Displacement Design Guide
Displacement Design Guide
w w w. p r i c e - h v a c . c o m
Contents
Displacement Ventilation
Displacement Ventilation Introduction .................... J8 - J10 Typical Applications ................................................................. J9 Terminology . .......................................................................... J10 Displacement Ventilation Characteristics ............. J11 - J14 Thermal Plume..........................................................................J11 Stratification Height..................................................................J11 Room Airflow Pattern. .............................................................. J12 Diffuser Air Flow Pattern. ......................................................... J13 Contaminant Distribution........................................................ J13 Temperature Distribution........................................................ J14 Location of Returns.................................................................. J14 Thermal Comfort. .......................................................... J15 J16 Ventilation Effectiveness. ...................................................... J17 Heating with Displacement Ventilation. ............................ J18 Humidity Control........................................................... J19 J20 Design Suggestions ................................................................ J19 Direct Expansion Rooftop Units.............................................. J19 Dehumidification and Heat Recovery.......................... J19 J20 Acoustics........................................................................ J21 J22 Designing with AHUs and RTUs........................................... J23
Loading Within the Space. .......................................... J24 J25 Loads ....................................................................................... J24 Sensible and Latent Loads...................................................... J25 Diffuser Types. ................................................................ J26 J27 Diffuser Layout and Location................................................ J28 DV Supply Air Methods.......................................................... J29 Component Selection and Installation.............................. J29 Air Volume Calculations ............................................. J30 J31 Design Procedure. .................................................................... J31 Design Examples.............................................................J32 - J37 Small Office Example.................................................. J32 J34 Boardroom Example..................................................... J35 J37 Special Applications Supplement..............................J38 - J52 Displacement Ventilation for Industrial Applications....J39 Machine Shop Example................................................ J40 J43 Displacement Ventilation and Schools........................ J44 J45 Classroom Example...................................................... J46 J48 Displacement Ventilation and Healthcare................... J49 J51 References ................................................................................. J52
Price has partnered with Krantz Products USA Inc., North American Distributor for Krantz, the world leader in displacement ventilation diffusers, to offer a complete system for displacement ventilation distribution. The Krantz Komponenten industrial diffusers have been the preferred specification for industrial applications since Krantz Komponenten first pioneered the North American market. Krantz Komponenten diffusers are offered to the U.S. and Canadian HVAC markets exclusively through Price.
Copyright E.H. Price Limited 2007. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-3
DISPLACEMENT vENTILATION
Price Industries works hard to promote the use of sustainable building materials and innovative air distribution technologies to improve the air quality and environment integrity in the built environment. Price has a long history of designing and promoting products systems that are energy efficient and ideal for use in Green Building designs. Price is committed to the continual introduction of new products and systems that further the goals outlined by the USGBC.
Green Tip Green Tips provide useful insight into some opportunities for making design decisions which might help in designing a sustainable building. Some pointers are provided for both the LEED and the Green Globes rating systems.
Control Tip Control Tips are provided to maximize the understanding of all of the control opportunities and issues with Displacement Ventilation systems. In some cases these will help reduce control complexity or optimize control effectiveness.
Product Tip Product Tips provide a link between the design guide section and the product section to assist the design engineer in selecting product with the recommended characteristics.
DISPLACEMENT VENTILATION
J-4
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Displacement Ventilation
Design Guide
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-5
DISPLACEMENT vENTILATION
Typical Applications
Displacement ventilation is an effective method of obtaining good air quality and thermal comfort in the occupied space. Spaces where displacement ventilation has been successfully used are: - Schools - Classrooms - Hospitals - Dining Rooms - Conference Rooms - Industrial Spaces Displacement ventilation is usually a good choice in the following cases: - Where the contaminants are warmer and/or lighter than the room air. - Where the supply air is cooler than the room air. - Where the room heights are 9 feet or more. - Where low noise levels are desired. Overhead Air Distribution may be a better choice than displacement ventilation in the following cases:
DISPLACEMENT VENTILATION
- Where ceiling heights are below 8 feet. - Where disturbances to room airflow are strong. - Where contaminants are colder and/or denser than the ambient air. - Where cooling loads are high and radiant cooling is not an option.
J-6
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Terminology
Adjacent Zone The adjacent zone is defined as the distance from the diffuser face to a point where the velocity of the airstream is reduced below to 40 FPM measured 1 above the floor. Buoyancy The vertical force exerted on a volume of air that has a density lower than the ambient air. Breathing Zone The estimated height at which occupants will inhale the surrounding air. CFD Computational Fluid Dynamics.The analysis of a space utilizing computers to simulate fluid motion. An example of output from a CFD analysis is shown in Figure 8. Displacement Ventilation Room ventilation created by room air displacement, by introducing air at low level in a space at a lower air temperature than the room air. Draft Unwanted local cooling of a body caused by movement of air. Draft Temperature The effective temperature based on the temperature and velocity of the supply air causing discomfort. Green Globes A sustainable building rating system from the Green Building Initiative (GBI). IAQ Indoor Air Quality. LEED Leadership in Energy and Environmental Design. A sustainable building rating program from the US Green Building Council. Length, Adjacent Zone The Length of the adjacent zone is the length from the diffuser face to a specified velocity, typically 40 FPM, refer to Figure 6. Mixed Ventilation Air diffusion where the mixing of supply and room air is intended. Occupied Zone An imaginary box in the room defined as 6 feet above the floor and not less than 24 inches from the walls.
DISPLACEMENT vENTILATION
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Percent Dissatisfied (PD) ASHRAE defines the percent dissatisfied as the percentage of people predicted to be dissatisfied with their environment due to draft. Predicted Mean Vote (PMV) L Vote, PMV, is an index The Predicted Mean that predicts the mean value of the votes of a large group of persons in relation to a scale defined by ASHRAE W [ASHRAE Standard 55 2004] Predicted Percentage of Dissatisfied (PPD) ASHRAE defines the predicted percentage of dissatisfied as an index that establishes a quantitative prediction of the percentage of thermally dissatisfied people determined from PMV. In real terms it is a measure of the thermal comfort performance in a space. Thermal Plume The air current rising from a hot body. Stratification When the temperature of the space varies with height. Upper Zone The space above the occupied zone. Ventilation Effectiveness The ratio of contaminants in the exhaust to the contaminates at the breathing level. An indication of how well a space is extracting contaminates, and an indication of IAQ. Width, Adjacent Zone The width of the adjacent zone is the width from the diffuser face to a specified velocity, typically 40 FPM, refer to Figure 7.
Figure 6
Figure 7
W
Figure 8
J-7
DISPLACEMENT VENTILATION
q1
q2 Yst q0
J-8
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Partition
Green Tip Because displacement ventilation systems are gravity driven, caution must be used in sloped applications. A theater with even seating, will require less diffusers in the lower sections of the theater and more in the upper to compensate the natural movement of the air to the lower portion of the theater.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-9
DISPLACEMENT vENTILATION
Contaminant Distribution Contaminant distribution in a space is influenced by several factors such as supply air method, contaminant source type, location within the space, heat sources, and space height. Displacement ventilation improves occupant air quality by reducing the contaminants in the lower portion of the room. The general upward motion of air causes contaminants to concentrate within the upper zone ( Figure 20 ). With mixing ventilation, contaminants are diluted with supply air and are distributed evenly throughout the space. The figure represents contamination distribution in a room supplied with mixing and displacement ventilation for a typical case where the contaminant source is warm (a person, for example). For displacement ventilation case, because the upward convection around a person brings clean air from lower level to the breathing zone, the air in the breathing zone is cleaner than the room air at the same height. Contaminants that are heavier than air need to be extracted at a lower level if they present a safety concern.
