Symmetra PX UPS: Operation and Maintenance Manual
Symmetra PX UPS: Operation and Maintenance Manual
10-80 kW 208 V
Contents
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Functional Schematic Dual Mains / Single Mains . . . . . . . . . . . . 9 Control Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Control Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Status Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Set-up Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Accessories screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Logging Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Display screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Diag screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Help screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Network Connection/APC Web Management Card . . . . . . . . . 17 Quick Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
990-1430 REV01
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
General Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 General Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Module failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Threshold Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Network Cable Installation (if required) . . . . . . . . . . . . . . . . . . 31 System Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Life Support Policy/Warranty . . . . . . . . . . . . . . . . . . . . . . . . . 34
Life Support Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Factory Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
ii
990-1430 REV01
Indicates that more information is available on this subject in a different section of this manual.
Indicates that more information is available on the same subject in a different manual.
<40 lb
40 - 70 lb.
70 - 120 lb
>120 lb
990-1430 REV01
WARNING! Hazardous electrically-charged parts inside the UPS are energized from the battery supply even when the AC power is disconnected. Follow Total Power Off Procedure to completely de-energize the system.
CAUTION! For congurations including customer-supplied external batteries, refer to manufacturers battery installation and maintenance instructions.
Indicates that a switch or current protection device is in the ON position. Indicates the OFF position for a switch or a breaker Indicates that a switch is in the STAND-BY position
990-1430 REV01
UPS
INTELLIGE NCE MODULE INTELLIGE NCE MODULE
1
?
SE YN SA TB EL ME
XR Communica tions
CAUTION! To ensure solid stability, do not pull Battery Units out beyond the Red Disconnect Line unless completely removing them from the enclosure.
1
Set the DC Disconnect on ALL Battery Enclosures in your conguration to the OFF position.
BATTERY UNIT
2
Disconnect all Battery Units by removing or pulling out to Red Disconnect Line.
BATTER Y UNIT
3
Set the upstream Utility Power to the OFF or LOCKED OUT position. If the UPS has dual mains supply, set both supplies to the OFF or LOCKED OUT position. Note: Follow proper lock out tag procedures.
ON
Sy Ba 10 mm sic - 40
Battery Enclosure
OFF
OFF
990-1430 REV01
Introduction
After the UPS has been wired electrically, it is ready for start-up. This guide will allow you to quickly start up the UPS. It contains information on Safety, System Components, Securing the UPS, Module Installation, Network Cable Installation, Start-Up Procedure, and Basic Troubleshooting.
990-1430 REV01
PowerView Display Battery Communication Cable Bypass Static Switch Module System ID Card
S B 10 ym as - m ic 40 et O k ra per W at , 20 PX io 0 n V G uid
Power Module
DOCU
MEN
T ST OR
AGE
S E YN S A T B E L ME
Syste
m Po wer Su
pply
Port 1 Port 2
XR Co mmuni cation
Rese
t
10/10 0Bas RXTX e-T 10/10 0 Sta
PSU
Sub
Supp
Link
ly
Terminators
nitor
Card
Battery Comm Card PSU Sub Supply Switch Gear Monitor Card
990-1430 REV01
Weights
UPS (empty) 600 lb. (275 kg) Power Module 60 lb. (26 kg)
990-1430 REV01
Operation
The PowerView is the user control interface used to congure the functionality, monitor the system, set alarm thresholds, and to provide audible and visual alarms.
Four LED indicators report the operational status of the UPS. Five navigation keys are used to select and open menu items, to access information, change system parameters, and to launch contextsensitive help.
LOAD ON
ON BATT
BYPASS
Chrg 100% Load 000% 120Vin 000Vout 60Hz Runtime: 00hr 30m
ESC
FAULT
1 2 3 4
7 8
LOAD ON LED
ON BATT LED BYPASS LED FAULT LED LCD UP and DOWN navigation keys ENTER key HELP key ESC key
When green, the Symmetra PX UPS is providing power to the load equipment. When yellow, power is owing from the batteries to the Power Modules. When yellow, power to the load is being supplied through the Static Bypass Switch. When red, an fault condition exists. Displays alarms, status data, instructional help, and conguration items. Selects menu items and accesses information. Opens menu items and input changes to system parameters. Launches context-sensitive help. Returns to previous screen displayed.
