CCVT and CC Instruction Manual
CCVT and CC Instruction Manual
CCVT CC
Contents
Page Introduction 3 Construction and Types 4 Capacitor Voltage Transformers 4 Coupling Capacitors 4 Heaters 4 Inspection 4 Shielding Ring 4 Storage & Transportation 4 Installation 4 Erection 4 Capacitor Assembly Instructions 4 Connections 6 Commissioning and Routine Maintenance 6 Electrical Tests 7 Capacitance Bridge Testing 7 Capacitance and Dissipation Factor Measurements 7 Precautions for High Voltage Testing 8 Connection of a Non-Linear (Magnetic) Burden 9 CVT Principle of Operation 9 Main Components 9 Auxiliary Components 9 For after sales assistance 22
Illustration
Fig. 1 Fig. 2 Fig. 3 Fig. 4 Fig. 5 Fig. 6 Fig. 7 Fig. 8 Fig. 9 Sectioned Perspective View of a Typical Capacitor Voltage Transformer Capacitor units assembly and connection Low Voltage Terminal Box for CVT Capacitance and Dissipation Factor Temperature Correction Curves for Paper-Film/PXE Capacitor Schematic Diagram of a typical CVT Capacitor Voltage Transformer with One Capacitor Section (Test 1 to 2) Capacitor Voltage Transformer with Two Capacitor Sections (Test 1 to 3) Capacitor Voltage Transformer with Three Capacitor Sections (Test 1 to 4) Capacitor Voltage Transformer with Four Capacitor Sections (Test 1 to 5)
Page 5 5 6
8 10 11 12 13 15
Tables
Table I Troubleshooting Table II Types: TCVT , TECF, TECP, TEVF, TEMF, TEVP, TERP, TEMP & TETP Table III Types: TCVT , TEICF, TEIRF and TEIMF Table IV Types: TEHCF, TEHCP, TEHMF, and TEHMP Table V Electrical Performance Page 18 19 20 20 21
Introduction
Trench Limited manufactures a comprehensive range of capacitor voltage transformers (CVTs) and coupling capacitors (CCs). All basebox types utilize the same design principles and manufacturing techniques, the information detailed in this manual is applicable in general, except where noted. The circuit diagrams, drawings and other data in this manual may vary in minor details, from the equipment supplied. In all cases the diagrams supplied by the factory and identified with the equipment will be correct in all details. The contents of this manual are designed to cover most situations, which may occur in practice. If any additional information is required, please contact Trench Limited.
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Installation
Erection
CCs or CVTs with more than one capacitor unit are shipped with the units disassembled. They are crated in sets with all components required to assemble one CVT unit in one crate. Capacitor units must not be interchanged with capacitors from different CVTs. Assembling of CVTs can be performed with assistance of a lifting crane. The use of rope slings with a chokertype hitch arranged to bear on the upper metal flange is an effective way of lifting the capacitor units. Assembling can be carried out as follows: Mount the basebox and bottom capacitor assembly on its pedestal and prepared foundation and assemble subsequent capacitor units on top in accordance with the instructions detailed below.
Coupling Capacitors
Types TECF, TECP, TEICF, TEHCF and TEHCP are coupling capacitors (CCs) for use in power line carrier (PLC) coupling schemes. They consist of an assembly of one or more capacitor units of a flat base design with no carrier accessories or mounted on an air-filled aluminum basebox complete with carrier accessories. The film/paper/PXE fluid insulation system represents a premium system of a low dielectric loss design and outstanding stability performance.
Heaters
Note that Trench oil filled EMUs do not require heaters. In the low voltage terminal box, heaters may be installed to prevent condensation during long storage periods in very humid environments. Power rating of heaters could be up to 15 watts and dual voltages 120/240V or 240/480V. Once the CVT is in service it is not recommended to keep the heater on especially when ambient temperature exceeds 40C.
Inspection
All shipments should be inspected upon arrival for chipped or damaged porcelains, metallic parts and oil leaks. The LV terminal box should be opened and examined for loose components or broken wiring. If transit damage has been found, file a claim with the Transit Company and notify Trench Limited immediately.
Shielding Ring
When a shielding ring is supplied, refer to the outline drawing regarding the way the shielding ring should be mounted on the unit. Check the shielding ring for any scratches or sharp points, which may have been caused during transit and file smooth before installation.
