Contactor
Contactor
AC 1030
TO
M ER FI
ST
CU
QU
AL
IT Y
... A LW
Registered by UL to
ISO 9002
YS
A
DLA starters
Mounting plate, including a built-in Line contactor, is designed to integrate an ABB manual motor starter, Type MS325 Four DLA starter sizes, DLA9 - DLA26 Suitable for use with 3 phase motors up to 25 FLA UL Listed and CSA certified for 1200A group motor installation with fuses or breaker UL, IEC, CSA, VDE & most other international standards
Overload relays
Available for starter construction with A Line contactors and separate panel mounting Designed for close couple mounting for 11 contactors, A9 - A110 Class 10 adjustable overload relays are standard with all ABB Line starters UL Listed & CSA Approved
Control relays
AC or DC operated DIN rail or panel mounting 600 V heavy duty design, A600-10A, Q300-5A Snap-on accessories Coils are easily interchangeable Fixed contacts are double break type for positive contact on low current applications NEMA, UL, IEC, CSA, VDE & most other international standards
AC 1030 6/98
This catalog is published for information purposes only and is not all inclusive. For additional information on products or technical information, consult ABB Control Inc. The installation and use of ABB Control Inc. products should be in accordance with the provisions of the U.S. National Electrical Code and/or other local codes or industry standards that are pertinent to the particular end use. Installation or use not in accordance with these codes and standards could be hazardous to personnel and/or equipment.
Overload relays
Table of contents
Item
Product category
Page No.
Subject
Product category
Page No.
A
Accessories Accessories Accessories Accessory combinations, possible Accessory mounting information Accessory mounting information Adapter, shaft Additional terminal block Approvals Auxiliary contact blocks Auxiliary contact blocks Auxiliary control blocks Auxiliary lead terminals Control relays Contactors Overload relays Contactors Contactors Control relays DLA starters Contactors All products DLA starters Contactors Control relays Contactors 4.5 1.9 - 1.17 3.5 - 3.6 1.18 1.19 4.6 - 4.7 2.4 1.15 V 2.4 1.9 4.5 1.9
L
Latches, mechanical Lead terminals, auxiliary Contactors Contactors DLA starters Contactors Contactors Control relays Contactors Contactors Contactors Contactors 1.10 1.9 2.2 1.10 1.9 4.5 1.10 1.6 1.29 1.20
M
Manual motor starters, MS325 Marker, identification Mechanical interlocks Mechanical interlocks Mechanical latches Mechanically interlocked contactors Motor data Mounting positions
B
Bell alarm contact blocks Busbars DLA starters DLA starters 2.4 2.4
O
Overload Overload Overload Overload relay dimensions relay technical data relay tripping curves relays, Type TA Overload Overload Overload Overload relays relays relays relays 3.11 - 3.12 3.7 - 3.9 3.10 3.4
C
Capacitive switching contactors CE Mark Coil voltages & codes Coils Coils Connection kits for phase to phase Connection kits for reversing contactors Connection kits for wye-delta starters Contact blocks, auxiliary Contact blocks, auxiliary Contact blocks, bell alarm Contactor accessories Contactor dimensions Contactor technical data Contactors for capacitive switching Contactors, mechanically interlocked Contactors, non-reversing Contactors, reversing Control blocks, auxiliary Control relays, Type N & KC Control relay accessories Control relay dimensions Control relay technical data Contactors All products Contactors Contactors Control relays Contactors Contactors Contactors Contactors DLA starters DLA starters Contactors Contactors Contactors Contactors Contactors Contactors Contactors Control relays Control relays Control relays Control relays Control relays 1.8 5.2 1.13 1.13 4.5 1.14 1.14 1.14 1.9 2.4 2.4 1.9 - 1.17 1.30 - 1.40 1.18 - 1.28 1.8 1.6 1.4 - 1.5 1.7 4.5 4.4 4.5 4.11 - 4.12 4.8 - 4.10
P
Padlocking devices Phase to phase connection kits Pneumatic timers Pneumatic timers Possible accessory combinations DLA starters Contactors Contactors Control relays Contactors 2.4 1.14 1.9 4.5 1.18
R
Relay, interface Reversing contactor connection kits Reversing contactors Contactors Contactors Contactors 1.10 1.14 1.7
S
Selection guide, overload relay Shaft adapter Shunt trips Supporting terminal Surge suppressors Surge suppressors Overload relays DLA starters DLA starters DLA starters Contactors Control relays 3.3 2.4 2.4 2.4 1.9 4.5
T
Technical data Technical data Technical data Technical data Terminal block, additional Terminal blocks Terminal marking & positioning Terminal, supporting Terminals, auxiliary lead Terms & conditions Timers, electronic Timers, pneumatic Timers, pneumatic Tripping curves Type KC control relay Type N control relay Type TA overload relays DLA starters Control relays Contactors Overload relays Contactors DLA starters Contactors DLA starters Contactors Terms & conditions Contactors Contactors Control relays Overload relays Control relays Control relays Overload relays 2.4 4.8 - 4.10 1.18 - 1.28 3.7 - 3.9 1.15 2.4 1.16 - 1.17 2.4 1.9 5.1 1.11 1.9 4.5 3.10 4.4 4.4 3.4
D
Description, contactors Description, control relays Description, overload relay Dimensions Dimensions Dimensions DLA starter dimensions DLA starters Door mounting kits Contactors Control relays Overload relays Overload relays Control relays Contactors DLA starters DLA starters DLA starters 1.2 - 1.3 4.1 - 4.3 3.1 - 3.2 3.11 - 3.12 4.11 - 4.12 1.30 - 1.40 2.7 2.2 2.4
E
Electrical interlocks Electrical interlocks Electronic timers Contactors Control relays Contactors 1.9 4.5 1.11
F
Features Features Four pole contactors DLA starters Contactors Contactors 2.1 1.1 1.5
U
Undervoltage trip DLA starters 2.4
W
Wye-delta starter connection kits Contactors 1.14
G
General information DLA starters 2.3
I
Identification markers Identification markers IEC coordination tables Interface relay Interlocks, electrical Interlocks, electrical Interlocks, mechanical Interlocks, mechanical Contactors Control relays DLA starters Contactors Contactors Control relays Contactors Control relays 1.10 4.5 2.4 1.10 1.9 4.5 1.9 4.5
AC 1030 6/98
K
Kits, door mounting DLA starters 2.4
II
List prices shown in this publication supersede all previously published documentation and are subject to change without notice.
This above alphanumeric reference is an extract of AC 5030, Alphanumeric Reference, which contains all products sold by ABB Control Inc.
AC 5030 is available on disk for Windows and Macintosh as a MicroSoft Excel 5.0 document. An ASCII text version of the data is also included for use in other spreadsheet and database applications.
Catalog number List price Disc. Pg. sched. no. Catalog number List price Disc. sched. Pg. no. Catalog number List price Disc. sched. Pg. no. Catalog number List price Disc. Pg. sched. no.
A110-30-00-84 A110-30-11-84 A110M-30-11-84 A110R-30-11-84 A12-30-01-84 A12-30-10-84 A12M-30-01-84 A12M-30-10-84 A12R-30-01-84 A12R-30-10-84 A16-22-00-84 A16-30-01-84 A16-30-10-84 A16-40-00-84 A16M-30-01-84 A16M-30-10-84 A16N0-30-10-84 A16N0M-01-84 A16N0M-10-84 A16N0R-01-84 A16N0R-10-84 A16R-30-01-84 A16R-30-10-84 A26-22-00-84 A26-30-01-84 A26-30-10-84 A26-40-00-84 A26M-30-01-84 A26M-30-10-84 A26N1-30-10-84 A26N1M-01-84 A26N1M-10-84 A26N1R-01-84 A26N1R-10-84 A26R-30-01-84 A26R-30-10-84 A30-30-01-84 A30-30-10-84 A30M-30-01-84 A30M-30-10-84 A30R-30-01-84 A30R-30-10-84 A40-30-01-84 A40-30-10-84 A40M-30-10-84 A40M-30-11-84 A40R-30-10-84 A40R-30-11-84 A45-22-00-84 A45-40-00-84 A50-30-00-84 A50-30-11-84 A50-40-00-84 A50M-30-11-84 A50N2-30-11-84 A50N2M-11-84 A50N2R-11-84 A50R-30-11-84 A63-30-00-84 A63-30-11-84
$ 450.00 $ 480.00 $ 1,365.00 $ 1,628.00 $ 84.00 $ 84.00 315.00 315.00 375.00 375.00 165.00 102.00 102.00 165.00 345.00 345.00 102.00 345.00 345.00 413.00 413.00 413.00 413.00 228.00 183.00 183.00 228.00 405.00 405.00 183.00 405.00 405.00 480.00 480.00 480.00 480.00 252.00 252.00 548.00 548.00 623.00 623.00 297.00 297.00 639.00 639.00 750.00 750.00 360.00 360.00 300.00 330.00 413.00 713.00 330.00 713.00 810.00 810.00 342.00 372.00
AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA
1.4 1.4 1.6 1.7 1.4 1.4 1.6 1.6 1.7 1.7 1.5 1.4 1.4 1.5 1.6 1.6 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.5 1.4 1.4 1.5 1.6 1.6 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.4 1.4 1.6 1.6 1.7 1.7 1.4 1.4 1.6 1.6 1.7 1.7 1.5 1.5 1.4 1.4 1.5 1.6 1.4 1.6 1.7 1.7 1.4 1.4
A63M-30-11-84 A63R-30-11-84 A75-22-00-84 A75-30-00-84 A75-30-11-84 A75-40-00-84 A75M-30-11-84 A75N3-30-11-84 A75N3M-11-84 A75N3R-11-84 A75R-30-11-84 A9-22-00-84 A9-30-01-84 A9-30-10-84 A9-40-00-84 A95-30-00-84 A95-30-11-84 A95M-30-11-84 A95R-30-11-84 A9M-30-01-84 A9M-30-10-84 A9N00-30-10-84 A9N00M-01-84 A9N00M-10-84 A9N00R-01-84 A9N00R-10-84 A9R-30-01-84 A9R-30-10-84 AE110-30-00-04 AE110-30-11-04
$ 870.00 $ 1,013.00 $ 525.00 $ 383.00 $ 413.00 $ 525.00 $ 1,155.00 $ 413.00 $ 1,155.00 $ 1,298.00 $ 1,298.00 $ 120.00 $ 78.00 $ 78.00 $ 120.00 $ 420.00 $ 450.00 $ 1,230.00 $ 1,425.00 $ 255.00 $ 255.00 $ 78.00 $ 255.00 $ 255.00 $ 315.00 $ $ $ $ $ 315.00 315.00 315.00 660.00 690.00
AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA
1.6 1.7 1.5 1.4 1.4 1.5 1.6 1.4 1.6 1.7 1.7 1.5 1.4 1.4 1.5 1.4 1.4 1.6 1.7 1.6 1.6 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.4 1.4 1.6 1.7 1.5 1.5 1.4 1.4 1.5 1.6 1.4 1.6 1.7 1.7 1.4 1.4 1.6 1.7 1.5 1.4 1.4 1.5 1.6 1.4 1.6 1.7 1.7 1.4 1.4 1.6 1.7 1.10
BC16-22-00-04 BC16-30-01-04 BC16-30-10-04 BC16-40-00-04 BC16M-30-01-04 BC16M-30-10-04 BC16N0-30-10-04 BC16N0M-01-04 BC16N0M-10-04 BC16N0R-01-04 BC16N0R-10-04 BC16R-30-01-04 BC16R-30-10-04 BC25-22-00-04 BC25-30-01-04 BC25-30-10-04 BC25-40-00-04 BC25M-30-01-04 BC25M-30-10-04 BC25N1-30-10-04 BC25N1M-01-04 BC25N1M-10-04 BC25N1R-01-04 BC25N1R-10-04 BC25R-30-01-04 BC25R-30-10-04 BC30-30-00-04 BC30-30-22-04 BC30M-30-01-04 BC30M-30-10-04 BC30R-30-01-04 BC30R-30-10-04 BC9-22-00-04 BC9-30-01-84 BC9-30-10-84 BC9-40-00-04 BC9M-30-01-04 BC9M-30-10-04 BC9N00-30-10-04 BC9N00M-01-04 BC9N00M-10-04 BC9N00R-01-04 BC9N00R-10-04 BC9R-30-01-04 BC9R-30-10-04 BED110 BED40 BED50 BED75 BED95 BEM110-30 BEM16-30 BEM26-30 BEM40-30 BEM75-30 BES110-30 BES75-30 BEXT-75 BSM16-30 BSM25-30BC
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
210.00 147.00 147.00 210.00 435.00 435.00 147.00 435.00 435.00 503.00 503.00 503.00 503.00 273.00 228.00 228.00 273.00 495.00 495.00 228.00 495.00 495.00 570.00 570.00 570.00 570.00 267.00 297.00 668.00 668.00 743.00 743.00 165.00 123.00 123.00 165.00 345.00 345.00 123.00 345.00 345.00 405.00 405.00 405.00 405.00
AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA
1.5 1.4 1.4 1.5 1.6 1.6 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.5 1.4 1.4 1.5 1.6 1.6 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.4 1.4 1.6 1.6 1.7 1.7 1.5 1.4 1.4 1.5 1.6 1.6 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.15 1.14 1.14
BSM30-30BC CA5-01 CA5-04E CA5-04M CA5-04N CA5-10 CA5-11/11E CA5-11/11M CA5-22E CA5-22M CA5-22N CA5-31E CA5-31M CA5-40E CA5-40N CAL5-11 CC5-01 CC5-10 CCL5-01 CDL5-01 DB200 DB25/25A DB25/32A DB80 DLA12-30-84 DLA16-30-84 DLA26-30-84 DLA9-30-84 DR25-A-110 DR25-A-220/380 DR25-A-24 DR25-A-48 DR25-A-500 DS25-A-110 DS25-A-220/380 DS25-A-24 DS25-A-48 DS25-A-500 DX25 KBC30-* KBC30G-* KC22E-04 KC31E-04 KC40E-04 KC44E-04 KC62E-04 LC26-B1 LC30-T LD110 LK110 LK75-A LK75-A1 LW110 MS325-0.16 MS325-0.25 MS325-0.40 MS325-0.63 MS325-1.0 MS325-1.6 MS325-12.5
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
45.00 15.00 30.00 30.00 30.00 15.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 15.00 15.00 45.00 45.00
AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA MA MA MA MA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA MA MA MA MA MA MA MA
1.14 1.9 1.9 1.9 4.5 1.9 1.9 1.9 1.9 1.9 4.5 1.9 1.9 1.9 4.5 1.9 1.9 1.9 1.13 1.13 3.5 3.5 3.5 3.5 2.2 2.2 2.2 2.2 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 4.5 1.13 4.4 4.4 4.4 4.4 4.4 3.5 3.5 1.15 1.9 1.9 1.9 1.15 2.2 2.2 2.2 2.2 2.2 2.2 2.2
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ 60.00 $ 30.00 $ 38.00 $ 45.00 $ 131.00 $ 153.00 $ 234.00 $ 117.00 $ 60.00 $ 60.00 $ $ $ $ $ $ $ $ $ $ 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 15.00 60.00
AE110M-30-11-04 $ 1,785.00 AE110R-30-11-04 $ 2,048.00 AE45-22-00-04 $ 420.00 AE45-40-00-04 $ 420.00 AE50-30-00-04 $ 345.00 AE50-30-11-04 AE50-40-00-04 AE50M-30-11-04 AE50N2-30-11-04 AE50N2M-11-04 AE50N2R-11-04 AE50R-30-11-04 AE63-30-00-04 AE63-30-11-04 AE63M-30-11-04 AE63R-30-11-04 AE75-22-00-04 AE75-30-00-04 AE75-30-11-04 AE75-40-00-04 AE75M-30-11-04 AE75N3-30-11-04 AE75N3M-11-04 AE75N3R-11-04 AE75R-30-11-04 AE95-30-00-04 AE95-30-11-04 AE95M-30-11-04 AE95R-30-11-04 BA5-50 $ $ $ $ $ 375.00 473.00 803.00 375.00 803.00
