This document provides technical specifications for the HXHD-A high temperature hydrobox, including: 1. Features of the unit such as providing heating through heat recovery from VRV systems and the ability to heat water from 25-80°C. 2. Specifications including dimensions, weight, refrigerant used, water pressure and temperature ranges, electrical specifications, and performance data. 3. A selection procedure that defines indexes for the unit and provides a method for calculating its heating capacity based on the outdoor unit and other indoor components in the system.

Uploaded by

Luis Carlos
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
337 views

HXHD-A Technical Data (EEDEN13-204) PDF

This document provides technical specifications for the HXHD-A high temperature hydrobox, including: 1. Features of the unit such as providing heating through heat recovery from VRV systems and the ability to heat water from 25-80°C. 2. Specifications including dimensions, weight, refrigerant used, water pressure and temperature ranges, electrical specifications, and performance data. 3. A selection procedure that defines indexes for the unit and provides a method for calculating its heating capacity based on the outdoor unit and other indoor components in the system.

Uploaded by

Luis Carlos
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

Air Conditioning

Technical Data
High temperature hydrobox for VRV
EEDEN13-204
HXHD-A
VRV Systems HXHD-A 1
Indoor Unit HXHD-A
TABLE OF CONTENTS
HXHD-A
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Selection procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wi r i ngDi agrams- Si ngl ePhase 11
8 External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
So undPowe r Spec t r um16
So undPressur eSpectr um 17
10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11 Hydraulic performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Stati cPr essureDr o pUni t 19
Indoor Unit HXHD-A
1
VRV Systems HXHD-A 2
1 Features
I n d o o r U n i t V R V S y s t e m s H X H D - A H i g h t e m p e r Air to water connection to VRV for applications such as bathrooms,
sinks, underfloor heating, radiators and air handling units
Free heating provided by transferring heat from areas requiring
cooling to areas requiring heating or hot water
Uses heat pump technology to produce hot water efficiently,
providing up to 17% savings compared to a gas boiler
Possibility to connect thermal solar collectors to the domestic hot
water tank
Leaving water temperature range from 25 to 80C without electric
heater
Super wide operating range for hot water production from -20 to
+43C ambient outdoor temperature
Saves time on system design as all water-side components are fully
integrated with direct control over leaving water temperature
Various control possibilities with weather dependant set point or
thermostat control
The indoor unit and domestic hot water tank can be stacked to save
space, or installed next to each other, if only limited height is available
Requires no gas connection or oil tank
Connectable to VRV III heat recovery (REYAQ-P)
3
2
VRV Systems HXHD-A 3
Indoor Unit HXHD-A
2 Specifications
2-1 Technical Specifications HXHD125A
Heating capacity Nom. kW 14.0 (1)
Casing Colour Metallic grey
Material Precoated sheet metal
Dimensions Unit Height mm 705
Width mm 600
Depth mm 695
Packed unit Height mm 860
Width mm 680
Depth mm 800
Weight Unit kg 92
Packed unit kg 103
Packing Material EPS / Cardboard / MDF / Wood (pallet) / Metal
Weight kg 8.75
Pump Type DC motor
Nr of speeds Inverter controlled
Nominal ESP unit Heating kPa 37.0 (2)
Expansion vessel Volume l 7
Max. water pressure bar 3
Pre pressure bar 1
Sound power level Nom. dBA 55
Sound pressure level Nom. dBA 42 (5) / 43 (6)
Night quiet mode Level 1 dBA 38 (5)
Operation range Heating Ambien
t
Min. C -20
Max. C 20 / 24 (11)
Water
side
Min. C 25
Max. C 80
Domestic hot water Ambien
t
Min. CDB -20
Max. CDB 43
Water
side
Min. C 45
Max. C 75
Refrigerant Type R-134a
Charge kg 2
Refrigerant circuit Gas side diameter mm 12.7
Liquid side diameter mm 9.52
High pressure side Design pressure bar 38
Water circuit Piping connections diameter inch G 1" (female)
Piping inch 1"
Safety valve bar 3
Manometer Yes
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes
Heating water
system
Water
volume
Min. l 20
Max. l 200
Refrigerant oil Type FVC50K
Charged volume l 0.75
Refrigerant side heat
exchanger
Type Plate heat exchanger
Quantity 1
Plates Quantity 66
Material AISI 316
Insulation material Felt type
Indoor Unit HXHD-A
2
VRV Systems HXHD-A 4
2 Specifications
Notes
(1) EW 40C; LW 45C; Dt 5C; ambient conditions: 7CDB/6CWB
(2) For water Dt 5C