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Connections
The basebox should be solidly grounded by means of a grounding cable connected to the aluminum ground pad located on the side of the basebox. All low voltage and carrier terminals are in the air-filled low voltage terminal box located on the front side of the basebox (Fig. 3). Low voltage secondary terminals are provided in the oil/air seal plate assembly (Fig. 3). Secondary wiring entrance to the low voltage box is by 4 x 5 (102 x 127 mm) gland plate with provision for 1 (32 mm) knock out conduit entry by bosses. Carrier entrance to the low voltage box is by 5/8 (16mm) internal diameter entrance bushing, with customer connection directly on the carrier terminal stud. Caution (refer to Fig. 3) The ground connection for the surge protective device (P2 terminal) must never be removed during normal service conditions. This provides the ground for the magnetic unit. The carrier terminal must always be connected to ground, either directly, if no carrier is required, or via the drain coil.
DANGER
HAZARD AND BODILY INJURY OR EQUIPMENT DAMAGE Only qualified maintenance personnel should operate, service or maintain this equipment. This document should not be viewed as sufficient for those who are not otherwise qualified to operate, service, or maintain the equipment discussed. This bulletin is intended to provide accurate and authoritative information only. Trench Limited assumes no responsibility for any consequences arising out of the use of this bulletin. The successful operation of this equipment depends upon proper handling and installation. Neglecting fundamental installation requirements can lead to personal injury as well as damage to electrical equipment or other property. Before servicing equipment, disconnect all sources of electrical power. Assume that all circuits are live until they have been completely de-energized, tested, grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding. Carefully inspect the area around the transformer for tools and objects left near the unit. For safety, at least two qualified individuals must be present during installation. Failure to observe these precautions may result in equipment damage, severe personal injury, or death!
It is recommended to check the protective gap annually. The life of this device depends on the frequency and duration of system switching. Unless specified otherwise in the connection diagram of the CVT, the protective device across P1 and P2 is a Siemens gas-filled surge protector type SI-A 350 with a.c. sparkover voltage of 250 volts rms and a tolerance of +/-20%. If the sparkover voltage of the device is outside this range, it needs a replacement. When this protective device is installed, it is important to make sure the metallic ends make good contact in the holder.
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
If a preventive maintenance program calls for regular electrical tests, the following procedures may serve as a guide for tests on a routine basis as governed by your usual practice. If it is the practice of your utility to conduct a check at the time of commissioning, then these same procedures may be followed at this time. If the CVT is utilized for PLC only, the potential ground switch must remain in the open position.
With ground switch still closed, measure C2. Remove ground connection at CAR terminal and measure between this terminal and basebox. Compare to C2 value marked on main nameplate or previous measurements. Measure C total, from HV terminal to CAR terminal with ground switch open and grounding links removed from P2 and CAR terminals. Depending on the type of bridge used, there may be difficulties in obtaining a balance for DF as leakage currents through the insulation of the transformer windings will cause apparent DF readings below the true value or even to be negative, although capacitance value obtained will be correct. A change of measurement C total from one routine test to another would be an indicator that additional investigation is required. Note that, on the bottom capacitor unit, the lower end plate is isolated from the capacitor electrodes and cannot be used as a connection point.
Electrical Tests
See precautions for HV testing on page 8 before doing the tests. Measure capacitance and dissipation factor of each capacitor unit. It is important to use equipment with a capacitance measurement error of less than 0.5% in order to detect a capacitor element failure. This can be achieved by the use of Low Voltage Capacitance Bridge. All measurements taken should be corrected to 20C using Fig. 4. As there will always be differences between the calibrations of various capacitance measuring equipment, the initial capacitance readings on installation should be recorded and used as a basis for comparison with subsequent measurements made with the same test equipment. M easure the transformation ratio of the unit (CVTs only). The purpose of this test is to verify the continuity of the CVT circuit only. The use of Doble Test equipment as a power supply to the HV terminal and measurement of secondary voltage is a convenient method of doing this measurement.