$ 930.00 $ 930.00 $ 447.00 $ 477.00 $ 1,080.00 $ 1,208.00 $ 570.00 $ 488.00 $ 518.00 $ 570.00 $ 1,365.00 $ 518.00 $ 1,365.00 $ 1,493.00 $ 1,493.00 $ 525.00 $ 555.00 $ 1,440.00 $ 1,635.00 $ 15.00
$ 36.00 $ 72.00 $ 72.00 $ 72.00 $ 144.00 $ 144.00 $ 6.00 $ 6.00 $ 30.00 $ 23.00 $ $ $ $ $ 15.00 15.00 15.00 96.00 96.00
$ 225.00 $ 53.00 $ 165.00 $ 180.00 $ 195.00 $ 180.00 $ 23.00 $ 30.00 $ 45.00 $ 165.00 $ $ $ $ $ 90.00 75.00 15.00 23.00 30.00
AC 1030 6/98
III
MS325-16 MS325-2.5 MS325-20 MS325-25 MS325-2BB MS325-2BB1 MS325-2BB2 MS325-4.0 MS325-4BB MS325-4BB1 MS325-4BB2 MS325-6.3 MS325-9.0 MS325-AS MS325-BB1 MS325-H MS325-HES MS325-HG MS325-HGES MS325-HK02 MS325-HK11 MS325-HK20 MS325-NT MS325-SA MS325-SA1 MS325-SA3 MS325-SK01 MS325-SK10 MS325-SM1 MS325-ST110 MS325-ST230 MS325-ST24 MS325-ST3 MS325-UA110 MS325-UA230
$ 128.00 $ 110.00 $ 141.00 $ 149.00 $ 16.00 $ 20.00 $ 20.00 $ 110.00 $ 22.00 $ 25.00 $ 25.00 $ 110.00 $ 128.00 $ 10.00 $ 17.00 $ $ $ $ $ 52.00 52.00 60.00 60.00 22.00
MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA MA
2.2 2.2 2.2 2.2 2.4 2.4 2.4 2.2 2.4 2.4 2.4 2.2 2.2 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
MS325-UA24 MS325-UA400 MS325-UA415 MS325-UA48 MS325-UA480 MS325-UA60 N22E-84 N31E-84 N40E-84 N44E-84 N53E-84 N62E-84 N71E-84 N80E-84 RA30 RA5 RC5-1/133 RC5-1/250 RC5-1/440 RC5-1/50 RC5-2/133 RC5-2/250 RC5-2/440 RC5-2/50 RV-BC6/250 RV-BC6/380 RV-BC6/60 RV5/133 RV5/250 RV5/440 RV5/50 TA110DU110 TA110DU90 TA25DU0.16 TA25DU0.25
$ $ $ $ $
MA MA MA MA MA MA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA
2.4 2.4 2.4 2.4 2.4 2.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 1.10 1.10 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 4.5 4.5 4.5 1.9 1.9 1.9 1.9 3.4 3.4 3.4 3.4
TA25DU0.4 TA25DU0.63 TA25DU1.0 TA25DU1.4 TA25DU1.8 TA25DU11 TA25DU14 TA25DU19 TA25DU2.4 TA25DU25 TA25DU3.1 TA25DU32 TA25DU4.0 TA25DU5.0 TA25DU6.5 TA25DU8.5 TA42DU25 TA42DU32 TA42DU42 TA75DU25 TA75DU32 TA75DU42 TA75DU52 TA75DU63 TA75DU80 TA80DU42 TA80DU52 TA80DU63 TA80DU80 TE5S-115 TE5S-230 TE5S-24 TP180DA TP180IA TP40DA
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $
63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00 63.00
AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 1.11 1.11 1.11 1.9 1.9 1.9
TP40IA UA110-30-00-84 UA110-30-11-84 UA26-30-10-84 UA40-30-10-84 UA50-30-00-84 UA50-30-11-84 UA75-30-00-84 UA75-30-11-84 UA95-30-00-84 UA95-30-11-84 VE5-1 VE5-2 VM5-1 WB75A-* ZA110-* ZA16-* ZA40-* ZA75-* ZAE110-* ZAE75-* ZL110 ZL50 ZL63 ZL75 ZL95 ZLT45 ZLT50 ZLT75
$ $ $ $ $ $ $ $ $ $
108.00 525.00 570.00 225.00 338.00 345.00 375.00 450.00 480.00 465.00
AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA
1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.10 1.13 1.13 1.13 1.13 1.13 1.13 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15
$ 55.00 $ 60.00 $ 60.00 $ 60.00 $ 120.00 $ $ $ $ 120.00 120.00 120.00 120.00 $ 75.00 75.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 26.00 26.00 26.00 30.00 30.00 30.00
$ 495.00 $ 45.00 $ 45.00 $ 21.00 $ 84.00 $ $ $ $ $ 60.00 24.00 30.00 57.00 90.00
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ 63.00 $ 78.00 $ 78.00 $ 78.00 $ 102.00 $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ 102.00 102.00 102.00 102.00 102.00 135.00 135.00 135.00 135.00 120.00 120.00 120.00 108.00 108.00 108.00
$ 22.00 $ 22.00 $ 5.00 $ 25.00 $ 10.00 $ $ $ $ $ $ $ $ $ $ 25.00 22.00 22.00 16.00 55.00 55.00 55.00 55.00 55.00 55.00
AC 1030 6/98
IV
A Line contactors
A9 A110
Maximum UL/CSA horsepower ratings Includes NEMA sizes 00 3 CE mark Compact space saving design Standard auxiliary contact configurations: A9 A40 1 N.O. or 1 N.C. A50 A110 1 N.O. and 1 N.C. Can be supplied without auxiliaries Additional auxiliary contact blocks are available D.C. ratings & D.C. control operation available Fast, snap-on DIN rail mounting Double break contact design Snap-on front mounted accessories include mechanical latch, pneumatic timer, and 1 & 4 pole auxiliary contact blocks Common accessories for A9 A110 contactors Complete range of 4 pole contactors 21A 105A Easy coil change Captive terminal screws NEMA, UL, IEC, CSA, VDE and most other international standards UL File No: E39231 (A9 A75) UL File No: E79416 (A95 A110) CSA File No: LR56745 (A9 A75) CSA File No: LR19700 (A95 A110) Touch safe design: All connection terminals are protected against accidental touch Terminals supplied open for ease of wiring Operates over an extended voltage range of 85% to 110% of rated control voltage Screwdriver guide holes
Index
Features ................................................ 1.1 Description .................................. 1.2 1.3 Non-reversing ............................. 1.4 1.5 Mechanically interlocked ...................... 1.6 Reversing .............................................. 1.7 For capacitor switching ......................... 1,8 Accessories ............................... 1.9 1.17 Technical data ......................... 1.18 1.28 Motor data ........................................... 1.29 Approximate dimensions ........ 1.30 1.40
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
AC 1030 6/98
1.1
Contactors
A & AE
Application
A Line contactors are mainly used for controlling 3-phase motors and for controlling power circuits corresponding to their operating characteristics up to 690 and even 1000 VAC. and 440 VDC.
Contactors
6-
1-
2-
3-
4-
5-
0 A50-3
Connecting point for control leads in top part of main terminals of A50 A75 contactors. For A95 & A110 contactors these are additional power connections. Terminal marking according to IEC 947-4-1, EN 50005, EN 50012 and NEMA standards.
16-
2-
3-
4-
Terminals delivered in open position with captive screws (screws of unused terminals must be tightened). Screwdriver guidance for all terminals makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 Part. 100. All A9 A40 contactor terminals as well as A45 A110 contactor auxiliary contact and coil terminals ensure IP20 degree of protection according to IEC 947-1.
2 T1
A9 A110
Terminal screws: Posidrive (+,-) N 2 for all A9 A40 terminals and for A50 A110 coil terminals. M8 screws with 6.5 mm slot for A50 A75 main terminals. M8 hex threaded socket screw for A95 & A110 main terminals.
A9-30-10-84
Frame size Power pole 30 = 3 N.O. 40 = 4 N.O. 22 = 2 N.O. & 2 N.C. Coil voltage (see coil voltage selection chart) Auxiliary contacts 10 = 1 N.O. & 0 N.C. 01 = 0 N.O. & 1 N.C. 11 = 1 N.O. & 1 N.C. 00 = No auxiliary provided Coil voltage selection chart
Hz
Cntr type 12
60 A 50 A DC BC 07 DC AE 80
24 81 81 01 81
AC 1030 6/98
1.2
BC
Contact types
3 pole contactors with built in N.O. or N.C. auxiliary contact for BC9 BC25 contactors. 4 pole contactors: 4 N.O. or 2 N.O. & 2 N.C. without any auxiliary contacts.
A
ABB
ABB
ABB
Pos. 3 / Pos. 4
Pos. 1, 2, 5, 6
Quick mounting on mounting rail according to IEC 715 and EN 50022 standards: 35 x 7.5 mm 35 x 15 mm
V DC 220
Terminal screw types: Posidrive (+,-) N 2; M3.5 for all BC9 and BC16 terminals and BC18 BC30 coil terminals. Posidrive (+,-) N 2; M4 for BC18 and BC25 main terminals. Posidrive (+,-) N 2; M5 for BC30 main terminals. Holes for screw mounting (screws not supplied). Distance between holes according to EN 50003.
5L3
5-
13
2-
3-
Terminal marking according to IEC 947-4-1, EN 50005, EN 50012 and NEMA standards.
BC9-30-1
2-
2T1
3-
4T2
4- T3 6
5- 14
Terminals delivered in open position with captive screws (screws of unused terminals must be tightened). Screwdriver guidance for all terminals makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106Part. 100. Location of function marker.
BC9 BC30
Stops for attaching front mounted accessories.
BC9-30-10-04
Frame size Power pole 30 = 3 N.O. 40 = 4 N.O. 22 = 2 N.O. & 2 N.C. Coil voltage (see coil voltage selection chart) Auxiliary contacts 10 = 1 N.O. & 0 N.C. 01 = 0 N.O. & 1 N.C. 11 = 1 N.O. & 1 N.C. 00 = No auxiliary provided Coil voltage selection chart
Hz
Cntr type 12
AC 1030 6/98
60 A 50 A DC BC 07 DC AE 80
24 81 81 01 81
ABB
1.3
Contactors
2 5
20 20
20 55
1200 1200
Non Reversing
A26-30-10
A50-30-00 Standard
A95-30-00
Contactors
AC1 21 25 30 40
AC1 21 33
UL rated 1 0 1 0 1 0 1 0 1 0 0 2 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 2 0 1 0 1 0 1 0 1 0 1 0 1 A9-30-10-84 A9-30-01-84 A12-30-10-84 A12-30-01-84 A16-30-10-84 A16-30-01-84 A26-30-10-84 A26-30-01-84 A30-30-10-84 A30-30-01-84 A40-30-10-84 A40-30-01-84 A50-30-00-84 A50-30-11-84 A63-30-00-84 A63-30-11-84 A75-30-00-84 A75-30-11-84 A95-30-00-84 A95-30-11-84 A110-30-00-84 A110-30-11-84 $ 78 84 102 183 252 297 300 330 342 372 383 413 420 450 450 480 BC9-30-10-04 BC9-30-01-04 BC16-30-10-04 BC16-30-01-04 BC25-30-10-04 BC25-30-01-04 BC30-30-00-04 BC30-30-22-04 AE50-30-00-04 AE50-30-11-04 AE63-30-00-04 AE63-30-11-04 AE75-30-00-04 AE75-30-11-04 AE95-30-00-04 AE95-30-11-04 AE110-30-00-04 AE110-30-11-04 $ 123 147 228 267 297 345 375 447 477 488 518 525 555 660 690
50
45
32
10
10
25
30
41 54 65 80 95 110
10 15 20 25 30 30
15 20 25 30 30 40
30 40 50 60 60 75
40 50 60 75 75 100
NEMA rated
NEMA size Continuous current
00 0 1 2 3
9 18 27 45 90
1.5 3 7.5 10 25
1.5 3 7.5 15 30
2 5 10 25 50
2 5 10 25 50
1 1 1 1 1
0 0 0 1 1
60 A 50 A DC BC 07 DC AE 80
24 81 81 01 81
AC 1030 6/98
CONTACTORS:
1.4
Discount schedule AA
Non Reversing
A9-40-00
A26-40-00
A75-40-00
4 Pole
AC operated DC operated Standard Auxiliary contacts AC operated Catalog number List price DC operated Catalog number List price
21 30 40 65 80 105
21 30
0 0 0 0 0 0
0 0 0 0 0 0
21 30 40 65 105
21 30
0 0 0 0 0
0 0 0 0 0
60 A 50 A DC BC 07 DC AE 80
24 81 81 01 81
AC 1030 6/98
CONTACTORS:
Discount schedule AA
1.5
Contactors
Mech. Int'ld
A12M-30-10-84
General purpose current AC DC oper. oper. Motor switching current Maximum motor horsepower ratings 208V 240V 480V
A75M-30-11-84
Standard 575/600V Auxiliary contacts each contactor AC operated Catalog number
AE110M-30-11-84
DC operated List price Catalog number List price
Contactors
AC1 21 33 45
UL rated 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 A9M-30-10-84 A9M-30-01-84 A12M-30-10-84 A12M-30-01-84 A16M-30-10-84 A16M-30-01-84 A26M-30-10-84 A26M-30-01-84 A30M-30-10-84 A30M-30-01-84 A40M-30-10-84 A40M-30-11-84 A50M-30-11-84 A63M-30-11-84 A75M-30-11-84 A95M-30-11-84 A110M-30-11-84 $ 255 315 345 405 548 639 713 870 1155 1230 1365 BC9M-30-10-04 BC9M-30-01-04 BC16M-30-10-04 BC16M-30-01-04 BC25M-30-10-04 BC25M-30-01-04 BC30M-30-10-04 BC30M-30-01-04 AE50M-30-11-04 AE63M-30-11-04 AE75M-30-11-04 AE95M-30-11-04 AE110M-30-11-04 $ 345 435 495 668 803 1080 1365 1440 1785
NEMA rated
NEMA size Continuous current
00 0 1 2 3
9 18 27 45 90
1.5 3 7.5 10 25
1.5 3 7.5 15 30
2 5 10 25 50
2 5 10 25 50
1 0 1 0 1 0 1 1
0 1 0 1 0 1 1 1
Description
Mechanically interlocked contactors are designed for reversing, 2 speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: A9 A16 mounted on 35mm DIN rail A26 A110 mounted on common baseplate Power wiring is not included. The N.C. electrical interlock is provided with the mechanical interlock. A95 & A110 contactors have the N.C. electrical interlocks provided in the mechanical interlock.
60 A 50 A DC BC 07 DC AE 80
24 81 81 01 81
AC 1030 6/98
1.6
Discount schedule AA
Reversing
A16R-30-01-83 General purpose current AC DC oper. oper. Maximum motor horsepower ratings Motor switching current 208V 240V 480V
A75R-30-00-83 Standard 575V Auxiliary contacts each contactor AC operated Catalog number
AE110R-30-11-83 DC operated
AC1 21 33 45
UL rated 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 A9R-30-10-84 A9R-30-01-84 A12R-30-10-84 A12R-30-01-84 A16R-30-10-84 A16R-30-01-84 A26R-30-10-84 A26R-30-01-84 A30R-30-10-84 A30R-30-01-84 A40R-30-10-84 A40R-30-11-84 A50R-30-11-84 A63R-30-11-84 A75R-30-11-84 A95R-30-11-84 A110R-30-11-84 $ 315 BC9R-30-10-04 BC9R-30-01-04 $ 405 503 570 743 930 1208 1493 1635 2048
375 413 BC16R-30-10-04 BC16R-30-01-04 480 BC25R-30-10-04 BC25R-30-01-04 623 BC30R-30-10-04 BC30R-30-01-04 750 810 AE50R-30-11-04 1013 1298 1425 1628 AE63R-30-11-04 AE75R-30-11-04 AE95R-30-11-04 AE110R-30-11-04
NEMA size
Continuous current
00 0 1 2 3
9 18 27 45 90
1.5 3 7.5 10 25
1.5 3 7.5 15 30
2 5 10 25 50
2 5 10 25 50
1 0 1 0 1 0 1 1
0 1 0 1 0 1 1 1
$ 315
BC9N00R-10-04 BC9N00R-01-04
413 BC16N0R-10-04 BC16N0R-01-04 480 BC25N1R-10-04 BC25N1R-01-04 810 AE50N2R-11-04 1298 AE75N3R-11-04
Description
Reversing contactors are designed for reversing type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: A9 A16 mounted on 35mm DIN rail A26 A110 mounted on common baseplate The N.C. electrical interlock is provided with the mechanical interlock. A95 & A110 contactors have the N.C. electrical interlocks provided in the mechanical interlock.
For additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $20 to list price for each additional auxiliary, and see page 1.18 for available combinations.
