0% found this document useful (0 votes)
238 views2 pages

s010 Usa OPGW Standard PDF

Optical core is made of optical fibers covered by one or more loose buffer tubes that leave the fibers free from strain even at highest operating loads. In sections where there is a high contamination or in the proximity of the sea, Prysmian recommend greasing the cable. Aluminum tube provides the cable with: high short circuit capacity minimizing material best solution to avoid cable corrosion a perfect sealing for the optical core a high crush resistance the wires of. Aluminum clad steel. Aluminum alloy.provides the

Uploaded by

Alberto García
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
238 views2 pages

s010 Usa OPGW Standard PDF

Optical core is made of optical fibers covered by one or more loose buffer tubes that leave the fibers free from strain even at highest operating loads. In sections where there is a high contamination or in the proximity of the sea, Prysmian recommend greasing the cable. Aluminum tube provides the cable with: high short circuit capacity minimizing material best solution to avoid cable corrosion a perfect sealing for the optical core a high crush resistance the wires of. Aluminum clad steel. Aluminum alloy.provides the

Uploaded by

Alberto García
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

OPGW

OPTICAL GROUND WIRES


with capacity up to
96
optical fibres

Ref: s010
Introduction
Features and benefits
This cable has been custom designed to best match
with customer requirements from optical, electrical,
mechanical, quality and cost point of view,
optimizing diameter, weight, breaking load and
short circuit capacity.
Optical core is made of optical fibers [1] covered by
one or more loose buffer tubes [2] that leave the
fibers free from strain even at highest operating
loads.
In sections where there is a high contamination or
in the proximity of the sea, Prysmian recommend
greasing the cable.
A Prysmian patented hydrogen absorbent jelly [3] is
used to protect optical fibers from hydrogen attack.
The aluminum tube [4] provides the cable with:
high short circuit capacity minimizing material
best solution to avoid cable corrosion
a perfect sealing for the optical core
a high crush resistance
[1]
[2]
[3]
[4]
[5]
[6]

The wires of...


aluminum clad steel [5].
aluminum alloy [6].
...provides the cable with:
the required strength.
best solution to avoid cable corrosion.
the remaining short circuit capacity.

Fibre characteristics
See our technical document reference 4377
SMLight G.652.B, FreeLight G.655.D, multimode
50/125 and multimode 62.5/125 optical fibers and
document reference 4647 MagniLight G.652.D.

PRYSMIAN 2006, All Rights Reserved.


The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the
written consent of Prysmian. The information is believed to be correct at the time of issue. Prysmian reserves the right to amend this
specification without prior notice. This specification is not contractually valid unless specifically authorised by Prysmian.

Rev.:
06

Date:
27-jul-11

Issued by:
V. Ghinaglia
page 1 of 2

OPTICAL GROUND WIRES


with capacity up to
96
optical fibres

OPGW
Ref: s010
Cable characteristics

Optical unit composed by 1 to 4 tubes.


Temperature range: -40C to 80C
Lay direction armor: left (S) or right (Z)

FIBER
(max)

OPGW REFERENCE

TOTAL
CONDUCTOR
AREA

OVERALL
DIAMETER

(kA)sec

in

mm

in

mm

lbs/ft

kg/m

lbs

kg

FAULT
CURRENT

WEIGHT

RBS

SAG10
CHART #

12

OPGW 18A46 (7546)

41

0.1232

79.5

0.465

11.8

0.308

0.458

16226

7360

1-1421

12

OPGW 18B34 (7521)

51

0.1232

79.5

0.465

11.8

0.228

0.340

10362

4700

1-1439

12

OPGW 28C56 (7520)

56

0.1468

94.7

0.504

12.8

0.374

0.556

20349

9230

1-1442

12

OPGW 28D43 (7562)

70

0.1468

94.7

0.504

12.8

0.288

0.428

13735

6230

1-917

24

OPGW 34D55 (7522)

68

0.1500

96.5

0.528

13.4

0.367

0.546

18409

8350

1-1450

24

OPGW 34D43 (7772)

81

0.1500

96.5

0.528

13.4

0.287

0.427

12147

5510

1-1439

24

OPGW 40E61 (7557)

81

0.1650

106.6

0.552

14.0

0.410

0.611

21142

9590

1-1453

24

OPGW 40F46 (7523)

98

0.1650

106.6

0.552

14.0

0.311

0.463

13558

6150

1-1438

36

OPGW 45F62 (7524)

95

0.1765

113.9

0.571

14.5

0.415

0.617

20569

9330

1-1461

36

OPGW 45G49 (7525)

110

0.1765

113.9

0.571

14.5

0.327

0.486

13801

6260

1-1438

36

OPGW 54H73 (7526)

118

0.2018

130.2

0.607

15.4

0.487

0.725

24846

11270

1-1457

36

OPGW 54J57 (7527)

141

0.2018

130.2

0.607

15.4

0.381

0.567

16667

7560

1-1439

48

OPGW 64K78 (7540)

151

0.2227

143.7

0.646

16.4

0.519

0.773

25111

11390

1-1461

48

OPGW 64K64 (7541)

172

0.2227

143.7

0.646

16.4

0.425

0.641

18056

8190

1-1439

48

OPGW 83N105 (7543)

239

0.2878

185.7

0.724

18.3

0.707

1.052

35054

15900

1-1453

48

OPGW 83P80 (7552)

292

0.2878

185.7

0.724

18.3

0.537

0.799

22531

10220

1-1438

72

OPGW 67K78 (7995)

154

0.2229

143.8

0.659

16.7

0.531

0.784

25573

11600

1-1461

72

OPGW 67K63 (7996)

177

0.2229

143.8

0.659

16.7

0.426

0.630

17747

8050

1-1438

72

OPGW 73L88 (7999)

182

0.2446

157.8

0.691

17.3

0.595

0.879

29784

13510

1-1450

72

OPGW 73M70 (7997)

212

0.2446

157.8

0.691

17.3

0.476

0.704

20624

9355

1-1439

96

OPGW 62J72 (8000)

138

0.2080

134.2

0.637

16.2

0.489

0.723

23192

10520

1-1166

96

OPGW 62J57 (8001)

159

0.2080

134.2

0.637

16.2

0.384

0.568

15079

6840

1-1441

96

OPGW 84N104 (7994)

230

0.2818

181.8

0.726

18.4

0.701

1.036

35163

15950

1-1453

96

OPGW 84P81 (7632)

277

0.2818

181.8

0.726

18.4

0.547

0.808

23545

10680

1-1439

Routine tests
100% of optical fibers will be measured by OTDR technique before leaving factory.

Installation procedure
Prysmian recommends installing the cable described in this specification following the latest version of our
"Installation procedures for OPGW fiber optic cable" reference SIG-07-PE-PA-013, "Instruction for the installation of
the EWMJ joint box" reference SIG-07-PE-PA-015 and "Instruction for the installation of the EWJ joint box"
reference SIG-07-PE-PA-008.
PRYSMIAN 2006, All Rights Reserved.
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the
written consent of Prysmian. The information is believed to be correct at the time of issue. Prysmian reserves the right to amend this
specification without prior notice. This specification is not contractually valid unless specifically authorised by Prysmian.

Rev.:
06

Date:
27-jul-11

Issued by:
V. Ghinaglia
page 2 of 2

You might also like