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
If solidly bolted bus connections are to be used, it is recommended that suitable insulating supports be installed to isolate the CVT for test purposes. Shorting links normally used across these insulating supports may then be easily removed during tests and replaced afterwards. The test methods for assemblies which have 1, 2, 3 or 4 capacitor units, are detailed below and from page 11 to 17. R emove carrier ground connection for the duration of the capacitance and dissipation factor test G round the basebox solidly to the test set C lose the voltage tap ground switch I MPORTANT: Replace carrier connection immediately after test, before energizing. NOTE: It is not unusual for dissipation factor (DF) measurements made at 10kV or below to exceed factory values, which are measured at operating voltage. If DF exceeds 0.4 %, consult Trench Limited. Example for use of Fig. 4 1. Make measurement at field temperature. Example: Temperature = -10C Capacitance = 10050 pF Dissipation Factor = 0.065% 2. Find our factory values from test report. Example: Capacitance = 10 000 pF Dissipation Factor = 0.055% 3. Calculate predicted values at field temperature. Example: Capacitance at -10C = 100.25% of factory value = 10025 pF 4. Dissipation Factor at -10C = 113% of factory value = 0.062% Compare values from 1 and 4. Fig. 4 Capacitance and Dissipation Factor Temperature Correction Curves for Paper-Film/PXE Capacitor
Note: Measurement is done at normal operating voltage. Significant error on dissipation factor may result if measurement performed at low voltage (1-10kV).
WARNING
HAZARD OF ELECTRIC SHOCK. During storage, ensure that all capacitor insulator assemblies are shorted. Failure to observe these precautions can result in personal injury or product damage.
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Auxiliary Components
All items referred to are identified on the connection diagram. The choke coil assembly prevents the grounding of the carrier signal when the voltage tap ground switch is closed. The harmonic suppression filter prevents sustained ferroresonance oscillations. It consists of a resistor in series with a saturable reactor and a parallel resistor. The reactor is designed to saturate above the highest over-voltage rating to form a loading circuit, which will dampen sub-harmonic ferroresonant oscillations. The protective gap (item 4 Fig. 5) is a voltage sensitive device wired in series with a loading resistor on a secondary winding of the series reactor. The protective gap is normally open circuit, but goes in short circuit mode when the intermediate voltage exceeds the overvoltage factor of the CVT, or when the secondary current causes the thermal burden rating (shown in Table V) to be exceeded. This has the effect of de-tuning the CVT and limiting the secondary current available during overvoltage and external short circuit conditions. The protective gap also serves to further limit ferroresonance oscillations. If the fault condition persists for more than about thirty seconds, the protective gap will not reset from the short circuit mode and must be replaced. Its location inside the low voltage terminal box facilitates replacement. The drain coil, gap and carrier ground switch are supplied if the CVT is to function as a coupling capacitor for power line carrier.
CAUTION on operation of potential ground switch: The potential ground switch position (see Fig. 5, item 7) is provided for maintenance purposes only. It is not meant to be closed on permanent basis, due to increased stress of C1 capacitor elements. Closing the potential ground switch for more than 8 hours is not recommended.
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Fig. 5
UNIVERSAL BOX
Legend:
1 2 3 4
Series Reactors Intermediate Voltage Transformer Harmonic Suppression Filter Sealed Protective Gap
5 6 7 8
Secondary Terminal Board Faraday Field Potential Ground Switch Choke Coil & Gap Assembly
Note: connection between internal terminals L1L8 and A, DO are made at the factory as required for each unit.