DISPLACEMENT VENTILATION
Green Tip The potential IAQ increase and reduction in airborne illness transmission are substantial, but are typically not addressed in dollar figures. Recent publications and studies have shown the increase in IAQ to increase performance in schools (Ref. ASHRAE JournalVolume 48 Number 10 Oct. 2006). A publication from Capital E shows the estimated costs with improved IAQ for schools, but could be applied to other areas as well. See the Ventilation Effectiveness section for further discussion.
J-10
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
9 8 7 6 5 4 3 2 1 64 66 68 70 72 74 76 78 80
DISPLACEMENT vENTILATION
be exhausted properly from the space. If the exhaust is located lower than 7 feet there may be some polluted/hot air remaining within the occupied zone. For lower ceilings it is best to place the return above the heat source in the space. Product Tip Where additional cooling is required, chilled ceiling systems can be used to remove additional heat from the space. For more information on chilled ceiling systems see the Radiant Systems section.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-11
Thermal Comfort
Thermal Comfort ASHRAE Standard 55 defines thermal comfort as a condition of the mind which expresses satisfaction with the thermal environment . This definition is based on the fact that each person defines what is thermally comfortable based upon their own physiological and psychological states. To no small part, a building occupants preferred thermal environment is based upon what they are normally exposed to and as a result, expect to find in any space they enter. Today, most building occupants expect a narrow range of temperature, air velocity and humidity and if the environment is out of their preconceived expectations, a thermal complaint will occur. Another issue affecting thermal comfort is the fact that when a person first enters a new thermal environment, they may not find that environment acceptable for a period of time if they have experienced different thermal conditions or different activity levels just prior to entering the space. This period of adaptation may take up to an hour before the person becomes satisfied with the new thermal environment. Unless the building is only occupied by one occupant and the occupant is in complete control of his or her thermal environment, there will always be at least one occupant who will express dissatisfaction with the building HVAC systems. As a result, ASHRAE defines the goal for the thermal environme nt as an acceptance by a substantial majority (at least 80%) of the building occupants. Most building HVAC designers would prefer to never hear feedback from the occupants of a building that they have designed no feedback would indicate a good design as most people will complain about being hot or cold, but rarely will a building occupant give kudos for being thermally comfortable. The factors that must be addressed when defining conditions for human thermal comfort include: metabolic rate radiant temperature humidity clothing insulation air temperature air speed
80 80 % % %
Figure 22: Acceptable range of operative temperature and humidity [ASHRAE Standard 55 2004]
Data based on ISO 7730 and ASHRAE STD 55 Upper Recommended Humidity Limit 0.012 humidity ratio
.014
.012
1.0 Clo
0.5 Clo
.010
.006
80 80
% % %
.005
70
60
50
% % % %
.004
40
30
20
.002
Figure 23: Effect of air velocity on acceptable range of operative temperature and humidity [ASHRAE Standard 55 2004]
.010
.006
Most designers only consider the last three, but in reality, all six are of equal importance. ASHRAE Standard 55 defines a comfort zone that may be determined for a given range of humidity, air temperature, radiant temperature, air speed, metabolic rate, and clothing insulation. This comfort zone is typically defined in terms of a range of operative temperatures that will provide a thermal environment that a specific percentage of occupants will find acceptable. This method may be used in spaces where the occupants Met levels are within 1.0 Met to 1.3 Met and clothing has a clo value between 0.5 clo and 1.0 clo of thermal insulation. Most office spaces fall within these limitations. Figure 22 shows the range of operative temperatures for an 80% occupant acceptance. This range of operative temperatures are based on a 10% dissatisfaction criteria for whole body (general) thermal comfort (based on the PMV PPD index see ASHRAE Standard 55 for a description of the PMV PPD index) and an additional 10% dissatisfaction for local thermal comfort. Two zones are shown on these figures, one for 0.5 clo and one for 1.0 clo which is intended to be representative of when the outdoor environment is warm and cool, respectively. Figure 23 shows the effect of air velocity on the operative temperature.
.005
70 6
0% % % % %
.004
50
40
30
20
.002
DISPLACEMENT VENTILATION
J-12
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
100
90
% 10
100
90
% 10
Thermal Comfort
The predicted percentage dissatisfied is a measure of the thermal comfort performance in the built environment. There are several factors which are rolled into this calculation including draft, radiant asymmetry and stratification. It is this measure that is typically referenced with thermal comfort is examined or discussed. The most common complaint due to thermal comfort are either the occupant is too hot, or their hands and or feet are cold. You may have both complaints in the same building on the same day. Too high an air velocity can be a significant factor in generating these thermal complaints. The most sensitive part of the human body in the typical office environment is the back of the neck, which is shown in Figure 24. The ASHRAE design conditions of 70F , 50% humidity and 50 FPM, approximately 8% of the occupant will complain of a cool sensation. With a typical dead-band of a thermostat of +-2F , the complaint sensation may vary up to 25% occupant dissatisfaction. A common complaint for cold sensation is the feet. Figure 25 shows the combined effect of air velocity and temperature for this body part. The ankles are demonstratively not as sensitive as the back of the neck to the effect of velocity and only moderately impacted by mild temperature differences from set point. When a person experiences a drop in core body temperature, the body begins to restrict blood flow to the extremities, conserving heat for the critical internal organs. This leads to physically cold hands and feet. The cold complaint caused by draft is more commonly experienced in overhead air distribution than underfloor or displacement ventilation. In an improperly designed overhead air distribution system, the air may separate from and ceiling may directly impact building occupants. For displacement air distribution, the occupant should not be closer than two feet to the displacement diffuser. In displacement air distribution, the average room air velocity is just about 20 to 30 feet per minute. Since the natural convective air velocity of the occupant is about 30 fpm, this type of air distribution will not significantly disturb the natural convective air movement around the occupant. This will lead to higher occupant satisfaction due to the significantly lowered air velocity sensation and the self balancing heat load of the occupant from the low velocity cool fresh air at the occupants feet. In stratification air distribution systems, to maintain thermal comfort, it is important to maintain no more than a 5F (3C) temperature difference between the occupants head and feet. A gradient larger than this value may lead the occupant to become aware that his or her feet are cooler than their head.
