LS 101 Daylighting Controller Cut Sheet
LS 101 Daylighting Controller Cut Sheet
Figure 1:
LS-101
DESCRIPTION
The Watt Stopper LS-101 is an interior photosensor that automatically turns a zone of lights ON and OFF based on daylight levels. It is a low voltage device intended to signal a power pack or relay panel. The LS-101 is designed to require minimal adjustment at startup. For more advanced applications, an onboard display and two pushbuttons allow for adjustments, if needed. The display is hidden under a removable cover. To assist with adjustment, the LS-101 displays the current light level reading. Figure 2: Cover removed The LS-101 is designed to be either ceiling- or wallmounted. It has a wide range light sensor capable of measuring from 1 to 1400 footcandles.
Figure 3:
When the primary source of daylight is a skylight (toplighting), there are several options for mounting the LS-101. The recommended mounting locations are shown in Figure 4. Ideally, the sensor is mounted on the South sidew a l l looking North across the light well. It could also be mounted on the ceiling next to the skylight, looking down at the oor. A skylight may produce 5000 footcandles or more. If the sensor is mounted so that it looks up into the skylight, the daylight will exceed the maximum OFF setpoint of 1275fc which is too low for this orientation.
SELECTING A LOCATION
The LS-101 controls lights in areas that rece i ve enough daylight so that the electric lights can be reduced or switched OFF. It is important to select a location for the LS-101 where the daylight is representa t i ve of the daylight throughout the controlled zone. Note the path of shadows. Daylighting co n t rol will be problematic if part of a controlled zone is in shadows while another part has plentiful daylight. When the primary source of daylight is a window (sidelighting), the LS-101 is typica l ly ceiling mounted within the daylit zone which extends 12 feet or le ss in from the window. A good location is often between the window and the rst row of x t u res. Figure 3 shows a typical mounting location for a sidelit application.
Figure 4:
Copyright 2007 Watt Stopper/Legrand
Invert output
This feature is used to control devices that require a +24 VDC signal when the lights should be turned OFF and 0 VDC when the lights should be turned ON. The normal operation of the L S-101 provides a +24 VDC signal when the lights should be turned ON, but using this feature, the operation can be reve rsed from the Adjustment Menu Setup display to satisfy the applica t i o n .
OPERATION
The LS-101 features adjustable ON and OFF setpoints, OFF time delay as well as seve ral features to simplify adjustment. For basic operation, these three paramete rs are all that may need to be adjusted. While the ON and OFF setpoints are independently adjustable, the LS-101 features a built-in minimum deadband. Therefore, these two setpoints are always automatically separa ted by at least a minimum amount of deadband. When the sensed light level drops below the ON setpoint for 20 seconds, the output signal switches ON. In the LS-1 0 1 s default operation, this means that the LS-101 provides 24 VDC on the output (blue wire) when the lights should be ON. However, it is also possible to invert the output sta te. (Please see Invert output for further explanation.) Adjusting the ON setpoint also automatically adjusts the OFF setpoint to maintain the programmed deadband. Once the ON setpoint is changed, you can further adjust the OFF setpoint. In applications where the LS-101 sees the lighting from the controlled x t u res, it is important to have the ON and OFF setpoint separated by a deadband of at least as much as the light provided by the controlled x t u re.
Test Mode
The Te st mode temporarily shortens all of the time delays so that the light level switching functions can be quickly te sted. Te st mode is invoked in the installation process in two ways. A f ter either an ON or OFF setpoint has been changed, the L S-101 remains in Test mode for one minute. The LED blinks ON and OFF rapidly to indica te Test mode. During this minute, te st the LS-101 operation by either blocking the light reaching the sensor or by shining a bright light i n to the sensor. At the end of the minute, the normal time delays are reinsta ted. Te st mode can be activated for a longer period through a menu item on the display. From the Test mode menu, you can turn ON Te st mode for 30 minutes. Once turned ON, it can also be turned OFF from the Test mode menu.
