
0.00
TC
464
494
514
528
539
485
SHC
-60
-44
-25
-4
19
-129
50
kW
65.3
65.8
66.3
66.7
67.0
67.7
BF
0.01
0.03
0.05
0.06
0.08
0.00
TC
479
510
531
546
557
500
SHC
-47
-29
-8
14
38
-114
40
kW
62.2
62.8
63.3
63.8
64.1
64.6
BF
0.01
0.03
0.05
0.06
0.08
0.00
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
96
75 Dry Bulb
65.3 Wet Bulb (60% RH)
22,500
442
11
66.6
0.04
452
18
64.4
0.04
456
22
64.9
0.04
467
33
63.7
0.04
472
41
63.4
0.04
487
55
60.4
0.04
27,000
463
39
66.5
0.05
474
47
64.5
0.05
477
52
65.2
0.05
487
63
64.1
0.05
491
71
64.0
0.05
507
87
61.0
0.05
31,500
478
68
66.5
0.06
490
78
64.7
0.06
492
83
65.5
0.06
502
94
64.4
0.06
505
104
64.4
0.06
522
121
61.5
0.06
36,000
490
102
66.5
0.08
502
111
64.9
0.08
503
115
65.7
0.08
513
128
64.7
0.08
516
138
64.8
0.08
533
155
61.8
0.08
31,500
530
-141
70.2
0.06
542
-132
68.5
0.06
541
-128
69.5
0.06
549
-115
68.6
0.06
550
-104
68.9
0.06
568
-85
65.9
0.06
36,000
542
-131
70.3
0.07
554
-123
68.6
0.07
552
-118
69.6
0.07
560
-105
68.8
0.08
562
-93
69.1
0.08
580
-73
66.2
0.08
75 Dry Bulb
70.5 Wet Bulb (80% RH)
22,500
491
-156
70.1
0.01
502
-147
68.3
0.01
503
-143
69.2
0.01
512
-132
68.1
0.01
515
-123
68.1
0.01
532
-107
65.1
0.01
27,000
513
-150
70.1
0.04
525
-141
68.4
0.04
525
-137
69.3
0.04
534
-125
68.4
0.04
536
-114
68.5
0.04
553
-97
65.5
0.04
30,000
75
1285
535
70.8
0.12
1238
521
77.8
0.10
1191
506
86.0
0.28
1139
490
95.4
0.23
1080
471
106.1
0.20
72
1228
632
69.3
0.19
1186
617
76.5
0.18
1141
602
84.8
0.17
1090
585
94.3
0.16
1034
565
105.3
0.16
67
1138
786
67.4
0.15
1099
771
74.6
0.15
1056
754
83.1
0.14
1007
735
92.7
0.14
954
715
104.3
0.14
62
1050
935
65.7
0.14
1012
917
73.0
0.14
970
896
81.5
0.14
924
872
91.9
0.15
875
841
104.1
0.17
57
991
991
64.7
0.28
975
947
72.2
0.35
933
933
80.8
0.33
897
897
91.4
0.36
858
858
104.0
0.39
97
98
30,000
75
1261
494
70.6
0.10
1141
390
76.0
0.10
1073
340
83.4
0.10
1003
291
91.8
0.11
927
238
101.4
0.11
72
1167
547
68.5
0.14
1089
484
74.8
0.14
1024
437
82.3
0.14
955
387
90.7
0.14
882
335
100.6
0.14
67
1071
693
66.5
0.15
1003
638
73.0
0.15
945
596
80.5
0.15
866
533
89.0
0.15
823
508
99.7
0.15
62
986
841
64.8
0.16
939
805
71.5
0.16
889
767
79.5
0.17
836
727
88.8
0.17
779
686
99.5
0.18
57
932
932
63.9
0.27
892
892
70.8
0.29
850
850
79.0
0.30
805
805
88.5
0.32
756
756
99.4
0.34
57
998
998
65.0
0.41
964
964
72.1
0.42
876
876
79.0
0.43
825
825
88.2
0.45
813
813
99.9
0.46
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
48/50P2,P3,P4,P5100 (100 TON) STANDARD CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
20,000
25,000
30,000
35,000
40,000
20,000
TC
393
422
442
456
479
415
SHC
-127
-116
-104
-88
-56
-198
80
kW
75.0
74.6
74.6
74.7
73.8
77.0
BF
0.07
0.11
0.14
0.16
0.18
0.00
TC
413
443
464
479
491
436
SHC
-109
-96
-81
-64
-46
-178
75
kW
72.0
71.8
72.1
72.2
72.3
74.1
BF
0.07
0.11
0.14
0.16
0.18
0.00
TC
417
446
466
481
492
439
SHC
-103
-91
-75
-58
-40
-172
70
kW
72.4
72.5
72.8
73.1
73.2
74.8
BF
0.07
0.11
0.14
0.16
0.18
0.00
TC
429
457
477
495
507
450
SHC
-91
-76
-58
-53
-37
-158
60
kW
71.2
71.6
72.0
70.9
71.0
73.7
BF
0.07
0.11
0.14
0.16
0.19
0.00
TC
481
508
527
540
551
504
SHC
17
35
55
75
95
-47
50
kW
53.1
53.7
54.2
54.6
54.8
54.6
BF
0.08
0.13
0.16
0.19
0.21
0.03
TC
496
527
544
559
570
519
SHC
30
37
69
90
110
-34
40
kW
50.1
49.9
51.3
51.7
51.9
51.6
BF
0.08
0.12
0.16
0.19
0.21
0.03
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
75 Dry Bulb
65.3 Wet Bulb (60% RH)
25,000
398
-28
72.8
0.12
418
-11
69.9
0.12
423
-7
70.2
0.12
435
6
69.0
0.12
484
115
52.2
0.14
502
117
48.4
0.14
30,000
417
-3
72.7
0.15
438
15
69.9
0.15
442
20
70.5
0.15
454
34
69.5
0.15
503
145
52.7
0.17
520
159
49.8
0.17
35,000
431
21
72.8
0.17
453
42
70.1
0.17
456
47
70.8
0.17
468
63
69.9
0.17
516
175
53.2
0.19
534
189
50.2
0.19
40,000
453
60
71.9
0.19
465
70
70.2
0.19
467
75
71.0
0.19
482
79
69.0
0.20
526
204
53.4
0.21
545
219
50.5
0.21
35,000
492
-172
75.9
0.14
503
-161
74.4
0.14
504
-155
75.3
0.14
518
-151
72.8
0.12
564
-17
56.0
0.16
583
-1
53.0
0.16
40,000
504
-164
75.9
0.16
516
-152
74.4
0.16
515
-144
75.4
0.16
530
-143
72.9
0.15
574
-5
56.2
0.19
594
10
53.2
0.19
75 Dry Bulb
70.5 Wet Bulb (80% RH)
25,000
445
-195
76.5
0.05
466
-174
74.1
0.05
469
-169
74.9
0.05
479
-152
74.0
0.06
530
-37
55.2
0.08
550
-37
51.3
0.07
30,000
477
-179
75.7
0.10
488
-169
74.2
0.10
489
-162
75.1
0.10
503
-158
72.6
0.08
550
-28
55.6
0.13
568
-13
52.6
0.13
99
30,000
75
1373
585
73.9
0.14
1324
568
80.8
0.12
1275
552
89.0
0.10
1224
535
98.6
0.09
1166
516
109.9
0.08
72
1308
685
72.2
0.08
1265
670
79.2
0.07
1221
653
87.6
0.07
1170
635
97.3
0.07
1113
614
108.8
0.06
67
1210
852
69.7
0.06
1173
836
76.9
0.05
1131
819
85.5
0.05
1082
800
95.5
0.05
1027
778
107.6
0.05
62
1118
1010
67.5
0.06
1083
993
74.9
0.06
1041
971
83.4
0.06
995
945
94.0
0.07
945
912
106.5
0.09
57
1069
1069
66.4
0.24
1043
1043
73.8
0.25
1012
1012
82.5
0.28
975
975
93.0
0.30
933
933
105.5
0.33
100
62
1135
1072
68.2
0.13
1078
1010
74.9
0.14
1014
949
82.6
0.15
972
915
92.9
0.18
896
837
103.8
0.19
30,000
75
1306
470
72.1
0.04
1274
461
79.0
0.04
1171
370
86.3
0.04
1097
318
95.0
0.05
1010
255
105.2
0.05
72
1243
571
70.6
0.05
1213
560
77.6
0.06
1110
471
84.8
0.05
1041
422
93.8
0.05
971
374
104.6
0.05
67
1145
738
68.4
0.06
1136
745
76.2
0.06
1026
650
82.9
0.06
924
567
91.7
0.06
893
556
103.7
0.06
62
1080
929
67.0
0.07
1029
889
73.8
0.07
975
848
82.3
0.07
919
805
92.4
0.08
844
736
103.3
0.10
57
1025
1025
66.0
0.19
981
981
73.1
0.21
935
935
81.8
0.22
885
885
92.2
0.24
810
810
103.1
0.26
57
1114
1114
67.7
0.35
1051
1051
74.2
0.36
1012
1012
82.8
0.37
957
957
92.7
0.38
898
898
104.1
0.40
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 80).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. SHC values provided are in subcooling mode with the gas bypass
valve closed and reflect the maximum SHC in subcooling mode.
The P Series innovative modulating valve system can reduce SHC
as needed to meet the supply air set point requirement with minimal change in latent capacity. This will provide variable SHC to
meet the space load.
101
48/50P2,P3,P4,P5100 (100 TON) HIGH-CAPACITY COIL HOT GAS REHEAT MODE (cont)
Air Entering Evaporator Ewb (F)
Temp (F)
75 Dry Bulb
Air Ent
68 Wet Bulb (70% RH)
Condenser
Air Entering Evaporator Cfm
(Edb)
20,000
25,000
30,000
35,000
40,000
20,000
TC
432
462
483
498
509
455
SHC
-132
-120
-105
-86
-61
-211
80
kW
76.9
76.4
76.5
76.7
76.7
79.1
BF
0.01
0.04
0.06
0.07
0.09
0.00
TC
442
473
494
509
521
465
SHC
-126
-111
-93
-73
-51
-202
75
kW
74.7
74.6
74.8
75.0
75.1
77.1
BF
0.01
0.04
0.06
0.07
0.09
0.00
TC
446
475
495
509
520
467
SHC
-122
-108
-93
-71
-49
-199
70
kW
75.3
75.4
75.6
76.0
76.1
77.8
BF
0.01
0.04
0.06
0.07
0.09
0.00
TC
456
485
504
518
528
477
SHC
-110
-98
-80
-58
-35
-189
60
kW
74.0
74.3
74.7
75.1
75.3
76.7
BF
0.02
0.04
0.06
0.07
0.09
0.00
TC
461
488
507
520
530
481
SHC
-104
-89
-69
-47
-23
-181
50
kW
73.7
74.3
74.9
75.3
75.6
76.6
BF
0.02
0.04
0.06
0.07
0.09
0.00
TC
476
504
524
537
548
497
SHC
-90
-72
-51
-27
-2
-165
40
kW
70.7
71.4
72.0
72.5
72.8
73.6
BF
0.02
0.04
0.06
0.07
0.09
0.00
LEGEND
BF Bypass Factor
RH
Relative Humidity
Edb Entering Dry Bulb
SHC Sensible Heat Cap. (1000 Btuh)
Ewb Entering Wet Bulb
TC
Total Cap. (1000 Btuh) Gross
kW Compressor Motor Power
Input
NOTES:
1. The SHC is based on 75 F edb temperature of air entering evaporator coil. For edb temperatures other than 75 F, adjust SHC by
multiplying the correction factor and the cfm and then adding or
subtracting the value from the SHC.