Figure 24: Effect of air velocity and temperature difference on thermal comfort for the neck region [source: ASHRAE Fundamentals]
100 90 80 70 60 50 40 30 20 10 0 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5
Temperature Difference, F FEELING OF WARMTH NECK REGION FEELING OF COOLNESS
Figure 25: Effect of air velocity and temperature difference on thermal comfort for the ankle region [source: ASHRAE Fundamentals]
Air Velocity, FP
100 90 80 70
Air Velocity, FPM
40% 30% 20% 10%
60 50 40 30 20 10 0 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5
Temperature Difference, F FEELING OF COOLNESS FEELING OF WARMTH
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-13
DISPLACEMENT vENTILATION
Ventilation Effectiveness
Ventilation Effectiveness Ventilation effectiveness is a measure of the air distribution systems ability to remove airborne pollutants from a building space. This removal of airborne pollutants occurs through the injection of fresh, clean air through a diffuser into the space and removal of the dirtier room air through a return grille. One measure of the ventilation effectiveness is to compare the contamination level in the breathing zone to the contamination level present in the return air grille for a zone. Where: = Cpe/Cpbz Cpe = concentration of pollutants in the exhaust Cpbz = concentration of pollutants at breathing level If the zone (or room) is 100% mixed, the ventilation effectiveness, = 1.0, the air in the occupied breathing zone is as fresh (or dirty) as the air in at the return grille. If > 1.0, the air in the occupied breathing zone is fresher (cleaner) than the return air this indicates that the pollutants are being moved by the cleaner supply air away from the occupied zone and toward the return grille. If < 1.0, this indicates that the occupied breathing zone is dirtier than the return air and this lowered ventilation effectiveness is typically caused by short-circuiting of the supply air to the return grill and is considered a gross waste of pollution removal potential. The type of supply diffuser used will have a direct impact in the ventilation effectiveness of the building HVAC system. Typically, mixed ventilation systems are overhead air diffusers and have an average ventilation effectiveness of = 0.9. The overall ventilation effectiveness of overhead diffuser systems may vary due to diffuser type (0.7 < < 1.0 with average = 0.9) and mode of operation (heating or cooling). Well-designed displacement ventilation air distribution systems have a ventilation effectiveness that are at least = 1.2 and have the potential for greater ventilation effectiveness when used in combination with dedicated outdoor air systems and radiant heating/cooling systems. Table 1 shows data collected by Krantz for the ventilation effectiveness of various types of air distribution systems. Displacement diffusers are shown in the Krantz laboratory to have ventilation effectiveness higher than that of a fully mixed system. Green Tip Using displacement ventilation for schools is a great way to increase the ventilation effectiveness, indoor air quality of the space. CHPS credit EQ2.1: Thermal Displacement Ventilation is a two point credit for the use of displacement ventilation in the building. Also, both LEED and Green Globes have IAQ credits for the implementation of displacement ventilation.
Green Tip The high ventilation effectiveness from a properly designed displacement ventilation system can earn credits in Green Globes and LEED rating systems for higher indoor air quality.
Green Tip The Green Building Initiatives: Green Globes v.1 section 7 G.1.3 requires the zone distribution effectiveness Ez value to be greater than 0.9, and proven with ASHRAE 129-1997 (12 points possible). This is achievable with a properly designed displacement system.
Table 1: Ventilation Effectiveness for Different Types of Air Distribution Systems [Source: Krantz]
Measurement point in room In front of standing person In front of seated person Linear Displacement 1.2 1.6 Ceiling Outlets Floor Twist Outlets 1.2 1.65 Twist Outlets 0.88 0.96 Slot Outlets 0.93 0.97
1.3 1.95
1. 3 2.0
0.90 0.97
0.92 0.96
DISPLACEMENT VENTILATION
J-14
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-15
DISPLACEMENT vENTILATION
Humidity Control
Humidity control is extremely important and exists in most climates, not just the traditional hot and humid climates. Controlling humidity is the most common question when discussing the concepts of underfloor air distribution, or displacement air distribution. Controlling humidity means different things to different people as their personal perspectives are different. In the office environment, humidity control means limiting the upper humidity level to the guidelines of ASRHAE Standard 55 in order to provide good thermal comfort. Museums often need humidity levels to be maintained in a narrow range to slow or prevent decay in artwork and historical displays. Temperature control is automatically part of a building HVAC equipment design, while humidity control is not always automatically included in buildings located in areas that are not considered hot and humid. If humidity control is included, it may only be to maintain a humidity level that does not exceed the recommended upper limit of ASRHAE Standard 55. In fact, most buildings experience a drift of humidity levels from hour to hour. Building Shells Are Sources of Humidity All buildings leak air through the building shell. In a humid climate, the amount of leakage is directly related to how much energy must be expended to control the humidity level in the interior spaces. The ASRHAE Humidity Control Design Guide for Commercial and Institutional Buildings encourages designers to think of buildings as very leaky refrigerators . This is an accurate analogy as most tight constructed buildings have been determined to leak around a minimum of one air changes in three hours. Poorly constructed buildings may experience two air changes an hour, or more. This leakage is a direct transfer of moisture into or out of the interior zones and needs to be accounted for in the building moisture loads. When an open plenum return is used in an exterior zone, the HVAC designer must take care to prevent negative pressurization in the plenum space.This negative pressurization can and will cause air to infiltrate through the building walls and will provide a transport of moisture from the outside if the outside environment has more moisture in the air than the interior does.The best solution to this issue is to use ducted returns. In an effort to minimize the ductwork in an underfloor or displacement designed building, the returns should be placed close to the air handling equipment, or duct chases. Design Suggestions The HVAC designer is responsible for the control of humidity levels and his selection of equipment will make or break the design. Although there are many factors which will affect the control of humidity in the space, this discussion will focus on major issues and make some recommendations that will assist in building design. Pretreat Ventilation Air In a humid climate, the biggest source of moisture is typically the ventilation air from the outside. This typically accounts for about 50 to 80% of the building moisture load in typical commercial buildings. It is entirely likely that when this ventilation air is pretreated for humidity control, the entire building humidity load will be controlled without any additional moisture removal. Figure 29A illustrates one approach for humidity control commonly known as Side-Stream Bypass. The cooling coil is operated to produce 50-55F leaving air temperature for dehumidification. A portion of the return air is bypassed before the coil and mixed with the conditioned air to achieve proper temperature and humidity prior to delivery to the displacement diffuser. Only the outdoor air and a part of the return air are actually directed through the coil. This moisture control of the outside air will require the outside air to be cooled to a temperature below the dewpoint. In an underfloor or displacement air distribution system that will mean the supply air temperature from the air handling equipment will be significantly lower than the recommended design supply zone air temperatures. The air will need to be reheated to prevent occupant dissatisfaction from the temperature of the supply air. Designers typically size the cooling coils on peak sensible load (the hottest part of the weather cycle). Unfortunately, the peak latent load is typically not connected to the peak sensible load. This means that the total load (sensible + latent) may peak when the outdoor dew point temperature is the highest, not the dry bulb temperature. Another option for humidity control is the series type fan powered terminal (Figure 29B). In this application the primary air is cooled to 55F or less at the air handler to provide dehumidification. The fan terminal is used to increase the supply air temperature to an acceptable level before entering the zone. Conditioned air is supplied to the primary valve of the terminal via a supply duct. Return air is induced into the return air opening from the return air plenum. The fan delivers a constant air volume to the zone. The proportion of primary and return air is controlled to maintain a supply air temperature above 63F .
