Feeder Protection: For Overhead Lines and Cables in Isolated Neutral or Compensated Networks Specification
Feeder Protection: For Overhead Lines and Cables in Isolated Neutral or Compensated Networks Specification
for overhead lines and cables in isolated neutral or compensated networks Specification
Feeder protection for overhead lines and cables in isolated neutral or compensated networks
Version Date Pages
Version 15F-AB2 B
10-09-2012
3 (16)
1 2 3
Feeder protection relay for outgoing feeders ....................................................................................................... 4 General ................................................................................................................................................................ 4 Mechanical design and mounting ........................................................................................................................ 5 3.1.1 Current connections ........................................................................................................................... 5 3.1.2 Mounting ............................................................................................................................................. 5 3.2 LHMI ............................................................................................................................................................ 5 3.2.1 Circuit breaker control ........................................................................................................................ 5 3.2.2 Indications and LEDs .......................................................................................................................... 6 3.2.3 Web server functionality ..................................................................................................................... 6 3.2.4 Local/Remote switch .......................................................................................................................... 6 3.3 Binary inputs and outputs ............................................................................................................................ 6 3.3.1 Trip outputs and master trip ................................................................................................................ 7 3.3.2 Self supervision and IRF output ......................................................................................................... 7 3.4 Current input channels ................................................................................................................................ 7 4 Protection ............................................................................................................................................................. 8 4.1 Current based protection ............................................................................................................................. 8 4.1.1 Non-directional overcurrent protection ............................................................................................... 8 4.1.2 Admittance based or directional earth-fault protection ....................................................................... 8 4.1.3 Transient/Intermittent earth fault......................................................................................................... 9 4.1.4 Negative sequence overcurrent protection ......................................................................................... 9 4.1.5 Phase discontinuity protection ............................................................................................................ 9 4.2 Other protection functions ........................................................................................................................... 9 4.2.1 Thermal overload protection ............................................................................................................... 9 4.2.2 Breaker-failure protection ................................................................................................................... 9 4.3 Optional protection functions ....................................................................................................................... 9 4.3.1 Auto-reclosing ................................................................................................................................... 10 4.3.2 ARC protection ................................................................................................................................. 10 4.3.3 Earth-fault protection ........................................................................................................................ 10 5 Measurements ................................................................................................................................................... 11 5.1 Phase currents .......................................................................................................................................... 11 5.2 Residual current ........................................................................................................................................ 11 5.3 Current sequence components ................................................................................................................. 11 5.4 Residual voltage ........................................................................................................................................ 11 6 Disturbance, fault and event recording .............................................................................................................. 12 6.1 Event registration ...................................................................................................................................... 12 6.2 Fault records ............................................................................................................................................. 12 6.3 Disturbance records .................................................................................................................................. 13 6.4 Time synchronization ................................................................................................................................ 13 7 Condition monitoring .......................................................................................................................................... 13 7.1 Self supervision ......................................................................................................................................... 13 8 Communication interfaces ................................................................................................................................. 14 8.1 IEC 61850 GOOSE messaging ................................................................................................................. 14 8.2 User authorization ..................................................................................................................................... 14 9 Setting and configuration software..................................................................................................................... 14 10 Environmental conditions ................................................................................................................................... 15 11 Quality assurance and standards ...................................................................................................................... 15
4 (16)
The specification highlights constructional features and software functions that are required within the specific relay application area. The specification applies to design, manufacture, supply, testing and operation of protection, measuring and control functions intended for outgoing feeder applications in electrical power systems of either underground neutral cable or over headline construction primarily suitable for networks which directly or resistance earthed neutrals.
2 General
The provided relay shall work reliably and selectively as apart of a protection system. The relay must not operate at faults occurring outside the protection zone. Internal faults or disturbances in the auxiliary supply or measurement circuits may not result in un-correct operation of the device. Each start or trip provided by the relay must generate clear and reliable indications. These indications must be transferable to an upper level system over the station bus. The relay shall be of a numerical communicating type offering extensive protection, control and measuring functions in one enclosed unit. The protection relay basic design and data modeling shall be based on the IEC 61850 standard. Special attention has to be paid in minimizing the replacement time of a defective unit, preferably by means of plug-in units. The relay shall have full flexibility in terms of assigning any binary input and output signal to the internal logic circuits. The following specification highlights the most important features of the relay. In no means the following shall be regarded as a complete specification for the relay. In addition the relay must fulfill the relevant IEC standards and be suitable for the intended applications, as described in the complete set of specifications, or otherwise communicated to the prospective Bidders.