2. Interpolation is permissible.
3. Correction Factor = 1.10 x (1 BF) x (edb 75).
4. Cooling capacities are gross and do not include deduction for
indoor fan motor heat.
5. Capacity table includes impact of outdoor fan staging at temperatures below 75 F.
102
75 Dry Bulb
65.3 Wet Bulb (60% RH)
25,000
437
-23
74.4
0.04
448
-15
72.2
0.04
451
-12
72.8
0.04
462
-2
71.6
0.04
467
5
71.5
0.04
482
21
68.6
0.04
30,000
457
7
74.2
0.06
469
15
72.4
0.06
471
16
73.1
0.06
481
29
72.1
0.06
485
38
72.1
0.06
501
55
69.2
0.06
35,000
472
37
74.4
0.07
483
48
72.7
0.07
485
51
73.5
0.07
494
62
72.5
0.07
498
72
72.6
0.07
514
91
69.8
0.07
40,000
483
73
74.4
0.09
494
82
72.8
0.09
495
84
73.7
0.09
505
99
72.8
0.09
507
110
72.9
0.09
525
129
70.1
0.09
35,000
522
-201
78.9
0.07
534
-188
77.3
0.07
532
-183
78.3
0.07
540
-169
77.6
0.07
541
-158
77.9
0.07
559
-136
75.1
0.07
40,000
534
-185
79.0
0.09
546
-174
77.4
0.09
544
-172
78.3
0.09
551
-157
77.7
0.09
552
-145
78.1
0.09
570
-122
75.3
0.09
75 Dry Bulb
70.5 Wet Bulb (80% RH)
25,000
486
-210
78.7
0.01
497
-201
77.0
0.02
497
-200
77.8
0.02
507
-187
76.9
0.02
509
-177
77.1
0.02
526
-158
74.2
0.02
30,000
507
-208
78.8
0.04
519
-196
77.1
0.05
518
-196
78.0
0.05
526
-180
77.3
0.05
528
-169
77.5
0.05
545
-148
74.7
0.05
AIRFLOW
(cfm)
6,000
7,500
9,000
10,500
12,000
13,500
15,000
AIRFLOW
(cfm)
6,000
7,500
9,000
10,500
12,000
13,500
15,000
0.2
Rpm
222
248
278
311
344
379
415
0.4
Bhp
0.59
0.94
1.46
2.16
3.08
4.25
5.69
Rpm
284
300
323
349
378
410
442
1.8
Rpm
567
575
581
588
598
610
626
Bhp
3.84
4.57
5.38
6.31
7.41
8.71
10.25
Bhp
0.91
1.28
1.80
2.52
3.44
4.62
6.06
2.0
Rpm
595
604
611
617
625
637
651
Bhp
4.30
5.10
5.97
6.95
8.08
9.41
10.98
1.4
1.6
Rpm
504
511
517
526
539
555
575
Bhp
2.93
3.54
4.25
5.10
6.12
7.36
8.87
Rpm
536
544
550
558
569
583
601
Bhp
6.76
7.86
9.03
10.28
11.65
13.18
14.92
Rpm
738
752
761
769
775
782
790
3.0
Rpm
717
730
739
746
752
759
768
Bhp
3.38
4.05
4.81
5.70
6.75
8.02
9.55
3.2
Bhp
7.27
8.43
9.66
10.97
12.39
13.98
15.75
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
103
0.2
Rpm
Bhp
246
0.84
266
1.14
310
1.98
357
3.20
406
4.87
430
5.89
7,000
8,000
10,000
12,000
14,000
15,000
AIRFLOW
(cfm)
7,000
8,000
10,000
12,000
14,000
15,000
AIRFLOW
(cfm)
7,000
8,000
10,000
12,000
14,000
15,000
0.4
Rpm
Bhp
301
1.19
315
1.50
350
2.36
390
3.60
435
5.28
458
6.31
1.8
Rpm
577
583
594
609
629
641
Bhp
4.40
4.94
6.16
7.67
9.57
10.69
2.0
Rpm
606
612
623
636
655
666
Bhp
4.91
5.49
6.79
8.36
10.30
11.44
1.6
Rpm
Bhp
547
3.90
552
4.39
564
5.55
580
7.01
603
8.86
616
9.96
3.0
Rpm
730
738
751
762
774
782
Bhp
7.58
8.37
10.06
11.97
14.18
15.44
3.2
Rpm
752
760
774
785
796
804
Bhp
8.14
8.97
10.74
12.72
14.99
16.28
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
104
1.4
Rpm
Bhp
514
3.40
519
3.87
532
4.96
551
6.36
576
8.18
590
9.26
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
AIRFLOW
(cfm)
8,000
10,000
12,000
14,000
16,000
18,000
20,000
AIRFLOW
(cfm)
8,000
10,000
12,000
14,000
16,000
18,000
20,000
0.2
Rpm
252
290
330
372
415
459
503
Bhp
0.98
1.67
2.65
3.96
5.67
7.84
10.51
0.4
Rpm
303
333
369
407
447
488
530
1.8
Rpm
571
579
590
607
629
656
687
Bhp
4.60
5.75
7.21
9.07
11.41
14.28
17.71
Bhp
1.33
2.11
3.18
4.61
6.44
8.72
11.51
2.0
Rpm
600
608
618
633
653
678
707
Bhp
5.14
6.36
7.87
9.78
12.16
15.09
18.60
Rpm
507
517
532
554
581
612
645
Rpm
726
736
744
753
766
783
804
1.4
Bhp
3.55
4.58
5.94
7.72
9.95
12.69
15.98
1.6
Rpm
540
549
562
581
605
634
666
3.0
Bhp
8.04
9.62
11.43
13.60
16.22
19.39
23.17
Bhp
4.07
5.16
6.56
8.38
10.67
13.47
16.84
3.2
Rpm
748
758
766
775
787
803
Bhp
8.65
10.30
12.19
14.41
17.08
20.29
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
105
AIRFLOW
(cfm)
9,000
10,000
12,000
14,000
16,000
18,000
20,000
AIRFLOW
(cfm)
9,000
10,000
12,000
14,000
16,000
18,000
20,000
0.2
Rpm
276
296
339
382
427
473
519
Bhp
1.34
1.74
2.76
4.15
5.96
8.26
11.10
0.4
Rpm
323
339
376
416
458
501
545
1.8
Rpm
579
584
597
615
639
667
699
Bhp
5.23
5.85
7.36
9.29
11.71
14.69
18.25
Bhp
1.73
2.17
3.29
4.79
6.71
9.12
12.06
2.0
Rpm
608
613
625
641
663
689
719
Bhp
5.81
6.47
8.03
10.01
12.48
15.51
19.14
Rpm
516
522
539
562
590
623
658
Rpm
735
740
750
760
775
793
816
Bhp
4.11
4.68
6.09
7.92
10.23
13.08
16.50
1.6
Rpm
549
554
568
589
615
645
679
3.0
Bhp
8.91
9.75
11.63
13.87
16.58
19.86
23.77
Bhp
4.66
5.26
6.71
8.60
10.97
13.88
17.38
3.2
Rpm
757
763
772
783
796
813
Bhp
9.57
10.44
12.39
14.69
17.45
20.78
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
106
1.4
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
0.2
Rpm Bhp
207
1.04
235
1.69
265
2.59
295
3.78
327
5.31
359
7.23
392
9.59
AIRFLOW
(cfm)
1.8
10,000
12,500
15,000
17,500
20,000
22,500
25,000
AIRFLOW
(cfm)
10,000
12,500
15,000
17,500
20,000
22,500
25,000
Rpm
497
497
501
512
528
548
571
Bhp
7.27
7.73
8.63
10.09
12.09
14.60
17.63
0.4
Rpm
253
276
302
331
360
390
421
Bhp
1.50
2.23
3.23
4.52
6.15
8.16
10.60
2.0
Rpm
523
523
526
535
549
567
589
Bhp
8.39
8.83
9.67
11.07
13.06
15.59
18.66
Rpm
438
440
449
465
485
508
533
Rpm
639
641
641
643
649
660
676
1.4
Bhp
5.20
5.75
6.78
8.30
10.28
12.72
15.62
1.6
Rpm
468
469
476
489
507
528
552
3.0
Bhp
14.51
15.16
15.80
16.88
18.62
21.06
24.19
Bhp
6.20
6.70
7.67
9.17
11.17
13.65
16.62
3.2
Rpm
659
662
662
663
668
678
692
Bhp
15.81
16.55
17.19
18.21
19.89
22.28
25.39
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
107
AIRFLOW
(cfm)
12,000
15,000
18,000
21,000
24,000
27,000
30,000
AIRFLOW
(cfm)
12,000
15,000
18,000
21,000
24,000
27,000
30,000
0.2
Rpm
234
271
308
348
390
433
476
Bhp
1.54
2.65
4.22
6.36
9.19
12.80
17.29
0.4
Rpm
276
309
344
380
417
456
497
1.8
Rpm
504
509
521
543
570
601
634
Bhp
7.56
8.87
10.79
13.56
17.22
21.81
27.34
Bhp
2.03
3.27
5.00
7.29
10.24
13.93
18.50
2.0
Rpm
530
535
544
563
588
618
650
Bhp
8.57
9.95
11.85
14.60
18.28
22.93
28.56
Rpm
446
455
474
501
532
565
599
Rpm
641
650
654
662
678
700
726
Bhp
5.63
6.91
8.88
11.64
15.21
19.62
24.93
1.6
Rpm
476
482
498
522
551
583
617
3.0
Bhp
13.91
15.95
17.99
20.63
24.24
28.98
34.88
Bhp
6.58
7.85
9.81
12.58
16.20
20.71
26.14
3.2
Rpm
660
670
675
682
695
715
Bhp
15.01
17.23
19.36
21.99
25.58
30.31
701
23.41
719
24.87
738
26.38
713
26.97
730
28.40
747
29.89
731
31.67
747
33.08
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
108
1.4
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
AIRFLOW
(cfm)
14,000
17,500
21,000
24,500
28,000
30,000
AIRFLOW
(cfm)
14,000
17,500
21,000
24,500
28,000
30,000
0.2
Rpm
258
302
348
397
447
476
Bhp
2.23
3.92
6.36
9.74
14.18
17.29
0.4
Rpm
297
338
380
424
470
497
1.8
Rpm
507
519
543
575
612
634
Bhp
8.39
10.42
13.56
17.93
23.55
27.34