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19
60 A 50 A DC BC 07 DC AE 80
24 81 81 01 81
Discount schedule AA
1.7
Contactors
List price
Catalog number
List price
Capacitor Switching
Catalog number
List price
Contactors
Contactor type
12.5 16 20 27.5 35 40
25 32 40 55 70 80
30 40 50 70 75 85
1 1 0 1 0 1 0 1 0 1
0 0 0 1 0 1 0 1 0 1
UA26-30-10-84 UA30-30-10-84 UA50-30-00-84 UA50-30-11-84 UA75-30-00-84 UA75-30-11-84 UA95-30-00-84 UA95-30-11-84 UA110-30-00-84 UA110-30-11-84
$ 225 338 345 375 450 480 465 495 525 570
For 3 phase capacitors carrying out single bank or stepped bank compensation. Max. peak current : 100 times the capacitor nominal r.m.s. current at Ue 500V or 90 times for Ue>500V Electrical durability: 100,000 operating cycles.
220/240V 40 C 55 C 70 C 40 C 380/400/415V 55 C 70 C Power in kvar 50/60 Hz 440V 40 C 55 C 70 C 40 C 500/550V 55 C 70 C 40 C 660/690V 55 C 70 C Max. permissible peak current (kA) Ue 500V Ue >50C
UA26 12 11 UA30 16 16 UA50 20 20 UA75 30 30 UA95 35 35 UA110 40 40 * Use these values for Ue = 415V
9 11 20 25 30 35
20 27.5 33 50 60/65* 75
22 30 36 55 65 75
22 30 35 54.5 65 75
17 20 35 44 55 70
22 32 37.5 62.5 70 80
22 32 37.5 58.5 70 80
30 40 51 86 75 90
30 40 51 80 75 90
26 35 51 65 65 85
AC 1030 6/98
CONTACTORS:
1.8
Discount schedule AA
Accessories
List price
4 blocks: A9 A26 BC9 BC30 5 blocks: A30, A40 6 blocks: A45 A110 AE45 AE110 1 block: A9 A26-40-00 A30 A110 AE45 AE110 BC9 BC25-40-00 BC30-30-00 A9 A40-30-10 BC9 BC25-30-10
1 1 1 1 4 3 2 4 2 3 2 4 2
N.O. N.C. N.O. Early make N.C. Late break N.O. N.O. & 1 N.C. N.O. & 2 N.C. N.C. N.O./2 N.C.1 N.O. & 1 N.C. N.O. & 2 N.C. N.C. N.O./2 N.C.1
CA5-10 CA5-01 CC5-10 CC5-01 CA5-40E CA5-31E CA5-22E CA5-04E CA5-11/11E CA5-31M CA5-22M CA5-04M CA5-11/11M CAL5-11
$ 15
30
Pneumatic timers
Mounting on Timing range Contacts N.O. N.C. Catalog number List price
A9 A75
On delay 0.1 40 s On delay 10 180 s Off delay 0.1 40 s Off delay 10 180 s
1 1 1 1
1 1 1 1
$ 108
TP40DA
Interlocks
Feature Mounting on Contacts N.O. N.C. Catalog number List price
Mechanical/electrical Mechanical
2 2
$ 45 45 21
Note: Use type VE 5-2 for mechanical and electrical interlocking between contactors A40 and A50.
VE5-1
Varistor
A9 A110
24 50 VAC 50 133 VAC 110 250 VAC 250 440 VAC 24 50 VAC/DC 50 133 VAC/DC 110 250 VAC/DC 250 440 VAC/DC 24 50 VAC/DC 50 133 VAC/DC 110 250 VAC/DC 250 440 VAC/DC
RV5/50 RV5/133 RV5/250 RV5/440 RC5-1/50 RC5-1/133 RC5-1/250 RC5-1/440 RC5-2/50 RC5-2/133 RC5-2/250 RC5-2/440 $ 30
RC
A9 A40
RV5/50
RC5-1/50
RC
A45 A110
LK75-A
LK75-A1
LK110
$ 15 15 23
AC 1030 6/98
1.9
Contactors
CAL5-11
CA5-10
Accessories
24 VDC 24 VDC
RA5 RA30
$ 75
RA5
Identification marker
Mounting on Coil voltage Catalog number List price
A9 A110
Pack of 50
BA5-50
$ 15
Mechanical latches
For contactors Catalog number List price
Contactors
RA5 mounted on A75 contactor RA30 mounted on BC16 contactor BA5-50 WB75A-04
CONTACTORS: Description: 1.1 1.3
WB75A-5
$ 84
5 - Coil voltage suffix. Refer to Coil Voltage Selection chart and substitute the desired coil voltage suffix for the 5.
Coil voltage selection chart mechanical latches for B, BC, BE & A, AE contactors
50 Hz 60 Hz Voltage code
24 - 28 42 - 48 48 - 55 110 - 127 220 - 255 230 - 277 380 - 440 440 - 480
01 02 03 04 06 05 07 08 Operation: After closing, the contactor continues to be held in the closed position by the latching mechanisim should the supply voltage fail at the contact coil terminals. Contactor opening can be controlled: electrically by an impulse* (AC or DC) on the WB75A block coil. The coil is not designed to permanently energized. manually by pressing the pushbutton on the front face of the WB75A block. Mounting: WB75A is clipped onto the front face of the contactor.
Range: WB75A for contactors A9 A75, BC9 BC30, AE45 AE75 and control relays N and KC. Description: WB75A block: contains a mechanical latching device with electromagnetic impulse unlatching (AC or DC) or manual unlatching. Captive screw type connecting terminals, built-in cable clamps, M 3.5 (=, -) posidrive 1 screw with screwdriver guidance, delivered untightened and protected against accidental direct contact.
AC 1030 6/98
1.10
Accessories
List price
A9 A110
1 1 1
$ 120
Application
Utilization When used in wye-delta starters, the TE5S lags the wye connection and provides a lapse of 50 ms before the switchover to the delta connection.
TE5S-*
Chart
15
TE 5S t1
A1
t1+t2
Equivalent diagram
A1
15
Operation On energization, the green U indicator light (voltage applied) comes on. Contact 15 16 then immediately moves to the closed position. Count-down of the programmed time immediately commences. When the time delay has elapsed, contact 15 16 opens and at the same time the 50 ms lapse, t2, begins after which contact 15 18 moves to the closed position. The yellow R indicator light comes on. On de-energization, the U and R indicator lights go out and, after the 250 ms resetting time, the device is ready for a new cycle. Mounting Mounts on 35mm DIN rail.
16
TE5S
U
0.5 0.1 1.0
0.8 ... 8s t1 6 ... 60s
R
Star-Delta Timer
16
18
Front face
AC 1030 6/98
CONTACTORS:
18
A2
A2
1.11
Contactors
Description According to the type of device chosen, the electronic circuit has a 24 VAC/VDC, 110 120 VAC or 220 230 VAC supply. An output relay with reversing contact ensures high current switching. A twoposition switch allows selection of one of the two time delay ranges: 0.8 to 8 s or 6 to 60 s. The 0.1 to 1.0 adjustable knob allows an initial setting without steps within the previously selected range which can then be adjusted using a stopwatch. Note: We recommend that you allow for temperature drift for the final adjustment of the time delay setting. Drift: 0.2% per C. For example, a setting made at 20 C will yield a time delay shorter by 7% at 55 C in an enclosure. ( 0.2% per C i.e. 0.2 x 35 = 7%). The TE5S, which is not affected by these settings, establishes a fixed lapse of 50 ms between the opening of contact 15 16 and the closing of contact 15 18. It is this time delay that prevents from arc short-circuit during wye to delta switching.
Accessories
Technical data
Type Compliance with standards Rated insulation voltage Ui according to IEC 947-5-1 Rated supply voltage Uc Rated frequency limits Supply voltage range Overvoltage protection Load factor Average consumption
Contactors
Time delay range (t1 ) selected by switch Temperature drift Mechanical setting accuracy On-load reiteration accuracy under constant conditions Minimum time lapse (t2 ) Min. time lapse after 1 million operations Resetting time (maximum) Front panel display:
Rated operational voltage Ue acc. to IEC 947-5-1 Conventional free air thermal current Ith Rated operational current Ie acc. to IEC 947-5-1 DC- 13 24 VDC AC- 15 Permissible air temperature for operation for storage Mechanical durability in millions of operations Electrical durability in millions of operations On-load maximum switching frequency Shock and vibration withstand Fixing on mounting rail according to EN 50022 Connecting terminals Tightening torque Connecting capacity Rigid solid Flexible without cable end 24 115 VAC 220 230 VAC
A A A
C C
ops./h
N.m
1 or 2 x mm2 1 or 2 x mm
2
Degree of protection acc. to IEC 529, IEC 947-1 and EN 60 529 Housing Terminals IP 50 IP 20
AC 1030 6/98
CONTACTORS:
1.12
Accessories for A, AE, BC contactors & KC control relays Coils & coil voltage codes
Coils AC operated
For contactors Catalog number
Accessories
List price
$ 24 30 57 60 36 57 90 45
Coils DC operated
KC and BC9 BC30 AE45 AE75 AE95 AE110 Auxiliary including an insertion contact and a varistor for DC operated contactors AE45 AE75 AE95 AE110
ZA16-81
5 Coil voltage suffix. Refer to Coil Voltage Selection charts below and substitute the desired coil voltage code for the 5.
24 28 32 42 48 60 100 110 110 120 115 127 140 150 208 220
81 16 17 82 83 73 74 84 89 29 30 34 36
200 220 230 230 240 230 240 230/4001 380 400 400 415 440 500 550 660 690
200 220 230 240 240 260 277 230/4001 380 400 415 415 440 480 500 600
75 80 88 42 62 63 48 85 86 51 53 55 56 58
12 24 42 48 50 60
07 01 02 16 17 03
80 81 82 83 21 84
22 04 27 05 33 34
85 86 87 88 89 38
AC 1030 6/98
1.13
Contactors
Accessories
A1 1 A2 2 3 4 5 6 1 2 3 4 5 6
A1
A2
A9 A16 A26 A30, A40 A50 A75 A95, A110 BC9, BC16 BC25 BC30
$ 23 30 45 165 180 23 30 45
Application
Connections between the main poles of two 3 pole contactors mounted side by side so that they operate as reversing contactors.
Description
Contactors
A1 1 A2 2 3 4 5 6 1 2 3 4 5 6 A1 A2
The sets are made up of three reversing connections and three phase to phase connections. BEM16-30 BEM26 and 40-30 BEM75 and 110-30 BSM16-30, BSM25 and 30-30BC Insulated, Insulated, Insulated, Insulated, solid, rigid copper wires stranded, rigid copper wires solid copper bars solid, rigid copper wires
BES75-30 BES110-30
$ 75 90
A95 A110
Application
Connections between the main poles of a wye-delta starter.
Description
1 3 5
These sets are made up of: Three line contactor/wye contactor connections line side. Three wye contactor/delta contactor connections load side. The shorting connection for the "S" contactor. BED40 BED50 BED110 Insulated, stranded, rigid copper wires. Insulated, solid copper bars.
BED75
The above connection sets allow a mechanical interlock unit to be mounted between the wye and delta contactors if required.
AC 1030 6/98
CONTACTORS:
1.14
Accessories
List price
LD-110
$ 30
Application
The LD110 terminal block is designed to increase the connection capacity of the contactor on which it is mounted: A(E)95 or A(E)110.
Description
Block housing three connectors: 1 per phase. Each connector is equipped with an HC, M8 socket head screw and has the following connection details: Stranded conductor (1) 62/0 OR (2) 41/0 Busbar max. width 12 mm
Mounting
LD110
Terminal extensions
Dimensions Mounting on contactors Hole mm Bar mm Catalog number List price
6.5 6
12X3 15x3
BEXT-75 LW-110
$ 15
Application
They are designed to increase the width of the contactor terminal pads to allow larger connectors to be mounted.
BEXT-75
Description
Terminal extension sets contain 3 bars.
Contact kits
For contactors Catalog number List price
3 Pole A/AE A/AE A/AE A/AE95-30 A/AE110-30 4 Pole A/AE45-40 A/AE50-40 A/AE75-40 ZL75 ZLT45 ZLT50 ZLT75 150 150 210 ZL50 ZL63 ZL75 ZL95 ZL110 $ 113 135 158 225 255
AC 1030 6/98
CONTACTORS:
1.15
Contactors
The LD110 terminal block can be mounted in the terminal slots located on line or load side of contactor.
Accessories
A1
A2
A1
A2
1L1
3L2
5L3
A1
1L1
3L2
5L3
NC
NO
21 NC
A1
1L1
3L2
5L3
13 NO
A1
1L1 3L2
5L3
2T1
4T2 6T3
A2
A2 2T1 4T2 6T3 NC 22
A2
2T1
4T2
6T3
NO 14
A2
2T1 4T2
6T3
A9 A40-30-01
A1 A2
A9 A40-30-10
A9 A40-30-01
A9 A40-30-10
A1
R3
R5
1L1
3L2
5L3
7L4
Contactors
A1
R3
R5
A1
1L1
3L2
5L3
7L4
R4
R6
A2
2T1
4T2
6T3
8T4
A2
A2 2 R4 R6 8 A2 2T1 4T2 6T3 8T4
1L1
6-
3L2
5L3
5-
13
21
31
43
NO NC 14 22
NC NO 32 44
6-
NO NC 14 22
NC NO 32 44
5-
A1
1L1
3L2
5L3
13 NO
21 NC
31 NC
43 NO
2T1
4T2 6T3
A2
A2
2T1
4T2 6T3
NO 14
NC 22
NC 32
NO 44
A9 A16-30-22
A1 A2
A50 A110-30-22 2
A1 A2
1L1
3L2
5L3
A1
1L1
3L2
5L3
13 NO
21 NC
31 NC
43 NO
53 NO
A1
1L1 3L2
5L3
13X 21X NO NC
2T1
4T2
6T3
A2
A2
2T1
4T2 6T3
NO 14
NC 22
NC 32
NO 44
NO 54
A2
2T1 4T2
6T3
NO 14X
NC 22X
A9 A40-30-32
A9 A40-30-32
Other possible contact combinations with auxiliary contacts added by the user
A1 1L1 3L2 5L3 13 NO 21 NC
A1
A2
A1
A2
A1
A2
A1
A2
NO 14 NC 22
=
2NO
=
23NO
Combination 11
A1 1L1 3L2 5L3 13 NO 21 NC 33 NO
Combination 11
A1 A2
A9 A40-30-10 + CA5-01
Combination 21
A1 A2
Combination 21
A1 1L1 3L2 5L3 13X 21X 31X 43X NO NC NC NO
A1
A2
A1
A2
1L1
13X 21X
3L2
5L3
43X 31X NO 13X NC 21X
1L1
3L2
5L3
43X NO 31X NC
1L1
3L2
5L3
7L4
1L1
3L2
5L3
7L4
A2 2T1 4T2 NO NC NC 6T3 14X 22X 32X NO 44X
=
22X 14X 32X 44X NC 22X NO 14X
+
32X NC 44X NO
6- 13 2- 3- 4- 5NO 6- 14 2- 3- 4- 5-
6- 1- 2- 3- 4- 5-
=
6- 1- 2- 3- 4- 5-
-3 NO -4
Combination 22
A1 1L1 3L2 5L3 7L4 13 NO
AC 1030 6/98
2T1
4T2
6T3
A2
2T1
4T2
6T3
A2
2T1
4T2
6T3
8T4
A2
2T1
4T2
6T3
8T4
A2
A2
2T1
4T2
6T3
8T4
NO 14
Combination 22
CONTACTORS:
A50 A75-30-11
+ CAL5-11
Selection: 1.4 1.8
Combination 10
A45 A75-40-00
+ CA5-10
Combination 10
Motor data: 1.31 Dimensions: 1.32 1.42
1.16
Accessories
A1
1L1 3L2
5L3
1L1
3L2
5L3
NO 13X
1L1
3L2
5L3 C D L 5 6T3
A3
1L1
3L2
5L3 C C L 5
A2
2T1 4T2
6T3
V d.c.