2 3
4 5 6
7 8 9
990-1430 REV01
Operation
Press ESC ESC until you get to the Top-Level Status Screen, which provides you with basic system status information.
Chrg 100% Load 000% 120Vin 000Vout 60Hz Runtime: 0hr 0m
Top-Level Status Screen (factory default)
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to command, congure, and monitor the system.
Selector Arrow
Top-Level Menu
Bat Voltage: 218V Bat Capacity 100.0% Runtime: 01hr 30min 32 Batts, 00Bad
Battery Module Status Screen
Capacity: 80.0kVA Fault Tolerance: n+1 Total UPS Modules: 9 Bad UPS Modules: 00
Power Module Status Screen
and Enter
Low Batt Dur: 2min 20sec Shutdwn Dly: Return Dly: 0sec Return Bat Cap: 0%
Shutdown Menu
Low Batt Dur: 10min Shutdwn Dly: 20sec Return Dly: 0sec Return Bat Cap: 0%
Shutdown Menu
990-1430 REV01
Operation
Control Functions
Turn load on/off:
Control Sub-Menu
UPS into Bypass Do Self Test Simulate Power Fail Graceful Reboot
UPS IS BYPASSED
Control Menu
Bypassed Screen
990-1430 REV01
Operation
Control Screen
From the Control screen, you can select the following items:
UPS into Bypass Do Self Test Simulate Power Fail Graceful Reboot Graceful Turn Off Start Runtime Cal Turn Load On/Off Place into or return from maintenance bypass operation Initiate a system of self-tests and diagnostics. Simulate a power failure Turn off and start load equipment in an ordinary manner. Shut down load equipment in an orderly manner. Begin runtime calibration of the UPS. Apply power to or shut down the Symmetra PX UPS
10
990-1430 REV01
Operation
Status Functions
Verify general module status:
Capacity: 80.0kVA Fault Tolerance: n+1 Total Pwr Modules: 9 Bad Pwr Modules: 0
Top-Level Menu
Top-Level Menu
Status Screen
Bat Voltage: 218.6V Bat Capacity: 100.0% Runtime: 1hr 30min 32 Batts, 0 Bad
Top-Level Menu
990-1430 REV01
11
Operation
Status screens
The status screen display information regarding load, battery, power module voltage, and current.
Status Screen 1.
Vin Vout Iout The input voltage (V), output voltage (V), and output current (A) for each phase (1-3).
Status Screen 2.
%load assuming no redundancy Percentage of the load in relation to the total capacity of all power modules.
Status Screen 3.
%load allowing for n+ redundancy Percentage of the load, allowing for the redundancy in your system.
Status Screen 4.
Frequencies The input and output frequency in hertz (Hz).
Status Screen 5.
Batt Voltage Batt Capacity Runtime #Batts #Bad Actual voltage of the DC bus (volts). Percentage of battery capacity available The available runtime for battery operation in hours and minutes The number of installed battery modules. The number of failed battery modules.
12
990-1430 REV01
Operation
Status Screen 6.
Capacity: kVA Fault Tolerance Total Pwr Modules Bad Pwr Modules The system load capacity. The congured redundancy for your UPS (n+0, n+1, n+2...). The number of power modules installed The number of failed power modules installed
Status Screen 7.
Alarm Thresholds Fault Tolerance n+0 Runtime hr min load: kVA Settings congured for the thresholds that trigger alarms. The alarm threshold for reduced redundancy. The alarm threshold for reduced runtime. Alarm indication of the load exceeding the congured redundancy
Status Screen 8.
Self Test Lst Xfr Status IM RIM Status of the last self-test Information on the last transfer to battery operation. General UPS status. Status of the main intelligence module. Status of the redundant intelligence module.
Set-up Functions
Display parameters are set to factory defaults.