Bhp
2.80
4.67
7.29
10.80
15.35
18.50
2.0
Rpm
533
542
563
593
628
650
Bhp
9.46
11.48
14.60
18.99
24.69
28.56
Rpm
451
471
501
537
576
599
Rpm
648
653
662
681
708
726
1.4
Bhp
6.42
8.50
11.64
15.88
21.29
24.93
1.6
Rpm
480
495
522
556
594
617
3.0
Bhp
15.29
17.62
20.63
24.96
30.82
34.88
Bhp
7.37
9.42
12.57
16.89
22.41
26.14
3.2
Rpm
668
674
682
698
723
Bhp
16.52
18.99
21.99
26.29
32.15
701
23.41
719
24.87
738
26.38
715
27.67
732
29.10
749
30.58
739
33.51
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
109
0.2
Rpm Bhp
255
0.95
291
1.51
330
2.28
371
3.28
413
4.56
456
6.12
500
7.99
AIRFLOW
(cfm)
1.8
6,000
7,500
9,000
10,500
12,000
13,500
15,000
AIRFLOW
(cfm)
6,000
7,500
9,000
10,500
12,000
13,500
15,000
Rpm
594
605
617
633
652
676
703
Bhp
5.43
6.16
7.02
8.12
9.52
11.25
13.30
0.4
Rpm Bhp
313
1.35
340
1.93
372
2.73
408
3.76
447
5.07
487
6.66
528
8.58
2.0
Rpm
623
635
646
660
679
701
726
Bhp
6.09
6.88
7.76
8.86
10.27
12.00
14.07
1.4
Rpm
530
541
555
574
598
626
656
1.6
Bhp
4.14
4.78
5.61
6.71
8.11
9.81
11.83
3.0
Rpm
747
765
777
788
800
816
835
Bhp
9.42
10.64
11.76
12.95
14.37
16.11
18.20
Bhp
4.78
5.46
6.30
7.40
8.80
10.51
12.56
3.2
Rpm
769
787
800
811
823
838
856
Bhp
10.10
11.41
12.60
13.82
15.26
16.99
19.09
859
17.90
880
18.82
876
20.00
896
20.92
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
110
Rpm
563
574
587
604
626
651
680
FAN PERFORMANCE 50P2,P3035 UNITS WITH DISCHARGE PLENUM AND 50P4,P5035 UNITS
AIRFLOW
(cfm)
7,000
8,000
10,000
12,000
14,000
15,000
0.2
Rpm Bhp
285
1.35
311
1.81
367
3.04
426
4.74
486
6.98
517
8.33
AIRFLOW
(cfm)
1.8
7,000
8,000
10,000
12,000
14,000
15,000
AIRFLOW
(cfm)
7,000
8,000
10,000
12,000
14,000
15,000
Rpm
607
615
636
663
698
718
Bhp
6.03
6.58
7.94
9.83
12.31
13.78
0.4
Rpm Bhp
337
1.78
358
2.25
406
3.52
459
5.26
515
7.55
544
8.92
2.0
Rpm
637
645
664
689
722
741
Bhp
6.74
7.32
8.70
10.59
13.08
14.56
1.4
Rpm
542
551
576
609
649
671
1.6
Bhp
4.66
5.16
6.51
8.38
10.83
12.27
Rpm
576
584
606
637
674
694
3.0
Rpm
764
775
792
810
834
849
Bhp
10.39
11.20
12.82
14.76
17.27
18.78
Bhp
5.34
5.86
7.21
9.09
11.55
13.01
3.2
Rpm
786
797
815
833
856
869
Bhp
11.13
12.00
13.69
15.66
18.17
19.69
855
16.57
876
17.51
897
18.45
876
19.10
897
20.04
890
20.61
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
111
AIRFLOW
(cfm)
8,000
10,000
12,000
14,000
16,000
18,000
20,000
AIRFLOW
(cfm)
8,000
10,000
12,000
14,000
16,000
18,000
20,000
0.2
Rpm
293
343
395
449
504
559
615
Bhp
1.62
2.66
4.09
5.97
8.32
11.20
14.66
0.4
Rpm
344
385
431
481
533
586
640
1.8
Rpm
603
623
648
677
712
749
790
Bhp
6.23
7.70
9.50
11.73
14.45
17.73
21.61
Bhp
2.10
3.19
4.68
6.62
9.06
12.04
15.59
2.0
Rpm
632
651
674
702
735
771
811
Bhp
6.87
8.41
10.26
12.54
15.30
18.61
22.52
Rpm
541
563
592
626
663
705
749
Rpm
757
776
794
817
843
873
1.4
Bhp
4.97
6.31
8.01
10.16
12.81
16.01
19.83
3.0
Bhp
10.07
12.08
14.25
16.76
19.73
23.23
Bhp
5.60
7.00
8.75
10.93
13.62
16.86
20.71
3.2
Rpm
779
798
817
838
863
Bhp
10.71
12.82
15.07
17.64
20.65
883
21.58
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
112
1.6
Rpm
573
594
620
652
688
727
770
FAN PERFORMANCE 50P2,P3050 UNITS WITH DISCHARGE PLENUM AND 50P4,P5050 UNITS
AIRFLOW
(cfm)
9,000
10,000
12,000
14,000
16,000
18,000
20,000
AIRFLOW
(cfm)
9,000
10,000
12,000
14,000
16,000
18,000
20,000
AIRFLOW
(cfm)
9,000
10,000
12,000
14,000
16,000
18,000
20,000
0.2
Rpm
324
349
403
459
515
573
630
Bhp
2.15
2.74
4.23
6.17
8.63
11.65
15.28
0.4
Rpm
369
392
439
490
544
599
654
1.8
Rpm
617
628
654
686
721
761
803
Bhp
7.08
7.87
9.74
12.06
14.88
18.27
22.27
Bhp
2.67
3.28
4.82
6.83
9.34
12.44
16.14
2.0
Rpm
645
656
680
710
744
782
823
Bhp
7.77
8.59
10.51
12.88
15.74
19.17
23.21
Rpm
556
569
599
634
674
716
762
Rpm
770
780
800
824
852
884
1.4
Bhp
5.73
6.46
8.23
10.46
13.20
16.50
20.43
1.6
Rpm
587
599
627
660
698
739
783
3.0
Bhp
11.34
12.35
14.56
17.15
20.24
23.88
Bhp
6.40
7.16
8.98
11.25
14.03
17.37
21.34
3.2
Rpm
793
802
822
845
872
Bhp
12.07
13.12
15.39
18.04
21.17
866
18.94
886
19.85
892
22.12
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
113
AIRFLOW
(cfm)
10,000
12,500
15,000
17,500
20,000
22,500
25,000
AIRFLOW
(cfm)
10,000
12,500
15,000
17,500
20,000
22,500
25,000
0.2
Rpm
217
248
281
315
351
389
427
Bhp
1.21
2.01
3.13
4.64
6.64
9.20
12.39
0.4
Rpm
258
286
317
348
381
414
449
1.8
Rpm
500
498
501
514
535
561
590
Bhp
7.48
8.63
10.03
12.05
14.76
18.17
22.27
Bhp
1.71
2.63
3.90
5.55
7.64
10.25
13.48
2.0
Rpm
527
525
526
536
554
579
606
Bhp
8.46
9.76
11.17
13.17
15.88
19.34
23.51
Rpm
440
440
450
471
497
525
555
Rpm
639
646
644
643
649
663
683
1.4
Bhp
5.56
6.52
7.95
10.00
12.65
15.91
19.82
3.0
Bhp
13.41
15.76
17.71
19.70
22.31
25.78
30.13
Bhp
6.51
7.54
8.95
10.99
13.68
17.03
21.04
3.2
Rpm
659
667
666
663
668
680
699
Bhp
14.41
16.99
19.11
21.18
23.77
27.20
31.56
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
114
1.6
Rpm
471
469
476
493
516
543
573
FAN PERFORMANCE 50P2,P3060 UNITS WITH DISCHARGE PLENUM AND 50P4,P5060 UNITS
AIRFLOW
(cfm)
12,000
15,000
18,000
21,000
24,000
27,000
30,000
AIRFLOW
(cfm)
12,000
15,000
18,000
21,000
24,000
27,000
30,000
AIRFLOW
(cfm)
12,000
15,000
18,000
21,000
24,000
27,000
30,000
0.2
Rpm
241
281
323
366
410
455
500
Bhp
1.82
3.14
5.03
7.61
10.97
15.23
20.52
0.4
Rpm
280
316
355
395
437
479
522
1.8
Rpm
486
498
518
546
577
611
648
Bhp
7.94
9.90
12.57
16.07
20.49
25.91
32.43
Bhp
2.41
3.87
5.92
8.66
12.20
16.65
22.11
2.0
Rpm
511
520
539
564
594
628
663
Bhp
8.91
10.93
13.66
17.23
21.74
27.26
33.90
Rpm
433
450
476
507
541
578
616
Rpm
624
627
636
653
676
703
1.4
Bhp
6.11
7.95
10.50
13.85
18.07
23.26
29.52
1.6
Rpm
460
474
498
527
560
595
632
3.0
Bhp
14.16
16.63
19.65
23.51
28.38
34.33
Bhp
7.01
8.90
11.52
14.94
19.27
24.58
30.97
3.2
Rpm
645
646
654
669
691
718
Bhp
15.28
17.86
20.95
24.86
29.77
35.82
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
115
AIRFLOW
(cfm)
14,000
17,500
21,000
24,500
28,000
30,000
AIRFLOW
(cfm)
14,000
17,500
21,000
24,500
28,000
30,000
0.2
Rpm
268
316
366
417
470
500
Bhp
2.64
4.67
7.61
11.61
16.88
20.52
0.4
Rpm
304
348
395
444
493
522
1.8
Rpm
493
515
546
583
623
648
Bhp
9.17
12.07
16.07
21.32
27.96
32.43
Bhp
3.32
5.54
8.66
12.87
18.35
22.11
2.0
Rpm
516
535
564
600
639
663
Bhp
10.19
13.14
17.23
22.59
29.35
33.90
Rpm
444
472
507
547
590
616
Rpm
625
634
653
680
1.4
Bhp
7.27
10.03
13.85
18.86
25.22
29.52
3.0
Bhp
15.77
19.09
23.51
29.29
Bhp
8.20
11.03
14.94
20.08
26.59
30.97
3.2
Rpm
645
652
669
695
Bhp
16.96
20.39
24.86
30.71
LEGEND
50P3,P5 units only.
Bhp Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Component Pressure Drop data table before using Fan Performance tables.
3. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
116
1.6
Rpm
468
493
527
565
607
632
AIRFLOW
(Cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
AIRFLOW
(Cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
0.2
Rpm
211
232
253
275
298
320
343
367
390
Bhp
2.35
3.27
4.42
5.83
7.53
9.55
11.91
14.65
17.78
0.4
Rpm
243
261
281
301
321
342
364
386
408
1.8
Rpm
416
423
432
443
455
470
485
501
518
Bhp
9.12
10.62
12.36
14.38
16.70
19.38
22.43
25.89
29.76
Bhp
3.06
4.06
5.31
6.82
8.62
10.75
13.22
16.06
19.31
2.0
Rpm
437
442
450
460
472
486
500
516
533
Bhp
10.10
11.68
13.50
15.58
17.98
20.72
23.83
27.36
31.32
Rpm
372
381
393
406
420
436
453
471
489
Rpm
531
533
537
543
551
561
573
585
599
1.4
Bhp
7.21
8.57
10.17
12.05
14.25
16.79
19.70
23.00
26.73
1.6
Rpm
395
402
413
425
438
453
469
486
504
3.0
Bhp
15.29
17.31
19.53
21.98
24.72
27.80
31.26
35.11
39.41
Bhp
8.15
9.58
11.25
13.20
15.46
18.07
21.05
24.43
28.24
3.2
Rpm
548
550
553
559
566
576
586
599
612
Bhp
16.38
18.48
20.78
23.32
26.14
29.29
32.81
36.74
41.11
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan and high-capacity power exhaust units, add component pressure drop for economizer. Do not add component pressure
drop for power exhaust.
3. See Component Pressure Drop data table before using Fan Performance tables.
4. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
117
AIRFLOW
(Cfm)
15,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
AIRFLOW
(Cfm)
15,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
0.30
Rpm
Bhp
620
3.02
655
3.52
725
4.68
795
6.08
867
7.75
939
9.71
1012 11.99
1084 14.61
1157 17.60
0.60
Rpm
Bhp
671
3.91
703
4.45
769
5.71
836
7.22
904
9.00
974 11.07
1044 13.46
1115 16.18
1186 19.28
2.10
Rpm
Bhp
902
8.97
922
9.69
968 11.32
1019 13.20
1073 15.39
1131 17.90
1191 20.74
1253 23.94
1317 27.51
2.40
Rpm
Bhp
944 10.10
963 10.86
1006 12.55
1054 14.51
1105 16.76
1161 19.33
1219 22.25
1280 25.52
1342 29.18
2.70
Rpm
Bhp
984 11.25
1003 12.06
1043 13.82
1088 15.84
1137 18.15
1191 20.79
1247 23.78
1306 27.12
1367 30.86
3.00
Rpm
Bhp
1023 12.42
1041 13.27
1079 15.12
1122 17.21
1169 19.58
1220 22.28
1274 25.33
1332 28.75
1391 32.57
4.50
Rpm
Bhp
1198 18.44
1214 19.56
1247 21.91
1282 24.42
1321 27.15
1363 30.18
1409 33.54
1458 37.28
1510 41.42
4.80
Rpm
Bhp
1229 19.67
1245 20.85
1278 23.31
1312 25.91
1350 28.74
1390 31.83
1435 35.26
1483 39.05
1534 43.25
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan high-capacity power exhaust units, add component
pressure drop for economizer. Do not add component pressure drop
for power exhaust.
118
3. See Component Pressure Drop data table before using Fan Performance tables.
4. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
AIRFLOW
(Cfm)
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
AIRFLOW
(Cfm)
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
0.2
Rpm
232
253
275
298
320
343
367
390
414
437
Bhp
3.27
4.42
5.83
7.53
9.55
11.91
14.65
17.78
21.36
25.39
0.4
Rpm
261
281
301
321
342
364
386
408
431
454
1.8
Rpm
423
432
443
455
470
485
501
518
536
555
Bhp
10.62
12.36
14.38
16.70
19.38
22.43
25.89
29.76
34.11
38.92
Bhp
4.06
5.31
6.82
8.62
10.75
13.22
16.06
19.31
22.99
27.13
2.0
Rpm
442
450
460
472
486
500
516
533
550
568
Bhp
11.68
13.50
15.58
17.98
20.72
23.83
27.36
31.32
35.73
40.63
Rpm
381
393
406
420
436
453
471
489
508
528
Rpm
533
537
543
551
561
573
585
599
614
630
1.4
Bhp
8.57
10.17
12.05
14.25
16.79
19.70
23.00
26.73
30.90
35.55
1.6
Rpm
402
413
425
438
453
469
486
504
523
542
3.0
Bhp
17.31
19.53
21.98
24.72
27.80
31.26
35.11
39.41
44.18
49.45
Bhp
9.58
11.25
13.20
15.46
18.07
21.05
24.43
28.24
32.49
37.23
3.2
Rpm
550
553
559
566
576
586
599
612
626
641
Bhp
18.48
20.78
23.32
26.14
29.29
32.81
36.74
41.11
45.94
51.27
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan and high-capacity power exhaust units, add component pressure drop for economizer. Do not add component pressure
drop for power exhaust.
3. See Component Pressure Drop data table before using Fan Performance tables.
4. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
119
AIRFLOW
(Cfm)
17,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
AIRFLOW
(Cfm)
17,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
0.30
Rpm
Bhp
690
4.07
725
4.68
795
6.08
867
7.75
939
9.71
1012 11.99
1084 14.61
1157 17.60
1231 20.97
1304 24.75
0.60
Rpm
Bhp
735
5.05
769
5.71
836
7.22
904
9.00
974 11.07
1044 13.46
1115 16.18
1186 19.28
1258 22.76
1330 26.65
2.10
Rpm
Bhp
945 10.47
968 11.32
1019 13.20
1073 15.39
1131 17.90
1191 20.74
1253 23.94
1317 27.51
1382 31.48
1448 35.87
2.40
Rpm
Bhp
984 11.68
1006 12.55
1054 14.51
1105 16.76
1161 19.33
1219 22.25
1280 25.52
1342 29.18
1406 33.23
1471 37.71
2.70
Rpm
Bhp
1022 12.91
1043 13.82
1088 15.84
1137 18.15
1191 20.79
1247 23.78
1306 27.12
1367 30.86
1429 35.00
1493 39.57
3.00
Rpm
Bhp
1059 14.17
1079 15.12
1122 17.21
1169 19.58
1220 22.28
1274 25.33
1332 28.75
1391 32.57
1452 36.78
1515 41.43
4.50
Rpm
Bhp
1230 20.72
1247 21.91
1282 24.42
1321 27.15
1363 30.18
1409 33.54
1458 37.28
1510 41.42
1565 45.98
1622 50.99
4.80
Rpm
Bhp
1261 22.06
1278 23.31
1312 25.91
1350 28.74
1390 31.83
1435 35.26
1483 39.05
1534 43.25
1587 47.88
1643 52.96
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan and high-capacity power exhaust units, add component pressure drop for economizer. Do not add component pressure
drop for power exhaust.
120
3. See Component Pressure Drop data table before using Fan Performance tables.
4. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
AIRFLOW
(Cfm)
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
AIRFLOW
(Cfm)
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
0.2
Rpm
275
298
320
343
367
390
414
437
461
485
509
Bhp
5.83
7.53
9.55
11.91
14.65
17.78
21.36
25.39
29.92
34.96
40.54
0.4
Rpm
301
321
342
364
386
408
431
454
477
500
523
1.8
Rpm
443
455
470
485
501
518
536
555
574
593
613
Bhp
14.38
16.70
19.38
22.43
25.89
29.76
34.11
38.92
44.25
50.10
56.52
Bhp
6.82
8.62
10.75
13.22
16.06
19.31
22.99
27.13
31.77
36.91
42.61
2.0
Rpm
460
472
486
500
516
533
550
568
586
605
625
Bhp
15.58
17.98
20.72
23.83
27.36
31.32
35.73
40.63
46.03
51.98
58.49
Rpm
406
420
436
453
471
489
508
528
548
568
589
Rpm
543
551
561
573
585
599
614
630
646
663
1.4
Bhp
12.05
14.25
16.79
19.70
23.00
26.73
30.90
35.55
40.69
46.36
52.59
1.6
Rpm
425
438
453
469
486
504
523
542
561
581
601
3.0
Bhp
21.98
24.72
27.80
31.26
35.11
39.41
44.18
49.45
55.25
61.59
Bhp
13.20
15.46
18.07
21.05
24.43
28.24
32.49
37.23
42.47
48.23
54.56
3.2
Rpm
559
566
576
586
599
612
626
641
657
674
Bhp
23.32
26.14
29.29
32.81
36.74
41.11
45.94
51.27
57.14
63.54
669
59.06
680
60.98
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan and high-capacity power exhaust units, add component pressure drop for economizer. Do not add component pressure
drop for power exhaust.
3. See Component Pressure Drop data table before using Fan Performance tables.
4. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
121
AIRFLOW
(Cfm)
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
AIRFLOW
(Cfm)
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
0.30
Rpm
Bhp
795
6.08
867
7.75
939
9.71
1012 11.99
1084 14.61
1157 17.60
1231 20.97
1304 24.75
1378 28.97
1452 33.65
1526 38.81
0.60
Rpm
Bhp
836
7.22
904
9.00
974 11.07
1044 13.46
1115 16.18
1186 19.28
1258 22.76
1330 26.65
1402 30.97
1475 35.75
1548 41.02
2.10
Rpm
Bhp
1019 13.20
1073 15.39
1131 17.90
1191 20.74
1253 23.94
1317 27.51
1382 31.48
1448 35.87
1515 40.70
1583 45.98
1652 51.76
2.40
Rpm
Bhp
1054 14.51
1105 16.76
1161 19.33
1219 22.25
1280 25.52
1342 29.18
1406 33.23
1471 37.71
1537 42.64
1604 48.01
1671 53.88
2.70
Rpm
Bhp
1088 15.84
1137 18.15
1191 20.79
1247 23.78
1306 27.12
1367 30.86
1429 35.00
1493 39.57
1558 44.57
1624 50.05
1691 56.01
3.00
Rpm
Bhp
1122 17.21
1169 19.58
1220 22.28
1274 25.33
1332 28.75
1391 32.57
1452 36.78
1515 41.43
1579 46.53
1644 52.08
1710 58.13
4.50
Rpm
Bhp
1282 24.42
1321 27.15
1363 30.18
1409 33.54
1458 37.28
1510 41.42
1565 45.98
1622 50.99
1681 56.46
1742 62.43
4.80
Rpm
Bhp
1312 25.91
1350 28.74
1390 31.83
1435 35.26
1483 39.05
1534 43.25
1587 47.88
1643 52.96
1701 58.50
1761 64.54
LEGEND
48/50P3,P5 units only.
Bhp Brake Horsepower
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Component Pressure Drop table.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan and high-capacity power exhaust units, add component pressure drop for economizer. Do not add component pressure
drop for power exhaust.