DISPLACEMENT VENTILATION
J-16
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Humidity Control
Direct Expansion Roof Top Units DX packaged roof top units may be used to condition raised floor cavities and displacement ventilation. However, care must be exercised to select the proper sized equipment and controls to maintain moisture removal. The issue is that at part-loads, the coil temperature is often raised to prevent sub-cooling the zone. This means that not enough moisture will be removed by the cooling coil which will allow the humidity levels to rise in an uncontrolled manner. Simply sizing the coil for the highest total load will not prevent this issue in latent capacity if the control is based upon only the zone dry-bulb temperature and not also the humidity level. Control Tip When a DX system is oversized, the compressors will remove the cooling load with very little cycle time.Then the compressors shut down and the moisture on the coil will re-evaporate and be added to the air. Additionally, the ventilation air is still required and will also transport moisture into the zone. The net effect is a humid occupied zone. Dedicated Dehumidification and Energy Recovery When the exhaust air exits the building at the same point as the supply air enters, a heat exchanger can be used to provide reheat to the supply air which will reduce the load on the equipment to provide the suggested supply air temperatures for underfloor and displacement air distribution. When moisture loads are high, it is often cost effective to use separate dehumidification equipment such as an active Desiccant Dehumidifier (dry wheel, or liquid system), or a Mechanical Dehumidifier (condenser and evaporator coils in the air stream). Dehumidification Dehumidification is actually quite simple. Merely place enough dry air into the building space to absorb the excess humidity. Having said that, the issues complicated in that many different methods exist to take the moisture out of the air and many difficulties exist in the control of this equipment. ASHRAE has several recommendations for dehumidification of a building: Dry the ventilation air first as the bulk of the moisture load in buildings is due to the ventilation air. Lower the design dewpoint and raise the interior set point dry bulb temperature. When the occupants of a building are in a dry climate, RH < 45%, they will have the same perceived comfort level at 78F as they would at 74F and 50% RH. Interestingly, most people find the dryer and warmer combination more comfortable. Downsize the cooling equipment and use a dehumidifier. If the cooling system is not required to remove latent loads, it can typically have a smaller cooling capacity. This will raise the overall efficiency of the HVAC system and allow for more localized cooling in high sensible loadings such as call centers. This is a great approach for the use of fan air columns in a raised floor application. Remember to analyze the dehumidification cycle at the peak moisture removal load as well as the peak temperature point. Load Reduction Equipment It is outside the scope of this design guide to provide design criteria for the many different types of energy recover/load reduction equipment available on the HVAC market today. Several different systems that maybe appropriate for the building design are: Passive Desiccant Wheels these wheels can transfer between 10 and 90% of the heat and moisture difference between two air streams. These wheels do not use heated air to remove the moisture, but rely upon dry air. Active Desiccant Wheels these wheels use heated air to remove the moisture from the desiccant and can deeply dehumidify the air as a result. Heat Pipes these are often used to improve the operation of desiccant or mechanical dehumidifiers. They are sealed tubes that contain some liquid and a gas a low pressure. The liquid in the bottom of the tube will boil at low temperatures (cooling the air outside the tube) and drift upward where it will condense and reheat heat (heating the air outside the tube).These heat pipes are usually capable of transferring between 45 and 60% of the temperature difference between two air streams. Plate Heat Exchangers hot and cold air streams are separated by thin plates and the air passes through the exchanger in an x or z pattern. Plate heat exchangers are usually able to transfer between 60 and 65% of the temperature difference between the two air streams. Economizer Cycle For free-cooling , an economizer cycle is typically used. Unfortunately, most are merely temperature controlled and may not prevent humidity control issues year the entire year. Enthalpy control is often used, but do not always solve this issue. The theory for enthalpy control is to use outdoor air when the total heat outdoors (the enthalpy) is lower than the total heat inside. This approach does not consider the difference in dew points between inside and outside. Air with a lower enthalpy from the outside may contain more moisture than is desired in the space. It is recommended that all economizer cycles are set so that the outdoor air is never used when the outdoor dewpoint is higher than the interior dew point design point.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-17
DISPLACEMENT vENTILATION
Acoustics
Acoustics Considerations There are typically at least five primary sources of sound generation in a displacement ventilation application: fan powered terminals; control valves; diffusers; air-handling equipment and structuralborne sound. Fan Powered Terminals The first and most commonly considered is the sound generated by fan powered terminals. Fan powered terminals use either a PSC (permanent split-capacitor) motor or an ECM (electronically commutated motor) to drive a blower for VAV applications. These devices typically produce low to mid frequency sound energy which, if not properly accounted for and treated, may cause discomfort to the space occupants. The sound energy generated by terminals may be transmitted by three transmission paths into the occupied space: discharge sound from the terminal outlet through the ductwork and out the diffuser; and radiated sound from the terminal/induction opening (if present) directly through the ceiling or floor tile and by vibration energy from the fan/motor through the casing into the ceiling support structure or floor slab. Manufacturers (including Price Industries) who participate in the Air-Conditioning and Refrigeration Institute (ARI), terminal certification program (ARI 880) are required to calculate NC (noise criteria) values using predetermined sound transmission path attenuation factors in the ARI 885-98 Standard, Appendix E. Terminals Discharge Sound Transmission As long as the duct downstream from the terminal is lined, there will be some sound energy attenuation. The level of sound attenuated depends upon the ductwork configuration. The ARI 885-98 Standard attenuation factors used to estimate the NC values in the tabulated data for Price terminal units is based upon five feet of lined duct work, five feet of flex duct, space effect and flow division. A copy of the ARI 880 and 885 Standards may be downloaded at no cost from www.ari.org. Diffusers The second most commonly considered is the sound generated by the air outlet. Interestingly, they are typically not at fault for any sound generation issues other than perhaps direct radiated sound transmission from a terminal or a control valve located near the diffuser inlet. An example of diffuser noise is shown in Table 2.
10
0 SMALL OFFICE -10 LECTURE HALL -20 AUDITORIUM -30 ARENA -40 -50 -60 1 3 10 30 100 300 1000
Product Tip To estimate the actual NC values present in the design space, the Price Quick Select program for terminals may be used with the attenuation factors shown inTables 1 and 2. This program uses the data in the ARI 885-98 Standard and allows the user to build their ductwork configuration. Table 2: Sample Performance Data for a DF3
Unit Size [Face Area, ft] WxHxD 24 x 24 x 13 [7.7] Face Velocity FPM 20 30 40 50 Total Static Pres- Noise Pressure sure Criteria in.wg. in.wg. NC 0.02 0.04 0.06 0.01 0.02 0.03 7
DISPLACEMENT VENTILATION
J-18
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Acoustics
Diffusers Air Movement Generated Sound Largely due to their low pressure drop, displacement diffusers do not typically have NC values above NC 30. The NC values for the diffusers are calculated using ASHRAE Standard 70. See Table 2, on the previous page, for NC levels associated with a DF3 displacement outlet. The left column indicates the NC levels lower than 15 as ---, and shows the quiet nature of displacement diffuser. ASHRAE Standard 70 assumes that all diffusers are discharging air into a typical space that will experience a sound absorption of 10dB in all bands. The tabulated NC values may be corrected for the type of space in your design by using the formula below and the SEF factor from Table 3. Catalog NC = Room NC 10 + SEF 10*log10N Where: Room NC is the design goal SEF is the correction factor from Figure 1 N is the # of outlets in the space Example: Private Office space (Design NC = 30). 10 ft x 10 ft with 2.5 CFM/SF (295 CFM) From Figure 1, the SEF = 5. Number of supply diffusers is 1 (250 CFM) and the number of return diffusers is 1. Catalog NC = 30 10 + 5 10*log10(1+1) Catalog NC = 22 DF1 Diffuser (48x24x13) at 295 CFM generate an NC values < 15 NC. The return grill would be selected to have an NC values of 19 or less as well. Table 3: Suggested Discharge Sound Attenuation (dB) (see ARI 885-98 Standard for basic values and methodology used). Octave Band mid Frequency, Hz Component Description
Lined Discharge Duct with flex duct (see note a) Unlined Discharge Duct with flex duct (see note b) NO flex duct Lined Metal Duct (see note c) NO flex duct Unlined or Solid Metal Duct (see note d) Small Terminal < 300 CFM Med. Terminal 300 to 700 CFM Large Terminal > 700 CFM Small Terminal < 300 CFM Med. Terminal 300 to 700 CFM Large Terminal > 700 CFM Small Terminal < 300 CFM Med. Terminal 300 to 700 CFM Large Terminal > 700 CFM Small Terminal < 300 CFM Med. Terminal 300 to 700 CFM Large Terminal > 700 CFM
125
24 27 29 22 25 27 18 21 23 16 19 21 24 27 29 22 25 27 18 21 23 16 19 21
250
28 29 30 22 25 27 18 19 20 12 15 17 28 29 30 22 25 27 18 19 20 12 15 17
500
39 40 41 27 30 32 21 22 23 9 12 14 39 40 41 27 30 32 21 22 23 9 12 14
1000
53 51 51 28 31 33 33 31 31 8 11 13 53 51 51 28 31 33 33 31 31 8 11 13
2000
59 53 52 30 33 35 38 32 31 9 12 14 59 53 52 30 33 35 38 32 31 9 12 14
4000
40 39 39 22 25 27 28 27 27 10 13 15 40 39 39 22 25 27 28 27 27 10 13 15
8000
28 30 32 18 21 23 21 23 25 11 14 15 28 30 32 18 21 23 21 23 25 11 14 15
Product Tip These NC calculations are based on a ceiling present. If you do not have a ceiling, you must correct for that lack of absorption. Please consult an acoustician for assistance with this issue.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-19
DISPLACEMENT vENTILATION
Note a: based on 5ft lined duct (1in liner); 8 inch branch duct with 5ft of flex duct, occupant distance from sound sources of 5ft and 1 diffuser. Note b: based on 5ft unlined duct; 8 inch branch duct with 5ft of flex duct, occupant distance from sound sources of 5ft and 1 diffuser. Note c: based on 5ft lined duct (1in liner); 8 inch branch duct with 8 inch round solid metal duct (unlined), occupant distance from sound sources of 5ft and 1 diffuser. Note d: based on 5ft unlined duct 8 inch branch duct with 8 inch round solid metal duct (unlined), occupant distance from sound sources of 5ft and 1 diffuser.