AE50 AE110-30-00
A1 A2 A3 U 36 X
C D L 5
NC 21X
35 X
NC 22X NO 14X
A1
1L1 3L2
5L3
13X 21X NO NC
1 L1 2 T1 4 T2 6 T3
2T1
4T2 6T3
A3
2T1
4T2
2T1
4T2 6T3
A3
A2
2T1 4T2
6T3
NO 14X
NC 22X
3 L2 5 L3
AE50 AE75-30-00
AE50 AE75-30-11
AE95 AE110-30-00
AE50 AE110-30-11
Coil wiring
A1 1 R3 R5 7
V d.c. A2 A1 A3
A1
A2
A1
A2
A1
A2
1L1
NO 13X NC 21X
3L2
5L3 C C L 5 6T3
A3
R3
R5
7 C D L 5 8
A3
1L1
3L2
5L3
7L4 C D L 5 8T4
A3
A2
R4
R6
8
15 X
AE45 AE75-22-00
16 X
NC 22X NO 14X
A1
1L1
3L2
5L3
7L4
1 L1
2 T1
2T1
4T2
R4
R6
2T1
4T2
6T3
A2
2T1
4T2
6T3
8T4
7 L4
8 T4
AE95 AE110-30-11
AE45 AE75-22-00
AE45 AE75-40-00
AE45 AE75-40-00
Coil wiring
1L1
13
3L2
21 31
5L3
43
NO NC NC NO
A1 1L1 3L2 5L3
NC
NO
14
22
32
44
21 NC
A1
1L1
3L2
5L3
13 NO
A1
1L1
3L2
5L3
13 NO
21 NC
31 NC
43 NO
2T1
4T2 6T3
A2
A2 2T1 4T2 6T3 NC 22 A2 2T1 4T2 6T3 NO 14
A2
2T1
4T2 6T3
NO 14
NC 22
NC 32
NO 44
BC9 BC25-30-01
BC9 BC25-30-10
BC30-30-22
BC9 BC25-30-01
BC9 BC25-30-10
BC30-30-22
A1
A1
A1
1L1
3L2
5L3
R3
R5
A1
A1
R3
R5
A1
1L1
3L2
5L3
7L4
2T1
4T2 6T3
A2
R4
R6
8
A2
A2
2T1
4T2
6T3
8T4
BC30-30-00
BC9 BC25-22-00
BC9 BC25-40-00
A2
BC9 BC25-22-00
BC9 BC25-40-00
BC30-30-00
Other possible contact combinations with auxiliary contacts added by the user
A1 1L1 3L2 5L3 13 NO 21 NC 33 NO
A1
A1
A1
A1
1L1
3L2
5L3
1L1
3L2
5L3
A2 2T1 4T2 6T3 NO 14 NC 22 NO 34
=
25NO
13 21 NO NC 14 22
1-
22-
33-
4-
=
14-
-3 NO -4
-1 NC -2
Combination 21
A1 1L1 3L2 5L3 13 NO 21 NC
2T1
4T2
6T3
A2
2T1
4T2
6T3
A2
A2 2T1 4T2 6T3
NO 14
NC 22
AC 1030 6/98
Combination 21
CA5-10
Combination 11
BC30-30-00
+ CA5-10 + CA5-01
Combination 11
CONTACTORS:
1.17
Contactors
Accessories
Positioning
Pneumatic timers
Left side
Front face
CA5-10 or CA5-01
TP D or TP I
CAL 5-11
VE5-1 or VM 5-1
VE 5-2
Configurations of accessories are different depending on whether front or side mounted. N Contactor relays A and AE Contactors Type Main poles Built-in auxiliary contacts Accessories Front mounting Auxiliary contact blocks TP - A Pneumatic 1-pole CA54-pole CA5timer block Accessories Side mounting Auxiliary contact Blocks Interlock units 2-pole CAL5-11 q mechanical VM5q mech. + elec. VE5-
Contactors
N ............................... 1 N ............................... 1 N ................................... N ................................... N ................................... N ................................... N ................................... N ................................... A9 A26 A9 A26 A9 A26 A9 A26 A9 A16 A9 A26 A30, A40 A30, A40 A30, A40 A50 A75 A45 A75 A45, A75 A95, A110 A50 A75 A95, A110 AE50 AE75 AE45 AE75 AE45, AE75 AE95, AE110 A50 A75 AE50, AE75 A95, A110 AE95, AE110 3 3 4 2 0 0 0 2
2 2 E 3 1 E 4 0 E 4 5 6 7 8 1 0 0 0 4 3 2 1 0 0 1 0 0 E E E E E
1 1
1 to 4 CA51-pole blocks
or 1 TP - A block
1 to 2 + CAL5-11 block
1 to 2 + CAL5-11 blocks
or 1 CA54-pole block
or 1 TP - A block
3 0 2 2 3 0 3 2 3 0 1 0 3 0 0 1 3 0 3 2 3 4 2 3 0 0 2 0 0 0 0 0 0 0 0 0
or 1 CA5- 4-pole block or 1 TP - A block + 1 to 2 + 1 CA5- 1-pole block + 1 CA5- 1-pole block CAL5-11 blocks 1 CA5- 4-pole block or + 2 CA5- 1-pole blocks or 1 TP - A block + 2 CA51-pole blocks 1 TP - A block + 2 CA51-pole blocks 1 TP - A block + 2 CA51-pole blocks + 1 to 2 CAL5-11 blocks + 1 to 2 CAL5-11 blocks + 1 to 2 CAL5-11 blocks + 1 CAL5-11 block
or 1 VM/E 5-1 block + 1 CAL5-11 block or 1 VM/E 5-1 block + 1 CAL5-11 block or 1 VE5-2 block + 1 CAL5-11 block or 1 VE5-2 block + 1 CAL5-11 block or 1 VE5-2 block
3 0 2 2 3 0 2 2 3 4 2 3 3 3 3 3 0 0 2 0 0 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1
1 to 6 CA51-pole blocks
AC 1030 6/98
1 In mounting position 5 (see page 1.20), there should be no more than 2 "N.C." front-mounted auxiliary contacts The CAL 5-11 side-mounted blocks offer additional "N.C." contacts. 2 Whatever the mounting position (see page 1.20), there should be no more than 2 "N.C." front-mounted auxiliary contacts The CAL 5-11 side-mounted blocks offer additional "N.C." contacts.
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
1.18
Accessories
NC 01
02 NC
01 NC
A9 - A110 Contactor
NC 02
A9 - A110 Contactor
AC 1030 6/98
1.19
Contactors
Technical data
9 1/3 2 1.5 1.5 2 21 9 1/2 2 2 2 5 7.5 15 15 A600 600 10 7200 720 P600 600 5 0.2 0.7 1.04 18 10 2 9
.75 2 25 11 3/4 2 3 3 7.5 10 15 15 A600 600 10 7200 720 P600 600 5 0.2 0.7 1.04 18 10 2 9
27 2 3 7.5 7.5 10 40 28 2 5 7.5 10 20 25 35 35 A600 600 10 7200 720 P300 600 5 0.2 1.01 1.35 12 8 2 15
36 3 7.5 50 32 3 7.5 10 10 20 30 50 50 A600 600 10 7200 720 P300 600 5 0.2 1.2 1.54 84 2 20
65 65 65 2.25 81 1 40
90 25 30 50 105 80 7.5 15 25 30 60 75 105 105 A600 600 10 7200 720 P300 600 5 0.2 2.25 3 81 1 40
125 95 7.5 20 30 30 60 75 A600 600 10 7200 720 P300 600 5 0.2 3.5 6 6 2/0 1 50
140 110 10 25 30 40 75 100 A600 600 10 7200 720 P300 600 5 0.2 5 7 6 2/0 1 50
ABB
Pos. 4
Pos. 3 Pos. 1 30
ABB
Pos. 1
ABB
CONTACTORS:
1.20
ABB
Contactors
Mounting positions
Pos. 2 Pos. 6
30
30
ABB
AC 1030 6/98
Pos. 5
Technical data
A9 3 or 4
A12 3
A16 3 or 4
A26 3 or 4
A30 3
A40 3
A45 4
A50 3 or 4
A63 3
A75 3 or 4
A95 3
A110 3
Insulation characteristics
Rated insulation voltage Ui according to IEC947-4-1 and VDE0110 (Gr. C) according to UL/CSA Rated impulse withstand voltage Uimp. V V 1000 600 8 kV
with conductor cross sectional area Utilization category AC-3 for air temperature close to contactor 55C Rated operational current Ie / AC-3 (1)
A A A mm2
25 22 18 2.5
27 25 20 4
30 27 21 4
45 40 32 6
55 55 39 10
60 60 42 16
70 60 50 25
100 85 70 35
115 95 80 50
125 105 85 50
3-phase Motors
M 3
220-230-240 V 380-400 V 415 V 440 V 500 V 690 V 1000 V 220-230-240 V 380-400 V 415 V 440 V 500 V 690 V 1000 V
A A A A A A A kW kW kW kW kW kW kW Hz
17 17 17 16 14 10 4 7.5 9 9 9 9
26 26 26 26 22 17 6.5 11 11 15 15 15
40 37 37 37 33 25 11 18.5 18.5 22 22 22
53 50 50 45 45 35 23 15 22 25 25 30 30 30
65 65 65 65 55 43 25 18.5 30 37 37 37 37 33
75 75 72 70 65 46 28 22 37 40 40 45 40 37
96 96 96 93 80 65 30 25 45 55 55 55 55 40
Rated operational power AC-3 (1) 1500 r.p.m. - 50 Hz 1800 r.p.m. - 60 Hz 3-phase Motors
M 3
Rated frequency limits Mechanical durability in millions of operating cycles Max. mechanical switching frequency Max. electrical switching frequency Electrical durability Rated making capacity AC-3 according to IEC947-4-1 Rated breaking capacity AC-3 according to IEC947-4-1 Max. breaking capacity cos = 0.45 (cos = 0.35 for Ie > 100 A) Short-circuit protection for contactors without thermal O/L relays - Motor protection excluded1 Ue 500 V a.c. gG (gl) type fuses Rated short-time withstand current Icw at 40C ambient temp., in free air, from a cold state 1s 10 s 30 s 1 min 15 min Ie /AC-1 Ie /AC-3 at 440 V at 690 V for AC-1 for AC-3 for AC-2, AC-4
10 3600 600 600 150 600 600 150 600 600 150 600 600 150 300 300 150 300 300 150 600 1200 300
cycles/h cycles/h cycles/h cycles/h 600 1200 300 600 1200 300 600 1200 300 600 1200 300 600 1200 300
3600
see pages 1.27 1.30 10 x Ie AC-3 8 x Ie AC-3 A A 250 100 250 100 250 100 420 170 820 340 820 340 900 490 900 490 900 490 900 490 12 x Ie AC-3 8 x Ie AC-3 1160 800 1160 800
A A A A A A W
AC 1030 6/98
1 Please consult us for the protection of motor starters against short circuits.
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
1.21
Contactors
Technical data
A9 3 or 4
A12 3
A16 3 or 4
A26 3 or 4
A30 3
A40 3
A45 4
A50 3 or 4
A63 3
A75 3 or 4
A95 3
A110 3
Certifications approvals Air temperature close to contactor fitted with thermal O/L relay without thermal O/L relay for storage Climatic withstand Mounting positions: (see diagram, page 1.20) Positions 1 to 5 Position 6 Operating altitude Shock withstand acc. to IEC68-2-27 and EN60068-2-27 Mounting position 1 (See page 1.20) Mounting
C1
C C C
25 to + 55 (0.85 1.1 Uc) 40 to + 55 (0.85 1.1 Uc) / 40 to + 70 (Uc) 60 to + 80 acc. to IEC 68-2-30 and 68-2-11 UTE C 63-100 specification II Ambient temperature 55C and control voltage 0.85 1.1 Uc Ambient temperature 55 70C and control voltage equal to Uc Ambient temperature 55C and control voltage 0.95 1.1 Uc Ambient temperature > 55C unauthorized 3000 1/2 sinusoidal shock for 11ms: no change in contact position
25 to +55 (0.85 1.1Uc) 25 to +70 (0.85 1.1Uc) 40 to +70 acc. to IEC 68-2-30
Contactors
A B1
B2
Shock direction:
A, C1, C2 B1 B2
: 20 g : 5g : 15 g acc. to IEC715 35 x 15 EN50 022 75 x 25 EN50 023 2 x M6 M8 slotted screw head with single connector 13 x 10 mm HC, M 8 hexagon socket screw with single connector 14 x 14 mm acc. to IEC715 and EN50 023 75 x 25
C2
on mounting rail
acc. to IEC715 and EN50 022 35 x 7.5 mm 35 x 15 mm 2 x M4 (+,) pozidriv 2screw M 3.5 with cable clamp M4 with clamp M 5 with 2x(5.6x6.5mm) double connect.
by screws (not supplied) Connecting terminals (delivered in open position) Main poles
M 3.5 (+,-) pozidriv 2 screws with cable clamp (+,-) pozidriv 2 screw and cable clamp M 3.5 M4 min. max. 1.5 6 1.5 6 14 14 10 4.2 M 3.5 min. max. 2.5 16 2.5 16 2.5 10 2.5 10 min. - max. 1-4 0.75 2.5 0.75 2.5
1 1
Connecting capacity Main conductors (poles) Rigid solid ( 4 mm2) / rigid stranded ( 6 mm2) Flexible without cable end Bars or lugs: max. width hole 1 x mm2 2 x mm2 1 x mm2 2 x mm2 mm mm > 1 or 2 x mm2 1 x mm2 2 x mm2 min. max. 14 14 0.75 2.5 0.75 2.5 8 3.7 min. max. 6 50 6 25 6 35 6 16 min. max. 6 95 6 35 6 70 6 35 30 6 0.75 2.5 1 2.5 0.75 2.5 0.75 2.5 0.75 2.5
Auxiliary conductors (built in aux. terminals + coil terminals) Rigid solid Flexible without cable end Degree of protection acc. to IEC529, IEC947-1 and EN60529 Main terminals Coil terminals Auxiliary terminals
Protection against direct contact acc. to VDE0106 Part. 100 IP20 IP20 IP20 IP10
AC 1030 6/98
1 1 or 2 times 0.75 2.5 mm2 but with 0.75 and 1 mm2 cable end.
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
1.22
Technical data
A110 3
70C
Rated control circuit voltage Uc at 50 Hz at 60 Hz Operating time Between coil energization and: N.O. contact closing N.C. contact opening Between coil deenergization and: N.O. contact opening N.C. contact closing V V ms ms ms ms 10 26 7 21 4 11 9 16 8 21 6 18 4 11 7 14 20 690 24 600 8 27 7 22 4 11 7 14 10 25 7 22 7 15 10 18
690
Short circuit protection gG (gl) type fuses Rated short time withstand current Icw Insulating resistance at 500 V d.c. Min. switching capacity Non overlapping time between N.O. and N.C. contacts ms Heat dissipation per pole at 6 A Electrical durability Max. switching frequency AC-15 according to IEC947-5-1 making current: 10 x Ie with cos = 0.7 and Ue breaking current: Ie with cos = 0.4 and Ue The curve opposite shows the electrical durability of the built in auxiliary contacts with respect to the breaking current.
0.10
1200 cycles/h
3 2 1 0.5 0.3 0.2 0.1 0.02 0.05 0.1 0.2 0.3 0.5 1 2 3 4 5 6 10
AC 1030 6/98
This curve has been drawn for resistive and inductive loads up to 690 V, 40 - 60 Hz.
1.23
Contactors
Technical data
BC9 3 or 4
BC16 3 or 4
BC25 3 or 4
BC30 3
AE45 4
AE50 3 or 4
AE63 3
AE75 3 or 4
AE95 3
AE110 3
Insulation characteristics
Rated insulation voltage Ui according to IEC947-4-1 and VDE0110 (Gr. C) according to UL/CSA Rated impulse withstand voltage Uimp. V V 690 600 6 kV 1000 600 1000 600 8 kV 1000 600 8 kV
with conductor cross sectional area Utilization category AC-3 for air temperature close to contactor 55C Rated operational current Ie /AC-3 (1)
A A A mm2
22 20 17 2.5
28 25 23 4
45 40 32 6
55 45 36 6
70 60 50 25
100 85 70 35
115 95 80 50
125 105 85 50
Contactors
3 phase motors
M 3
220 230 240 V 380 400 V 415 V 440 V 500 V 690 V 1000 V 220 230 240 V 380-400 V 415 V 440 V 500 V 690 V 1000 V
A A A A A A A kW kW kW kW kW kW kW Hz
9 9 9 9 7 6 2.2 4 4 4 4 4
25 25 25 20 17 13 6.52 11 11 11 11 11
331 30 30 27 23 18 9 15 15 15 15 15
40 37 37 37 33 25 11 18.5 18.5 22 22 22
53 50 50 45 45 35 23 15 22 25 25 30 30 30 25 400
65 65 65 65 55 43 25 18.5 30 37 37 37 37 33
75 75 72 70 65 46 28 22 37 40 40 45 40 37
96 96 96 93 80 65 30 25 45 55 55 55 55 40
Rated operational power AC-3 (1) 1500 r.p.m. 50 Hz or 1800 r.p.m. 60 Hz 3 phase motors
M 3
Rated frequency limits Mechanical durability in millions of operating cycles Max. mechanical switching frequency Max. electrical switching frequency Electrical durability Rated making capacity AC-3 according to IEC947-4-1 Rated breaking capacity AC-3 according to IEC947-4-1 Max. breaking capacity with cos j = 0.45 (cos j = 0.35 for Ie > 100 A) Short-circuit protection for contactors without thermal O/L relay Motor protection excluded3 Ue 500 V a.c. gG (gl) type fuses Rated short-time withstand current Icw at 40C ambient temperature, in free air, from cold state Heat dissipation per pole 1s 10 s 30 s 1 min 15 min Ie /AC-1 Ie /AC-3 at 440V at 690V for AC-1 for AC-3 for AC-2, AC-4
10 3000 600 600 150 see page 1.27 1.30 10 x Ie / AC-3 8 x Ie / AC-3
A A
200 120
315 210
380 290
A A A A A A W W
AC 1030 6/98
1 32 A at 240V 2 7.5 kW at 240V 3 For the protection of motor starters against short circuits, please consult us.