122
3. See Component Pressure Drop data table before using Fan Performance tables.
4. Conversion Bhp to kW:
Kilowatts =
Bhp x .746
Motor efficiency
0.20
Rpm Bhp
380
0.95
440
1.69
504
2.73
575
4.17
650
6.09
729
8.57
809 11.57
891 15.47
0.40
Rpm Bhp
468
1.47
523
2.40
582
3.68
643
5.33
708
7.42
778 10.02
851 13.19
927 17.22
0.60
Rpm Bhp
543
2.01
591
3.08
647
4.55
705
6.42
766
8.73
829 11.43
896 14.90
967 19.08
1.80
Rpm Bhp
905
6.17
907
7.66
933
9.70
976 12.29
2.00
Rpm Bhp
956
6.98
953
8.53
975 10.52
1.8
Rpm Bhp
808
5.86
822
7.30
845
9.03
878 11.16
918 13.81
2.0
Rpm Bhp
850
6.47
861
8.00
881
9.80
910 11.98
48/50P2,P3,P4,P5055-100 UNITS
AIRFLOW
(Cfm)
10,000
12,000
14,000
16,000
18,000
20,000
22,000
24,000
0.2
Rpm Bhp
416
1.65
480
2.67
546
4.09
613
5.95
682
8.32
752 11.27
821 14.86
892 19.16
0.4
Rpm Bhp
469
2.03
524
3.09
584
4.55
647
6.46
712
8.88
779 11.89
846 15.53
915 19.89
0.6
Rpm Bhp
522
2.47
568
3.56
621
5.05
680
7.00
741
9.47
805 12.53
871 16.23
AIRFLOW
(Cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
0.2
Rpm Bhp
594 3.61
619 4.09
687 5.57
756 7.37
825 9.50
895 11.94
965 14.94
1035 18.43
1105 22.42
1176 26.96
1246 32.09
1317 37.83
1388 44.22
0.4
Rpm Bhp
594 3.61
652 4.76
718 6.35
786 8.25
853 10.50
922 13.08
990 16.21
1059 19.81
1128 23.93
1198 28.59
1267 33.83
1337 39.69
1407 46.21
0.6
Rpm Bhp
617 4.02
681 5.40
746 7.07
812 9.06
878 11.31
945 14.12
1013 17.36
1081 21.09
1149 25.33
1218 30.11
1287 35.47
1356 41.46
1.8
Rpm Bhp
772 7.62
825 9.30
881 11.20
939 13.62
1000 16.46
1061 19.76
1125 23.54
1189 27.83
1253 32.67
1319 38.08
1385 44.10
2.0
Rpm Bhp
795 8.25
847 9.99
901 11.96
958 14.43
1018 17.33
1079 20.69
1141 24.54
1204 28.91
1269 33.83
1333 39.32
1399 45.43
2.2
Rpm Bhp
816 8.89
867 10.59
921 12.74
977 15.25
1035 18.21
1095 21.62
1157 25.54
1220 29.98
1283 34.98
1348 40.55
1413 46.75
2.4
Rpm Bhp
836 9.52
887 11.31
940 13.52
995 16.10
1052 19.10
1112 22.58
1173 26.55
1235 31.06
1298 36.13
1362 41.78
2.6
Rpm Bhp
856 10.15
907 12.05
959 14.33
1013 16.96
1069 20.01
1128 23.54
1188 27.57
1249 32.14
1312 37.28
1375 43.00
3.8
Rpm Bhp
958 13.80
1011 16.44
1062 19.24
1113 22.30
1166 25.71
1220 29.55
1276 33.89
1334 38.78
1393 44.27
4.0
Rpm Bhp
973 14.42
1026 17.16
1078 20.07
1129 23.21
1181 26.69
1234 30.58
1290 34.98
1347 39.93
1406 45.46
123
AIRFLOW
(cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
AIRFLOW
(cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
AIRFLOW
(cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
Rpm
436
486
536
588
639
692
745
798
851
905
959
1013
1067
1121
Bhp
3.79
5.37
7.37
9.81
12.75
16.21
20.24
24.87
30.15
36.10
42.76
50.17
58.36
67.37
Bhp
5.48
7.12
9.14
11.57
14.46
17.86
21.82
26.37
31.55
37.41
43.98
51.30
59.40
Rpm
592
629
670
712
757
802
849
896
944
993
1042
1092
1142
Rpm
659
690
726
765
807
850
894
940
986
1033
1081
1129
Bhp
8.77
10.68
12.93
15.57
18.63
22.16
26.21
30.81
36.00
41.84
48.36
55.60
Rpm
752
777
806
840
877
917
958
1001
1045
1090
1136
Rpm
811
832
858
888
922
959
998
1040
1082
1126
1170
Bhp
12.23
14.46
16.99
19.89
23.20
26.95
31.20
35.98
41.33
47.29
Rpm
892
910
931
957
987
1020
1057
1095
1135
Rpm
943
959
978
1001
1029
1060
1094
1131
1169
Bhp
15.75
18.33
21.19
24.38
27.96
31.96
36.44
41.44
Rpm
1013
1029
1046
1066
1090
1118
1149
1.2
Rpm
626
660
698
739
782
827
872
918
965
1013
1062
1111
1160
Bhp
6.76
8.50
10.60
13.10
16.05
19.48
23.44
27.99
33.15
38.98
45.50
52.77
60.81
2.2
Rpm
782
805
832
864
900
938
979
1020
1064
1108
1153
Bhp
10.14
12.18
14.53
17.27
20.43
24.04
28.17
32.83
38.07
43.95
50.49
3.2
Rpm
918
934
955
979
1008
1040
1075
1113
1152
LEGEND
Bhp Brake Horsepower
124
Rpm
480
526
574
622
671
722
772
824
875
928
980
1033
1086
1139
0.2
Bhp
13.64
16.00
18.66
21.67
25.08
28.93
33.27
38.14
43.56
1.0
Bhp
6.11
7.80
9.86
12.32
15.23
18.65
22.60
27.14
32.31
38.14
44.69
51.98
60.05
2.0
Bhp
9.45
11.42
13.73
16.41
19.52
23.10
27.17
31.81
37.02
42.88
49.41
3.0
Bhp
12.93
15.23
17.82
20.78
24.14
27.94
32.23
37.05
42.44
4.0
Bhp
16.46
19.11
22.04
25.29
28.92
32.98
37.51
AIRFLOW (cfm)
12,000
14,000
0.16
0.20
6,000
0.06
8,000
0.09
10,000
0.12
0.00
0.22
0.02
0.21
0.02
0.09
0.09
0.24
0.08
0.00
0.31
0.05
0.29
0.03
0.15
0.18
0.21
0.42
0.22
0.00
0.41
0.06
0.37
0.05
0.22
0.31
0.38
0.71
0.46
0.00
0.52
0.08
0.46
0.08
0.30
0.48
0.60
1.09
0.79
0.07
0.041
0.062
0.045
0.05
0.03
0.06
0.12
0.11
0.055
0.100
0.067
0.07
0.07
0.11
0.18
0.16
0.070
0.148
0.099
0.09
0.12
0.18
0.26
0.22
0.087
0.206
0.142
0.11
16,000
0.25
18,000
0.30
20,000
0.35
0.01
0.64
0.09
0.55
0.11
0.41
0.68
0.86
1.58
1.20
0.01
0.76
0.11
0.65
0.15
0.53
0.92
1.17
2.17
1.71
0.02
0.89
0.13
0.75
0.20
0.66
1.19
1.53
2.86
2.31
0.03
1.03
0.15
0.86
0.25
0.81
1.50
1.93
3.66
3.01
0.18
0.26
0.36
0.29
0.104
0.274
0.195
0.14
0.26
0.36
0.47
0.37
0.123
0.351
0.259
0.17
0.35
0.47
0.59
0.46
0.143
0.436
0.333
0.20
0.46
0.60
0.73
0.55
0.165
0.536
0.417
0.23
AIRFLOW (cfm)
18,000 20,000 22,000
0.12
0.14
0.16
10,000
0.05
12,000
0.07
14,000
0.08
16,000
0.10
0.00
0.45
0.06
0.42
0.03
0.12
0.14
0.21
0.11
0.19
0.00
0.56
0.08
0.52
0.04
0.17
0.18
0.26
0.14
0.30
0.01
0.68
0.09
0.62
0.05
0.22
0.22
0.32
0.18
0.40
0.01
0.81
0.11
0.73
0.07
0.28
0.27
0.37
0.23
0.51
0.02
0.94
0.13
0.84
0.08
0.34
0.31
0.43
0.27
0.62
0.02
1.08
0.15
0.96
0.10
0.42
0.36
0.50
0.32
0.73
0.15
0.055
0.09
0.20
0.081
0.11
0.07
0.10
0.13
0.26
0.108
0.14
0.09
0.13
0.17
0.32
0.136
0.17
0.12
0.16
0.22
0.39
0.165
0.20
0.15
0.20
0.26
0.47
0.194
0.23
24,000
0.19
26,000
0.21
28,000
0.24
30,000
0.26
0.03
1.22
0.17
1.08
0.12
0.50
0.41
0.56
0.37
0.85
0.03
1.38
0.19
1.21
0.14
0.59
0.47
0.63
0.42
0.97
0.04
0.22
0.17
0.68
0.52
0.70
0.48
1.09
0.05
0.24
0.19
0.78
0.59
0.78
0.54
1.21
0.06
0.27
0.22
0.82
0.65
0.86
0.60
1.34
0.18
0.24
0.32
0.55
0.224
0.27
0.21
0.29
0.38
0.64
0.255
0.31
0.24
0.34
0.44
0.73
0.287
0.35
0.28
0.39
0.51
0.83
0.320
0.38
0.32
0.45
0.59
0.94
0.353
0.43
125
FILTERS
30% Pleated (2-in.)
65% Pleated (2-in.)
4-in. Filters (field convert)
POWER EXHAUST (48/50P2, P3 Units)
POWER EXHAUST (48/50P4, P5 Units)
LOW GAS HEAT (48P2,P3 Units)
HIGH GAS HEAT (48P2,P3 Units)
LOW GAS HEAT (48P4,P5 Units)
HIGH GAS HEAT (48P4,P5 Units)
ELECTRIC HEAT*
108 kW
216 kW
AIRFLOW (cfm)
27,000
30,000
33,000
0.22
0.26
0.30
15,000
0.10
18,000
0.12
21,000
0.15
24,000
0.19
36,000
0.34
39,000
0.39
42,000
0.43
44,000
0.47
0.01
0.14
0.10
0.01
0.15
0.13
0.02
0.17
0.16
0.02
0.18
0.19
0.03
0.19
0.23
0.04
0.21
0.27
0.05
0.23
0.31
0.06
0.25
0.35
0.07
0.27
0.39
0.08
0.29
0.44
0.09
0.31
0.47
0.06
0.25
0.24
0.34
0.21
0.51
0.08
0.35
0.31
0.43
0.29
0.70
0.11
0.46
0.39
0.53
0.37
0.91
0.14
0.59
0.47
0.63
0.45
1.13
0.18
0.73
0.55
0.74
0.53
1.37
0.22
0.90
0.65
0.86
0.61
1.62
0.27
1.07
0.75
0.98
0.70
1.89
0.32
1.27
0.86
1.11
0.78
2.17
0.37
1.48
0.97
1.24
0.87
2.47
0.43
1.71
1.09
1.38
0.96
2.79
0.47
1.84
1.18
1.48
1.02
3.01
0.05
0.08
0.07
0.12
0.10
0.16
0.13
0.20
0.16
0.26
0.20
0.32
0.24
0.39
0.29
0.46
0.34
0.54
0.40
0.63
0.44
0.69
HYDRONIC COIL
0.15
0.20
0.26
0.32
0.39
0.47
0.55
0.64
0.73
0.83
0.94
0.122
0.165
0.209
0.255
0.304
0.353
0.405
0.458
0.16
0.13
0.20
0.16
0.25
0.20
0.31
0.25
0.37
0.29
0.43
0.35
0.50
0.40
0.58
0.46
0.514
0.66
0.52
0.570
0.74
0.58
0.609
0.80
0.63
126
Electrical data
Please refer to the RTUBuilder software for the unit electrical data. The unit electrical data may also be found in the
unit Installation Instructions.