(3) Sound level is valid in free field condition because it is measured in a semi-anechoic room. Measured value under actual installation conditions will be higher due to environmental
noise and sound reflections.
(4) Values are sound pressure values measured at all sides (front, back, left, right, top) at 1m distance. The values do not occur simultaneously on all mentioned sides.
(5) Sound levels are measured at: EW 55C; LW 65C
(6) Sound levels are measured at: EW 70C; LW 80C
(7) In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys
(system impedance) Zmax
(8) EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for
equipment with rated 75A
(9) EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input
Water side Heat
exchanger
Water flow rate Min. l/min 5
Heating Nom. l/min 40.1 (2)
Heating Type Plate heat exchanger
Quantity 1
Plates Quantity 72
Material AISI 316
Water volume l 2.2
Insulation material Felt type
Water filter Diameter perforations mm 1
Material Brass
Cascade compressor Quantity 1
Motor Type Hermetically sealed swing compressor
Starting method Direct on line
Installation place Indoor
2-2 Electrical Specifications HXHD125A
Power supply Phase 1~
Frequency Hz 50
Voltage V 220-240
Voltage range Min. % -10
Max. % 6
Current Zmax Text 0.46
Minimum Ssc value kVa 1,459
Maximum running
current
Heating A 16.5
Recommended fuses A 20
Wiring connections For power supply Quantity 2G
Type of wires Select diameter and type according to national and local regulations
Benefit kWh rate
power supply
installations
Quantity 2G+2G
Type of wires Select diameter and type according to national and local regulations
For power supply
multi tenant
Quantity 2G
Remark Select diameter and type according to national and local regulations
For connection with
outdoor unit
Quantity 2
Remark F1 + F2
Power supply intake Both indoor and outdoor unit
Multi tenant Power supply Voltage V 24
Voltage
range
Min. % -20
Max. % 20
Current Maximum running
current
A 1
Recommended
fuses
A 3.15
2-1 Technical Specifications HXHD125A
3
2
VRV Systems HXHD-A 5
Indoor Unit HXHD-A
2 Specifications
current \> 16A and 75A per phase
(10) Ssc: Short-circuit power
(11) Field setting
Indoor Unit HXHD-A
3
VRV Systems HXHD-A 6
3 Selection procedure
HXHD125A
REYAQ-P
3TW60669-2A
I. Denitions
Index denition of HXHD125A
1) ndex for selecting piping, calculating refrigerant charge and total connection ratio
ndex = 125 (see installation manual & technical specs 3TW60651-1)
2) ndex for performing unit capacity calculation/selection
ndex depends on leaving water temperature = 125 (details are explained below)
SeIection procedure
- Outdoor unit heating capacity (design point conditions) = HC
o
[kW] See heating capacity table outdoor unit
- Outdoor unit power input (design point conditions) = PI
o
(kW) See heating capacity table outdoor unit
- HXHD125A capacity calculation index = R To be looked up (see table below)
- VRV DX indoor capacity index total = S To be looked up (depends on VRV DX indoor unit type)
- Total indoor capacity index = index VRV DX connected + HXHD125A capacity calculation index = S + R = J To be calculated
- HXHD125A heating capacity (design point conditions) = HC (kW) To be calculated
- HXHD125A power input (design point conditions) = PI (kW) To be calculated
- HXHD125A cascade step power input = P (kW) To be looked up
HC = HC
o
/J * 112
InformationaI remark
P = P
o
/J*R + P
: total power input required to operate the cascade system = fraction of outdoor unit power input + HXHD cascade step power input
IIa. Cascade step power input IIb. Integrated heating capacity
and HXHD-A capacity caIcuIation index correction coefcient for REYAQ
RWT [C] 30 40 45 55 65
LWT [C] 35 45 55 65 75
P [kW] 1.50 1.79 1.83 2.33 3.25
R 103 100 100 96 88
RwT = erler|r Waler lerperalure lrleraled |eal|r capac|ly = A [|w]
LwT = |eav|r Waler lerperalure va|ue |ver |r lao|e ol capac|ly c|aracler|sl|cs = 8 [|w]
lrleraled correcl|or laclor lor lrosl accuru|al|or =
A = 8
III. ExampIe
A. Make clear design point
0X |rdoor ur|ls: 1 5.5 |w -ZC08/-Z.Cw8 ouldoor aro|erl cord|l|ors / 20C |rdoor
aro|erl cord|l|ors
waler |eal|r 12|w -ZC08/-Z.Cw8 ouldoor aro|erl cord|l|ors / 5C LwT
Requ|red capac|ly lor ou||d|r : 31|w
o vRv 0X |rdoor ur|ls 50 lype
o lXl0
o REYA011
A1. Calculate total indoor capacity index
vRv |rdoor ur|ls: 1 50 lype: 3
lXl0125A: R
J = R 3
A2. HXHD specifcations at design point
lC = lC
o
/ J 112
Pl = Pl
o
/ J R P
leal|r capac|ly |ell lor 0X |rdoor ur|ls
leal|r capac|ly |ell lor 0X |rdoor
B. Check connection ratio
Al |easl 1lXl0-A 0K
0X correcl|or ral|o: 50 > x > 130 200/350 5Z 0K
lXl0-A correcl|or ral|o > 100 125/350 3 0K
Tola| correcl|or ral|o: 80 > x > 200 325/350 93 0K
InIet port temperature of heat exchanger (C/RH 85%)
-7 -5 -3 0 3 5 7