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
1.24
Technical data
BC9 3 or 4
BC16 3 or 4
BC25 3 or 4
BC30 3
AE45 4
AE50 3 or 4
AE63 3
AE75 3 or 4
AE95 3
AE110 3
Certifications approvals Air temperature close to contactor with a thermal O/L relay mounted without thermal O/L relay mounted for storage Climatic withstand Mounting positions: (see drawing page 1.20)
according to IEC 68-2-30 and 68-2-11 UTE C 63-100 specification II - 55 C: 0.85 to 1.1 Uc - = 55 to 70 C: Uc - 55 C: 0.95 to 1.1 Uc - > 55 C: not acceptable Position 5: see tables p. 1.19 Positions 1,3 ,4 Positions 2,6 m
C1
Operating altitude Shock withstand acc. to IEC68-2-27 and EN60068-2-27 Mounting position 1 (See page 1.20) Mounting
A B1
B2
Shock direction:
C2
A, C1, C2 : 20 g B1 : 5g B2 : 15 g Note: only on plate for A95 and A110 according to IEC715 and EN50 022 35 x 7.5 mm 35 x 15 mm 2xM4 (+,-) pozidriv 2 screw with cable clamp M 3.5 M4 M5 according to IEC715 35 x 15 EN50 022 75 x 25 EN50 023 2xM6 M8 slotted screw head with single connector 13 x 10 mm HC, M8, hexagon socket screw with single connector 14 x 14 mm acc. to IEC715 and EN 50 023 75 x 25
on mounting rail
by screws (not supplied) Connecting terminals (delivered in open position) Main poles
M 3.5 (+,-) pozidrive 2 screw with cable clamp (+,-) pozidriv 2 screw with cable clamp M 3.5 M4 min. max. min. max. 1.5 6 1.5 6 1.5 4 1.5 4 8 3.7 2.5 10 2.5 10 2.5 6 2.5 6 10 4 min. max. 14 1 2.5 0.75 2.5 Protection against direct contact according to VDE 0106 Part. 100 IP10 IP20 IP10 IP10 IP20 IP20 min. max. 6 50 6 25 6 35 6 16 13 5 min. max. 6 95 6 35 6 70 6 35 30 6
Connecting capacity Main conductors (poles) Rigid solid ( 4 mm2) / rigid stranded ( 6 mm2) Flexible without cable end Bars or lugs: Auxiliary conductors (built in auxiliary terminals + coil terminals) Rigid solid Flexible without cable end1 Degree of protection acc. to IEC529, IEC947-1 and EN60529 Main terminals Coil terminals Auxiliary terminals 1 x mm2 2 x mm2 1 x mm2 2 x mm2 max. width hole 1 or 2 x mm2 1 x mm2 2 x mm2 min. max. 14 14 1 2.5 0.75 2.5 mm mm >
AC 1030 6/98
1.25
Contactors
Technical data
The curve opposite shows the electrical durability of the built in auxiliary contacts with respect to the breaking current.
Million ops.
Contactors
*The use of surge suppressors increases the opening time on a scale of 1.1 to 1.5 for a varistor suppressor and on a scale of 4 to 8 for a diode suppressor.
Operational current frequency Rated making capacity Rated breaking capacity Short circuit protection gG (gl) type fuses Rated short time withstand current Icw Insulation resistance at 500 V d.c. Min. switching capacity Non overlapping time between N.O. and N.C. contacts Heat dissipation per pole at 6 A Electrical durability Max. switching frequency AC-15 according to IEC947-5-1 making current: 10 x Ie with cos = 0.7 and Ue breaking current: Ie with cos = 0.4 and Ue
2 0.15
This curve has been drawn for resistive and inductive loads up to 690 V, 40 60 Hz.
AC 1030 6/98
CONTACTORS:
1.26
Technical data
Millions of operations 10
9 7 5 3 1 9 7 5 3
0.5
0.3 0.2
9 7 5 3 1
1 3 5 7 9
1 3 5 7 9
AC 1030 6/98
CONTACTORS:
1.27
Contactors
A6 3 A7 5 A9 5 A1 10
A3 0 A4 0
A4 5 A5 0
A1 6
A2 6
A9 A1
Technical data
Millions of 10 operations
2 1.5 1
9 7 5 3 1 9 7 5 3 1
A6 3 A7 5 A9 5
A9
A1
A1
A2
A3
A4
A5
Millions of 10 operations
3 2
9 7 5 3
9 7 5 3 1
0.5
1 3 5 7 9 1 3 5 7 9 1 3 5 7 9
0.3 0.2
A1
10
Contactors
CONTACTORS:
0.5
1 3 5 7 9 1 3 5 7 9 1 3 5 7 9
0.3
1 3 5 7 9 1 3 5 7 9
AC 1030 6/98
2
Description: 1.1 1.3
5
Selection: 1.4 1.8
10
20
30
50
100
200
Motor data: 1.31
300
Dimensions: 1.32 1.42
1.28
Technical data
Switching cage motors; starting, reverse operation and step-by-step operation. The breaking current Ie is equal to 6 x Ie, where Ie is the motor rated operational current (Ie = motor full load current)
2 A1 6
A4
A5
A3
A6
A9
A1
A7
5 A9 5
A2
1 3 5 7 9
1 3 5 7 9
AC 1030 6/98
CONTACTORS:
1.29
Contactors
9 7 5 3
A1
10
Technical data
Millions of operations
10 5 3 2
9 7 5 3 1
9 7 5 3 1
9 7 5 3 1
9 7 5 3 1
A9 A1
Contactors
CONTACTORS:
9 7 5 3 1
9 7 5 3 1
1 3 5 7 9
0.005 2 3 5 10 20 30 50 100 200 300 500 1000 427 Breaking current Ic (A)
AC 1030 6/98
1.30
Motor data
Technical data
1/10 1/8 1/6 1/4 1/3 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 500
3.0 3.8 4.4 5.8 7.2 9.8 13.8 16.0 20.0 24.0 34.0 56.0 80.0 100.0 135.0
4.0 4.8 6.4 9.0 11.8 16.6 26.4 38.0 48.0 72.0 94.0 118.0 138.0 180.0 226.0
4.4 6.4 8.4 12.0 13.6 19.2 30.4 44.0 56.0 84.0 108.0 136.0 160.0 208.0 260.0
1.5 1.9 2.2 2.9 3.6 4.9 6.9 8.0 10.0 12.0 17.0 28.0 40.0 50.0 68.0 88.0 110.0 136.0 176.0 216.0
2.0 2.4 3.2 4.5 5.9 8.3 13.2 19.0 24.0 36.0 47.0 59.0 69.0 90.0 113.0 133.0 166.0 218.0
2.2 3.2 4.2 6.0 6.8 9.6 15.2 22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0 192.0 248.0 312.0 360.0 480.0 602.0
1.0 1.2 1.4 1.8 2.3 3.2 4.5 5.1 6.4 7.7 10.9 17.9 27.0 33.0 44.0 56.0 70.0 87.0 112.0 139.0
1.3 1.8 2.3 3.3 4.3 6.1 9.7 14.0 18.0 27.0 34.0 44.0 51.0 66.0 83.0 103.0 128.0 165.0 208.0 240.0 320.0 403.0 482.0 560.0 636.0 786.0
2.5 3.5 4.0 5.0 6.0 8.5 14.0 21.0 26.0 34.0 44.0 55.0 68.0 88.0 108.0
1.0 1.2 1.6 2.3 3.0 4.2 6.6 9.0 12.0 18.0 23.0 29.0 35.0 45.0 56.0 67.0 83.0 109.0 135.0 156.0 208.0
1.1 1.6 2.1 3.0 3.4 4.8 7.6 11.0 14.0. 21.0 27.0 34.0 40.0 52.0 65.0 77.0 96.0 124.0 156.0 180.0 240.0 302.0 361.0 414.0 477.0 590.0
2.0 2.8 3.2 4.0 4.8 6.8 11.2 16.0 20.0 27.0 35.0 44.0 54.0 70.0 86.0
0.8 1.0 1.3 1.8 2.4 3.3 5.3 8.0 10.0 14.0 19.0 24.0 28.0 36.0 45.0 53.0 66.0 87.0 108.0 125.0 167.0
0.9 1.3 1.7 2.4 2.7 3.9 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0 52.0 62.0 77.0 99.0 125.0 144.0 192.0 242.0 289.0 336.0 382.0 472.0
AC 1030 6/98
1 To obtain full load currents for 200V and 208V motors, increase corresponding 220 240V ratings by 15 percent and 10 percent. 2 To obtain full load currents for 265V and 277V motors, decrease corresponding 220 240V ratings by 13 percent and 17 percent.
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
1.31
Contactors
Dimensions
00.00
00.00
Inches
Millimeters
2.68
68
0.22 1.73
44 5.5
1.38
35
2.91
74
2.36
60
1.97
50
0.18
4.5
Contactors
2.91
74
5.50
139.7
2.68
68
4.06
103
0.22
5.5
1.38
35
2.32
59
2.36
60
1.97
50
0.18
4.5
2.68
68
1.73
44
0.22
5.5
1.38
35
2.91
74
2.36
60
1.97
50
3.46
88
133.5
5.26 0.18
4.5
RESET
0.14
3.5
0.24
6
3.74
95
5.50
139.7
2.68
68
4.06
103
0.22
5.5
1.38
35
2.32
59
2.91
74
2.36
60
1.97
50
3.46
88
5.26
133.5
0.18
4.5
RESET
0.14
3.5
AC 1030 6/98
0.24
6
3.74
95
CONTACTORS:
1.32
00.00
00.00
Inches
Millimeters
Dimensions
3.44
87.3
0.35
9
1.77
45
3.54
90
2.76
70
3.15
80
0.17
4.2
5.25
133.4
3.44
87.3
4.64
117.9
4.84
123.0
0.35
9
2.32
59
0.22
5.5
133.4
5.25 3.54
90
4.64
117.9
2.76 3.15
70 80
0.17
4.2
1.77
45
2.72
69
3.44
87.3
2.13
54
0.35
9
1.77
45
3.54
90
2.76
70
3.15
80
4.10
104.2
5.79
147
0.17
4.2
RESET
0.53
13.5
0.24
6
4.31
109.5
3.69
93.6
5.25
133.4
3.44
87.3
4.64
117.9
4.84
123.0
0.35
9
2.32
59
0.22
5.5
5.25
133.4
174.5
6.87 5.79
147
3.54
90
4.64
117.9
2.76 3.15
70 80
4.10
104.2
AC 1030 6/98
RESET
0.17
4.2
0.52 0.24
13.5
CONTACTORS:
1.33
Contactors
3.69
Dimensions
Approximate dimensions for 3 pole, AC operated A contactors & starters A30 & A40
4.26
108.3
00.00
00.00
Inches
Millimeters
4.02
102
2.13
54
0.35
9
1.77
45
3.54
90
2.76
70
3.15
80
0.17
4.2
A30 & A40 + VM5 or VE5 Mechanically interlocked contactor, 3 pole, AC operated
4.60
117
5.25
133.4
4.64
117.9
Contactors
CONTACTORS:
4.26
108.3
4.84
123.0
4.02
102
2.32
59 9
0.22
5.5
0.35
133.4
5.25 3.54
90
4.64
117.9
2.76 3.15
70 80
0.17
4.2
1.77
4.26
108.3
45
2.72
69
4.02
102
0.35
9
1.77
45
3.54
90
2.76
70
3.15
80
4.20 6.44
163.5 TA25DU32 ONLY
5.87
149
106.7
0.17
4.2
RESET
0.35
8.8
0.24
6
4.08
104
4.02
102
2.13
54
0.35
9
1.77
45
3.54
90
2.76
70
3.15
80
4.09
104
154.5
6.08
0.17
4.2
RESET
0.33
8.3
AC 1030 6/98
0.24
6
4.43
112.5
1.34
00.00
00.00
Inches
Millimeters
Approximate dimensions for 3 pole, AC & DC operated A contactors & starters A30 A(E)75
4.60
117
Dimensions
A30 & A40 + VM5 or VE5 + TA25 Reversing starter , 3 pole, AC operated
5.25
133.4
4.64
117.9
4.26
108.3
4.84
123.0
4.02
102
2.32
59 9
0.22
5.5
0.35
133.4
5.25 3.54
90
4.64
117.9
7.25
191
6.44
163.5 TA25DU32 ONLY
5.87
149
RESET
0.17
4.2
0.35
8.8
0.24
6
4.08
104
1.77
45
2.72
69
A30 & A40 + VM5 or VE5 + TA42 Reversing starter , 3 pole, AC operated
4.60 5.25
133.4 117
4.64
117.9
4.26
108.3
4.84
123
4.02
102
2.32
59 9
0.22
5.5
0.35
5.25
133.4
3.54
90
4.64
117.9
154.5
6.08
RESET
0.17
4.2
0.33
8.3
1.77
45
2.72
69
4.00
101.5
2.76
70
0.39
10
2.36
60
4.33
110
3.94 3.54
100 90
AC 1030 6/98
0.24
6.2
CONTACTORS:
1.35
Contactors
Dimensions
Approximate dimensions for 3 pole, AC & DC operated A contactors & starters A(E)50 A(E)75
4.54
115.3
00.00
00.00
Inches
Millimeters
A(E)50 A(E)75 + VM5 or VE5 Mechanically interlocked contactor, 3 pole, AC & DC operated
6.00
152.5
6.62
168.2
4.25
108
6.10
155
4.00
101.5
3.00
76.3
0.22
5.5
0.39
10
6.50
165
5.87 4.33
110 149
3.54
90
3.94
100
Contactors
0.24
6.2
2.36
60
3.35
85
4.00
101.5
2.76
70
0.39
10
2.36
60
4.33
110
3.94
100
3.54 4.88 90
124
6.93
176
0.24
6.2
RESET
0.62
15.8
0.24
6
4.45
113
A(E)50 A(E)75 + VM5 or VE5 + TA75 Reversing starter, 3 pole, AC & DC operated
4.54
115.3
6.62
168.2
4.25
108
6.00
152.5
6.10
155
4.00
101.5
3.00
76.3
0.22
5.5
0.39
10
165
6.50
3.54 4.33
110
5.87
149
90
3.94 4.88
100 124
8.25
209.5
6.93
176
RESET
0.24
6.2
AC 1030 6/98
0.24
6
0.62 4.45
15.8 113
2.36
Technical data: 1.20 1.30
60 Motor data: 1.31
3.35
85
CONTACTORS:
1.36
00.00
00.00
Inches
Millimeters
Approximate dimensions for 3 pole, AC & DC operated A contactors & starters A(E)95 & A(E)110
4.86
123.5
Dimensions
3.54
90
0.39
10
3.07
78
5.35
136
5.83
148
4.96
126
0.24
A(E)95 & A(E)110 + VE5 Mechanically interlocked contactor, 3 pole, AC & DC operated
8.70
221
6.2
5.17
131
7.91
200.1
7.68
195
4.86
123.5
3.90
99
0.31
8
0.39
10
8.10
205.7
4.33
148
7.28
185
4.96
126
5.35
136
0.24
6.2
3.07
4.13
105
78
4.61
117
3.54
90
0.39
10
3.07
78
5.35
136
4.96
126
6.38
162
8.43
214
0.24
6.2
RESET
1.00
25.4
AC 1030 6/98
0.24
6
CONTACTORS:
4.49
1.37
Contactors
Dimensions
Approximate dimensions for 3 pole, AC & DC operated A contactors & starters A(E)95 & A(E)110
4.86
123.5
00.00
00.00
Inches
Millimeters
3.54
90
0.39
10
3.07
78
5.35
136
4.96
126
6.93
176
10.16
258
Contactors
0.24
6
0.24
6.2
RESET
0.98
25
5.16
131
A(E)95 & A(E)110 + VE5 + TA80 Reversing starter, 3 pole, AC & DC operated
8.70
221
5.17
131
7.91
200.1
7.68
195
4.86
123.5
3.90
99 10
0.31
8
0.39
205.7
8.10 4.33
148
4.96 7.28
185 126
5.35
136
9.97
248
6.38 8.43
214
162
RESET
0.24
6.2
0.98 0.24
6 25
4.49
114
3.07
78
4.10
104
A(E)95 & A(E)110 + VE5 + TA110 Reversing starter, 3 pole, AC & DC operated
8.70
221
5.17
131
7.91
200.1
7.68
195
4.86
123.5
3.90
99 10
0.31
8
0.39
205.7
8.10 4.33
148
4.96
126
7.28
185
5.35
136
11.45
290
6.93 10.16
258 176
0.24
RESET
AC 1030 6/98
6.2
0.98
25
CONTACTORS:
1.38
00.00
00.00
Inches
Millimeters
Approximate dimensions for 4 pole, AC & DC operated A contactors & starters A9 A(E)75
2.91
74
Dimensions
2.68
68
0.22 1.73
44 5.5
1.38
35
2.91
74
2.36
60
1.97
50
0.18
4.5
3.69
93.6
3.44
87.3
0.35
9
1.77
45
3.54
90
2.76
70
3.15
80
0.17
4.2
4.45
113
3.62
92
0.39
10
3.23
82
4.33
110
3.94 3.54
100 90
0.24
6.2
4.00
101.5
2.76
70
0.39
10
2.36
60
4.33
110
3.94 3.54
100 90
AC 1030 6/98
0.24
6.2
CONTACTORS:
1.39
Contactors
Dimensions
00.00
00.00
Inches
Millimeters
0.18
4.5
3.18
81.0
2.76
70.0
2.36
60.0
0.35 1.75
44.0 9.0
1.38
35.0
Contactors
0.24
5.5
4.68
119.0
1.77
45.0
2.76 3.34
84.8 70.0
2.36
60.0
0.35 2.12
54.0 9.0
0.24
5.5
4.72
120.0
1.77
45.0
3.15 3.55
90.0 80.0
2.76
70.0
2.13
54.0
AC 1030 6/98
CONTACTORS:
1.40
00.00
00.00
Inches
Millimeters
Approximate dimensions for A & BC contactors Accessories for A9 A(E)110; BC9 BC30
Dimensions
ON-POSITION LATCH
PNEUMATIC TIMER
TYPE A9-16 A26 A30-40 A50-75 AE50-75 A45 A95-110 AE95-110 BC9, BC16 BC25 BC30 IN
MM
A 2.20
56
B 3.96
100.5
C 4.21
107
D 5.71
145
E 5.00
127
F
5.04 128
IN
MM
2.20
56
4.72
119.8
4.97
126.3
6.47
164.3
5.76
146.3
IN
MM
2.20
56
5.30
134.5
5.55
141
7.05
179
6.34
161
IN
MM
3.23
82
5.27
133.9
5.52
140.3
7.03
178.5
6.32
160.4
IN
MM
4.09
104
5.73
145.5
5.98
152
7.48
190
6.77
172
IN
MM
4.02
102
5.91
150
6.16
156.5
7.28
185
6.58
167
IN
MM
5.53
140.5
5.79
147
IN
MM
5.77
146.5
6.02
153
7.52
191
6.81
173
IN
MM
AC 1030 6/98
CONTACTORS:
1.41
Contactors
Notes
Dimensions
00.00
00.00
Inches
Millimeters
Contactors
AC 1030 6/98
CONTACTORS: Description: 1.1 1.3 Selection: 1.4 1.8 Accessories: 1.9 1.19 Technical data: 1.20 1.30 Motor data: 1.31 Dimensions: 1.32 1.42
1.42
DLA starters
DLA
DLA starters
General information
The construction of DLA starters is based on ABB A Line contactors. The mounting plate, including a built-in A contactor, is designed to integrate an ABB manual motor starter type MS325. Starters can be easily made with protection against overloads and short-circuits (Type I or Type II coordination). The technical characteristics of these devices are identical to A Line contactors. The advantages are as follows: Simplified installation: DLA starters mount onto 35 x 15 mm exclusively DIN rail (EN 50022) Direct mounting of manual motor starter MS 325 Contactor coil terminals accessible on lower side. High performance as a result of the combination of the MS325 manual motor starter with high breaking capacity and the new A Line contactor ensuring high electrical durability. Accessory types: on manual motor starter: set of bus bars, external operating mechanism, padlock holder, auxiliary contact, undervoltage coil, shunt trip, etc.