INSTALLATION
The LS-101 is designed to be mounted in either of two ways. For suspended ceiling tile, a threaded nipple with a lock nut is attached to the L S-101. See Figure 5.
Figure 5:
Temporary Override
When using the display and buttons, it is possible to temporarily override the output ON or OFF from the display and onboard buttons. This feature is useful for observing that the correct lights are being co n t rolled and all other components in the system are functioning co r rectly. (Please see the Display functions for further explanation.) Figure 6:
For sheetrock or other solid surfaces, rst remove the threaded nipple by squeezing it near the base of the LS-101. Then use the t wo screw holes located under the cover. Screws are not provided. Select #6 pan head screw s appropriate for the mounting surface, typica l ly about 7/8 long. Removing the nipple from the back side of LS-101
page 2
Visit our website for FAQs: www.wattstopper.com Call 800.879.8585 for Technical Support
For measuring light, the rotation of the light sensor is not critical, but it may simplify setup and adjustment. Rotate the LS-101 so you can approach it from the side with the status LED. In a typical ceiling application, rotate the LS-101 so that the light sensor is nearest the window. In a wall mount application, it should be rotated so that the light sensor is near the top.
WIRING
IMPORTANT: All low voltage wiring must be isolated from any line voltage wiring. Low voltage wiring should not be insta l led within the same conduit as line voltage wiring. The unit has 5 co lor-coded wires. Connect to wires with insulation ra ted for the application. Normally recommended wire is 18 AWG 3 or 4 co n d u c tor cable with 300 Volt insulation. When the optional wall switch override is used, a separate 18 AWG 2 co n d u c tor with 300 volt insulation is recommended.
Figure 8:
Two connections are optional. Cap unused wires. See Operation for more information. White connects to the Occupancy Sensor output, see Figure 9. Yellow connects to the Wall Switch Override, see Figure 10. Figure 11: Occupancy Sensor, providing Hold OFF when unoccupied, ON when occupied AND low light level
Figure 9:
The display automatically shuts down after 10 minutes without a button press. Attach the cover onto the L S-1 0 1.
Adjustment Menu
The menu is arranged so that the most common adjustments are readily accessible. For many applications, only the ON Setpoint needs to be adjusted. For more advanced applications, the SETUP menu offe rs more options. There are also two special indicato rs that may appear above the normal characte rs in the display: MEM and OV R. MEM shows which value is programmed into the LS-101. When stepping through the available choices, MEM appears for the currently programmed choice. The MEM indica tor appears for any new value pro g rammed into the LS-101. For instance, if the Select button is used to step to a new value and then the Select button is pressed and held, afte r two seconds MEM appears. This indica tes the new value is now programmed. OVR appears when the LS-101 is being overridden. There are two ways to override the LS-101. The rst is to use the Select button when viewing the Control (CTRL) menu. The second is to use the wall switch override, if insta l led. The rst press of either of these overrides turns on the OVR indicator to show that the LS-101 is being overridden.
Buttons
There are two buttons, one on each side of the display, labeled Menu and Select. The Menu button moves the display forward through the menus. The Select button has two functions: 1. Press and release Select to step through the adjustment choices. 2. Press and hold Select until MEM appears in the display to change the adjustment to the selection shown in the display.
Display
When the LS-101 is powered up, the display shows: LS101 #.# #.# indica tes the products internal ve rsion number. This display also occ u rs if the LS-101 is reset to factory defaults. The display goes to sleep when there is no activity. If no b u t tons are pressed for 10 minutes, then the display goes blank. Pressing either button wakes up the display.