Top-Level Menu
Settings Menu
990-1430 REV01
13
Operation
Setup screens
From the Setup screen, you can select the following items:
Shutdown Congure the following system shutdown conditions: Low Batt Dur: Low battery duration is the time from low battery signal to the shutdown of the load. This signal is sent to the server using shutdown software (PC + PCNS). Shutdwn Dly: Shutdown delay is the time from when the UPS receives a shutdown command (usually sent by a server) to the shutdown of UPS power to the load equipment. This delay allows load equipment time to nish shutdown processes. Return Dly: Return delay is the amount of time the UPS wants to turn on after a power outage has ended. Return Bat Cap: Return battery capacity is the minimum percentage of battery capacity required for the UPS to turn the load on. Defaults Return all UPS settings to their default values. Output Frequency Set the desired output frequency Alarms Redundancy: The state of redundancy that will trigger an alarm. Choices are: N+0 an alarm will occur only when there is more load than all functioning power modules can support; N+1 an alarm will occur when there are no spare power modules in good condition; N+2 an alarm will occur when there is only one functioning power module. Load: When the load is greater than this threshold, an alarm will sound. Runtime: When the time the UPS can power the load is less than this threshold, an alarm will sound. This alarm is the result of an increase in load or a decrease in battery capacity. Bypass Set the conditions in which the UPS will automatically go into bypass operation. Copy Copy the UPS settings. Other Self Test: Set the UPS to perform a self-test automatically at periodic intervals. USP ID: Provide a unique name for the UPS. Vout Reporting: Set the reporting to the number of the tap to which the most signicant load is wired on the output transformer. Output: Set the UPS output voltage. BatFrAmpHour: Set the Ampere-Hour rating of external battery enclosures that are not APC Symmetra PX Battery Enclosures.
14
990-1430 REV01
Operation
Accessories screen
Control Status Setup Accessories Logging Display Diags Help
Top-Level Menu
From the Accessories screen, you can view the status of APC accessories connected to the UPS.
Logging Screen
Top-Level Menu
The Logging screen allows you to customize the UPS log. The following items are accessible from this screen:
View Log Point to an entry in the log and press the Enter key to view a description of the event. The display logs the most recent 64 events. View statistics of the events logged. Set the type of events that are recorded in the log. To log a type of event, choose On. View the list of event types. Power Events UPS Control Events User Activities UPS Fault Events Measure UPS Events For each group, press the Enter key to display each event listed under the group. Clear Log Clear all events currently stored in the log.
990-1430 REV01
15
Operation
Display screens
Control Status Setup Accessories Logging Display Diags Help
Top-Level Menu
The Display screens allow you to customize the UPS display interface. The following items are accessible from this screen:
Date: Password Information Set the correct date (day:month:year) and time (hour:minute). Protect the password against unauthorized conguration changes. View the model number, serial number, date of manufacture, and revision number of the display interface. Congure the audible alarm interface.: At UPS At Disp Vol Click Set the contrast on the LCD. Personalize the Top-Level Status screen. Choose each line you want displayed from a list of options. To change a line, move the selection arrow to the line you want to change and press the ENTER key. Scroll up or down the list to nd the data you want displayed and press the ENTER key to save you changes. Press the ESC key to discard your changes.
Beeper
Contrast Cong
Diag screens
Top-Level Menu
The Diagnostic screens provide information for use in troubleshooting. The following items are accessible from this screen:
16
990-1430 REV01
Operation
Lists any failures found. If any status except ON or OK is displayed, a module or card must be replaced. The Faults and diagnostics screen will describe the location of the failed module/ card. If you do not have a redundant intelligence module installed, you must place the UPS in bypass operation before you remove an intelligence module. Lists external device status. If any status except ON or OK is displayed, a module, card or battery must be replaced. If you do not have a redundant intelligence module installed, you must place the UPS in bypass operation before you remove an intelligence module.
Help screens
To access the display interface context-sensitive help screens, press the ? key.