5 (16)
3.2 LHMI
The LHMI shall support local measurement, event and alarm views through its LCD display. It shall also enable the parameter settings. It shall be possible to choose either the main menu or the measurement view as the default view. The LCD is to be fitted with at least four rows of characters with easily readable font size. 3.2.1 Circuit breaker control It shall be possible to control a circuit breaker e by means of designated control buttons. It shall be possible to interlock the circuit breaker close command directly by a binary input, by a protection relay internal interlocking logic and thermal protection operation or by a protection relay trip command output operating in lockout mode.
6 (16) 3.2.2 Indications and LEDs Each start and trip from every protection function must be clearly indicated. It must also be possible to transfer the start and trip signals to the binary outputs if required and it must be possible to transfer them to an upper level system via communication link. The resetting of indications and alarm LEDs shall be easy, preferably by pressing one button only. The LHMI shall include at least eleven (11) freely programmable alarm LEDs for status indication. It shall be possible to insert a written clarification on a paper strip beside each of the LEDs to indicate the assigned function of the LED. 3.2.3 Web server functionality The relay shall be equipped with web server functionality to cater for remote HMI features, using commonly available web browser software. The web server functionality shall utilize the same user authority handling principles, as defined later on in this specification for the LHMI functionality. Activation of the web server shall need user intervention, thus the functionality shall be disabled as a default. 3.2.4 Local/Remote switch The LHMI shall be equipped with a Local/Remote switch including status indication. The operation rights of the L/R switch shall be covered the with user authorization procedures of the relay. When in local mode, the remote control commands to the circuit breaker shall be ignored and vice versa in remote mode.
7 (16) It shall be possible, by software, to freely assign the binary inputs and outputs to the protection relay internal function logic. Also possibility to introduce simple logic functions, in the form of AND and OR gates including signal inversion, in front of the binary inputs and outputs shall also be foreseen. As an example; a possibility to energize a binary output from a number of internal relay signals (OR-gate) shall be available. 3.3.1 Trip outputs and master trip Two binary outputs shall be dimensioned for circuit breaker trip purposes, introducing trip circuit supervision functionality and a possibility for double pole operation. It shall be possible to exclude the tripping circuit supervision functionality from the outputs physically by changing the protection relay terminal connections. If required it must be possible to block all trip outputs by means of a single setting (master tripIn order to prevent the closing of a circuit breaker after a trip without resetting, there must be so called "lock-out" mode available. The trip circuit must be supervised. 3.3.2 Self supervision and IRF output The relay shall be equipped with extensive self-supervision capabilities. In case of internal failure, the relay shall in no case issue a false trip signal. The failure code shall be visible on the protection relay LHMI (Local Human Machine Interface) display. The failure codes shall give detailed information about the situation. The end user documentation shall support the interpretation of the failure code in detail and by simple means. A dedicated IRF (Internal Relay Fault) output must be available in order to provide IRF status to external systems.
8 (16)
4 Protection
To handle periodic changes in the primary circuit switching conditions, i.e. the network topology, there shall be support for at least four (4) different setting banks for each of the protection functions. The change of setting bank shall take place commonly for all of the protection functions. It shall be possible to change the setting bank locally from the LHMI, using a binary input signal and remotely through the communication link. The change of setting bank shall happen rapidly and it shall not result in a protection relay restart, a relay malfunction or a communication break. The protection functions listed below shall be regarded as the compulsory basic protection features. It shall be possible to either enable or disable each protection stage, depending on the requirements of the actual application.