REYAQ10/12P 0.97 0.95 0.90 0.86 0.87 0.92 1.00


REYAQ14/16P 0.96 0.94 0.89 0.85 0.86 0.91 1.00
3 200
R 9
J 29
HC [kW] 12.5
P [kW] 5.39
[kW] 22.1 (x33.5200/255)
[kW] 5.59
Loo| up |r |eal|r capac|ly lao|e [=l (Ta |rdoor, Ta ouldoor, lP)]
Loo| up |r |eal|r capac|ly lao|e [=l (Ta |rdoor, Ta ouldoor, lP)]
Loo| up lao|e aoove [=l (|eav|r Waler lerrperalure)]
Loo| up lao|e aoove [=l (|eav|r Waler lerrperalure)]
o 0ec|de ouldoor ur|l lP c|ass
3: 0eperds or 0X |rdoor ur|l se|ecl|or
R: Loo| up lao|e aoove
J: (3, R)
Capac|ly .30
p [|W| 2.33
lC
o
[|w| 33.1
P|
o
[|w| 9.11
3
4
VRV Systems HXHD-A 7
Indoor Unit HXHD-A
4 Combination table
HXHD-A
REYAQ-P
3TW60659-1A
NOTES
1 To ore ouldoor ur|l, ru|l|p|e |ydrooox ur|ls car oe correcled (>100 correcl|or ral|o, lurl|er |rlorral|or, see lec|r|ca| dala)
2 A|| vRv |rdoor ur|ls car oe correcled.
I. Outdoor/Indoor combination tabIe
Heating onIy hydrobox
indoor unit
Outdoor unit REYAQ10P REYAQ12P REYAQ14 REYAQ16P
lXl0125A 0 0 0 0
II. Kit avaiIabiIity
1. Kits connected to the outdoor unit
Reference Description REYAQ10P REYAQ12P REYAQ14P REYAQ16P
KlR0(V)22V29l8 Relrel |eader 0 0 0 0
KlR0(V)22V1l8 Relrel |eader 0 0 0
KlR0(V)22VZ5l8 Relrel jo|rl 0 0
KlR0(V)22V20T8 Relrel jo|rl 0 0 0 0
KlR0(V)22V29T9 Relrel jo|rl 0 0 0 0
KlR0(V)22V1T8 Relrel jo|rl 0 0 0
KlR0(V)22VZ5T8 Relrel jo|rl 0 0
KlR0(V)23V29l8 Relrel |eader 0 0 0 0
KlR0(V)23V1l8 Relrel |eader 0 0 0
KlR0(V)23VZ5l8 Relrel jo|rl 0 0
KlR0(V)23V20T8 Relrel jo|rl 0 0 0 0
KlR0(V)23V29T9 Relrel jo|rl 0 0 0 0
KlR0(V)23V1T8 Relrel jo|rl 0 0 0
KlR0(V)23VZ5T8 Relrel jo|rl 0 0
KwC25C150 0ra|r par ||l (1) 0 0 0 0
83v0100P8 0 (A2) 0 (A2) 0 (A2) 0 (A2)
83v010P8
83v0 oox lor leal Recovery (IndividuaI 8rarc|
3e|eclor)
0 (A2) 0 (A2) 0 (A2) 0 (A2)
83v0250P8 0 (A2) 0 (A2) 0 (A2) 0 (A2)
83v10100Pv 83v0 oox lor leal Recovery (MuIti 8rarc| 3e|eclor) 0 (A2) 0 (A2) 0 (A2) 0 (A2)
83v0100Pv 0 (A2) 0 (A2) 0 (A2) 0 (A2)
EK83v0LNP 3ourd reducl|or ||l lor |rd|v|dua| 83v0 oox (A1) 0 0 0 0
8l0P2A1 0||la| Pressure aue ||l 0 0 0 0
(A1): 0r|y ava||ao|e lor |rd|v|dua| 83v0 ooxes (rol poss|o|e lor Cerlra| 83v10/83v0). (A2): - Vu|l| lerarl |s poss|o|e - Need correcl opl|or-PC8 0TA111A1 lo eac| 83v0-oox & reed corpal|o|e |rdoor ur|l.
A||oWs lo reduce operal|r sourd ol 83v0-oox (requ|res 1 sourd ||l per 83v0 - oox) - Nol requ|red lor |ydro oox lXl0125A, or|y lor correcl|or ol 0X |rdoor ur|ls.
2. Kits connected to the indoor unit
Reference Description Indoor Unit
HXHD125A
EKlT3200[AC| 3la|r|ess doresl|c |ol Waler lar| 200 | 0
EKlT320[AC| 3la|r|ess doresl|c |ol Waler lar| 20 | 0
EKlT3u200[AC| 3la|r|ess doresl|c |ol Waler lar| 20 | uK - vers|or 0
EKlT3u20[AC| 3la|r|ess doresl|c |ol Waler lar| 20 | uK - vers|or 0
EKlwP300A PP lar| 0