Rese
Display Remote Power View
Display/Co mputer Interface
t
10/1
Compute Interfacer
Port
XR Communic ation
Reset
Link-RX/ 10/100Ba se-T TX Status 10/100
AP9617 Network Managem ent Card
Link-
RX/T 10/1 X 00
00Bas
e-T
Statu
A P9
617
Netw ork M
ana gem
ent
Car d
Serial port
Sy m B 10 m asi - 4 et c 0 ra O kW per , PX ati 20 on 0 V G uid e
DOCU MEN T
STOR AGE
990-1430 REV01
17
Operation
Quick Conguration
Disregard the procedures in this section if you have an APC InfrastruXure Manager as part of your system. See the InfraStruXure Managers documentation for more information. You must congure three TCP/IP settings before the Management Card can operate on a network: IP address Subnet mask Default Gateway From the PowerView Display:
Top-Level Menu
Accessories Menu
If a Default Gateway is unavailable, use the IP address of a computer located on the same subnet as the Management Card that is usually running. The Management Card uses the Default Gateway to test the network when trafc is very light. See Watchdog Features in the Introduction of the Network Management Card Users Guide CD (.\doc\usrguide.pdf) for more information about the watchdog role of the Default Gateway. The Management Card Users Guide CD is located in the documentation storage tray.
18
990-1430 REV01
1
INTELLI GENCE MODUL E INTELLI GENCE MODUL E
XR Commun ications
To de-activate the module, turn Locking Latch (with arrow pointing towards the module) counterclockwise until it points downwards.
990-1430 REV01
19
Pull out the module. Display shows message saying it has decreased the number of power modules. Reverse procedures for installation. Unscrew springactivated knobs on both sides of the module until they pop out. Standing on either side of the UPS, 2 people can now pull the module almost free of the UPS (the lock mechanism prevents the module from being pulled clear of the UPS). With the module still resting in the UPS, release the lock by pushing the black plastic tab on either side of the module
INTELLIG ENCE
MODULE
INTELLIG ENCE
MODULE
2
?
XR Commun ications
System
Power Supply
Display Remote PowerView
Display
Display
/ Computer Interface
Port
XR Communication
1 Port 2
Disp lay /
System
Power Supply
Por t
XR Com
1 Por t 2
mun
icatio
Reset
PSU
Sub
Link-
Supply
AP961 7 Net
RX/T 10/10X 0
Statu
work
Manag
ement
Car d
System
Power Supply
Loosen the 2 Phillips screws at both sides of the card. Carefully pull out the card. Reverse procedures for installation. Display shows message saying it has registered the new card.
10/10 0Base -T
Display
Disp
System
lay / Com pute r Inte rface
Power Supply
Port
1 Port 2
XR Com
mun
icatio
PSU
Sub
Supply
20
990-1430 REV01
Loosen the 2 Phillips screws at both sides of the module (top of module). As soon as the left side screw is loose, the module will be deactivated. Display shows message saying it has decreased the number of cards. Reverse procedures for installation.
INTELLIG ENCE
MODULE
INTELLIG ENCE
MODULE
INTELL IGENC E
MODU LE
INTELL IGENC E
MODU LE
990-1430 REV01
21
See section on Warranty for more information 5. If the Symmetra PX UPS is covered by an APC service contract, have that information available and give ti to the representative.
Part
80kW Enclosure Only 10kW Power Module Intelligence Module Symmetra 3-Phase 80 kVA Bypass Static Switch Module System Power Supply Card PSU Supply Board Display and Computer Interface Card Switch Gear Monitoring Card System ID Card Battery Communication Card Web Card, SNMP Battery Enclosure only
No
SYCF80KF SYPM10KF SYMIM4 SYSW80KF SYCSPS SYCSS SYCDCI SYCSGMON SYCSYSID SYCXRCOM AP9617 Web/ Management Slot Card SYCF8BF
WARNING! Only trained persons familiar with the construction and operation of the equipment, and the electrical and mechanical hazards involved, may install and remove system components.
22
990-1430 REV01
Troubleshooting
This section lists all of the alarm and status messages that are displayed on the UPS display interface. A suggested corrective action is listed with each message to help you troubleshoot problems.
If a problem is reported, ensure that the system component in question is correctly installed (refer to section on Modular & Card Replacement.
General Status
Display Message
Input Freq outside congured range
Meaning
The input frequency to the UPS is outside the congured range. The output frequency will not synchronize with the input frequency. Normal bypass is not available.