Figure 32: Variable Frequency Drives [source: Siemens Building Technologies Ltd.]
DISPLACEMENT VENTILATION
J-20
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
1ft 1ft 6 ft
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-21
DISPLACEMENT vENTILATION
Convection
Radiation
J-22
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Diffuser Type
A wide variety of displacement air diffuser types are available to suit the location restrictions and dcor of a particular room or space. In some cases the diffusers are custom fabricated to meet an areas unique architectural design. Some common displacement diffuser types are described as follows: 1. Rectangular Units Rectangular units are typically placed against a wall or partition. If only the face of the unit is active, a one-way pattern is produced as seen in Figure 38. If both the face and sides are active, a three-way pattern results (Figure 39). The three-way diffuser has a higher air volume capacity than the one-way. Diffuser inlets are usually at the top of the unit, although bottom or rear inlets are available. One version of the rectangular units is designed to be integrated into the wall (Figure 40). A narrow plenum and rectangular inlet are characteristic of this design. Another version of a rectangular unit has no plenum or inlet and is designed for plenum feed applications. These units can be mounted in a stair riser, wall, cabinet, etc. and are supplied with a field fabricated plenum shown in Figure 41. 2. Corner Units Corner units are specifically designed to fit into a 90 corner in a room. Supply inlets can be located at the top or bottom of the unit. Flat or circular faces are available depending on the desired look. A 90 radial pattern is produced by corner units (Figure 42).These diffusers are ideal for applications where wall space may be limited as corners are available for use. 3. Displacement Linear Enclosure Linear enclosure can act as both a supply diffuser and as a heating source. These enclosure are suited for perimeter locations. As a heating source they are designed so that the heating element does not interfere with the air temperature or air flow patterns (Figure 43). Figure 38: One-Way Diffuser Figure 39: Three-Way Diffuser
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-23
DISPLACEMENT vENTILATION
Diffuser Type
4. Semi-circular Units Shown in Figure 44 Semi-circular units are typically placed against a wall or pillar. Supply inlets can be located at the top, bottom or rear of the unit. A 180 radial pattern is produced. 5. Circular Units Circular units can supply high volumes of air to a space because the air is distributed in a complete 360 radial pattern (Figure 45). The supply inlet can be located at the top or bottom of the units. Circular units are typically placed free-standing in large interior spaces such as halls, lobbies, walkways, lounges, etc. 6. Floor Mounted Units Displacement diffusers are available for integration with a raised floor distribution system. The round floor displacement unit produces a low velocity radial pattern across the floor as seen in Figure 46. The floor mounted grilles can provide a linear pattern from the grille face. Displacement floor grilles can also be fan assisted (Figure 47) when additional air volumes are required and a fan terminal is not economical. 7. Industrial Diffusers For the industrial environment diffusers need to be able to withstand impact from moving equipment, or able to be mounted above the working space and designed to supply air deep into the space (Figure 48). The Price industrial flat diffuser is intended to be placed on the industrial floor space and provide supply air.The robust design allows this diffuser to withstand the impact forces common to the industrial sector.The Krantz line of industrial diffusers are designed to be mounted above the occupied zone, and have integrated heating and cooling supply air modes. Figure 44: Semi Circular Diffuser Figure 45: Circular Diffuser
DISPLACEMENT VENTILATION
J-24
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
30 ft
15 ft
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-25
DISPLACEMENT vENTILATION
Mounting Plate
DISPLACEMENT VENTILATION
J-26
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Overhead Lighting
Actual zone air flow rate is the maximum of the cooling air flow and the ventilation rate. The supply air temperature is calculated from:
Where the temperature difference between head and foot is given by:
and:
Using r and cf = 0.95 BTU/h*ft*F from ASHRAE fundamentals. The exhaust air temperature can be calculated from:
J-27
DISPLACEMENT vENTILATION
Where:
Design Procedure
The following step by step design procedure is offered as a simplified approach to determine ventilation rate and supply air temperature for typical displacement ventilation applications. The procedures presented are based on the findings of ASHRAE Research Project RP-949 and the procedure outlined in the ASHRAE Design Guide. For a complete explanation and derivation of the assumptions and equations used to develop this procedure, please refer to the ASHRAE Design Guide.The design procedure applies to typical North American office spaces and classrooms. These procedures should be used with care when applied to large spaces such as theaters or atria, a computational fluid dynamic analysis (CFD) of large spaces is recommended to optimize the air supply volume. Only the sensible loads should be used for the preceding calculations. These calculations are only for determining the airflow requirements to maintain the set point in the space, the total building load remains the same as with a mixing system. Step 1: Determine the Summer Cooling Load Use a cooling load program or the ASHRAE manual method to determine the design cooling load of the space in the summer. If possible, assume a 1F/ft. vertical temperature gradient in the space in the computer simulation as the room air temperature is not uniform with displacement ventilation. Itemize the cooling load into the following categories: The occupants, desk lamps and equipment, Qoe (Btu/h) The overhead lighting, Ql (Btu/h) The heat conduction through the room envelope and transmitted solar radiation, Qex (Btu/h).