MAXIMUM
Bhp
BkW
7.5
5.60
10
7.46
15
11.19
20
14.92
25
18.65
30
22.38
40
29.84
Bhp
8.7
9.5
10.2
11.8
15.3
18.0
22.4
23.4
28.9
29.4
35.6
34.7
42.0
MAXIMUM AMPS
230 v
460 v
22.0
12.0
28.0
15.0
43.8
21.9
58.2
28.7
73.0
36.3
82.6
41.7
55.0
BkW
6.49
7.09
7.61
8.80
11.41
13.43
16.71
17.46
21.56
21.93
26.56
25.89
31.33
RATED
EFFICIENCY
91.7
91.7
91.7
91.7
93.0
93.0
93.6
93.6
93.6
93.6
93.6
93.6
94.5
LEGEND
Bhp Brake Horsepower
BkW Brake Kilowatts
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with the Energy Independence Security Act
(EISA) of 2007.
BkW
MAX BHP
MAX BkW
30
40
50
60
75
22.4
29.8
37.3
44.8
59.5
34.7
42.0
57.5
69.0
86.25
25.9
31.3
42.9
51.5
64.3
MAX AMPS
460 V
48.0
55.0
71.0
75.0
95.5
575 V
N/A
N/A
N/A
N/A
N/A
RATED
EFFICIENCY
93.6
94.5
94.5
95.4
95.4
LEGEND
Bhp Brake Horsepower
BkW Brake Kilowatts
N/A Not Available
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with the Energy Independence Security Act
(EISA) of 2007.
127
BkW
MAX BHP
MAX BkW
20
30
40
50
60
14.9
22.4
29.8
37.3
44.8
23.6
36.0
46.8
58.8
69.0
17.6
26.9
34.9
43.9
51.5
LEGEND
Bhp Brake Horsepower
BkW Brake Kilowatts
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with the Energy Independence Security Act
(EISA) of 2007.
128
RATED
EFFICIENCY
91.7
93.0
93.6
93.6
93.6
Controls
Control components
The 48/50P Series rooftops use the ComfortLink control
system that has been developed for use in Carrier Commercial equipment. The control system monitors all operating
conditions in the rooftop unit as well as controlling the compressors, economizers, fans, heat and other devices. It also
has the capability of communicating with the Carrier Comfort Network devices using the CCN protocol and other
popular protocols including BACnet, MODBUS, LonWorks,
etc.
The system uses a microprocessor and a series of boards,
each with inputs and outputs. A local network communications bus (LEN) ties all the boards together into a system and
enables the boards to communicate.
For the 48/50P Series, the control consists of the following key components:
Main base board (MBB) The MBB is the center of
the ComfortLink control system. It contains the major portion of the operating software and controls the operation
of the unit. The MBB continuously monitors inputs and
controls outputs, as well as sends and receives data over
the LEN and CCN communications channels. The board is
located in the main control box.
Rooftop control board (RXB) The RXB controls
many unit functions. The RXB controls the actuators for
the economizer hydronic heating valve and humidifier
valve using a digital communications signal. This signal also
provides operation and diagnostic data on the actuators.
The RXB also has relay outputs to control condenser fans,
second stage power exhaust, minimum load valve and the
heat interlock output. The RXB board is located in the
main control box.
Compressor expansion board (CXB) The CXB
provides additional compressor control outputs and is used
on models with more than four compressors. This board is
located in the main control box.
Options control board (EXB) The EXB is used on
units with the optional return fan, digital scroll compressors or when control of a humidifier is required. This board
is located in the main control box.
Expansion valve board (EXV) The EXV board is located in the main control box.
Staged gas heat board (SCB) When the optional
staged gas heat is used, the SCB board will be installed and
control the operation of the gas valves. It also provides additional sensors for monitoring of the supply-air temperature. This board is located in the main control box.
Modulating gas heat boards When the optional
modulating gas heat is used, one timer relay board (TR1)
and one signal conditioner board (SC30) will be installed in
the heating compartment. The two boards in combination
with SCB board provide control to the modulating gas heat
section. Refer to the Unit Controls and Troubleshooting
book for information on modulating gas control.
Integrated gas controller (IGC) One IGC is provided with each bank of gas heat exchangers. It controls the
direct spark ignition system and monitors the rollout
switch, limit switches, and induced-draft motor Hall Effect
sensor. For units equipped with modulating gas heat, the
Controls (cont)
The control also checks on various other operation parameters in the units to make sure that safety limits are not exceeded and the compressors are reliably operated.
The P Series ComfortLink controls offers three control
approaches to mechanical cooling: constant volume,
SAV, and VAV, all with multiple stages of cooling.
COOLING CONTROL OPTIONS
CONTROL TYPE
COOLING CONTROL
METHOD
Unit
Application
Demand Source
P2,P4
CV,SAV
SPT or TSTAT
P3,P5
VAV
RAT or SPT
Control type The control type determines the selection of the type of cooling control as well as the technique
for selecting a cooling mode. The control types are:
VAV-RAT and VAV-SPT Both of these configurations
refer to standard VAV operation. If the control is occupied,
the supply fan is run continuously and return-air temperature will be used in the determination of the selection of the
cooling mode. VAV-SPT differs from VAV-RAT only in that
during the unoccupied period, space temperature will be
used instead of return-air temperature to start the fan for
ten minutes before the return-air temperature is allowed to
call out any mode.
CV SAV TSTAT-Multiple Stage This configuration will
force the control to monitor the thermostat inputs (Y1,Y2)
to make a determination of mode. Unlike traditional 2stage thermostat control, the unit is allowed to use multiple
stages of cooling control and perform VAV-style capacity
control.
CV SAV SPT-Multiple Stage This configuration will
force the control to monitor a space temperature sensor to
make a determination of mode. The unit is allowed to use
multiple stages of cooling control and perform VAV-style
capacity control.
Cooling control method Two different cooling control methods are used to step through the available stages
of capacity. Depending on the unit size, cooling control
method and presence of an MLV, this may range from 2
up to 5 stages of capacity control. These methods are:
Multiple Stage Evaporator Discharge Temperature
(EDT) The capacity of the economizer and compressors
are controlled based on the evaporator air discharge temperature and supply air temperature set point. This control
method uses an adaptive PID (proportional, integral, derivative) algorithm to calculate the estimated change in supply-air temperature before engaging or disengaging the
next stage of cooling. The algorithm compensates for varying conditions, including changing flow rates across the
evaporator coil, to provide better overall control of compressor staging.
Multiple Adaptive Demand This control method will
base the capacity of the economizer and compressors on
the evaporator air discharge temperature and one of two
supply air temperature set points. The control will be able
to call out a LOW COOL or a HIGH COOL mode and
130
maintain a low or high cool supply air set point. The unit
will use either the input from a conventional thermostat to
turn the Y1, Y2 signals into a high and low demand signal,
or with a space temperature sensor use a differential from
set point to determine the mode. Once the mode has been
established the control uses the same algorithm as with
VAV control.
Integrated economizer For each of the above modes
of operation all mechanical cooling will first be delayed
while the unit attempts to use the economizer for free cooling. Once the economizer is at full capacity, the control will
then supplement the free cooling with as much mechanical
cooling as required. To prevent any rapid changes in cooling, the control will also use the economizer to trim the
cooling supplied.
131
Controls (cont)
When the space CO2 level exceeds set point for the minimum ventilation level condition, the ComfortLink controls
will begin to open the outside air damper position to admit
more ventilation air and remove the additional contaminants. As the space CO2 level approaches the set point for
maximum design ventilation level condition, the outside air
damper position will reach the maximum ventilation level
damper position set point limit. Damper position will be
modulated in a directly proportional relationship between
these two CO2 set point limits and their corresponding
damper position limits.
In most applications a fixed reference value can be set for
the outdoor air quality level, but the control also supports
the addition of an outdoor air quality sensor that will be
compared to the indoor or return IAQ sensor. If an OAQ
(outdoor air quality) sensor is connected, the demand set
point levels will be adjusted automatically as the outdoor
CO2 levels vary. Also, if the outdoor CO2 level exceeds a
user-configured maximum limit value, then outside air
damper position will be limited to the minimum ventilation
damper set point value. The control can also receive these
signals through the CCN system.
The IAQ and OAQ measurement levels are displayed by
the ComfortLink scrolling marquee in parts per million
(ppm).
Outdoor air CFM control Minimum space ventilation requirements can also be maintained by applying the
minimum outdoor air cfm control option. This option provides an airflow monitoring station at the outside air damper inlet. The ComfortLink controls can be programmed to
monitor this airflow rate and to override the current outside
air damper position to maintain a minimum quantity of
outdoor air at the users design set point even as the units
supply fan slows during part load operating periods.
Fire and smoke controls interface The unit can be
equipped with an optional return air smoke detector. The
smoke detector is wired to stop the unit and send a message to a remote alarm system if a fault condition is detected. If the controls expansion module is added, the control
will support smoke control modes including evacuation,
smoke purge, and pressurization.
Demand limiting The control supports demand limiting using one or two fixed capacity limits initiated by discrete input switches or a variable capacity limit function
based on an analog input signal. On CCN systems this can
be done through the network, or for non-CCN network
jobs this can be done by adding the controls expansion
module.
Diagnostics
The ComfortLink controls have fully integrated all controls
and sensors into a common control system. The control
monitors these inputs as well as many of the routines to
provide advanced diagnostics and prognostics. These include adaptive logic to allow the unit to continue to operate
in a reduced output mode and automatic resets where applicable. The last 10 alarms and alerts are stored in memory and can be accessed through the display. The alarms
can also be monitored through the Carrier Comfort Network connection. The unit also supports the use of the
132
Control interface
The ComfortLink controller can interface with an i-Vu
Open control system, a BACnet building automation system, or Carrier Comfort Network devices. This will allow
for the use of all system control programs. These include:
Network Service Tool
System Pilot device
Touch Pilot device
i-Vu Open control system software
ComfortVIEW software
CCN Web software
ComfortID system
Contact Carrier Controls Marketing for more information. The control can also provide interface with other energy management systems with the addition of either the
BACnet/MODBUS Carrier translator or the LonWorks
Carrier translator.
Several contact connection points have been provided in
the main control box for interface to external controls and
systems. These are summarized in the Interface Connection table. External controls use the following interface
points:
Start/Stop (On/Off) Start/Stop is accomplished with
a contact closure between terminals 3 and 4 on TB201.
