Criteria For Selecting A Residual-Current Device: Content
Criteria For Selecting A Residual-Current Device: Content
Content
When installing inverters, there are often uncertainties when using a residual-current device. For PV plants, above all DIN VDE 0100-410 (IEC 60364-4-41:2005) and DIN VDE 0100-712 (IEC60364-7-712:2002) may be applied. Residual-current devices are used as protection against indirect contact (personal safety).
RCD-UEN110430
Version 3.0
1/11
Technical Information
Definition
1 Definition
1.1Protective Measure According to DIN VDE 0100-410 (IEC 60364-4-41:2005)
According to this standard, a measure protecting against electric shock consists of two safety precautions: Basic protection: protection from direct contact. Fault protection: protection in the event of a fault. This safety precaution takes effect when the basic protection ceases to be effective and prevents physical damage. The installation of a PV plant on the AC side is generally protected through automatic disconnection of supply. Apart from the insulation of live parts as basic protection, fault protection is also established through protective electric bonding and through a disconnection device. It must disconnect within the specified time after occurrence of the fault (at 230 VAC: 0.2 s in TT grounding systems or 0.4 s in TN grounding systems).
1.2Grounding Systems
TT Grounding System
2/11
Technical Information
Definition
TN Grounding Systems
TN-C Grounding System
3/11
Technical Information
Definition
ZS in TN grounding system
4/11
Technical Information
Disconnection Options
2 Disconnection Options
Automatic disconnection can be established through protective electric bonding combined with a miniature circuit-breaker or a residual-current device in accordance with DIN VDE 0100-410 (IEC 60364-4-41:2005).
TT grounding system: A residual-current device is required as primary fault protection. If , then the miniature circuit-breaker can also guarantee protection through automatic disconnection.
Example: Disconnection through miniature circuit-breaker in case of a fault in the TN-C-S grounding system
5/11
Technical Information
Disconnection Options
6/11
Technical Information
3.4Additional Protection
SMA Solar Technology AG recommends always installing a residual-current device as additional protection in order to achieve the highest possible degree of safety. It can also provide the function of an all-pole disconnecting switch, which is frequently required for other reasons or regulations.
7/11
Technical Information
8/11
Technical Information
The integrated all-pole sensitive residual-current monitoring unit (RCMU) results in additional safety. For inverters with grounding conductor monitoring, this must be activated. These statements also apply to versions of the listed devices with deviating power.
9/11
Technical Information
Calculation Examples
5 Calculation Examples
The selection of suitable electric equipment as fault protection through automatic disconnection is illustrated in 2 examples below. It is always assumed that the necessary protective electric bonding is being carried out simultaneously. The values used are examples which cannot be used as guideline values for the respective grounding system or application.
5.1Calculation Example 1
1 Sunny Boy SB 2100TL; fused with a miniature circuit-breaker B16A; TN grounding system; loop impedance Zs = 1.5 ; barn roof:
LS B16A has a short-circuit operating current Ia of 80 A (B-characteristics: factor 5; Inom of the miniature circuit-breaker = 16 A => 5 x 16 A = 80 A). At 230 V, 153 A can flow through the fault loop ( ). The 153 A are higher than the required 80 A operating current of the miniature circuit-breaker. Therefore, the miniature circuit-breaker will disconnect safely within the specified time. LS B16A suffices as fault protection against indirect contact. However, since it is a barn, in this case an additional type A residual-current device with a rated residual current of max. 300 mA must be installed. That is required in accordance with DIN VDE 0100-482 (IEC 60364-4-42:2001-08) for fire protection reasons.
10/11
Technical Information
Calculation Examples
5.2Calculation Example 2
3 Sunny Mini Centrals SMC 6000TL; fused with one miniature circuit-breaker C32A each; TT grounding system; loop impedance Zs = 0.2 ; RA = 1.1 :
LS C32A has a short-circuit operating current of 320 A (C-characteristics: factor 10; Inom of the miniature circuit-breaker = 32 A => 10 x 32 A = 320 A). 230 V = 177 A ). At 230 V, 177 A can flow through the fault loop ( 1,3 The 177 A are lower than the required 320 A operating current of the miniature circuit-breaker. Therefore, the miniature circuit-breaker will not disconnect safely within the specified time. LS C32A is not sufficient as fault protection against indirect contact. First option: use of another miniature circuit-breaker (if possible) If using a miniature circuit-breaker B32A, the short-circuit operating current would be 160 A (B-characteristics: factor 5; Inom of the miniature circuit-breaker = 32 A => 5 x 32 A = 160 A). The operating current of the miniature circuit-breaker with B-characteristics would be less than the 177 A which would flow in the event of a fault. Therefore, these miniature circuit-breakers would disconnect within the specified time. The miniature circuit-breaker B32A suffices as fault protection against indirect contact. Second option: use of a residual-current device In case no other miniature circuit-breaker can be employed, a residual-current device must be used for fault protection. Since 3 transformerless inverters are being used, the rated residual current according to Section 4.2 "Operational Differential Currents" (page9) must be at least 300 mA. A residual-current device with a rated residual current If of 500 mA is selected. In addition, it should be tested according to the condition of 4 b (see page 9), whether the protective effects are sufficient: 50 V RA = 1,1 < , thus 1,3 x If A type A residual-current device with a rated residual current If of 500 mA guarantees fault protection against indirect contact.
11/11