10 Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Fig. 6 Capacitor Voltage Transformer with One Capacitor Section (Test 1 to 2) Test 1 - one capacitor section
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: F: S1 Switch: S2 Switch: C1 10kV GST-GROUND A Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: F: C2 2kV GND-RB F Disconnected (carrier lead) S1 Switch: Grounded S2 Switch: Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
11
Fig. 7 Capacitor Voltage Transformer with Two Capacitor Sections (Test 1 to 3) Test 1 - two capacitor sections
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: F: S1 Switch: S2 Switch: C1-1 10kV GAR-R B A Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: F: S1 Switch: S2 Switch: C1-2 10kV UST-R B A Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
12
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: F: C2 2kV GND-RB F Disconnected (carrier lead) S1 Switch: Grounded S2 Switch: Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Fig. 8 Capacitor Voltage Transformer with Three Capacitor Sections (Test 1 to 4) Test 1 - three capacitor sections
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-1 10kV GAR-R C B Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
13
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-2 10kV UST-R B C Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-3 10kV GAR-R B C Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
14
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A: F: C2 2kV GND-RB F Grounded Disconnected (carrier lead) S1 Switch: Grounded S2 Switch: Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Fig. 9 Capacitor Voltage Transformer with Four Capacitor Sections (Test 1 to 5) Test 1 - four capacitor sections
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-1 10kV GAR-R D C Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
15
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-2 10kV UST-R C D Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-3 10kV UST-R B C Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
16
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A, F: S1 Switch: S2 Switch: C1-4 10kV GAR-R B C Grounded Grounded Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Test Procedures Measure: Test Voltage: Circ. Desc.: HV Lead: LV Lead: A: F: C2 2kV GND-RB F Grounded Disconnected (carrier lead) S1 Switch: Grounded S2 Switch: Grounded
Note: S1: Carrier ground switch S2: Voltage tap ground switch L1: Drain coil L2: Choke coil
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
17
18 Possible Cause
Volt tap ground switch closed Remove external wiring and measure output voltage at terminals. If there is still no voltage, then proceed as follows: 1. Megger X and Y windings to tank should read 50 meg ohms or more. 2. Remove P2 ground link. 3. Open ground switch. 4. Megger P2 to tank should read 50 meg ohms or more. Remove P2 connection. Close volt tap ground switch. 1. Measure resistance from P2 connection to tank, should read less than 1000 ohms. Remove carrier ground connection and close volt tap ground switch. 2. Measure capacitance between CAR connection and basebox. This gives C2 value. 3. Measure capacitance from top of capacitor to basebox. This gives C1 value. Either of above tests will confirm integrity of tap lead from lower capacitor unit. 4. Measure P1 - P2, should read less than 75 ohms Confirm as per test 1.3.2 and 1.3.3. As per test 1.3.2 and 1.3.3. If no continuity, confirm that connections between capacitor units are made. If still no continuity, change capacitor unit. Check all connections. Check C2 value as per test 1.3.2. Remove external wiring to substation and re-check secondary output at terminals. Remove unit from service immediately for evaluation. Check C1 per 1.3.3 Replace capacitor unit if capacitance is more than 1% high. Check all connections. Remove unit from service immediately. Replace capacitor unit. As above (5) Check measurement equipment. Check harmonic suppression filter wiring and components, replace as necessary. See further section Connection of saturable (non-linear) burden. Replace surge protector. As above (8.1). In no case should oil be more than 10 mm (3/8) above mark. Check expansion chamber on top of lower capacitor unit. Consult factory immediately. In no case should oil level be more than 10 mm (3/8) below mark. Top up if necessary. Check for leaks around tank and report to factory if necessary. Replace expansion chamber. Inspect expansion chamber. If punctured, remove unit from service immediately. Consult factory. Open volt tap ground switch (up position)
Problem
Procedures
1.1
Table I Troubleshooting
1.4
1.5 Broken connection inside capacitor unit Poor secondary connection Failure of a C2 capacitor element Extreme load on secondary
2.1
2.2
2.3
High Secondary Output 3 Failure of one or more C1 capacitor elements Loose intermediate or secondary connections Oil contamination due to capacitor element arcing/failure Capacitor element failure Possible measurement error Malfunction of harmonic suppression filter Use of non linear (saturable) burden P1 - P2 surge protector shorted Faulty harmonic suppression filter Extremely high ambient temperature Oil leak in lower capacitor unit tap or carrier bushing Extremely low ambient temperature Basebox leaking oil Oil leak of expansion chamber Capacitor failure causing expansion chamber to puncture
Waveform Distortion
8.1
8.2
The following is a list of possible problems and their solutions. If difficulty is encountered at any stage, please contact Trench Limited.
