ME2121-2 Lab Report
ME2121-2 Lab Report
SEMESTER 3 2013/2014
Objective To examine the vapour compression refrigeration cycle of the air conditioner and evaluate the cooling capacity, power consumption and the Coefficient of Performance (COP) under different fan speeds.
Results Using the readings recorded in the raw data sheet as well as the psychrometric chart, In the high fan experiment, Flow rate = 7.7m3/min For air inlet, Ti = (24.3 0.1) oC Relative Humidity = (49.4 0.1)% Using psychrometric chart, Enthalpy, h = 49.0 kJ/kg of dry air Specific volume, v = 0.856 m3/kg of dry air Humidity ratio, w = 0.0095 kg moisture /kg of dry air Wet bulb temperature = 17.4 oC
For air outlet, To = (13.4 0.1) oC Relative Humidity = (85.2 0.1)% Using psychrometric chart, Enthalpy, h = 35.0 kJ/kg of dry air Specific volume, v = 0.823 m3/kg of dry air Humidity ratio, w = 0.0085 kg moisture /kg of dry air Wet bulb temperature = 12.3 oC
In the low fan experiment, Flow rate = 6.8m3/min For air inlet, Ti = (25.8 0.1) oC Relative Humidity = (45.4 0.1)% Using psychrometric chart, Enthalpy, h = 50.5 kJ/kg of dry air Specific volume, v = 0.860 m3/kg of dry air Humidity ratio, w = 0.0095 kg moisture /kg of dry air Wet bulb temperature = 17.8 oC
For air outlet, To = (13.8 0.1) oC Relative Humidity = (85.2 0.1)% Using psychrometric chart, Enthalpy, h = 36.0 kJ/kg of dry air Specific volume, v = 0.824 m3/kg of dry air Humidity ratio, w = 0.0085 kg moisture /kg of dry air Wet bulb temperature = 12.5 oC
QN1. Schematic Diagram of Refrigeration Cycle Temperature readings were taken at the points indicated by the squares and pressure readings were taken at points as shown by the circles.
Eout
Evaporator
Ein
T1
Cin Cin Cin
1 Expansion Device
T2
Cin Cin Cin
T4 T3
Cin Cin Cin
Cin
Cin Cin
Condenser
Cin
Cout
Heat rejected
Calculations QN2. (i) As there are 2 methods to calculate the cooling capacity of the air conditioner, both methods will be used and the average of the results obtained by each method will be taken.
=2118 W
=2023 W
=2183 W
=1994 W
Cooling capacity at high fan = 0.5(2118 + 2183) = 2151 W Cooling capacity at low fan = 0.5(2023 + 1994) = 2009 W
(ii)
The Energy Efficiency Ratio is the same, except that the capacity is expressed in Btu/h instead.
(iii)
The fraction of the capacity that goes to dehumidify the air is as follows:
17.9%
16.9%
(iv)
Error Analysis
The sensible heat transferred to the refrigerant, The relative error in the sensible heat can be expressed as:
since only the error caused by temperature measurement is taken into account. Therefore, the absolute error:
where
and
Similarly, the error in the latent heat transferred to the refrigerant can be established as follows: The latent heat transferred to the refrigerant,
The error in the cooling capacity and COP can be expressed as:
Error in COP:
Error in COP:
From the error calculations above, it can clearly be seen that most of the error is contributed by the error in the latent heat. This is most likely because the absolute humidity of air is not directly measurable in this experiment and relies on the psychrometric chart to obtain an estimate of the value, which is subject to human error. Furthermore, the change in absolute humidity is very small, which amplifies the significance of the error as well.
Diagram and sketches QN3. At high fan speed, Absolute pressure readings = Gauge pressure + 1 bar Pressure at evaporator inlet Pressure at evaporator outlet Pressure at condenser inlet Pressure at condenser outlet
QN4. Total heat rejection can be estimated to be the total energy of the hot exhaust air minus the initial energy of the air into the condenser.
kJ kJ
kJ kJ
The amount of heat rejected is very large. However, it may be possible to recover part of the energy rejected to the atmosphere. This is because the thermodynamic process in the compressor requires an increase in both temperature and pressure, therefore if the exhaust heat can somehow be transferred back to the compressor, some of the heat may possibly be converted to work, thus increasing the efficiency of the system. Conclusion Through this experiment, I have learnt about the workings of the air conditioner and its refrigeration cycle and evaluated its performance by calculating the cooling capacity, power consumption, the resulting Coefficient of Performance and Energy Efficiency Ratio. Also, the operation of the air conditioner rejects an extremely large amount of thermal energy into the atmosphere and we should look for ways to make this energy useful.