Remote Economizer Enable Enabling and disabling
of the economizer can be done by connecting a contact
closure to terminals 5 and 6 on TB201. The economizer can be configured for a switch closure changeover
for 3-position operation.
VAV Heating Interlock Interface with non-linkage
terminals can be done through TB201 terminals 9 and
10.
Remote IAQ Inputs External IAQ demand inputs can
be connected through terminals 7 and 8 on TB201.
Smoke Detectors Alarm Output Remote detector
alarm outputs can be connected through terminals 1
and 2 on TB201.
Fire Shutdown A remote fire shutdown signal can be
connected to 1 and 2 on TB201. The software can be
configured to shut the unit down on an open or closed
signal.
Fire Pressurization For a remote control of pressurization a contact closer can be connected to terminals
Controls (cont)
Adaptive cooling capacity control with up to 6 stages of
mechanical refrigeration capacity
Variable capacity control with digital scroll compressor
option
Occupied or unoccupied set point
Enable heating (if installed) or cooling during unoccupied periods as required to maintain space temperature
within the unoccupied set points
Adjustment of space temperature set points of 5 F
when using a T56 sensor
Support of IAQ sensor
365-day timeclock with backup (supports minute, hour,
and day of week, date, month, and year access). The
timeclock includes the following features:
Daylight savings time function
Occupancy control with 8 periods for unit operation
Holiday table containing up to 18 holiday schedules
Ability to initiate timed override from T55 or T56
sensors (for a timed period of 1 to 4 hours)
Temperature compensated start to calculate early
start times before occupancy
For units connected into a CCN network the time
clock can be integrated into the overall building
energy management system and be updated
remotely
For units connected to the CCN network the user can
also display all the unit information including I/O values
Maintenance, Configuration, Service, and Set Point
data tables
Indoor air quality (IAQ)
134
Sequence of operation
Cooling, constant volume (CV, SAV) units
On power up, the control module will activate the
initialization software. The initialization software will
determine the unit configuration and also initialize any
controls loops and input/output devices. All alarms and
configurations are saved in memory and maintained during
power outages. All alarms will be maintained in memory
and must be cleared through the display.
Constant volume and staged air volume conventional thermostat control If the unit is equipped with
a conventional thermostat with Y1, Y2, W1, W2 and G
connections then the control will perform the following
sequence.
When G is closed the indoor fan will turn on. G must be
closed for heating or cooling to occur. If Y1 is closed then
the control will first check the ability to use the economizer.
If the economizer can be used, the control will modulate
the damper open to maintain the low load economizer
leaving air temperature set point. If Y2 closes then the control will lower the leaving air temperature set point to the
configured set point. If the economizer can not satisfy the
135
Controls (cont)
If temperature compensated start is active then advance
pre-cool or heat of the space is enabled. If the unit is configured to use a pre-purge cycle then the ComfortLink
controls will start the unit in Vent mode based on a prestart time interval. If an IAQ sensor is being used and the
low IAQ control point is satisfied, then the mode will be
terminated.
If Cooling mode is required, then the controlling set
point will be the leaving air temperature set point. If an
economizer is present and the changeover control allows
the economizer to be used, then it will first attempt to control the leaving-air temperature using free cooling. If this
can not satisfy the load, then additional compressor stages
will be turned on to maintain the leaving-air temperature.
When both compressors and economizers are being used,
the control will use the economizer dampers to maintain
better control of the leaving-air and to help prevent high
compressor cycling. If the economizer can not be used
then it will be set to the minimum vent position. When using compressors, the leaving-air temperature will sequence
compressors on and off using a PID control loop. If the
unit is equipped with an optional hot gas bypass valve the
control will use the hot gas as an additional stage of capacity. When the first stage of cooling is required the control
will turn on a circuit A compressor and the hot gas bypass valve. When additional cooling is called for it will turn
off the hot gas bypass valve. The valve will also be used for
additional freeze protection of the coils when low
evaporator refrigerant temperatures are detected using the
suction pressure transducers.
When operating in cooling the control will also monitor
the supply duct pressure and send a 4 to 20 mA signal to
the factory-supplied inverter to control the speed of the fan
and the delivered cfm. If on a linkage system the control
will also support static pressure reset based on the needs of
the zones.
If the unit has been enabled for occupied heat and the
space temperature sensor (SPT), return air temperature
sensor (RAT) or linkage demand calls for heat, the control
will energize the electric heat or gas heat (if present) to
warm the space. In this mode the control will energize the
heat interlock relay which will signal the terminals to open
to the heating position. Note that for the linkage systems
the interlock relay connection is not required. Once the
Heat mode is enabled, the heat capacity will be controlled
by the return air temperature set point. Heating will continue until the return temperature set point is satisfied. If the
unit is configured for morning warm-up and the heating
demand is below the set point during the first 10 minutes
of operation, the control will energize full heating capacity
until the return air temperature set point is satisfied.
If the space temperature sensor (SPT), return air temperature sensor (RAT) or linkage demand requires that the
unit be in heating then the control will energize the electric
heat or gas heat (if present) to warm the space. In this
mode the control will energize the heat interlock relay
which should be connected to the terminals to indicate that
they should open to the heating position. The interlock relay connection is not required for the linkage systems.
Heating will continue until the mode selection sensor is
satisfied.
136
Application data
Ductwork Secure vertical discharge ductwork to roof
curb. Interior installation may proceed before unit is set in
place on roof. For horizontal discharge applications, attach
ductwork to unit, or field-supplied flanges can be attached
to horizontal discharge openings and all ductwork attached
to flanges. Units equipped with electric heat require a
90-degree elbow below the unit supply duct connection.
Thru-the-curb service connections Roof curb
connections allow field power wires and control wires to
enter through the roof curb opening.
change
to the gas orifice may be required at high altitudes. Contact
Carrier Application Engineering.
Minimum temperature Minimum allowable temperature of mixed air entering the heat exchanger during
half rate (first stage) operation is 50 F. There is no minimum mixture temperature during full-rate operation. Comfort conditioning may be compromised at temperatures below 50 F. Below 50 F entering-air temperature (EAT) both
stages of heat are engaged.
Internal unit design Due to Carriers internal unit
design (draw-thru over the motor), air path, and specially
designed motors, the full horsepower listed in the Physical
Data table and Motor Limitations table can be utilized with
extreme confidence. Using Carrier motors with the values
listed in the Physical Data and Motor Limitations tables will
not result in nuisance tripping or premature motor failure.
The unit warranty will not be affected.
Electric heat A field-supplied 90-degree elbow must
on heating.
Minimum ambient cooling operation temperature All units are equipped with factory economizers
to allow free cooling at any outdoor ambient. If mechanical
cooling is required, the units are designed to operate at
outdoor temperatures down to 32 F. With accessory Motormaster V control units can operate at outdoor temperatures down to 20 F. Outdoor-fan motor change out may
be required for Motormaster V applications.
Carrier recommends the installation of field-fabricated
wind baffles on all vertically oriented condenser coil surfaces when operating in environments with prevailing winds
of more than 5 mph and where temperatures drop below
32 F.
138
030-050
055-100
9.80
55.52
69.50
83.90
9.80
66.00
69.50
83.90
B
A
DISTANCE A HEIGHT B
123.0
156.8
200.4
200.4
6.6
6.6
6.6
6.6
279.2
6.6
139
a48-8438
POWER
EXHAUST
PRIMARY
CONDENSATE
DRAIN (TO
SERVICE
DRAIN)
RETURN
AIR
140
CONTROL BOX
ACCESS PANELS
AUXILIARY
CONDENSATE
DRAIN
(BOTH SIDES)
NATURAL GAS
SUPPLY LINE
(WITH SHUTOFF
VALVE 48P ONLY)
FIELDINSTALLED
SERVICE
DISCONNECT
SUPPLY
AIR
POWER
SUPPLY
141
a48-8440
142
a48-8441
EXB
143
a48-8442
144
a50-8378
145
a48-8443
146
Accessory
Accessory
Air Foil
Analog
Air Pressure Switch
Auxiliary
Compressor Contactor
Capacity
Compressor Circuit Breaker
Control Circuit Breaker
Crankcase Heater
Carrier Comfort Network
Cooling Coil Thermistor
Controls Expansion Module
Compressor Modulation Relay
Compressor
Current Sensor Board
Compressor Expansion Board
Digital Scroll Compressor
Digital Input
Discharge Pressure Transducer
Digital Unloader Solenoid
Economizer Control Board
Economizer
Equipment
Evaporator
Economizer Control Board
Exhaust
Expansion Valve Control Board
Fuse
Ground
HC
HIR
HMV
HPS
HVS
IAQ
IFC
IFCB
IFM
IGC
LEN
LLS
MBB
MGV
MLV
MP
OA
OAT
OD
OFC
OFM
OPT
PE
PEC
PECB
PEM
PL
PP
PTC
Heater Contactor
Heat Interlock Relay
Humidi-MiZer Modulating Valve
High-Pressure Switch
Humidi-MiZer Valve Solenoid
Indoor Air Quality
Indoor Fan Contactor
Indoor Fan Circuit Breaker
Indoor Fan Motor
Integrated Gas Controller
Local Equipment Network
Liquid Line Solenoid
Main Base Board
Main Gas Valve
Minimum Load Valve
Modular Motor Protector
Outdoor Air
Outdoor-Air Thermistor
Outdoor
Outdoor Fan Contactor
Outdoor Fan Motor
Option
Power Exhaust
Power Exhaust Contactor
Power Exhaust Circuit Breaker
Power Exhaust Motor
Plug Assembly
Plenum Pressure
Positive Temperature Coefficient
Power Reference
RA
RAT
RCB
RET
RF
RXB
SAT
SCB
SPT
STDU
TB
TRAN
UPC
VAV
VFD
Return Air
Return Air Thermistor
Rooftop Control Board
Return
Return Fan
Rooftop Control Board
Supply Air Thermistor
Staged Gas Control Board
Suction Pressure Transducer
Standard Tier Display Unit
Terminal Block
Transformer
Unitary Protocol Converter
Variable Air Volume
Variable Frequency Drive
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
To indicate common potential
only, not to represent wiring.
To indicate FIOP or Accessory
147
F.
G.
H.
I.
149
150
14)
15)
16)
17)
18)
19)
20)
21)
K.
L.
M.
N.
152
economical level. The user can also configure dew point limiting.
5. Modulating Power Exhaust with VFD:
Package shall include 2 double-width, doubleinlet centrifugal belt drive, forward-curved
power exhaust fans with variable frequency
drive control of each fan to maintain a field
adjustable interior space pressure set point.
a. Fan bearings shall be of the pillow block
type with an average design life of
200,000 hours.
b. Fans shall be statically and dynamically
balanced.
c. Bypass for the VFD shall be available as a
factory-installed option.