Types of coordination
IEC standard 947-4-1 (EN 60 947-4-1) defines two types of coordination according to the anticipated level of service continuity. The admissible damage limits for the control gear are defined. Coordination Type I: In the event of a short-circuit, the contactor or starter causes no danger to persons or facilities, and cannot function thereafter without repairs being made or parts being replaced. Coordination Type II: In the event of a short-circuit, the contactor or starter causes no danger to persons or facilities, and must be able to function thereafter. Light welding of contacts is possible.
Index
DLA Starter general information ........ Selection ............................................. MS325 General information ............... MS325 Accessories ............................ MS325 Technical data ....................... Approximate dimensions ....................
DLA STARTERS: General info: 2.1 Selection: 2.2 MS325 info: 2.3 MS325 Accessories: 2.4
AC 1030 6/98
2.1
DLA starters
DLA
DLA starters Type MS325 manual motor starter & DLA9 DLA 26 module
+
MS325-1.0 DLA9-30-84
=
DLA starter
MS325
0.10 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 1/8 1/4 1/3 1/2 1 1.5 2 1/10 1/6 1/3 1/2 1 2 2.5 3 3 1/2 1 1.5 2.5 3 5 5 7.5 1/2 3/4 1 2 3 5 7.5 10 10 15 1/2 3/4 1.5 3 5 7.5 10 10 15 20 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A 1200A MS325-0.16 MS325-0.25 MS325-0.40 MS325-0.63 MS325-1.0 MS325-1.6 MS325-2.5 MS325-4.0 MS325-6.3 MS325-9.0 MS325-12.5 MS325-16 MS325-20 MS325-25 $ 96 DLA9-30-84 110 $ 117
DLA starters
2.2
Ordering instructions
The MS325 manual motor starters and the DLA module must be ordered separately and assembled by customer.
AC 1030 6/98
Single phase motor ratings are based upon wiring all three poles in series. In group motor applications, use the lowest maximum fuse or MCCB size.
DLA STARTERS: General info: 2.1 Selection: 2.2 MS325 info: 2.3 MS325 Accessories: 2.4 MS325 Technical data: 2.5 2.6 DLA Dimensions: 2.7
DLA
branch using NEC Table 430-150 on the right. Select fuse from NEC Table 240-6 below. Where Imax falls between two fuse ampere ratings NEC 430-53 (c) permits going to the next high ampere rating. 2. Motor starter & protector selection Select the proper MS325 catalog number for each motor load from page 2.2 based on the actual motor full load current (FLA) using the "Thermal setting range" column for reference.
Selection
Group installation is an approach to building multi-motor control systems in accordance with Section 430-53 of the National Electrical Code. The selection of components used in group installations is a simple process which consists of several steps. First is the selection of the appropriate fuse as Branch Circuit Protective Device (BCPD). Second is the selection of the appropriate motor starter and protector. Third, the selected MS325 must be checked for UL listing with the selected BCPD and the available short circuit current at the application location. 1. Fused disconnect Calculate maximum fuse size according to NEC 430-53 (c). Imax (fuse size) = 175% x FLC (full load current for largest motor) + the sum of FLC (full load current for largest motor) + the sum of FLC values for other motors on that
MS325 data
Motor rating at 460V Horsepower FLA, AC3 MS325 Contactor
1/2 3 5 7.5 10
INCOMING LINES A B C
ISOMAX MCCB or Fusible Switch (If specified)
I>
2
I>
4
I>
6
1M
I>
2
I>
4
I>
6
2M
I>
2
I>
4
I>
6
3M
I>
2
I>
4
I>
6
4M
I>
2
I>
4
I>
6
5M
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
1C
T1 T2 T3 T1 T2 T3
2C
T1 T2 T3
3C
T1 T2 T3
4C
T1 T2 T3
5C
MOTOR
MOTOR
MOTOR
MOTOR
MOTOR
AC 1030 6/98
1 These values of full-load current are for motors running at speeds usual for belted motors and motors with normal torque characteristics. Motors built for especially low speeds or high torques may require more running current, and multispeed motors will have full-load current varying with speed, in which case the nameplate current rating shall be used. The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120, 220 to 240, 440 to 480, and 550 to 600 volts.
DLA STARTERS: General info: 2.1 Selection: 2.2 MS325 info: 2.3 MS325 Accessories: 2.4 MS325 Technical data: 2.5 2.6 DLA Dimensions: 2.7
2.3
DLA starters
DLA
MS325-UA24
$ 55
Shunt trips
Item description List price
$ 55
$ 22
Supporting terminal
Item description Catalog number List price
MS325-AS
$ 10
DLA starters
DLA STARTERS:
Padlocking devices
Item description Catalog number List price
MS325-SA1 MS325-SA3
$ 10 25
MS325-BB1
Handle & front gray plate Emergency red OFF handle, yellow front plate Neutral terminal, 8 AWG, blue Gray handle, black flange Emergency OFF red handle, yellow flange
$ 52 52 5 60 60
Terminal blocks
Item description Catalog number List price
MS325-SM1 MS325-BB1
$ 16 17
Busbars
Item description MS325-SM1 Catalog number List price
2 MS 325, without auxiliary contacts 2 MS 325, with 1 auxiliary contacts 2 MS 325, with 2 auxiliary contacts 4 MS 325, without auxiliary contacts 4 MS 325, with 1 auxiliary contacts 4 MS 325, with 2 auxiliary contacts
$ 16 20 20 22 25 25
MS325-2BB
1 N.O. 1 N.C.
MS325-SK10 MS325-SK01
$ 22
Shaft adapter
MS325-4BB Item description Catalog number List price AC 1030 6/98
MS325-SA
MS325 Technical data: 2.5 2.6
$ 25
DLA Dimensions: 2.7
2.4
Discount schedule MA
DLA
General data
Rated voltage Rated current Rated frequency Electrical and mechanical life endurance Mounting position Ambient temperature Temperature compensation Wire range Standards IEC 157-1, 292-1, 337-1 VDE 0660 part 101, 104, 106, 200 SEV 1090-1, 1092-1, 1093-1 Approvals UL: E137861 (MS 325); E90353 (Auxiliary contact blocks) CSA: LR 15332 NEMKO, DEMKO, FI, SEV, KEMA, KEUR 600 V 25 A (14 setting ranges, 0.1 to 25A) 50 60 Hz 100,000 operations Optional -25C to +50C -25C to + 50C 14 8 AWG
Maximum switching capacity for DC loads using 3 main current paths in series
DC Load DC 1 Voltage 60V 110V 220V 440V 60V 110V 220V 440V 60V 110V 220V 440V Amps 25 25 25 25 25 25 25 25 25 25 25 25
DC 2/3
Tripping values
Thermal tripping setting ranges (A) 0.1 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 9.0 12.5 16 20 25 Magnetic tripping operating current (A) 1.6 2.5 4.0 6.3 12 19 30 48 75 108 150 192 240 300
DC 4/5
Auxiliary leads
Type load Carrying capacity of aux. contacts Thermal permanent current Ith Rated operating for current Ie AC11 up to 220VAC 380VAC 500VAC 60VDC 110VDC 220VDC 440VDC Voltage Amps 6 2 1.5 1.2 1.5 1 0.3 0.1
DC11 up to
Low voltage trip Rated voltage Rated frequency Rated power Operating voltage Drop out (% of nominal control voltage) Pull in
2 h 1 40 20 10 6 4 2 min 1 40 20 10 6 4
3 pole
Tripping time
2 pole
2 1 0.6 0.4 0.2 s 0.1 0.06 0.04 0.02 0.01 0.006 0.004 0.002 0.001
AC 1030 6/98
10
12
14
16
18
2.5
DLA starters
DLA
AA
DLA 9-30
* Ambient temperature 30 C
DLA starters
DLA STARTERS:
DLA 26
* Ambient temperature 30 C
AC 1030 6/98
Selection: 2.2
2.6
DLA
4.27
108.5
1.77
45
8.39
213
35x15 mm EN 50022
6.50 3.08
78.2
0.17
4.2
for M4
DLA 26
2.13
54
4.27
108.5
1.77
45
8.39
213
35x15 mm EN 50022
6.50
3.08
78.2
0.17
4.2
for M4
0.20
5
AC 1030 6/98
DLA STARTERS:
Selection: 2.2
165
2.7
DLA starters
0.20
165
DLA
Notes
DLA starters
AC 1030 6/98
DLA STARTERS: General info: 2.1 Selection: 2.2 MS325 info: 2.3 MS325 Accessories: 2.4 MS325 Technical data: 2.5 2.6 DLA Dimensions: 2.7
2.8
Description
Available for starter construction with A Line contactors and separate panel mounting Designed for close couple mounting for 11 contactors, A9 A110 Separate base mounting available for all overload relays Class 10 adjustable overload relays are standard with all ABB Line starters Reset can also be adjusted to function as a stop button Screwdriver guide holes All terminal screws are available from the front UL File No: E48139 CSA File No: LR98336 Trip indication Remote trip and reset option available Single phase and phase unbalance protection Isolated alarm circuit (N.O.) contact Ambient compensation: -25C to +55C (-13oF to +131oF) Manual test Manual or automatic reset Factory calibrated and tested Wide adjustment range
TA25DU 0.16
Frame size Amp rating
Index
AC 1030 6/98
Features ............................................... 3.1 OLRs for A9 A110 ............................ 3.4 Technical data ..................................... 3.7 Approximate dimensions ................... 3.12
OVERLOAD RELAYS: General info: 3.1 3.2 Selection: 3.3 3.4 Accessories: 3.5 3.6 Technical data: 3.7 3.10 Dimensions: 3.11 3.12
3.1
Overload relays
Description
Product range
Standard relays: Types: TA25DU, TA42DU, TA75DU, TA80DU, TA110DU TA25 to TA110 are directly connected in the motor circuit.
The tripping curves (cold or warm starting, 3 phases and 2 phases) are shown on page 3.10 The relays are built to be self protecting in the event of an overload until the short circuit protection device is activated.
No effect
No effect
No effect
Overload relays
OVERLOAD RELAYS: General info: 3.1 3.2 Selection: 3.3 3.4
AC 1030 6/98
3.2
Selection guide
Types
TA25DU
TA42DU
TA75DU
TA80DU
Main characteristics
Construction 3 pole with ambient temperature compensation. Protection against single phase operation. Built in auxiliary contacts: 1N.O. + 1N.C.
Resetting Setting ranges Number from to 18 0.1 0.16A 24 32A 3 18 25A 29 42A
Convertible:
A30 A40 A50 A63 A75 AE50 AE63 AE75 A95 A110 AE95 AE110
Accessories
Tripping coil Resetting coil Terminal shroud Function markers DS25-A DR25-A Terminals protected against direct contact (without the addition of terminal shrouds) BA5-50
AC 1030 6/98
OVERLOAD RELAYS:
3.3
Overload relays
Selection
TA25DU
0.1 0.16 0.25 0.4 0.63 1.0 1.3 1.7 2.2 2.8 3.5 4.5 6.0 7.5 10 13 18 24
0.16 0.25 0.4 0.63 1.0 1.4 1.8 2.4 3.1 4.0 5.0 6.5 8.5 11 14 19 25 32
TA25DU0.16 TA25DU0.25 TA25DU0.4 TA25DU0.63 TA25DU1.0 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4.0 TA25DU5.0 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 TA25DU32 TA42DU25 TA42DU32 TA42DU42 TA75DU25 TA75DU32 TA75DU42 TA75DU52 TA75DU63 TA75DU80 TA80DU42 TA80DU52 TA80DU63 TA80DU80 TA110DU90 TA110DU110
$ 63
A30 A40
TA42DU
18 25 22 32 29 42 18 22 29 36 45 60 29 36 45 60 25 32 42 52 63 80 42 52 63 80
78
A(E)50 A(E)75
102
135
A(E)95 A(E)110
65 90 80 110
TA75DU
165
Overload relays
TA80DU TA110DU AC 1030 6/98 1 To select an overload relay for BC9 BC30 contactors, delete the A from the catalog number. Ex.: BC9-30-01-04 contactors with setting range of 1.3 1.8: OLR catalog number will be T25DU1.8
OVERLOAD RELAYS: General info: 3.1 3.2 Selection: 3.3 3.4 Accessories: 3.5 3.6 Technical data: 3.7 3.10 Dimensions: 3.11 3.12
3.4
Discount schedule TAA TA25 Discount schedule TBA TA42, TA75 Discount schedule TCA TA80, TA110
Accessories
List price
0.1 24 18 100
25 32 80 200
$ 30 38 45 60
DB25/25A
LC30-T LC26-B1
$ 6 6
DX25
$ 15
Description
LC terminal blocks can be used to convert standard connections into Faston connections: 2 x 6.3 mm or 4 x 2.8 mm per pole. The connections are protected against accidental contact. The LC30-T has a terminal block for the 3 power terminals and a second for the 4 auxiliary terminals of a TA25 DU thermal O/L relay. The LC26-B1 has two identical terminal blocks each for 3 power terminals. This block allows the power terminals to be mounted with two DB25 kits or a TA25DU thermal O/L relay and DB25 kit assembly. NOTE: According to DIN 46429 part 1 and NFC 20-120 the max. capacity of a Faston connection is 25 A.