DISPLACEMENT VENTILATION
Step 3: Determine Flow Rate of Fresh Air Standard 62-2004 Ventilation Rate Procedure includes default values for ventilation effectiveness. From standard 62-2004: Equation 6-1 is used to determines the Breathing Zone Outdoor Air Flow Vbz and Equation 6-2 Is used to determine the Zone Outdoor Air Flow Voz
where Ez = 1.2 for displacement ventilation per Table 6.2 . Step 4: Determine Supply Air Flow Rate Choose the greater of the required flow rate for summer cooling and the required ventilation rate as the design flow rate of the supply air,
Step 5: Determine Supply Air Temperature The supply air temperature can be determined from the ASHRAE Design Guide equations and simplified to:
Step 2: Determine the Cooling Load Ventilation Flow Rate, Vh The flow rate required for summer cooling, using standard air, is:
Step 6: Determine Exhaust Air Temperature The exhaust air temperature can be determined by the following method:
Step 7: Selection of Diffusers The goal is to maximize comfort in the space and minimize the quantity of diffusers. At a maximum, ASHRAE suggests a 40 fpm face velocity, but this value may increase or decrease depending on the space and comfort requirements. A CFD simulation can validate the design and is recommended for larger spaces, contact your local Price representative about CFD modeling.
J-28
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Occupants Set Point Floor Area Exterior Wall Area Volume Qoe Ql Qex QT
2 72 F 120 ft 90 ft 1080 ft 1012 BTU/h 819 BTU/h 450 BTU/h 2281 BTU/h
The loads are broken down as follows: Qoe = (2 People X 250 BTU/h) + 308 BTU/h = 808 BTU/h Ql = 120 ft X 6.82 BTU/h/ft = 819 BTU/h Qex = 90 ft X 5 BTU/h/ft = 450 BTU/h QT = 2077 BTU/h Total cooling load for this space (QT) is 2077 BTU/h, and approximately 17.31 BTU/h/ft. ASHRAE Standard 62-2004 requires 0.06 CFM/ft outdoor airflow rate required per unit area, Ra, and 5 CFM/Person outdoor airflow rate required per person, Rp, be delivered to the space for moderately active office work applications. For displacement ventilation a ventilation effectiveness, or zone air distribution effectiveness (Ez), assumed to be 1.2 (table 6-2, ASHRAE Standard 62-2004).
DISPLACEMENT vENTILATION
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-29
Determine the Fresh Air Flow Rate and Breathing Zone Ventilation Effectiveness
Note: Some local codes may not allow the discount for VE, or may have stricter requirements, and they should be used instead of this calculation. Example: Title 24 in California. The total supply air volume for cooling is then the maximum value between Vh and Vr.
DISPLACEMENT VENTILATION
J-30
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Flow Visualization A CFD analysis was run for this example using the conditions, calculated airflow and supply air temperature for the small office with the DF1W to give a visual representation of the temperature distribution, air movement, and draft temperatures in the space. Figure 57 shows the temperature profiles across the space. The DF1W produces the predicted temperature stratification in the space. Also visible are the heat plumes off of the occupants and computer. The seated occupant is experiencing ambient air temperatures from 69 to 72 F , and the standing occupant 69 to 75 F . Both are within the thermal stratification comfort conditions set by ASHRAE. Figures 58 and 59 depict the velocity profiles. From the velocity profile images, slow moving air is visible throughout the space. The images also show the plumes off of the occupants and computer as well as the general shape of the air pattern leaving the diffuser. Figure 60 shows the predicted draft temperature for the space. The range in which people will feel the most comfortable, is indicated in green. The DF1W diffuser seems to produce a thermally comfortable environment, and reiterates that occupants need to be located at an appropriate distance from the diffuser. Figure 57: DF1W Temperature Profile Figure 58: DF1W Velocity Profile
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-31
Boardroom Example
Space Design The owner of a new office building wants to use a displacement ventilation system for all occupied spaces. This example examines a private boardroom that is located in the center of the building without any exterior surfaces. The space is designed for 8 occupants, a computer with LCD monitor, a projector, T8 florescent lighting, and has a control temperature of 72F . The room is 24 ft wide, 14 ft long, and 10 ft from floor to ceiling. There is a large white board at the west end of the room and cabinets along the south and east end of the room. The owner and architect want the displacement diffusers in the space to fit seamlessly into the room. Space Considerations The head to foot gradient recommended by ASHRAE is 3.6F from head to foot for seated occupants. Some of the assumptions made for the space are as follows: Load per person is 250 BTU/h Lighting load in the space is 6.82 BTU/h/ft Computer and LCD load is 308 BTU/h Projector load is 188 BTU/h The specific heat and density of the air or this example will be 0.24 BTU/lbF and 0.075 lb/ft respectively. Occupants Set Point Floor Area Volume Qoe Ql Qex QT The loads are broken down as follows: Qoe = (8 People X 250 BTU/h) + 308 BTU/h + 188 BTU/h = 2496 BTU/h Ql = 336 ft X 6.82 BTU/h/ft = 2294 BTU/h Qex = 0 BTU/h QT = 4790 BTU/h Total cooling load for this space (QT) is 4790 BTU/h, and approximately 14.26 BTU/h/ft. ASHRAE Standard 62-2004 requires 0.06 CFM/ft outdoor airflow rate required per unit area, Ra, and 5 CFM/Person outdoor airflow rate required per person, Rp, be delivered to the space for moderately active office work applications. For displacement ventilation a ventilation effectiveness, or zone air distribution effectiveness (Ez), is assumed to be 1.2 (table 6-2, ASHRAE standard 62-2004). 8 72 F 336 ft 3360 ft 2496 BTU/h 2294 BTU/h 0 BTU/h 4790 BTU/h
DISPLACEMENT VENTILATION
J-32
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Boardroom Example
Determine the Airflow Rate to meet the Cooling Load
Determine the Fresh Air Flow Rate and Breathing Zone Ventilation Effectiveness
Note: Some local codes may not allow the discount for VE, or may have stricter requirements, and they should be used instead of this calculation. Example: Title 24 in California. The total supply air volume is then the maximum value between Vh and Vr.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-33
DISPLACEMENT vENTILATION
Boardroom Example
Selection of Diffusers For this application we have three goals set by the owner: 1. Quiet operation 2. Thermal comfort to the space 3. Diffusers must be hidden Inherently, displacement ventilation diffusers are quiet, but care has to be taken to limit the sound generated from the HVAC air supply. Price recommends limiting the duct velocity to 1200 fpm, to minimize noise from ductwork. For thermal comfort a face velocity of 40 fpm is required. At 126 CFM a diffuser face area of 6.68 ft would be required. To make these diffusers as unobtrusive as possible there a two options; mount them in the wall, or as part of the furniture. Layout of the Boardroom For a concealed look, the DF1R displacement diffuser could be installed at the base of the cabinets, or in the wall under the whiteboard in a pressurized plenum. Two diffusers at 60x8 will be able to meet the 40 fpm requirement. The diffusers can be placed on any of the walls in the room, but they must ensure that sedentary occupants will be located at least 2 feet from the diffuser.