Corrective Action
Option 1: Improve the frequency of the incoming voltage. Option 2: Widen range of acceptable incoming frequency using the display interface. Select Start-UP, Setup, OUtput, Freq Select). Option 3: Proceed with startup. Normal bypass is not available. Option #1: Improve the incoming voltage. Option #2: Proceed with startup. Normal bypass is not available.
The Symmetra PX UPS will function online with the input voltage, but in the event that bypass is required, the input voltage is not adequate to power the load equipment. Input voltage is not adequate to start the Symmetra PX UPS. If start-up proceeds, the Symmetra PX UPS will function in battery operation. An Intelligence Module has been installed into the Symmetra PX UPS. An Intelligence Module has been removed from the Symmetra PX UPS. An intelligence Module has been installed into the Symmetra PX UPS. An Intelligence Module has been removed from the Symmetra PX UPS.
Intelligence Module inserted Intelligence Module removed Redundant Intelligence Module inserted Redundant Intelligence Module removed
No corrective action necessary. Check that the intelligence modules are properly inserted and that the fastening screw is tight. No corrective action necessary. Check that the intelligence modules are properly inserted and that the fastening screw is tight.
990-1430 REV01
23
Troubleshooting
Display Message
# of batteries changed since last ON
Meaning
At least one battery module has been added or removed from the UPS since the last time the Power ON command was used. At least one battery module has been added or removed from the UPS since the last time the Pwr ON command was used. At least on battery module has been added to the system. At least one battery module has been removed from the system. At least one power module has been added to the system At least one power module has been removed from the system.
Corrective Action
Check that all battery units are installed correctly.
Check that all power modules are properly inserted, the two fastening screws are tight, and the locking latch is engaged. No corrective action necessary. Ensure that all battery units are properly inserted. No corrective action necessary. Check that all power modules are properly inserted, the two fastening screws are tight, and the locking latch is engaged. No corrective action necessary.
# of batteries increased # of batteries decreased # of Pwr Modules increased # of Pwr Modules decreased
At least one external battery cabinet has been connected to the Symmetra PX UPS At least one external battery cabinet has been disconnected from the Symmetra PX UPS
Ensure that all Battery Enclosures communication cables are properly connected and that the LEDs are illuminated on the Battery communication cards. No corrective action necessary.
Redundancy Restored
A loss of power module redundancy occurred and the redundancy has been restored. Either additional modules have been installed or the load has been reduced.
24
990-1430 REV01
Troubleshooting
General Fault
Display Message
Need Bat Replacement The Redundant Intelligence Module is in control UPS Fault
Meaning
One or more battery modules are in need of replacement The Main Intelligence Module has failed, and the redundant intelligence module is functioning as the primary intelligence module. A fault has occurred in a power module. This will always occur with a power module failure message. The Symmetra PX UPS has transferred to battery operation due to the input going out of acceptable range. At this time the batteries will discharge until the input is restored to an acceptable range. The Symmetra PX UPS has shut down because an overload occurred and bypass is not available.
Corrective Action
Refer to Module Replacement Section for procedures. Replace the Main Intelligence Module.Refer to Module Replacement Section for procedures. Contact APC Technical Support at (1) (800) 800-4272. No corrective action necessary. Note: Runtime is limited in duration. Prepare to shut down the Symmetra PX UPS and the load equipment or restore incoming voltage. Option 1: Reduce the load to eliminate overload. Option 2: If possible, add power modules to eliminate overload. Option 3: Replace failed power modules to eliminate overload. Correct the input voltage problem.
On Battery
Load Shutdown from Bypass. Input Freq/Volts outside limits Fault, Battery Charger Failure Fault, Internal Temp exceeded normal limits Input circuit breaker tripped open
The Symmetra PX UPS has transferred to battery operation because the input is out of acceptable range. The battery charger in one or more of the power modules failed The temperature of one or more battery units has exceeded system specications. The input circuit breaker on the Symmetra PX UPS is open. Input voltage is disconnected to the Symmetra PX UPS.
Refer to Module Replacement Section for procedures. Ensure that the ambient temperature meets the specications of the system. Option 1: If this occurs with an overload condition, decrease the load and reset the breaker. Option 2: If no overload condition exists, reset the breaker. If it trips open again, contact APC Technical Support at (1) (800) 800-4272. Contact APC Technical Support at (1) (800) 800-4272.