DB200
LC26-B1
AC 1030 6/98
OVERLOAD RELAYS:
3.5
Overload relays
Accessories
DS25-A remote tripping coil 24V 48V 110V 220/380V 500V DS25-A remote resetting coil 24V 48V 110V 220/380V 500V DR25-A-24 DR25-A-48 DR25-A-110 DR25-A-220/380 DR25-A-500 DS25-A-24 DS25-A-48 DS25-A-110 DS25-A-220/380 DS25-A-500
$ 60
DS25A
Application
The DS25-A coil is used for remote electrical tripping of the TA25 DU thermal O/L relay and is connected to the relay's normally closed 95-96 auxiliary contact. The DR 25-A coil is used for remote electrical resetting of the TA25DU thermal O/L relay which is adjusted for "Manual resetting"; it is connected to the relay's normally open 97-98 auxiliary contact. The coils are not designed for continuous duty. Impulse duration: 0.2 to 0.35 s. Set the button to "Man" (Manual resetting). Mounting: clipped on to TA25DU thermal O/L relay.
DR25A
Installation diagrams
For connection of DS25-A to TA25DU relay For connection of DR25-A to TA25DU relay
L1 STOP
21 22
START OL
13 14 A1
L2/N
L1 STOP
21 22
START OL
13 14 A1
L2/N
Overload relays
L1 3.6
A2
95
96
A2
95
96
M
13 14
M
13 14
OVERLOAD TRIP
E1 E2
OVERLOAD RESET
OL
97 98 E1 E2
OL RESETTING COIL
AUTO
24 14 A1
L2/N OL
L1
OFF HAND
23 13
AUTO
24 14 A1
L2/N OL
A2
95
96
A2
95
96
OVERLOAD TRIP
E1 E2
OVERLOAD RESET
OL
97 98 E1 E2
OL TRIPPING COIL
OVERLOAD RELAYS: General info: 3.1 3.2 Selection: 3.3 3.4 Accessories: 3.5 3.6 Technical data: 3.7 3.10
OL RESETTING COIL
Dimensions: 3.11 3.12
AC 1030 6/98
Technical data
120
Switching frequency
100 80 60 40 20 0 0
ta
1s
To avoid nuisance tripping, TA and T thermal O/L relays have been designed to withstand roughly 15 switching operations per hour with an approximately equal distribution between working and rest cycles. In these conditions, the motor starting time must not exceed 1 second and the starting current must be lower than or equal to 6 times the motor In. For intermittent operations, the diagram opposite specifies relay operating limits. Example: Motor starting time: ................. 1 sec. Load factor: ............................. 40 % Switching frequency: ............... 60 ops./h according to diagram
ta = s 0.5
ta
=1
ta =
.5s
3s
ta = 3.5
1.4
20 40 60 Closing time
80 100(%)
1.3 1.2 1.1 1.0 0.9 -20 -10 0 10 20 30 Ambient temperature 40 50 No tripping
Ambient temperature compensation Thermal O/L relays are compensated against ambient temperature variations by a compensation bimetal which is sensitive to the ambient temperature. Thermal O/L relays are designed to operate between 5 C and +40 C in compliance with standard IEC947-4-1. For a wider range of 25 C to +55 C consult the graph opposite. Example: tripping at 25 C. Tripping takes place before 1.5 times the setting current. Resetting: TA25DU TA110DU thermal O/L relays have convertible manual/automatic resetting. Delivery: in manual resetting mode.
AC 1030 6/98
OVERLOAD RELAYS:
3.7
Overload relays
Technical data
TA42DU
TA75DU
TA80DU
TA110DU
UL, CSA, IEC94741, VDE0660, NF C63 650, BS4941, EN60947-4-1 600V (UL); 690V (IEC) 6 40 to +70 25 to +55 (maximum values: see page 3.7) Humidity in alternate climate KFW, 30 cycles
1
C C
15
multiples of g multiples of g
12 8 Latching below the contactor, screw fixing on main terminals Using screws: 2 x M4 or 35 mm EN50022 TA25DU setting ranges: from 0.1-0.16A to 18-25 A M4 M5 TA25DU setting ranges: 24-32 A
Terminals and cross-sectional areas for main conductors (motor side) screw terminal with cable clamp via tunnel connector flat type for lug or busbar conductor cross-sectional area rigid solid or rigid stranded flexible with cable end recommended busbars Terminals and cross-sectional area for auxiliary conductors screw terminal (screw size) with cable clamp conductor cross sectional area rigid solid or rigid stranded AWG mm2 mm2 mm
M6 81
M6 81
HC, M8 61 16 35 16 35 12 x 3
M 3.5 AWG
2
Overload relays
2 x 18 24
3
Degree of protection according to IEC144, IEC529 DIN 40 050, NFC 20-010 and VDE110/ Part. 106
Pole characteristics
Number of poles Setting ranges Tripping class according to IEC9474 Operating frequency Tripping frequency without untimely tripping Resistance per phase in m and heat dissipation in W at the maximum current setting Protection fuses co-ordination with short circuit protection devices Hz 3 see page 3.4 10A 0 400 Up to 15 ops./h or 60 ops./ h with 40 % load factor when neither the starting current of 6 x In nor the starting time 1s are exceeded. see page 3.9
AC 1030 6/98
1 On a support at an angle of 30 in relation to the vertical plane (standard position). Other positions possible except mounting on a horizontal plane (in this case the tripping mechanism would be located above the bimetals). 2 All the terminals are protected against direct contact according to VDE0106/Part. 100. (without additional terminal shrouds). 3 All the terminals are protected against direct contact according to VDE0106/Part. 100. (with additional terminal shrouds).
OVERLOAD RELAYS: General info: 3.1 3.2 Selection: 3.3 3.4 Accessories: 3.5 3.6 Technical data: 3.7 3.10 Dimensions: 3.11 3.12
3.8
Technical data
from to A A 0.1 0.16 0.25 0.4 0.63 1.0 1.3 1.7 2.2 2.8 3.5 4.5 6.0 7.5 10 13 18 24 0.16 0.25 0.4 0.63 1.0 1.4 1.8 2.4 3.1 4.0 5.0 6.5 8.5 11 14 19 25 32
AC 1030 6/98
OVERLOAD RELAYS:
3.9
Overload relays
Technical data
TA25DU
TA42DU
TA75DU
TA80DU
TA110DU
TA-DU and T-DU thermal O/L relays are 3 pole with manual or automatic resetting mode selection. The reset button can also be used for stopping. Built in auxiliary contacts are physically separate and, consequently, can be used in different circuits (control circuit/indication circuit). Each relay is temperature compensated and ensures phase failure protection. Protective relays up to size TA75DU are protected against direct contact from the front face. The connecting terminals are delivered in open position with (+,-) posidrive screws and screwdriver guidance. It is advisable to tighten unused terminal screws.
TA110DU
(tripping class 10A)
120 100 80 60 40 20 10 8 6
Minutes
Minutes
Minutes
4 2 1 40 20
4 2
4 2 1 40 20
Tripping time
Tripping time
2 Phases
1 40 20
Tripping time
Overload relays
2 Phases
3 Phases 2 Phases
3 Phases
Seconds
Seconds
10 8 6 4 2
2 Phases 3 Phases
10 8 6 4 2
Seconds
3 Phases
10 8 6 4 2
3 Phases
2 Phases
AC 1030 6/98
OVERLOAD RELAYS:
3.10
00.00
00.00
Inches
Millimeters
Dimensions
TA25DU
0.51
13
3.70
94
3.15
80
TA25DU32 only
0.24
6
1.73
44
3.70
94
TA42DU
0.51
13
3.54
90
0.24
6
2.13
54
4.35
110.5
1.18
30.0
0.47
12.0
95.7
12.5
2 - M4 Mtg. Slots
2.12
54.0
4.37
111.0
TA110DU
1.48
37.5
0.24
6.0
5.44
138.1
2.52
64.0
6 - 0.21 HOLES
.61
15.5
AC 1030 6/98
3.14
80.0
0.24
6.0
120.1
4.73
0.07
1.7
1.98
50.2
OVERLOAD RELAYS:
3.11
Overload relays
3.77
0.50
00.00
00.00
Inches
Millimeters
1.73
44
0.24
6
0.35
6
1.38
35
0.51
13
3.31
84
1.88
48
0.17
4.2
4.25
108
0.24
6
0.35
6
1.38
35
0.51
13
4.41
112
1.88
48
0.17
4.2
2.36
60
0.24
6
1.97
50
Overload relays
OVERLOAD RELAYS:
0.51
13
3.86
98
2.95
75
0.17
4.2
AC 1030 6/98
3.12
Description
A.C. or D.C. operated DIN rail or panel mounting 600 volt heavy duty design, A600-10 amp, Q300-5 amp Snap-on accessories available: 1 & 4 pole adder deck Pneumatic on & off delay timer Mechanical latch Coils are easily interchangeable NEMA, UL, IEC, CSA, VDE and most other international standards Fixed contacts are double break type for positive contact on low current applications Terminals supplied in open position for ease of wiring Touch safe design: All connection terminals are protected against accidental touch Terminal screws are captive with saddle type clamps for fast wiring and are easily accessible from the front Screwdriver guide holes Regulations and standards have been written to ensure that safety is maintained: United States ANSI B11.19-1990 ANSI B11.20-1991 Germany SVA ZH1/457 France INRS United Kingdom BIA Switzerland SA The ABB Type N & KC 4 and 8 pole relays are designed with Positive Guided contacts and fulfill the regulations or standards shown. The relays can provide positive safety for the N.O. and N.C. contacts which assure that the N.O. contacts will not close before any N.C. contact opens. Therefore, if one of the contacts weld due to abnormal conditions in the control circuit, the other contacts will also remain in the same position as when the welding occurred. This means that the open contacts must maintain an air distance 0.5mm when the coil is energized at 110% Vc or when it is de-energized.
Index
Features ............................................. 4.1 Description .......................................... 4.2 Selection, AC & DC operated ............ 4.4 Accessories ........................................ 4.5 Technical data .................................... 4.8 Approximate dimensions .................. 4.11 Technical data: 4.8 4.10 Dimensions: 4.11 4.12 4.1
AC 1030 6/98
CONTROL RELAYS:
Selection: 4.4
Control relays
Description
Application
Type N control relays are used for switching auxiliary circuits and control circuits.
Description
AC operated with laminated magnetic circuit. 2 versions: 4 pole or 8 pole. The width of 8 pole devices is identical to that of 4 pole devices; only the depth is increased. Side by side mounting possible. Self cleaning auxiliary contacts. Alone or by itself or with a 4 pole CA5 auxiliary contact block, these devices offer positive safety between their auxiliary contacts.
Holes for screw mounting (screws not supplied). Distances between holes according to EN50 002.
Quick mounting on 35 x 7.5 mm DIN mounting rail according to IEC715 and EN50 022.
NO - 23 5- 13 6
NO7- 33NO8-
43NO
Location of function marker.
N40E
Terminals delivered in open position with captive screws (screws of unused terminals should be tightened). Screwdriver guidance for all screws makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 Part. 100 and offer IP 20 degree of protection according to IEC947-1.
5- 14NO
Control relays
CONTROL RELAYS:
60 N 50 N DC BC-KC 07
24 81 81 01
220 240 277 380 415 440 480 500 600 75 80 42 48 86 86 51 53 55 80 85 86 55 05 33 AC 1030 6/98
Selection: 4.4
4.2
Description
Description
Magnetic circuit variants: KC types: d.c. operated with solid magnetic circuits. 2 versions: 4 pole or 8 pole The width of 8 pole devices is identical to that of 4 pole devices; only the depth is increased. Bifurcated auxiliary contacts. Alone or mounted with a 4 pole CA5 auxiliary contact block, these devices offer positive safety between their auxiliary contacts.
Quick mounting on 35 x 7.5 mm or 35 x 15 mm DIN mounting rail according to IE715 and EN50 022.
V DC 24
A1
13
23
7-
33
8-
43
5-
6-
Holes for screw mounting (screws not supplied). Distances between holes according to EN50 002.
KC 40 E
Terminals delivered in open position with captive screws (screws of unused terminal should be tightened). Screwdriver guidance for all screws makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 Part. 100.
5-
14
6- 24
7-
34
8-
44
All terminal screws: M 3.5, posidrive (+,-) N 2
24 81 81 01
CONTROL RELAYS:
Selection: 4.4
4.3
Control relays
Selection
N40E-1
KC22-E
A.C. operated
Contact configuration N.O. N.C. Catalog number List price
D.C. operated
Contact configuration N.O. N.C. Catalog number List price
4 3 2 4 5 6 7 8
0 1 2 4 3 2 1 0
$ 60
4 3 2 4 6
0 1 2 4 2
$ 72 144
120
60 N 50 N DC BC-KC 07
24 81 81 01
Control relays
AC 1030 6/98
CONTROL RELAYS: General info: 4.1 4.3 Selection: 4.4 Accessories: 4.5 4.7 Technical data: 4.8 4.10 Dimensions: 4.11 4.12
4.4
Accessories
Positioning
List price
1 Front face 4 2 1
1 2 4 1
$ 15
30
Side
CAL5-11 CA5-10
Pneumatic timers
Timing range Contacts N.O. N.C. Catalog number List price
On delay 0.1 40s On delay 10 180s Off delay 0.1 40s Off delay 10 180s
1 1 1 1
1 1 1 1
$ 108
Interlocks
Feature TP40DA Contacts N.O. N.C. Catalog number List price
Mech./elec. Mechanical
VE5-1 VM5-1
$ 45 21
Varistor
24 50 VAC 50 133 VAC 110 250 VAC 250 440 VAC 24 50 VDC 50 133 VDC 110 250 VDC 250 440 VDC
VE5-1
$ 30
RC
Identification marker
RV5/50 RC5-1/50 Feature Catalog number List price
Pack of 50
BA5-50
$ 15
$ 26
Coils
BA5-50
ZA16-5
$ 24
KBC30-5
$ 60
5 Select the coil voltage from the Control Relay Coil Voltage Selection chart and substitute the letter code for the 5 as the last digit in the catalog number.