9.1
9.2
10.1
10.2
11.1
11.2
12.1
12.2
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
CAUTION: BEFORE PERFORMING ANY TESTS ENSURE THAT UNIT HAS BEEN COMPLETELY DE-ENERGIZE
Table II Types: TCVT, TECF, TECP, TEVF, TEMF, TEVP, TERP, TEMP & TETP
PARAMETER Maximum System Voltage UNIT 72.5 kV 72.5 115 & 67.08 350- 600:1 10,000 20,800 165 140 350 123 123 115 & 69 600- 1,000:1 6,000 12,500 265 230 550 145 145 115 & 67.08 700- 1,200:1 5,000 10,400 320 275 650 170 170 115 & 65.7 800- 1,400:1 4,300 8,300 370 325 750 245 245 300 300 362 362 115 & 69 1,800- 3,000:1 2,150 4,100 785 680 1,550 420 420 115 & 63.9 2,000- 3,600:1 1,650 3,500 785 680 1,550 550 550 (1) 115 & 69 (1) 115 & 63.9 (1) 2,700-4,500:1 (1) 2,500-4,500:1 1,430 2,800 900 780 1,800
*Rated Secondary Voltage V *Transformation ratio Total capacitance TECF, TCVT, TEVF, TEMF pF
115 & 69 69 1,200- 2,500:1 2,000:1 3,000 6,200 525 460 1,050 2,500 5,200 640 570 1,300
TECP, TCVT, TEVP, pF TEMP, TETP Power frequency withstand (Hipot) - dry 1 min. kV - wet 10 sec. Full wave withstand (BIL) 1.2 x 50 microsecond kV
Dimensions TCVT, TECF, TEVF & TEMF (with Low Profile Base Tank)
Number of capacitor units Overall Height in. mm in. mm in. mm in. mm 1 54 5/8 1388 40 1/4 1022 71.7 1820 27 3/4 705 410 185 1394 6.2 No 1 66 7/16 1688 52 1/16 1322 124.0 3150 39 9/16 1005 450 203 1057 4.7 No 1 74 5/16 1888 59 15/16 1522 147.6 3750 47 7/16 1205 475 215 899 4.0 No 1 82 5/8 2098 68 1/4 1734 180.4 4583 55 11/16 1415 505 229 787 3.5 No 1 2 2 147 5/16 3741 132 15/16 3376 360.9 9166 111 7/16 2830 730 331 360 1.6 Yes (1) 3 188 3/8 4784 174 4420 442.9 11250 142 5/16 3615 855 387 259 1.15 No 2 193 3/4 4921 179 3/8 4556 496.1 12600 157 7/8 4010 895 406 247 1.1 Yes 105 11/16 130 3/4 2684 3321 91 5/16 2319 248.0 6300 78 15/16 2005 590 267 562 2.5 Yes 116 3/8 2956 295.3 7500 94 7/8 2410 670 303 427 1.9 No
lb. *Weight kg Max. Horizontal terminal pull in 80 mph (130 km/h) wind lb. kN referring to capacitor porcelain strength Shielding ring
Dimensions TCVT, TECP, TEVP, TERP, TETP (with Low Profile Base Tank) & TEMP (with Universal Base Tank)
Number of capacitor units Overall Height (Add 5 in./130 mm for TEMP) Total Section Height Creepage Distance Strike Distance in. mm in. mm in. mm in. mm 1 55 3/8 1406 41 1041 71.7 1820 27 3/4 705 490 223 1641 7.3 No 1 67 3/16 1706 52 13/16 1341 124.0 3150 39 9/16 1005 550 249 1236 5.5 No 1 75 1906 60 5/8 1540 147.6 3750 47 7/16 1205 585 266 1079 4.8 No 1 83 5/16 2116 68 15/16 1751 180.4 4583 55 11/16 1415 620 281 922 4.1 No 1 106 9/16 2706 92 3/16 2342 248.0 6300 78 15/16 2005 720 326 764 3.4 Yes 2 132 3/8 3363 118 2997 295.3 7500 94 7/8 2410 815 369 495 2.2 No 2 3 2 195 3/8 4963 181 4597 496.1 12600 157 7/8 4010 1080 490 292 1.3 Yes 148 15/16 189 3/4 3783 4820 134 9/16 3418 360.9 9166 111 7/16 2830 880 399 427 1.9 Yes (1) 175 3/8 4455 442.9 11250 142 5/16 3615 1040 472 292 1.3 No
*Weight lb. (add 69 kg/150lbs. for TEMP) kg Max. Horizontal terminal pull in 80 mph (130 km/h) wind lb. kN referring to capacitor porcelain strength Shielding ring
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
19
*Rated Secondary Voltage V *Transformation ratio Total capacitance pF Power frequency withstand (Hipot) - dry 1 min. kV - wet 10 sec. Full wave withstand (BIL) kV 1.2 x 50 microsecond Number of capacitor units in. **Overall Height mm Total Section Height Creepage Distance Strike Distance *Weight in. mm in. mm in. mm lb. kg