990-1430 REV01
25
Troubleshooting
Module failure
Display Message
Bad Battery Module
Meaning
A battery module has failed and requires replacement. A power module has failed and requires replacement. The Main Intelligence Module has failed and requires replacement.
Corrective Action
Refer to Module Replacement Section for procedures. Refer to Module Replacement Section for procedures. Replace the Main Intelligence Module. Refer to Module Replacement Section for procedures. Replace the Redundant Intelligence Module. Refer to Module Replacement Section for procedures.
Threshold Alarm
Display Message
Redundancy has been lost
Meaning
The Symmetra no longer detects redundant power modules. Either power module(s) have failed, or the load has increased.
Corrective Action
Option 1: If possible, install additional power modules. Option 2: Replace failed modules. Refer to Module Replacement Section for procedures. Option 1: If possible, install additional power modules. Option 2: Replace failed modules. Refer to Module Replacement Section for procedures. Option 3: Decrease load or recongure threshold. Option 1: Allow the battery modules to recharge. Option 2: If possible, increase the number of battery modules. Option 3: Reduce load or recongure threshold. Reduce load or re-congure threshold.
Actual power module redundancy has fallen below user-specied redundancy alarm threshold. Either power module(s) failed or the load increased.
The predicted runtime is lower than the user-specied minimum runtime alarm threshold. Either the battery capacity has decreased, or the load has increased
The load has exceeded the user specied load alarm threshold
26
990-1430 REV01
Troubleshooting
Display Message
Load is No Longer above Alarm Threshold
Meaning
The load exceeded the load alarm threshold and the situation has been corrected either because the load decreased or the threshold was increased. The system runtime dropped below the congured minimum and has been restored. Additional battery modules were installed, the existing battery modules were recharged, the load was reduced, or the threshold was raised.
Corrective Action
No corrective action necessary
Bypass
Display Message
Bypass is not in range (either freq or voltage)
Meaning
The frequency and/or voltage is out of acceptable range for bypass. This message occurs when the Symmetra is online, and indicates that the bypass mode may not be available if required. The Symmetra PX UPS is stuck in the bypass position and cannot go online. The Symmetra PX UPS is stuck in the on-line position and cannot go to bypass. The Symmetra PX UPS has transferred to bypass mode because a fault has occurred The load exceeded the system power capacity. The Symmetra PX UPS has switched to bypass mode The Symmetra PX UPS is in bypass because it has been commanded into bypass or due to an internal fault. The bypass relay has malfunctioned.
Corrective Action
Option 1: Correct the input voltage to provide acceptable voltage and/or frequency. Option 2: Decrease the sensitivity to input frequency. (Select Startup, Setup, OutputFreq, and select a value). Contact APC Technical Support. at (1) (800) 800-4272. Contact APC Technical Support. at (1) (800) 800-4272. Contact APC Technical Support. at (1) (800) 800-4272. Option 1: Decrease the load. Option 2: If possible, add a power module to the system. No corrective action necessary. If other alarms exist, troubleshoot base on other alarms. Contact APC Technical Support. at (1) (800) 800-4272.
Backfeed contactor stuck in OFF position Backfeed contactor stuck in ON position UPS in bypass due to internal fault UPS in bypass due to overload System is in Maintenance bypass Fault, Bypass Relay Malfunction
If the system works in bypass, ensure the presence of AC mains supply input. If a problem persists, note UPS model #, serial #, and date purchased before calling Tech Support at: 1 (800) 800 4272.
990-1430 REV01
27
13/14-mm wrench
CAUTION! Do not move the UPS after the stabilizing feet have been lowered, or equipment damage may occur.
28
990-1430 REV01
WARNING! Only APC-trained personnel familiar with the construction and operation of the equipment, and the electrical and mechanical hazards involved, may install and remove system components.
CAUTION!
Before installing any modules in the UPS, ensure that the System Enable Switch is left in the STAND-BY position (if not, see section on Total Power Off.