Flow Visualization A CFD analysis was run for this example using the conditions, calculated airflow and supply air temperature for the small office with the DF1W to give a visual representation of the temperature distribution, air movement, and draft temperatures in the space. Figure 61 shows the temperature profiles across the space and a reasonable temperature stratification is predicted. Also visible are the heat plumes off of the occupants and computer. The seated occupant is experiencing ambient air temperatures from 69 to 72 F , and the standing occupant 69 to 75 F . Both are within the thermal stratification comfort conditions set by ASHRAE. Figures 62 depict the velocity profile. The images show the plumes off of the occupants and computer as well as the general shape of the air pattern leaving the diffuser and slowly entering the zone. Figure 63 depicts the draft temperature for the space. Again, the range in which people will feel the most comfortable is indicated in green. The DF1R diffusers produce a thermally comfortable space. Figure 61: DF1R Temperature Profile Figure 62: DF1R Velocity Profile
DISPLACEMENT VENTILATION
J-34
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-36
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
The loads are broken down as follows: Qoe = (35 People X 375 BTU/h) + (33880 + 64390 + 31050 + 38180 + 30436 + 56610) BTU/h = 267671 BTU/h Ql = 7920 ft X 10.234 BTU/h/ft = 81053 BTU/h
DISPLACEMENT vENTILATION
Qex = (2670 ft X .045 BTU/h/ftF X 18F) + (7920 ft X .031 BTU/h/ ftF X 18F) = 6582 BTU/h QT = 355306 BTU/h Total cooling load for this space (QT) is 355306 BTU/h, and approximately 44.86 BTU/h/ft. ASHRAE Standard 62-2004 requires 0.18 CFM/ft outdoor airflow rate required per unit area, Ra, and 10 CFM/Person outdoor airflow rate required per person, Rp, be delivered to the space machine shop applications. For displacement ventilation a ventilation effectiveness, or zone air distribution effectiveness (Ez), assumed to be 1.2 (table 6-2, ASHRAE standard 62-2004).
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-37
Determine the Fresh Air Flow Rate and Breathing Zone Ventilation Effectiveness
Note: Some local codes may not allow the discount for VE, or may have stricter requirements, and they should be used instead of this calculation. Example: Title 24 in California. The total supply air volume for cooling is then the maximum value between Vh and Vr.
DISPLACEMENT VENTILATION
J-38
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
In this example, diffusers are placed on the columns, to keep the floor area clear.The entire floor surface must be serviced by the diffusers, so an appropriate adjacent zone must be selected. To provide the proper floor coverage an adjacent zone of 20 feet is selected. The 14 diameter diffuser provides the 20 feet adjacent zone for the smallest pressure drop and noise level at 1165 CFM. For the 14025 CFM the space requires a total of 12 diffusers, each with a supply air volume rate of 1169 CFM. For further instructions on heating mode operation see the industrial diffusers section of this design guide. Layout of the Shop The diffusers should be mounted on columns evenly throughout the space about 9 feet above floor level. For the diffusers with heat/ cool changeover, the Bowden cable should be mounted in close proximity to the diffuser and needs to be accessible to the occupants. As with commercial applications, returns should be located as high as possible in the space.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-39
DISPLACEMENT vENTILATION
Performance Notes: 1. The maximum supply air penetration depth for floor mounted diffusers when cooling largely depends on the number and intensity of the heat sources. Under normal circumstances a max supply air penetration of 32 ft with 10 inch unit and 82 ft with 25 inch unit.
DISPLACEMENT VENTILATION
J-40
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Benefits from a Displacement Ventilation System As described throughout this design guide, there are several benefits to applying a displacement type system to commercial spaces. The major benefits are: Longer Free Cooling periods due of higher supply air temperatures Lower System Pressure Requirements Higher indoor air quality Improved thermal comfort Low noise generation from diffusers These benefits correlate to the cost of running a building as well as the health and well being of the occupants. In certain markets, the longer free cooling periods allow for an economizer to run longer during the day, leading to a lower operating equipment cost of the building. As well, the lower system pressure can allow for a reduction in the size of the fan or motor driving the fan to that zone, which will lead to lower energy consumption for the building during operation. In a displacement ventilation system, the natural thermal plumes of each occupant drive the movement of air, and each person is delivered the amount of cooling that they require.Because this air has not been mixed with room air the air moving up the occupant is cool and unpolluted. This results in a stratified environment, with fresh, cool air at the lower portions and warm, polluted air a high level in the space. This leads to the high indoor air quality, as the occupants thermal plumes dictate the required amount of air delivered to the occupant.These benefits have been translated into cost savings, in a 2006 report by Gregory Kats at Capital E, the thermal comfort and air quality of schools were presented as a dollar and performance value. Furthermore, this report collected the findings of various researchers demonstrating the reduction in transmission of airborne illnesses. Figures 72 and 73 show these reductions by increasing the ventilation rate and applying pollutant source controls, respectively.
87.3% Flu
67.0% SBS
46.0% Resipatory 35.0% SBS 33.6% SBS 33.0% SBS 20.0% Resipatory
Drinka et al 1996
Jaakkda Brundage Bourbeau Fisk & et al & et al Rosendfeld 1985 1997 Miettinen 1995 1995
Sundell 1996
85.0% Colds
23.6% Asthma
Wieslander et al 1997
Jaakkda et al 1994
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-41
DISPLACEMENT vENTILATION
100%
Rp = outdoor airflow rate required per person by space Pz = zone population Ra = outdoor airflow rate required per area by space Az = zone area Ez = zone air distribution effectiveness Voz is the required outdoor air flow rate The zone ventilation effectiveness is approximately 1.0 for an ideal overhead air distribution system, and conservatively estimated to be 1.2 for a displacement ventilation. A displacement ventilation system will require at least 20% less outdoor air than a overhead mixing system, so a system designed with displacement ventilation will require less outdoor air to increase the performance within schools. Product Tip The DFXi Industrial Displacement Diffuser , shown in Figure 74 is a more robust diffuser and can be incorporated into a commercial design. This is desirable in spaces such as gymnasiums and high traffic areas such as hallways and foyers. See the industrial displacement ventilation product section for further detail. The low noise levels generated by a displacement system is also a desirable feature for school applications. Spaces such as auditoriums, band rooms, libraries or any space that demands acoustical performance are the perfect application for this quiet system.
DISPLACEMENT VENTILATION
J-42
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Classroom Example
The Space Design The local school board is looking for ways to improve the IAQ of the classrooms, as is has been shown to increase student performance and reduce absenteeism.They want to use displacement ventilation in the spaces due to a recognized increase in ventilation effectiveness while ensuring comfort within the rooms. This example examines a typical classroom in this school. The classroom is designed for 25 children and 1 teacher, three computers with LCD monitors, T8 florescent lighting, and has a control temperature of 74F . The room is 25 ft wide, 30 ft long, and 10 ft from floor to ceiling level. There is one exterior wall, facing NW, with 100 ft of window, and the room has an exposed ceiling. The Space Considerations As previously discussed, ASHRAE standard 55-2004 stipulates the maximum combination of velocity and temperature in the occupied zone, ppd due to draft, as well as the stratification in the space. In a classroom, the occupants tend to be seated throughout the majority of the day; the stratification for a sedentary seated person according to ASHRAE standard 55-2004 is 3.6F . Some of the assumptions made for the space are as follows: Load per person is 250 BTU/h Lighting load in the space is 6.826 BTU/h/ft Computer loads are 308 BTU/h each Average Solar/Conduction load through the exterior wall is 14.6 BTU/h/ft The specific heat and density of the air or this example will be 0.24 BTU/lbF and 0.075 lb/ft respectively Occupants Set Point Floor Area Exterior Wall Volume Qoe Ql Qex QT The loads are broken down as follows: Qoe = (26 People X 250 BTU/h) + (3 Computers X 308 BTU/h) = 7424 BTU/h Ql = 750 ft X 6.826 BTU/h/ft = 5120 BTU/h Qex = 300 ft X 14.6 BTU/h/ft = 4381 BTU/h QT = 17044 BTU/h Total cooling load for this space (QT) is 16925 BTU/h, and approximately 22.6 BTU/h/ft. ASHRAE Standard 62-2004 requires 0.12 CFM/ft outdoor airflow rate required per unit area, Ra, and 10 CFM/Person outdoor airflow rate required per person, Rp, be delivered to the space for classroom applications. For displacement ventilation a ventilation effectiveness, or zone air distribution effectiveness (Ez), is assumed to be 1.2 (table 6-2, ASHRAE standard 62-2004).