55 11/16 78 15/16 1415 2005 985 446 1435 6.4 No 1135 515 1083 4.83 No
142 5/16 157 7/8 3615 4010 1715 778 493 2.2 No 1755 795 493 2.2 No
Max. Horizontal terminal pull in 80 mph (130 km/h) wind referring lb. kN to capacitor porcelain strength Shielding ring
*Rated Secondary Voltage V *Transformation ratio Total capacitance TEHMF, TEHCF pF Total capacitance TEHMP, TEHCP pF Power frequency withstand (Hipot) - dry 1 min. kV - wet 10 sec. Full wave withstand (BIL) kV 1.2 x 50 microsecond Number of capacitor units in. **Overall Height mm Total Section Height Creepage Distance Strike Distance *Weight in. mm in. mm in. mm lb. kg
Max. Horizontal terminal pull in 80 mph (130 km/h) wind referring lb. kN to capacitor porcelain strength Shielding ring
* Not applicable to TEHCF, TEHCP ** Not applicable to TEHCF with flat base
20
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
100VA 225VA 250VA 500VA 550VA 700VA 700VA Class 3P, 50 VA ZZT (400 VA) 10% 1000 VA
100VA 250VA 300VA 600VA 700VA 1000VA 1000VA Class 3P, 50 VA ZZT (400 VA) 5% 1500 VA
Ferroresonance suppression Less than 10 % (of crest) in 200 milliseconds at 120% of rated voltage
(1) Two main windings are supplied as standard, with a third auxiliary winding available as an optional extra. (2) The accuracy class for total simultaneous loading is equal to the values given for each main winding. (3) On special demand
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
21
Note all this information is available from the main nameplate. Please supply the information regarding the problems or questions you may have.
www.trenchgroup.com
22
Instruction Manual for Coupling Capacitor Voltage Transformers & Coupling Capacitors
Trench Austria GmbH Paschinger Strasse 49 Postfach 13 AT-4060 Linz-Leonding Austria Phone: 43-732-6793-0 Fax: 43-732-671341 Trench China MWB (Shanghai) Co., Ltd. No. 3658, Jiancheng Road Minhang, Shanghai Peoples Republic of China 200245 Phone: 86-21-54720088 Fax: 86-21-54723118 Trench Shenyang Trench High Voltage Products Ltd., Shenyang No. 2 Zhengliang Er Rd., Jing Shen Xi San Str. Dao Yi Economic Development Zone Shenyang 110135 Peoples Republic of China Phone: 86-24-89722688 Fax: 86-24-89737200 Trench Limited Bushing Division 432 Monarch Avenue Ajax, Ontario Canada L1S 2G7 Phone: 905-426-2665 Fax: 905-426-2671 Trench Limited Coil Product Division 71 Maybrook Drive Scarborough, Ontario Canada M1V 4B6 Phone: 416-298-8108 Fax: 416-298-2209
Trench Limited Instrument Transformer Division 390 Midwest Road Scarborough, Ontario Canada M1P 3B5 Phone: 416-751-8570 Fax: 416-751-6952 Trench Limited Power Line Carrier Division 330 Finchdene Square Scarborough, Ontario Canada M1X 1A5 Phone: 416-847-5400 Fax: 416-291-5581 Trench France S.A. 16, Rue du Gnral Cassagnou B.P. 80070 FR-68302 St. Louis, Cedex, France Phone: 33-3 89-70-2323 Fax: 33-3 89-67-2663 Trench Germany GmbH Nrnberger Strasse 199 D-96050 Bamberg, Germany Phone: 49-951-1803-0 Fax: 49-951-1803-224 Trench Switzerland AG Lehenmattstrasse 353 CH-4052 Basel, Switzerland Phone: 41-61-315-51-11 Fax: 41-61-315-59-00 Trench Italia S.r.l. Strada Curagnata, 37 IT-17014 Bragno Cairo, Montenotte (SV) Italy Phone: 39-019-5161-111 Fax: 39-019-5161-401