At least 1 Battery Module (4 Battery Units) is required in the battery enclosure and the DC breaker to be on to start up the system. If using value line battery cabinets, battery conguration will need to be entered manually through display,
Installing
Starting from the lowest available bay, remove as many blind plates as the number of Power Modules to be installed. Install Power Modules and push completely into the UPS.
990-1430 REV01
29
Securing
1
Fasten screws using a screwdriver.
2
Engage Locking Latch. Turn knob on right side of UPS clockwise until arrow faces module.
?
Sy B 10 m as - m ic 40 et O kWra pe ra , 20 PX tio n 0V G ui de
DOCU
MENT
STOR AG
3
Make sure that the Locking Latch on Bypass Static Switch Module is engaged.
The Power Module will not start unless the Locking Latch is engaged. After the installation and securing of the Power Modules, make sure that the locking latch on the Bypass Static Switch Module is engaged
30
990-1430 REV01
Depress latches
4
INTELLIG ENCE MODULE
Pull out panel Remove left terminator from Port I. Save for reinstallation in Battery Enclosure. Install Battery Communication Cable in Port I. Lift panel off UPS
6
DOCU MENT STO RAGE
te Remoew r Vi Powe
Disp
lay rface 2
Reset
Route cables through front holes of UPS. Exit UPS from bottom or top as required
Disp
lay /
pu Com
te ter In
AP96
17 Ne
twork
geme Mana
nt
Port Port 1
ns icatio mmun XR Co
h Ge Switc
ar M
rd r Ca onito
If your UPS has been installed in-between devices and side panels cannot be removed the Bypass Static Switch Module can be removed to gain access.
990-1430 REV01
31
Utility Power ON
ON
SE YN SA TB EL ME
OFF
Wait approximately 30 seconds for system to boot up. Display will show a fault if Power Module Locking Latch is not engaged.
Press ESC until you get to the Top-Level Status Screen, which provides you with basic system status information
LOAD ON
ON BATT
BYPASS
Chrg 100% Load 000% 120Vin 000Vout 60Hz Runtime: 00hr 30m
Top-Level Status Screen
ESC
FAULT
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to command, congure, and monitor the system.
Top-Level Menu
32
990-1430 REV01
Press the down key and then the enter key to select Status. Verify that all power, battery and intelligence modules are detected by the system and are functioning correctly by scrolling down and reviewing all status screens. Please note that the intelligence modules are monitored under the Miscellaneous Status Screen (submenu under Status).
Bat Voltage: 218V Bat Capacity 100.0% Runtime: 01hr 30min 32 Batts, 00Bad
Typical Status Screen
If a problem is reported, ensure that the system component in question is correctly installed. If the problem persists, refer to Basic Troubleshooting.
The UPS is now ready to support the load equipment. For further operation, PowerView features, and conguration, see Basic Operation Guide and Product Manual CD (shipped with unit) and visit our website: www.apc.com. If you are using a network connection, please refer to the enclosed Product Manual CD.
990-1430 REV01
33
34
990-1430 REV01
Factory Warranty
APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installation or maximum 18 months after manufacturing. In the event that the unit fails to meet the foregoing warranty, APC shall for a period of one (1) year repair or replace any defective parts, without charge for on-site labor and travel if trained & authorized APC personnel has conducted start-up of the unit. An APC Start-Up Service must be performed/completed by APC or by service personnel authorized by APC. If not, the on-site factory warranty will be voided and replacement of defective parts only will be covered. APC shall have no liability and no obligation to repair the installed unit if nonauthorized APC personnel performed the start-up and such start-up caused the unit to be defective. APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY PURCHASERS OR ANY THIRD PERSONS MISUSE, NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD. THERE ARE NO WARRANTIES, EXPRESSED OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITHIN. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APCS EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APCS RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APCS SOLE LIABILITY AND PURCHASERS EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APCS WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES. IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
990-1430 REV01
35
Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.
Entire contents copyright 2003 American Power Conversion. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, Symmetra, and InfraStruXure are trademarks of American Power Conversion Corporation and may be registered in some jurisdictions. All other trademarks, product names, and corporate names are the property of their respective owners and are used for informational purposes only.
990-1430
05/2003