JemsStar Data Sheet
JemsStar Data Sheet
REVENUE METER
High precision and ease of use best describe the JEMSTAR revenue meter. Quick intuitive setup using Windows based software makes configuration a breeze. For revenue and billing, the JEMSTARs high accuracy guarantees that every measurement is properly accounted for. Anticipate loads in advance with our demand prediction option. Our advanced communication options provide many choices and protocol platforms for easy access to our metering data. For peace of mind, your site conditions are continuously monitored with our diagnostic tools that notify you quickly of any impending problem. Ease of Use The JEMSTAR is the easiest meter to configure with its Windows based JEMWARE Configuration Wizard and on-line help system. The quick intuitive process eliminates the need for specialized training and gets you up and running with minimal effort. The JEMSTAR meter is user friendly with its built-in menu-driven display and site verification tools. High Accuracy The JEMSTAR has a guaranteed accuracy of 0.07% on watt-hours with an unprecedented typical accuracy of 0.03%. When accounting for revenue, even a fraction of a percent can mean the difference of thousands of dollars. Accuracy is further enhanced with TLC, LLC and selectable gain adjustments on PTs and CTs. Power Quality The JEMSTAR records voltage sag and swells based on configurable thresholds so you can determine the quantity, severity and location of your power quality disturbances. In addition, the JEMSTAR logs current/ voltage THD, power factor, imbalance and frequency so you have the complete picture on power quality. Site Diagnostic Tools You will be notified automatically of site and diagnostics problems from configured threshold settings and system status diagnostics including Phone Home on Power Failure. Advanced Communication Many communication choices are available with RS232, RS-485, internal modems and optical probes.
Simultaneous communications are possible using industry standard protocols: DNP 3.0, Modbus RTU and ASCII, ANSI Tables, JEM Binary and support for MV90.
P O W E R
M E A S U R E M E N T
P R O D U C T S
SPECIFICATIONS
METER FORMS
Meter Forms: 5, 6, 8, 9 Demand Registers Fixed or sliding window Interval length: 1-60 minutes
COMMUNICATIONS
Optical Port (Standard) Type 2 19,200 Baud RS-232 & RS-485 (Optional) User configurable: 300 to 38400 Baud Internal Modem (Optional) User configurable: 300 to 14400 Baud Phone Home on Power Outage Modem (Optional) Modem/RS-485 CR (Communication Repeater) (Optional) Protocols Modbus ASCII or RTU (optional) DNP 3.0 (optional) ANSI Tables (optional) JEM Binary (standard) IEC 870-5-102 (standard)
INPUTS
Voltage 55-530 VAC auto-ranging Burden*: 0.5 VA @ 530V *Does not include auxiliary power requirements. Current 1 Amp: ANSI Class 2 5 Amps: ANSI Class 10 10 Amps: ANSI Class 20 Burden: 0.5 VA maximum Overload: 1.5x rated class current continuous, 20x rated class current for 0.50 sec Frequency range: 45-55 Hz, 55-65 Hz
LOAD PROFILE
4 channels of storage (standard) 12 channels of storage (optional) Programmable Interval 1-60 minutes 45 days storage using four channels at 15-minute intervals
TOTALIZATION (OPTIONAL)
Up to 2 contact inputs Up to 12 totalization measurements displayed and recorded
AUXILIARY POWER
55 530 VAC, 90 250 VDC S-base and A-base Normally derived from A-phase voltage input Switchboard Separate terminals, AC or DC Auxiliary Power Burden 15 VA maximum
MECHANICAL
Case Styles Socket connected (S base), small switchboard case, bottom connected (A-Base), meter retrofits (JEM-2 and others) Size and Weight S base: 5.5 pounds A-base: 7.5 pounds Switchboard case: 11.5 pounds
ACCURACY
Watthour 0.07% Reading (0.03% Typ.) Clock Synchronized to line or +3 minutes per month maximum error for internal reference. Loss Compensation Transformer Loss Compensation (TLC) and Line Loss Compensation (LLC) PT and CT Error Gain Correction
ENVIRONMENT
Operating Temperature -40O to 185OF (-40O to 85OC) Storage Temperature -40O to 185OF (-40O to 85OC) Humidity 5 to 95% relative humidity, non-condensing Surge Withstand (SWC) ANSI Standard C37.90.1-1989, ANSI Standard C62.41 Fast Transient IEC Standard 687 Section 5.5.4
MEASUREMENTS
Energy PolyPhase Quantities Watthour, VARhour, VAhour, Amphour, Qhour Energy Per Phase Quantities Watthour, VARhour, VAhour, Amphour, Qhour Instantaneous Quantities Per phase: +Watts, +VARs, Quadrant VARs, +VA, +Q, PF, Volts, Volts THD, Amps, Neutral Current, Amps THD, Volts2, Amps2 System: +Watts, +VARs, Quadrant VARs, +VA, +Q, PF, Volts, Amps, Amps2, average Volts, frequency
STANDARDS
Agency Standards and Certifications: ANSI Standard C12.16-1991 ANSI C12.20-1998 Accuracy 0.2% IEC Standard 687 Class 0.2 FCC Part 68, FCC Part 15 IEC 60687 CE Measurement Canada California ISO NY PSC
REGISTERS
50 Normal, 50 Alternate, 50 Test For customer support call:
POWER INSTRUMENTS
255 North Union Street Rochester, NY 14605 Tel: 585.263.7700 Fax: 585.454.7805 [email protected]
HEADQUARTERS
AMETEK Power Instruments 50 Fordham Road Wilmington, MA 01887 Tel: 978.988.4903 Fax: 978.988.4990 [email protected]
EUROPEAN HEADQUARTERS
Unit 20, Ridgeway Donibristle Industrial Estate Dalgety Bay, Dunfermline, KY119JN Scotland U.K. Tel: 44.1383.825630 Fax: 44.1383.825715 [email protected]
ISO 9001 Certified 2003, by AMETEK, Inc. All rights reserved. 5M303CW (210061)