Manual ATSC 1
Manual ATSC 1
Page 1 of 21
OPERATING MANUAL
NELESYS www.nelesys.com
www.nelesys.com
rev.0
Page 2 of 21
TABLE OF CONTENTS
1 DESCRIPTION ................................................................ 3
2
FEATURES ...................................................................... 3
3 OPERATION.....5 3.1 Operation Panel......5 3.2 DISPLAY....6 4 SETTING OPERATION....9 4.1 Manual/Auto mode settings....9 4.2 Parameter settings9 5 INSTALLATION and UNIT DIMENSIONS.15
www.nelesys.com
rev.0
Page 3 of 21
1. DESCRIPTION
The ATSC-1 is an Automatic Transfer System Control Module. It precisely measure/display two source 3-phase AC voltage and output free voltage controlling switch signal if any of the monitored two source AC voltage is abnormal. This module is suitable for a variety of ATS system and can be widely used to electric devices in many fields such as electric power, communication, petroleum, coaling, metallurgy, rail, municipal business, smart mansion etc.
2. FEATURES
Measure two source multi-parameters include over voltage, under voltage, over frequency, under frequency, miss phase. Compatible to multi-type of automatic transfer switches(ATS): no OFF position(two segments kind), such as SOCOMEC VS switch; one OFF position(three segments kind), such as SOCOMEC VE switch. two OFF position, such as the ATS composed of two circuit breakers or two contacts Nelesys ATS Compatible to automatic switching of two utility source, two generating power or between one utility source and one generating power; Microprocessor based design, LED display, tactile key operation; Measure and display two source 3-phase AC voltage precisely; ATS power switching circuits that supply for ATS; Configurable priority of supply able to set I# supply priority or II# supply priority or NONE supply priority; Function of start generator; Function of auto transfer when one switch closing failures and another works well; Auto/Manual button available, mandatory opening or closing switch in manual mode; Password to prevent the miss operation of non-professionals; Function of re-closing to prevent instantaneous power off aiming at switch
www.nelesys.com rev.0
Page 4 of 21
which opening as voltage being low; Function of re-closing while power off to prevent the abnormal On/Off operation from the mismatching between the operation unit and switch position; Pulse output closing and Opening signal(up to 20 seconds), output auto shutoff after switching is done; Transfer rest delay time is programmable; Two N line separating design; Industrial standard RS-232 communication interface to fulfill the remote controlling remote measuring remote communication function by the ModBus communication protocol; Parameters can be set in site or in monitor center and can not lose even power off; Module structure design, ABS plastic crust, embedded installation, plug connector, convenient maintenance
www.nelesys.com
rev.0
Page 5 of 21
3. OPERATION
3.1 Operation Panel
LED display screen can display multi -parameters of two power sources such as voltage, delay value, and setting value etc. push-button. The function is used to scroll screen or change a
programming value while in the programming mode. When this push-button is held down, the displayed value will be incremented/decremented to a lower/higher value as desired.
push-button. The
push-button and LED light viewing window. The initiate automatic operation.
function is used to
push-button and LED light viewing window. The initiate manual operation.
function is used to
www.nelesys.com
rev.0
Page 6 of 21
Lamp. The lamp will illuminate when #2 power is prior to transfer. #1 normal lamp: The lamp will illuminate when #1 power is normal, and will flash when #1 power is abnormal , and will extinguish when no power. #2 normal lamp: The lamp will illuminate when #2 power is normal, and will flash when #2 power is abnormal , and will extinguish when no power. #1 closed lamp: The lamp will illuminate when #1 power is connected with the load. #2 closed lamp: The lamp will illuminate when #2 power is connected with the load. Alarm lamp: The lamp will flash when any alarm occur.