page 4
Visit our website for FAQs: www.wattstopper.com Call 800.879.8585 for Technical Support
Footcandles (FC) This is normally the rst screen visible when any button is pressed. It displays the current light sensor reading, which updates once a second. Any object that changes the amount of light that reects into the light sensor will change the readings. Whenever possible, lean away or back down from the LS-101 to see if the light level readings increase. Remove objects from the sensors eld of view if they are not normally in the area. Control (CTRL) This screen displays the logical sta te of the output to the p ower pack, either ON or OFF. It also allows temporary override of the output. Press Select to to g g le the output to its opposite state. If the output was ON, one press turns it OFF and the OV R indica tor appears. The status indica tor LED also starts to ash slow ly. Press Select again to turn the output ON again while OV R indica tor remains lit. The output remains overridden ON or OFF until this screen is exited by pressing the Menu button. Upon exiting, the LS-101 automatically resumes automatic control, the OVR indica tor turns OFF and the LED stops its slow ash. If the display is left on this screen while the output is overridden, the override will timeout in 10 minutes and the L S-101 will return to automatic control. Observing the Fo o tcandles (FC) display while in override: If you want to observe the FC reading at the sensor while the lights are either ON or OFF, you can latch the override sta te, then maneuver the display back to the FC display to see how the lights ON or lights OFF states affect the light level coming i n to the sensor. To latch the output in an override sta te: 1. Access the CTRL menu ite m . 2. Press SELECT to override the output, then press and hold SELECT until the MEM indicator appears in the display. 3. To ca n cel the override, access the CTRL menu again then press the SELECT button or it will automatically timeout in 10 minute s . ON Setpoint (ON) When the light level drops below this setpoint for 20 seconds, the lights turn ON. Set this value for the lowe st level that is acce p table during times when the space is occupied. The ON setpoint range is from 1 to 850 footcandles. The default value is 7.5 fo o tcandles. Changing either the ON or OFF setpoint initiates Te st mode for one minute. During this one minute period, the time delays are temporarily made very short. Te st mode is indica ted by the rapidly ashing status indicator. OFF Setpoint (OFF) When the light level exceeds the OFF setpoint for the length of the Time Delay, the lights turn OFF. N o te that the OFF setpoint updates when the ON setpoint has been changed. The OFF Setpoint always maintains a deadband of 25%, 50%, 75% or 100% above the ON Setpoint. Any change in the ON setpoint causes the OFF setpoint to recalculate using the same percentage of deadband as selected for the previous value.
Time Delay (TIME) This adjustment determines how long the light level must remain above the OFF setpoint before the lights turn OFF. The available choices are 3 minutes, 10 minutes, 20 minute s and 30 minutes. The default value is 10 minute s .
Visit our website for FAQs: www.wattstopper.com Call 800.879.8585 for Technical Support
ORDERING INFORMATION
Catalog # LS-101 B series Power packs Description Light Sensor controller: Range 1 -1400 footcandles Output 24 VDC; 150 mA B120E-P 120 VAC; 60 Hz B277E-P 277 VAC; 60 Hz B230E-P 220-240 VAC; 50-60 Hz B347D-P 347 VAC; 60 Hz 120/277 VAC; 60 Hz, Output 24 VDC; 150mA with Hold-ON and Hold-OFF inputs
TROUBLESHOOTING
Display does not display any information Press either button to wake up the display. Verify that the LS-101 is being powe red with 24 VDC. Lights do not switch when desired Use the CTRL menu to manually te st ON and OFF control of the lighting. If the lights switch with manual control, then check the ON and OFF setpoints. Use te st mode to verify setpoints. Use the fo o tcandle display screen to compare the current values with the setpoints. LED is OFF If the controlled lights are ON, then the LED is likely o p e rating correctly. LED is blinking If the blink is slow (one blink every four seconds) then the LS-101s output has been forced ON or OFF by an override, from the optional wall switch, or the Control menu. If the blink is fast (one blink every second) then the LS-101 is in te st mode.
WARRANTY
Watt Sto p p e r / L e g rand warranties its products to be free of defects in materials and workmanship for a period of ve years. There are no obligations or liabilities on the part of Watt Stopper/Legrand for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to lo ss of property, revenue, or pro t, or cost of removal, installation or reinstallation.
Please Recycle
2800 De La Cruz Boulevard, Santa Clara, CA 95050 Te c h n i cal Support: 800.879.8585 www.wattstopper.com 07076r2 4/2007