AC 1030 6/98
60 N 50 N DC BC-KC 07
24 81 81 01
4.5
Control relays
Accessories
NC 01
01 NC
CA5-10 and CA5-01 Front-mounted 1-pole auxiliary contact blocks N22E N31E N40E Control Relay TP40DA TP180DA TP40IA TP180IA Pneumatic timer
Control relays
CAL5-11 Side-mounted 2-pole auxiliary contact block
01
02 NC
01 NC
5-1 VM
NC 02
N44E N53E N62E N71E N80E Control relay VM5-1 VE5-1 Interlock unit
AC 1030 6/98
CONTROL RELAYS:
Selection: 4.4
4.6
Accessories
CA5-10 and CA5-01 Front-mounted 1-pole auxiliary contact blocks TP40DA TP180DA TP40IA TP180IA Pneumatic timer
AC 1030 6/98
CONTROL RELAYS:
Selection: 4.4
4.7
Control relays
Technical data
10
7200VA
720VA
138VA
138VA
AC coil consumption
In rush Sealed
DC coil consumption
In rush Sealed
80VA
8VA
7.0W
7.0W
AC operating time
Pickup Dropout
DC operating time
Pickup Dropout
10 20ms
10 20ms
30 90ms
10 20ms
AC mechanical endurance
30 million operations
DC mechanical endurance
30 million operations
13
13
13
13
A1 23
A2 33 43
A2
13 NO
21 NC
31 NC
43 NO
A1
13 NO
21 NC
33 NO
43 NO
A1
13 NO
23 NO
33 NO
43 NO
NO NC NC NO
NO NC NO NO
NO NO NO NO
NO NO NO NO 51 61 71 81 NC NC NC NC
NO 14
NC 22
NC 32
NO 44
A2
NO 14
NC 22
NO 34
NO 44
A2
NO 14
NO 24
NO 34
NO 44
N22E, KC22E
N31E, KC31E
N40E, KC40E
NO NC NC NO 14 22 32 44 A2
NO NC NO NO 14 22 34 44 A2
NO NO NO NO 14 24 34 44 A2
52 62 72 82 NO NO NO NO 14 24 34 44 A2
N22E
N31E
N40E
N44E
A2
NO 14
NO 24
NO 34
NO 44
NO 54
NC 62
NO 74
NO 84
A2
NO 14
NO 24
NO 34
NO 44
NO 54
NC 62
NC 72
NC 82
N71E
A1 23 A2 43
A1 13 NO 23 NO 33 NO
N53E
43 NO 51 NC 61 NC 71 NC 81 NC
13
33
13
A1 23
33
A2 43
13
A1 23
33
A2 43
13
A1 23
33
A2 43
A1
13 NO
23 NO
33 NO
43 NO
53 NO
61 NC
71 NC
83 NO
NO NO NO NO 53 61 71 81 NO NC NC NC
NO NO NO NO 53 61 71 83 NO NC NC NO
NO NO NO NO 53 61 73 83 NO NC NO NO
NO NO NO NO 53 63 73 83
A2
A2
NO 14 NO 24 NO 34 NO 44 NO 54 NC 62 NC 72 NO 84
NO 14
NO 24
NO 34
NO 44
NC 52
NC 62
NC 72
NC 82
N44E
NO NO NO NO 54 64 74 84 NO NO NO NO 14 24 34 44 A2
A2
N62E
54 62 72 82 NO NO NO NO 14 24 34 44 A2
54 62 72 84 NO NO NO NO 14 24 34 44 A2
54 62 74 84 NO NO NO NO 14 24 34 44 A2
Control relays
A1
13 NO
23 NO
33 NO
43 NO
53 NO
63 NO
73 NO
83 NO
NO 14
NO 24
NO 34
NO 44
NO 54
NO 64
NO 74
NO 84
N53E
N62E
N71E
N80E
N80E
AC 1030 6/98
CONTROL RELAYS:
Selection: 4.4
4.8
Technical data
KC44, KC62 8
Insulation characteristics
Rated insulation voltage Ui acc. to IEC947-5-1 and VDE0110 (Gr. C) acc. to UL/CSA Rated impulse withstand voltage Uimp acc. to IEC947-5-1 V V kV 690 600 8
Air temperature near contactor for operation in free air: for storage: Climatic withstand Mounting positions:
C C
Positions 1 to 5 Position 6
-40 to +55 (0.85 1.1 Uc) / +55 to +70 (Uc) -60 to +80 according to IEC68-2-30 and 68-2-11 UTE C63-100, Specification II - < 55C : 0.85 1.1 Uc - = 55 - 70C : Uc - < 55C : 0.95 1.1 Uc - > 55C : not acceptable < 3000 1/2 sinusoidal shock, 11ms: no change in contact position
(see diagrams below) Operating altitude Shock withstand according to IEC 68-2-27 and EN 60068-2-27 Mounting pos. 1 (see below) Fixing on mounting rail with screws (not supplied) Connection terminals (delivered in open position, screws of unused terminals must be tightened) Connection capacity Rigid solid Degree of protection according to IEC529, IEC947-1 and EN60529 Pole terminals Coil terminals 1 x AWG 2 x AWG
C1 ABB
B1
B2
Shock direction:
C2
A, C1, C2 B1 B2
: 20 g : 5g : 15 g
35mm according to IEC715 and EN50022 2 x M4 M 3.5 (+,-) posidrive 2 screw with cable clamp
16 12 16 12
IP20 IP20
IP10 IP20
Mounting positions
Electrical durability of contacts utilization category AC 15 according to IEC947-5-1 making current: 10 x Ie with cos = 0.7 and Ue breaking current: Ie with cos = 0.4 and Ue The curves opposite show the electrical durability of the control relays as well as the add-on auxiliary contact blocks in relation to the breaking current Ic. These curves have been drawn for resistive and inductive loads up to 690V, 40 60 Hz.
30 20 10
Pos. 2
Pos. 6
30
30
CA5, CAL 5
5 3
4a
4a nd
nd
8-p
ole
Million ops
ABB
ole
KC
typ
es
Pos. 5
0.02
0.05
0.1
0.2
0.3
0.5
5 6
10
AC 1030 6/98
CONTROL RELAYS:
Selection: 4.4
4.9
Control relays
Pos. 4
Pos. 5
8-p
Nt
ype
Technical data
KC44, KC62 8
A A A A A
6 4 3 2 2
6 4 3 2 2
V VDC ms
ms ms ms ms
10 26 7 21 4 11 9 16
50 75 45 70 15 30 * 17 32 * *Using surge suppressors increases the opening time by a ratio of 1.1 to 1.5 for a varistor suppressor and by 4 to 8 for a diode suppressor.
Control relays
AC 1030 6/98
4.10
00.00
00.00
Inches
Millimeters
Approximate dimensions for Control relays Type N & KC, AC & DC operated
2.91
74
Dimensions
0.22 1.73
44 5.5
1.38
35
2.91
74
2.36
60
1.97
50
0.18
4.5
0.18 4.26
108.0 4.5
3.18
81.0
2.76 2.36
70.0 60.0
1.75
44.0
0.35
9.5
1.38
35.0
0.19
5.0
4.48
114.0
0.18
4.5
2.76 3.18
81.0 70.0
2.36
60.0
0.37
9.5
1.75
44.0
1.38
35.0
0.19
5.0
3.18
81.0
2.76 2.36
70.0 60.0
1.75
44.0
0.37
9.5
1.38
35.0
AC 1030 6/98
0.19
5.0
CONTROL RELAYS:
Selection: 4.4
4.11
Control relays
Dimensions
Inches
Millimeters
ON-POSITION LATCH
PNEUMATIC TIMER
TYPE N KC IN
MM
A 2.20
56
B 3.96
100.5
C 4.21
107
D 5.71
145
E 5.00
127
F
5.04 128
IN
MM
5.53
140.5
5.79
147
7.28
185
6.58
167
Control relays
AC 1030 6/98
CONTROL RELAYS: General info: 4.1 4.3 Selection: 4.4 Accessories: 4.5 4.7 Technical data: 4.8 4.10 Dimensions: 4.11 4.12
4.12
These terms and conditions govern all sales and shipments of control equipment products (including parts and accessories). ABB Control Inc. hereby gives notice of its objection to any different or additional terms and conditions except for such as may be expressly accepted by it in writing. Prices Prices are subject to change without notice. Prices will be the prices in effect at the time of shipment by ABB Control Inc. and include freight, prepaid and allowed to first destination in the continental United States. In the event of a price change, the effective date of the change will be the date shown on the new price discount sheets. However, where a price change is made by letter or telegram, the effective date will be given as part of the announcement. Taxes The price does not include any Federal, state or local property, license, privilege, sales, use, excise, gross receipts or other like taxes which may now or hereafter be applicable. Payment by ABB Control Inc. of any such taxes shall be for the account of purchaser. Standard terms of payment Standard terms of payment are according to the appropriate discount schedule (AC 5000 - AC 5002). Payment and late charges ABB Control Inc. may require full or partial payment in advance if, in its sole judgement, the financial condition of the purchaser, at any time prior to delivery, does not merit the terms of payment specified. If shipments are delayed by the purchaser or by reason of any of the causes referred to in the paragraph entitled "Excusable Delay", payments shall become due from the date when ABB Control Inc. is prepared to make shipment. Products held for the purchaser as a result of such delay shall be at the risk and expense of the purchaser. If the purchaser fails to pay any invoice when due, ABB Control Inc. may defer deliveries under this or any other contract with purchaser, except upon prior receipt of satisfactory security for or cash in payment of any such invoice. Failure on the part of purchaser to pay invoices when due shall at the option of ABB Control Inc. constitute a default under this contract. A service charge, the lesser of the highest rate allowed by law or 11/2% per month, or fraction thereof, for a maximum charge of 18% per annum will be charged on all overdue accounts. Delivery Delivery of products shall be FOB point of shipment regardless of transportation costs being "allowed", "prepaid" or collect". Where the scheduled delivery of products and parts is delayed by the purchaser or by reason of any of the causes referred to in the paragraph entitled Excusable Delay, ABB Control Inc. may deliver such products by moving them to storage for the account of and at the risk of the purchaser. Shipping dates are approximate and are based upon prompt receipt of all necessary information from purchaser. ABB Control Inc. reserves the right to make delivery in installments. Purchaser pick-up No allowance will be made in lieu of transportation charges if the purchaser accepts shipment at the factory, warehouse or freight station. Transportation charges will not be deducted from the purchase price. Origin, method of shipment and routing ABB Control Inc. shall determine the point of origin of shipment, the method of transportation and the routing of shipment. Costs for shipment by means requested by purchaser different from ABB Control Inc.'s standard means of shipment are invoiced to the purchaser as a separate charge. Freight charges will be added to the price of any order under $100. Excusable delay ABB Control Inc. shall not be liable for loss, damage, detention or delay, nor be deemed to be in default from causes beyond its reasonable control, including without limitation, fire, flood, strike or other labor difficulty, act or omission of any governmental authority or of the purchaser, insurrection or riot, embargo, delays or shortage in transportation or inability to obtain necessary labor, materials or manufacturing facilities from usual sources. In the event of delay in performance due to any such cause, the date of delivery will be postponed by such length of time as may be reasonably necessary to compensate for the delay. Warranty ABB Control Inc. warrants that on date of shipment to purchaser, the goods will be the kind and quality described herein, merchantable and free of defects in workmanship and material. If within one year from date of initial operation, but not more than eighteen months from date of shipment, should any failure to conform with this warranty appear within such time, ABB Control Inc. shall, if given prompt notice by purchaser, correct such nonconformity, at its option, either by repair or replacement F.O.B. repair facility or by refund of the purchase price of the nonconforming product or part. Return of products to ABB Control Inc. pursuant to this paragraph shall be at purchaser's risk and expense. The foregoing warranty is exclusive and in lieu of all other warranties of quality, expressed or implied, and all other warranties, including any warranty of merchantability or fitness for a particular purpose are hereby disclaimed. Correction of nonconformities in the manner and for the period of time provided above shall be purchaser's exclusive remedy and shall constitute fulfillment of all liabilities of ABB Control Inc. whether in warranty, strict liability, contract, negligence, tort or otherwise with respect to any nonconformance or defect in the product. The foregoing warranty shall not apply to any product which has been: a) improperly repaired or altered, b) subjected to misuse, misapplication, negligence or accident, c) used in a manner contrary to manufacturer's directions. Limitation of liability ABB Control Inc.'s liability to purchaser on any claim in connection with the product shall not exceed the purchase price of the product which gives rise to the claim.
IN NO EVENT SHALL ABB CONTROL INC. BE LIABLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES whether in warranty, contract, strict liability, tort, negligence or otherwise including but not limited to loss of profits or revenue, loss of use of the product or any associated product, cost of capital, cost of substitute products, facilities or services, downtime costs or claims of customers of the purchaser for such or other damages. Except as prohibited by law, all causes of action against ABB Control Inc. shall expire unless brought within one year of the time of accrual thereof. ABB CONTROL INC. NEITHER ASSUMES NOR AUTHORIZES ANYONE TO ASSUME FOR IT ANY OTHER OR FURTHER LIABILITY THAN AS SET OUT ABOVE. Patent indemnity ABB Control Inc. will at its own expense defend any suit which may be brought against the Purchaser based on a claim that any apparatus or part furnished under contract constitutes an infringement of any United States letter patent (provided ABB Control Inc. is notified promptly of such suit and copies of all papers therein are delivered to ABB Control Inc.), and ABB Control Inc. agrees to pay all judgements and costs recovered in any such suit and to reimburse the Purchaser for costs of expenses incurred in the defense of any such claim or suit. In case said apparatus or any part is held to constitute infringement and the use of the apparatus or part is enjoined, ABB Control Inc. shall at its own expense, either procure for the Purchaser the right to continue using the apparatus or part or replace it with non-infringing apparatus; or modify it so it becomes non-infringing, or remove the apparatus and refund the purchase price and the transportation and installation cost thereof. The foregoing states the entire liability of ABB Control Inc. for patent infringement by apparatus or any part thereof. Shipping loss or damage In the event of shipping loss or damage: 1) Notification must be given to ABB Control Inc. within 72 hours of delivery; 2) Written notice of apparent loss or damage must be made on the carrier's delivery receipt; and 3) Concealed damage must be immediately reported to the delivering carrier with a request for inspection. Purchaser shall comply with the foregoing procedure whether or not ABB Control Inc. has the risk of loss at the point of loss or damage to the shipment. Title risk of loss The products sold hereunder shall remain the property of ABB Control Inc. and shall remain personal property until fully paid for in cash, and purchaser agrees, if requested by ABB Control Inc. to execute a further security agreement covering the products sold, and to perform all acts which may be necessary to perfect and assure retention of title to such products by ABB Control Inc. Not withstanding any agreement with respect to delivery terms, risk of loss or damage shall pass to the purchaser and delivery shall be deemed to be complete upon delivery to a private or common carrier or upon moving into storage, whichever occurs first, at the point of shipment. Termination Any order or contract may be terminated by the purchaser only on written notice and upon payment of reasonable and proper termination charges, including without limitation, all costs identified to the order of contract incurred by ABB Control Inc. up to the date of notice of termination and all charges incurred by ABB Control Inc. in respect of the termination. Returns In no event will ABB Control Inc. be responsible for unauthorized return of products. Returns will be accepted only at ABB Control Inc.'s option and subject to terms specified by ABB Control Inc. Authorization and shipping instructions for return of products must be obtained from ABB Control Inc. prior to return shipment. Product must be returned with proper identification. When a purchaser requests authorization to return for his own reasons, the return is subject to a minimum restocking charge of 20% for standard inventoried product and for any transportation paid by ABB Control Inc., both out and ingoing. Returns will be accepted up to 60 days after invoice date. Goods returned for purchaser's reason are subject to inspection and must be in good working condition, as new, and in original cartons. Purchase orders Except as provided below, all orders must be in writing and show quantities and prices, complete description (including catalog numbers) of products requested and mutually agreed delivery dates. Verbal orders received via telephone or otherwise must be confirmed within 5 days either by mail, telex or the equivalent. Verbal orders with a purchase price over $5,000 will not be processed until such written confirmation is received. Unless otherwise agreed in writing, an addition to a previously entered order will be accepted only at then applicable prices, discount schedules, conditions of sale, etc. Special quotations Special quotations will automatically expire 30 days from issuance unless renewed in writing by ABB Control Inc. Assignment Any assignment of this contract, or any rights hereunder, without prior written consent of ABB Control Inc. by a duly authorized representative thereof shall be void. Partial invalidity If any provisions herein or portions thereof conflict with any statute or rule of law of the jurisdiction of applicable law or wherein the contract may be sought to be enforced, then such provisions or portions thereof shall be deemed void to the extent that they may so conflict, but without invalidating the remaining portions of such provisions or other provisions hereof. Remedies The remedies expressly provided for in the Conditions of Sale shall be in addition to any other remedies which ABB Control Inc. may have under the Uniform Commercial Code or other applicable law. Choice of law The construction and performance of this contract and the rights and remedies of the parties hereto shall be governed by the laws of the State of Texas.
AC 1030 6/98
5.1
VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660 CEI EN 60947-2 BS4752 NCF 120 IEC 947 UL489 CSA C22.2 VDE 0660
The CE Mark
Within the European Union, EU, conformity of products and the proper application of the CE marking to machines and control equipment is necessary for marketing electrical equipment. The intent is to ensure compliance with all relevant EU Directives.
Background
The guarantee of free trade of goods within the Community is the most important objective. This will eliminate trade restrictions that result from different technical regulations in each individual member country. Harmonization of existing European standards and regulations, is being accomplished and already partially realized. Based on this goal, a new concept for creating directives was formed in 1985 by the European Community (EC) Commission to produce directives with a wide range of application which contain only the most basic safety requirements.
The CE Mark
The CE mark is prescribed by law and assures the European free trade of goods. It is short for Communaut Europen, and is displayed on goods and/or packaging which acts as an external symbol for the inspection of products. It also illustrates the manufacturers responsibility to uphold the communitys directives.
AC 1030 6/98
5.2
Product scope
Industrial controls
Contactors Drive contactors Welding contactors Overload relays Starters, open & enclosed Manual motor starters Softstarters Control relays Pushbuttons Miniature controls Control circuit transformers Sensors Arc Guard systems
L O W V O L T A G E N E T W O R K Q U A L I T Y
ABB Control Inc. 1206 Hatton Road Wichita Falls, TX 76302 Tel. (800) 877-3232 (940) 397-7000 Fax (940) 397-7001 Email [email protected] Web www.abbcontrol.com
AC 1030 June, 1998