3.2 DISPLAY
Press the button to scroll the displaying screen
The first screen (display of the line voltage Uab or the delay time of the normality or the abnormality of the #1#2 power counted down)
www.nelesys.com rev.0
Page 7 of 21
or Display priority: (#1 power normal delay>#2 power normal delay>#1 power abnormal delay>#2 power abnormal delay>display of Uab line voltage) #1 power Uab line voltage will be displayed after all the display of delay is done. The second screen (Ubc: #1 line voltage)
www.nelesys.com
rev.0
Page 8 of 21
The screen will display the alarm state if there is alarm of #1 or #2 power. #1 closing failure #2 closing failure #1 opening failure #2 opening failure #1 power serious failure #2 power serious failure Both #1 and #2 power are closed at same time. Note: if there is alarm of #1 power or # II power, pressing the button,the
module will transfer to the manual mode, and the alarm state will be reset.
www.nelesys.com
rev.0
Page 9 of 21
4. SETTING OPERATION
4.1 Manual/Auto mode settings
Press the button to the auto mode, press the button to the manual
mode. z When the controlling module is set into Auto mode, the Auto lamp will be turned on. The controlling module will estimate the quality of both the power and close or open the switches automatically. If both the powers work well, the switches will be turned on according to the priority of them. If both the powers are normal at the same time, the switch that first close will supply for load. It will not be switched to another power until abnormality occurs in the power. z When the controlling module is set into the manual mode, the manual lamp will be turned on. Press the button to transfer the switches. Note: pressing the switch. button will take no effect to the two segments button, the button or the
be displayed as follows:
button
to circulate the number from 0 to 9. The parameters can not be set until the password is confirmed. The parameters are displayed as follows: The first screen: setting the normal delay time of the #1 power, range: (0-999s)
Press the
www.nelesys.com
rev.0
Page 10 of 21
The second screen: setting the normal delay time of the #2 power, range: (0-999s)
Press the
The third screen: setting the abnormal delay time of the #1 and #2 power, range: (0-999s)
Press the
The fourth screen: setting the delay time of the start generator, range: (0-999s)
Press the
Press the
000: No OFF postion (two segment switch) 001: One OFF postion (three segment switch) 002: Two OFF postion The sixth screen: setting the transfer priority of #1 and #2 power
Press the
000: no priority 001: #1 power prior to transfer 002: #2 power prior to transfer The seventh screen: quit the settings
Press the
000: quit without saving the above parameters 001: quit after saving the above parameters
www.nelesys.com rev.0
Page 11 of 21
Others: return to the settings Setting of other parameters: (only by the PC software via RS232 interface), the number in the bracket is the factory value. 1. Communication address 1-254 (1) 2. Transfer rest time 0-999S (5) 3. Stop generator delay time 0-999S (90) 4. Over voltage 201-300V (264) 5. Under voltage 140-200V (160) 6. ATS shut delay 0-20.0S(5.0) 7. ATS break delay 1-20.0S(5.0) 8. Delay for transfer over 0-5.0S(0) 9. Again shut delay 0-10.0S(0) 10. Again break delay 0-10.0S(0) 11. Digit input1(IN1) 1# ATS Abnormal Input 12. Digit input2(IN2) 2# ATS Abnormal Input 13. Digit output(relay K5) Gen Start Output(normal open) Note: The below table is the detail information for the above settings. Item Description It is the delay of #1 power from voltage Normal delay time of the #1 power abnormal to voltage normal. It is the delay of #2 power from voltage Normal delay time of the #2 power abnormal to voltage normal. Abnormal delay time of the #1 and It is the delay of #1 or #2 power from #2 power voltage normal to voltage abnormal. It is the delay form #1 power is Delay time of the start generator abnormal to start generator.
www.nelesys.com
rev.0
Page 12 of 21
Item
Communication address
Over voltage
Under voltage
Description When #1 power is set to priority transfer, if #1 and #2 is normal at the same time, the switch will transfer load to #1 power source. When #2 power is set to priority transfer, if #1 and #2 is normal at the same time, the switch will transfer load to #2 power source. When setting for no priority, if #1, 2 power is normal at the same time and #1,2 take no load, the switch will first transfer load to #1 power source. ONLY when #1 power is abnormal, the #2 power will supply for load; if the swtich have been taken loda,it will not switched to another power until abnormality occurs in the power. Setting the Modbus Slave ID of the controller you wish to communicate with. It is the delay from #1 power breaker opened to #2 power breaker start to close or from #2 power breaker opened to #1 power breaker start to close. It is the delay from #1 power is abnormal to send out start generator signal. It is the delay from #1 power is normal to send out stop generator signal. The setting are used to configure the #1 and #2 power over voltage point in the event of the #1 or #2 voltage rising above the setting value. This value can be adjusted to suit user requirements. The setting are used to configure the #1 and #2 power under voltage point in the event of the #1 or #2 voltage falling below the setting value. This value can be adjusted to suit user requirements. Breaker close pulse. If it is set to zero, it will held. Breaker open pulse.