DISPLACEMENT vENTILATION
26 74 F 750 ft 300 ft 300 ft 7500 BTU/h 7424 BTU/h 4381 BTU/h 17044 BTU/h
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-43
Classroom Example
Determine the Airflow Rate to meet the Cooling Load
Determine the Fresh Air Flow Rate and Breathing Zone Ventilation Effectiveness
Note that some local codes may not allow the discount for VE, or may have stricter requirements, and they should be used instead of this calculation. Example: Title 24 in California. The total supply air volume is then the maximum value between Vh and Vr.
DISPLACEMENT VENTILATION
Selection of Diffusers Because floor space is limited in a classroom, and wall space is typically covered with teaching material, either a ceiling mounted or corner mounted diffuser would be the ideal diffuser choice. As stated in previous examples, for comfort reasons, the diffusers for this space are limited to 40 fpm. With a supply air volume of 946 CFM and a face velocity of 40 fpm, 23.65 ft of diffuser face is required. Three 30x 42 DFIC corner diffusers will supply 946 CFM at 36.0 fpm, and occupants will need to be located at least 2 feet or more from the diffuser.
J-44
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Classroom Example
Layout of the Classroom The corner diffusers could be placed in any of the corners to supply this room, as long as the occupant is not within 2 feet of the diffuser face. CFD Representation of the Space A CFD analysis was run for this example using the conditions, calculated airflow and supply air temperature with the DF1C selected in the example for a visual representation of space dynamics. Figure 75 shows the temperature profile in the space. The DF1Cs function as predicted and creates an even stratification in the space. The seated occupants are experiencing the desired set point and the stratification in the space is not outside the comfort criteria. Figure 76 shows the temperature profile in the space with a isoplane showing the set point temperature of the space. All of the occupants are near or within the desired temperature, but at full load in the space, some over cooling may occur. Figure 77 shows the velocity profile in the space. The DF1Cs produces a prominent air pattern predicted to be up to 60 feet per minute, shown in red on the floor. Figure 78 shows the draft temperature profile in the space. The DF1C diffusers create the appropriate stratification in the space, but placement of the diffuser with respect to the occupants is critical. There is a prominent uncomfortable space directly in front of the diffusers. Figure 75: Temperature Profile Figure 76: Temperature Profile with a 74 F Isoplane
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-45
DISPLACEMENT vENTILATION
J-46
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Table 8: Waiting Room Comfort Test Method Supply CFM Supply ACH SA Temp OP Temp RA Temp Air Velocity, FPM PPD % 1 DV 1800 12 65 70 74 10 to 46 10 to 20 2 DV 1200 8 64 71 74 12 to 34 5 to 14 3 DV 900 6 65 72 76 12 to 30 5 to 12
DISPLACEMENT vENTILATION
Table 9: Waiting Room Vent Eff Test Method Supply CFM Vent Eff 1 Ceiling 1800 0.9 2 DV 1200 1.1 3 DV 900 1.0
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-47
DISPLACEMENT VENTILATION
J-48
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
References
1. 2001 ASHRAE Fundamentals Handbook, Space Air Diffusion, Chapter 32.11 2. Hakon Skistad, Displacement Ventilation, 1994, Control of the Built Environment series; 1, John Wiley & Sons Inc., England. 3. Hakon Skistad, Elisabeth Mundt, Peter Nielsen, Kim Hagstrom, and Jorma Railio, Displacement Ventilation in Non-Industrial Premises, Rehva Guidebook No 1, Federation of European Heating and Air Conditioning Associations, 2002. 4. Qingyan Chen and Leon Glicksman, Performance Evaluation and Development of Design Guidelines for Displacement Ventilation, Final Report to ASHRAE on Research Project RP-949. 5. Shiping Hu, Qingyan Chen, Leon Glicksman, Comparison of Energy Consumption between Displacement and Mixing Ventilation Systems for Different U.S. Buildings and Climates, ASHRAE Transactions 1999, V. 105, Pt. 2. 6. Xiaoxiong Yuan, Qingyan Chen and Leon Glucksman, A Critical Review of Displacement Ventilation, ASHRAE Transactions 1998 V. 104, Pt. 1. 7. Xiaoxiong Yuan, Qingyan Chen and Leon Glucksman, Performance Evaluation and Design Guidelines for Displacement Ventilation, ASHRAE Transactions 1999, V. 105, Pt.1. 8. U.S. Green Building Council, LEEDTM (Leadership in Energy & Environmental Design) - Green Building Rating System for New Construction & Major Renovations (LEED-NC) Version 2.1, November 2002 - revised 3/14/03, www.usbgc.com/leed. 9. ASHRAE Standard 62. 10. Qingyan Chen and Leon Glicksman, System Performance Evaluation and Design Guidelines for Displacement Ventilation , ASHRAE, Inc, 2003. 11. ASHRAE Standard 55. 12. Pawel Wargocki and David Wyon, Research Report on effects of HVAC on Student Peformance, ASHRAE Journal, Vol 48, No. 10, 2006. 13. Morton Blatt, Advanced HVAC Systems for Improving Indoor Environmental Quality and Energy Performance of California K-12 Schools: Applications Guide for Off-the-Shelf Equipment for Displacement Ventilation Use Consultant Report prepared for California Energy Commission, 2006. 14. Gregory Kats, Greening Americas Schools, Costs and Benefits, Capital E Report, October 2006.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
J-49
DISPLACEMENT vENTILATION
Notes
DISPLACEMENT VENTILATION
J-50
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.
2975 Shawnee Ridge Court Suwanee, Georgia USA 30024 Ph: 770.623.8050 Fax: 770.623.6404
IN THE UNITED STATES
US Head Office, Price Technical Center, Export Sales Office & Manufacturing Facilities in Atlanta, Georgia
Manufacturing Facilities & Price Technical Center West in Phoenix, Arizona Representation in major US cities
IN CANADA
638 Raleigh Street Winnipeg, Manitoba Canada R2K 3Z9 Ph: 204.669.4220 Fax: 204.663.2715
Canadian Head Office, Laboratory & Manufacturing Facilities in Winnipeg, Manitoba Sales Offices or Representation in all major Canadian cities
The founding principles of our company have never changed - business integrity, first class service and a commitment to people. Price manufacturing endeavors arose from our belief that we could supply superior products and services at a reasonable price. Our mission is to become the worldwide supplier of preference for air distribution products and services. You can rely on Price our products and services with confidence. Product Improvement is a continuing endeavor at Price. Therefore, specifications are subject to change without notice. Consult your Price sales representative for current specifications or more detailed information.
Warranty: The Company warrants and guarantees that all goods within this catalog that have been manufactured by the Company have been manufactured in accordance with the specifications published herein and will be free from defects in material and workmanship for a period of twelve (12) months from the date of Bill of Lading issued by the Company. The Company will replace defective product at its option, but will not be responsible for labor or material charges in replacing product or consequential damages. Any installation not conforming with the Company's specifications, manuals, bulletins or instructions or any misuse or any modification not authorized by the Company voids this warranty. This warranty is in lieu of all Provincial, State, and Federal statutory warranties and the conditions herein are in substitution and replacement of such warranties, statutory or otherwise.
w w w. p r i c e - h v a c . c o m
Price is a registered trademark of E.H. Price Limited. 2007. Printed in Canada 2007