6. High-Capacity Modulating Power Exhaust System (75 to 100 ton units only):
High-capacity modulating power exhaust system shall be factory-installed and contain fans
and motors, exhaust hoods and controls (including variable frequency drive and staging
sequence) to maintain space pressure at userconfigured set point.
a. Dual fan assemblies with individual motors.
b. Variable frequency drive for modulating
capacity of lead fan.
c. Staged control on lag fan.
d. Differential pressure transducer for monitoring space pressure.
e. Exhaust air hood assemblies containing
backdraft dampers on each fan outlet, factory installed.
f. All wiring and pressure tubing (except to
space pressure pickup location) shall be factory supplied and installed.
7. Return Fan/Building Pressure Control (75 to
100 ton units only):
a. Functions provided shall be:
1) Airflow control for return duct path
(dedicated to overcoming flow losses in
return duct system).
2) Modulate return airflow rate to track
supply fan airflow rate and maintain a
user set delta cfm between the supply
and return airflow.
3) Maintain building pressure by sensing
building pressure and modulating fan
speed.
b. Option shall consist of following hardware:
1) Plenum fan assembly, with welded steel
airfoil blade fan.
2) Spring isolation.
3) Belt-drive fan system, fixed pitch for
maximum belt life and reliability.
4) Variable frequency drive (VFD) for
return fan modulation control.
8.
9.
10.
11.
12.
13.
5) Supply air CFM and return air CFM sensors to measure supply and return airflow.
6) Exhaust damper with outlet hood.
7) Building pressure transducer.
c. Installation:
1) Site installation shall require supply and
installation of building pressure (BP)
sensing pick-up and tube to connect to
BP transducer in unit.
2) All other wiring and pressure tubing
shall be factory-supplied and factory
installed.
Barometric Relief Package:
a. Package shall relieve excess internal pressure and consist of damper assemblies,
hoods, damper screens, seal strips and
required hardware.
b. Damper assemblies shall close due to gravity
upon unit shutoff.
Pleated Filters:
Unit shall be factory equipped with MERV 7
pleated filters having the following characteristics:
a. Efficiency of no less than 30% based on testing per ASHRAE Standard 52.
b. Minimum average arrestance of 95%.
High-Efficiency Pleated Filters (75 to 100 ton
units only):
Unit shall be factory equipped with MERV 11
high-efficiency pleated filters having the following characteristics:
a. Filters shall have a design dust spot efficiency with an average of 60 to 65% based
on the ASHRAE Standard 52.1 test
method.
b. Filters shall have a minimum arrestance of
90%.
c. Filters shall be classified as a Class 2 air filter
according to UL Standard 900.
Bag Filters with Prefilters (30 to 70 ton units
only):
Unit shall be factory equipped with MERV 15
bag filters and 2-in. prefilters, and shall have an
average efficiency of 90% based on testing per
ASHRAE Standard 52.
Cartridge Filters with Prefilters (30 to 70 ton
units only):
Unit shall be factory equipped with cartridge filter mounting system with 2-in. prefilters.
Supply Fan Variable Frequency Drive:
Variable air volume and staged air volume units
shall be equipped with variable frequency drive
(VFD) inverter. The VFD shall be provided with
a metal enclosure and shall be factory-mounted,
153
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
156
37.
38.
39.
40.
41.
42.
43.
44.
45.
B. Unit Cabinet:
1. Constructed of galvanized steel (designated G90
per ASTM Standard A653 minimum coating
weight of 0.9 oz of zinc per square foot), bonderized and primer-coated on both sides and
coated with a baked polyester thermosetting
powdercoating finish on the outer surface.
2. Unit casing shall be capable of withstanding
ASTM Standard B117 500-hour salt spray test.
3. Sides shall have man size insulated, double
wall, hinged access doors for easy access to the
control box and other areas requiring servicing.
Each door shall seal against a rubber gasket to
prevent air and water leakage.
4. Interior cabinet surfaces (except heat exchanger
section) shall be insulated with flexible fireretardant dual-density (1.75-lb/cu ft) fiberglass
blanket, coated on the air side. Insulation coating shall be cleanable and shall contain an EPAregistered immobilized antimicrobial agent to
effectively resist the growth of bacteria and
fungi as proven by tests in accordance with
ASTM Standards G21 and G22.
5. Insulation shall be applied by means of adhesion using a water reducible adhesive sprayed
onto interior surface. Adhesive shall maintain a
satisfactory adhesion and cohesion within the
temperature range of 20 to 180 F and have
excellent resistance to water and water vapor
when cured.
6. Unit shall contain a sloped drain pan, to prevent standing water from accumulating. Pan
shall be fabricated of stainless steel. Unit shall
contain a factory-installed nonferrous main condensate drain connection.
7. Units shall be equipped with lifting lugs to facilitate overhead rigging.
C. Fans:
1. Supply Fan:
a. Unit shall have only one fan wheel, scroll,
and motor.
b. Fan scroll, wheel, shaft, bearings, drive components and motor shall be mounted on a
formed steel assembly which shall be isolated from the unit outer casing with factoryinstalled 2-in. deflection spring isolators and
vibration-absorbent fan discharge seal.
c. Fan shall be double-width, double-inlet, centrifugal belt driven forward-curve type with
single outlet discharge (standard) or centrifugal belt driven airfoil blade section type with
single outlet discharge (optional).
d. Fan wheel shall be designed for continuous
operation at the maximum rated fan speed
and motor horsepower.
e. Fan wheel and shaft shall be selected to
operate at 25% below the first critical speed
157
158
F.
G.
H.
I.
J.
K.
6)
7)
8)
9)
10)
9)
10)
11)
12)
13)
14)
15)
159
18)
19)
20)
21)
22)
23)
24)
25)
160
L.
M.
N.
O.
3. Integrated Economizer:
Dry bulb, differential dry bulb temperature,
enthalpy, or optional differential enthalpy controlled integrated type consisting of dampers,
actuator, and linkages in conjunction with control system to provide primary cooling using
outdoor air, enthalpy permitting, supplemented with mechanical cooling when necessary.
a. Economizer shall meet the requirements of
the California Energy commission airside
economizer acceptance test.
b. Dampers shall be a gear driven low-leakage
type.
c. Actuator shall have a spring-return feature
which shuts dampers upon a power interruption or unit shutdown. Actuators are capable
of internal diagnostics.
d. Equipped with a solid-state humidity sensor
that is capable of sensing outdoor-air heat
content (temperature and humidity) and controlling economizer cut-in point at most economical level. The user can also configure
dew point limiting.
4. Ultra Low Leak Economizer:
Dry bulb, differential dry bulb temperature,
enthalpy, or optional differential enthalpy controlled integrated type consisting of dampers,
actuator, and linkages in conjunction with control system to provide primary cooling using
outdoor air, enthalpy permitting, supplemented with mechanical cooling when necessary.
a. Economizer shall meet the requirements of
the California Energy commission airside
economizer acceptance test.
b. Dampers shall be a gear driven ultra lowleakage type with blade and edge seals.
Dampers shall exhibit a maximum leakage
rate of 4 cfm per square foot of area at
1 in. wg pressure differential when tested in
accordance with AMCA Standard 500.
c. Actuator shall have a spring-return feature
which shuts dampers upon a power interruption or unit shutdown. Actuators are capable
of internal diagnostics.
d. Equipped with a solid-state humidity sensor
that is capable of sensing outdoor-air heat
content (temperature and humidity) and controlling economizer cut-in point at most economical level. The user can also configure
dew point limiting.
5. Modulating Power Exhaust with VFD:
Package shall include 2 double-width, doubleinlet centrifugal belt drive, forward-curved
power exhaust fans with variable frequency
drive control of each fan to maintain a field
adjustable interior space pressure set point.
161
8.
9.
10.
11.
12.
13.
17.
18.
19.
20.
21.
163
22.
23.
24.
25.
26.
27.
28.
164
29.
30.
31.
32.
33.
34.
41.
42.
43.
44.
3) Tempering heat control, based on userconfigured ventilation supply air temperature set point, to eliminate cold draft
conditions with low mixed-air temperatures.
b. SCR heat control option shall consist of:
1) SCR controller capable of ensuring the
proper heating rates.
2) Supply air temperature thermistors with
duct-mounting base.
3) Limit switch temperature thermistors.
c. Field installation shall be limited to installing
three supply air temperature thermistors in
the supply duct. All other hardware and wiring shall be factory-completed.
Low Outdoor Sound:
Low sound fans for outdoor sound reduction
shall be available as a factory-installed option
for all units (except 35 ton units).
Low Ambient Control:
a. Control shall regulate fan motor speed in
response to the saturated condensing temperature of the unit. The control shall be
capable of operating with outdoor temperatures at 20 F.
b. Motormaster low ambient control shall be
available as a factory-installed option or fieldinstalled accessory for all units.
Short Circuit Current Rating (SCCR):
An optional SCCR of 65kA shall be provided
for 208/230 and 460 volt units. An optional of
25kA shall be provided for 575 volt units.
Low Compressor Sound Blanket:
Low compressor sound blanket accessory shall
be available for field installation.
165
Index
Airflow
Maximum 7, 138
Minimum 7, 138
Application data 138, 139
Auxiliary coil 138, 139
Chassis arrangement 30-32
Extended length 31, 32
Horizontal discharge 31, 32
Standard length 30, 31
Vertical discharge 30-32
ComfortID controls 4
ComfortLink controls 1,2, 132
Compressor staging 22,23
Control expansion module 129
Controls 129- 137
Cooling capacities 46-102
Digital scroll compressor 3, 22, 23
Dimensions 33-43
Accessory 39-43
Base unit 33-38
Economizer 131
Electrical data 127, 128
Electric heater capacity 12
Features/Benefits 1-5
Gas heat capacity 7-12
Guide specifications 148-165
48P2,P3,P4,P5 148-156
50P2,P3,P4,P5 157-165
Hinged access doors 3
Horizontal applications 31, 32
Humidi-MiZer system 3, 45
Indoor air quality (IAQ) 4, 131
Integrated gas controller (IGC) 5, 129
Maximum outdoor temperature 138
Minimum outdoor temperature 138
Model number nomenclature 6
Novation technology 2, 3
Options and accessories 29-32
Performance data 45-126
Physical data 13-28
48P2,P3,P4,P5 13-17, 22-28
50P2,P3,P4,P5 18-28
Piping and wiring (typical installation) 140
Power exhaust 4, 22
Drive data 28
Fan performance 123, 124
Motor limitations 128
Return fan 22, 28
Drive data 28
Roof curb dimensions 39-43
Condenser section roof curb 42, 43
Selection procedure 44
Smoke control 132
Staged gas control 3, 130
Static pressure drop 125, 126
Economizer 125, 126
Electric heat 125, 126
High-capacity coil 125, 126
Gas heat 125, 126
Hydronic coil 125, 126
Power exhaust 125, 126
Supply fan motor
Drive data 27
Motor limitations 127
Performance 103-124
Thru-the-curb connections 138
Unit-mounted disconnect 5
Variable frequency drive 4
Vertical discharge applications 4, 30-32
166
Weight
Operating 13-21
Options and accessories 27
Roof curb 27
Unit distribution 24-26
Wiring 141-147