www.nelesys.com
rev.0
Page 13 of 21
Description After the module has received a close state input, the breaker close output continue to held until the delay is expended. When the breaker fail to close for the first time, the module will open breaker, and then attempt to close for the second time, if the second time closing breaker is still failure, the module will send out closing breaker failure signal. When the breaker fail to open for the first time, the module will close breaker, and then attempt to open for the second time, if the second time opening breaker is still failure, the module will send out opening breaker failure signal. Description It is the input of #1 breaker fault such as the circuit breaker is short-circuit. It is the input of #2 breaker fault such as the circuit breaker is short-circuit. When the input is active, the breaker will be force to transfer to OFF position.
Configurable digit input define Digit Input Content Not used 1# ATS Abnormal Input IN1 2# ATS Abnormal Input Transfer to Off-Position
Not used 1# ATS Abnormal Input IN2 Same as above 2# ATS Abnormal Input Transfer to Off-Position NOTE: The above two Auxiliary digit inputs dont permitted the same selection choices. Configurable digit output(Relay K5) define Item Description Not used Reserve1 Factory used It include closing failure, opening failure Fault Output and breaker fault of #1, 2 source. It include #1 closing failure, opening Transition Failure Output failure and #2 closing failure, opening failure.
www.nelesys.com rev.0
Page 14 of 21
1# Volt Normal Output 1# Volt Abnormal Output 2# Volt Normal Output 2# Volt Abnormal Output Auto Position(mode) Output Manual Position(mode) Output 1# Shut Up Output 1# Shut Off Output 2# Shut Up Output 2# Shut Off Output
It is active when #1 voltage is normal. It is active when #1 voltage is abnormal. It is active when #2 voltage is normal. It is active when #2 voltage is abnormal. It is active in auto mode. It is active in manual mode. #1 closing breaker output. #1 opening breaker output. #2 closing breaker output. #2 opening breaker output. When the start generator signal is active, the output relay energized. When the start generator signal is inactive, the output relay de-energized. Here the DC supply is necessary. When the start generator signal is inactive, the output relay energized. When the start generator signal is active, the output relay de-energized.
www.nelesys.com
rev.0
Page 15 of 21
NO
1.5mm
www.nelesys.com
rev.0
Page 16 of 21
www.nelesys.com
rev.0
Page 17 of 21
7. SPECIFICATION
Power supply: DC: 9-35V come from engine-generator battery. AC: come from phase A and N of two source, voltage>140V Input voltage: 220V+30% 50Hz single-phase or 380V+30% 50/60Hz 3-phase 4 wires Power consumption: Less than 2VA in normal voltage Relay output: 10A 250VAC LO, NO output: 10A 250VAC Dimensions: 144x96x116mm Panel cutout: 138x92mm Weight: 0.83kg Operation condition: Temperature: -30 - +70Celsiur degree Humidity: 20 - 95% no concreting
www.nelesys.com
rev.0
Page 18 of 21
www.nelesys.com
rev.0
Page 19 of 21
Default
Please download the ATSC-1 configuration software from the below web site. www.nelesys.com
www.nelesys.com
rev.0
Page 20 of 21
10. LINK TO PC
This below figure show the link from PC to ATSC-1 module.
Timers and thresholds Item Range Normal delay time of the 0-999s #1 power Normal delay time of the 0-999s #2 power
www.nelesys.com
rev.0
Page 21 of 21
Abnormal delay time of the #1 and #2 power Delay time of the start generator Delay time of the stop generator Transfer rest time ATS shut delay ATS break delay Delay for transfer over Again shut delay Again break delay Over voltage Under voltage Others Item Transfer priority ATS type Module address
0-999s 0-999s 0-999s 0-999s 0-20.0s 1-20.0 0-5.0s 0-10.0s 0-10.0s 201-300V 140-200V
www.nelesys.com
rev.0