9 (16) 4.1.3 Transient/Intermittent earth fault In order to secure accurate operation, the transient/intermittent earth-fault protection must be based on a sampling function designed for the protection and clearance of intermittent and transient earth faults in distribution and subtransmission networks. Fault detection should be done from the residual current and residual voltage signals by monitoring the transients using predefined criteria. The sampling frequency shall be high enough for proper detection of transient / intermittent earth faults. The operate time characteristics must be definite time (DT). 4.1.4 Negative sequence overcurrent protection The protection shall consist of two different stages, covering setting range from 0.10 to 5 times pu. During an inrush situation when large amount of second harmonic is detected, it shall be possible, for each of the stages, to raise the setting value by a freely settable multiplier. 4.1.5 Phase discontinuity protection In order to achieve a capability to handle different load situations the protection shall be based on monitoring the negative sequence and the positive sequence current component ration (I2/I1). It shall be possible to block the operation of the stage by the starting signal from any of the earth- fault protection stages or by the inrush current situation detection.
10 (16) 4.3.1 Auto-reclosing The auto-reclosing function shall support at least five shots within a sequence, consisting of a settable mixture of high-speed auto-reclosing (HSAR) and delay auto-reclosing (DAR). It shall be possible to perform at least five consecutive shots, or block the auto-reclosing function, based on the nature of the detected fault. For easy setting and handling of the auto-reclosing function, no possibility (and no settings) for single-phase auto-reclosing shall be included. 4.3.2 ARC protection Arc protection shall be based on the detection of current and light simultaneously. During maintenance work at the substation, it shall be possible to change the operation criteria to light only, by control via a binary input. The current monitoring levels shall be separately adjustable for phase currents and the residual current. It shall be possible to monitor the busbar, circuit breaker and cable compartments simultaneously by means of compartment dedicated sensors. Tripping command to the up-stream circuit breaker shall be selective, based on the location of the ARC. The operating time of the protection shall be less than 15 ms, including the inherent delay of the output relays. 4.3.3 Earth-fault protection The relay shall offer various options for different earth-fault protection methods along with the traditional directional and non-directional earth-fault protection, such as earth-fault protection based on admittance criteria, watt-metric criteria or harmonics content in earth-fault current.
11 (16)
5 Measurements
There shall be measurements functions and indication in LHMI for analogue inputs (current and voltage) connected to the relay, as per the following:
12 (16)
6.1
Event registration The SoE (Sequence of Events information must be accessible locally via the user interface on the relay front panel or remotely via the communication interface of the relay. The information should further be accessible, either locally or remotely, using the web-browser based user interface. To collect sequence-of-events (SoE) information, the relay must incorporate a nonvolatile memory with a capacity of storing at least 1000 event codes with associated time stamps. The non-volatile memory must retain its data also in case the relay temporarily loses its auxiliary supply. The event log should facilitate detailed preand post-fault analyses of feeder faults and disturbances.
13 (16)
7 Condition monitoring
The condition monitoring functions of the device must constantly monitor the performance and the condition of the circuit breaker. When specified the monitoring should at least cover the spring charging time, SF6 gas pressure, the travel-time and the inactivity time of the circuit breaker.
14 (16)
8 Communication interfaces
The relay shall be of native IEC 61850 design, thus offering optimal connection interface to a substation automation systems based on the 61850-8-1 standard. The physical communication connection shall be based on an Ethernet bus either with galvanic 100BaseTX (RJ45) interface or optical 100BaseFX (LC) interface. For increasing station bus communication availability and reliability, the relay shall have support for Ethernet redundancy. At minimum, support for RSTP (Rapid Spanning Tree Protocol) redundancy shall be available, but more preferably HSR (High-availability Seamless Redundancy) or PRP (Parallel Redundancy Protocol) shall be supported. Other communication possibilities shall cover Modbus over WAN and Modbus serial. On the front side of the relay there shall be a local communication interface with an RJ45 connector. This connection shall be dedicated for the protection relay local user interface, allowing parameterization, disturbance recorder upload, etc using software tools.
15 (16)
10 Environmental conditions
The relay must fulfill the environmental conditions listed below. Description Operating temperature range Short-time service temperature range Relative humidity Value -25...+55C (continuous) -40...+85C (<16h) <93%, non-condensing
Electromagnetic compatibility tests The EMC immunity test level meets the requirements listed below: Description Value 1 MHz burst disturbance test, class III: According to IEC 61000-4-18 and IEC 60255-22-1, level 3 Electromagnetic compatibility tests Fast transient disturbance tests: All ports Mechanical tests Description Vibration tests (sinusoidal) Shock and bump test According to IEC 61000-4-4 and IEC 60255-22-4, class A 4 kV