EKlwP500A PP lar| 0
EKRP1l8AA 0||la| l/0 PC8 0
EKRP1AlTA 0erard PC8 (3) 0
EKRuAlT8 Rerole user |rlerlace [rerocor| (1) 0
EKRTwA w|red Roor l|erroslal (2) 0
EKRTR1 w|re|ess Roor l|erroslal (2) 0
EKRTET3 Rerole sersor lor Roor l|erroslal (2) 0
3. Kits connected to the domestic hot water tank
Reference Description Domestic hot water tank
EKHTS EKHTSU
200A 20A 200AA 20AA
EKulwlTA 0pl|or ||l lor uK EKlT3u200-20A - - 0 0
EKFVAlT8 (5) 0pl|or ||l lor loor rourled lar| 0 0 0 0
Remark: 0l|er coro|ral|ors are rol ararleed.
(1) For a||oWed |rsla||al|or, see lrsla||al|or Varua|
(2) Requ|res 0erard PC8 EKRP1AlTA
(3) Requ|res lo |rsla|| lo oe ao|e lo correcl Roorl|erroslal
(1) 3are corlro||er as supp||ed W|l| Cascade ur|l car oe rourled para||e| or or ol|er |ocal|or. ll 2 corlro||ers are |rsla||ed, l|e |rsla||er reeds lo se|ecl 1 rasler & 1 s|ave
(5) 0r|y requ|red |l lar| |s N0T rourled or lop ol cascade |rdoor ur|l
Indoor Unit HXHD-A
5
VRV Systems HXHD-A 8
5 Dimensional drawings
HXHD-A
3TW59914-1B(1)
If required (e.g. Wall xation)
Pressure gauge can be removed from waterlter, maximum distance
between waterlter and pressure gauge 600 mm Left Installation
Detail A
Detail A
Scale 1/3 Right installation
1 Remote control (delivered as accessory)
Installation location is outside the unit
2 Discharge pipe connection 12.7 solder (R410a)
3 Liquid pipe connection 9.5 solder (R410a)
4 R134a Service ports 5/16 are (2x)
5 Pressure gauge
6 Blow off valve
7 Drain valve water circuit
8 Air purge
9 Shut-off valves (2x)
10 Water lter
11 Water in connection G 1 (female)
12 Water out connection G 1 (female)
13 Control wiring intake (knock-out hole 37)
14 Power supply wiring intake (knock-out hole 37)
15 Knock-out holes for refrigerant piping and water piping
16 Levelling feet
17 Discharge stop valve 12.7 solder (R410a)
18 Liquid stop valve 9.5 solder (R410a)
3
5
VRV Systems HXHD-A 9
Indoor Unit HXHD-A
5 Dimensional drawings
HXHD-A
3TW59914-1B(2)
Left Installation
Screw xation of top plate
(both sides)
Min. 600
(Space required for switch box removal)
Right installation
Upwiring
Model A B C
HXHD-A 355 270 300
Indoor Unit HXHD-A
6
VRV Systems HXHD-A 10
6 Piping diagrams
3
7
VRV Systems HXHD-A 11
Indoor Unit HXHD-A
7 Wiring diagrams
7 - 1 Wiring Diagrams - Single Phase
Indoor Unit HXHD-A
7
VRV Systems HXHD-A 12
7 Wiring diagrams
7 - 1 Wiring Diagrams - Single Phase
3
7
VRV Systems HXHD-A 13
Indoor Unit HXHD-A
7 Wiring diagrams
7 - 1 Wiring Diagrams - Single Phase
Indoor Unit HXHD-A
8
VRV Systems HXHD-A 14
8 External connection diagrams
HXHD-A
REYAQ-P
2TW60656-1(1)
NOTES
lr case ol s|ra| cao|e or corrur|cal|or cao|e. Keep r|r|rur d|slarce lo poWer cao|es > 25rr.
0uldoor ur|l poWer supp|y (oerell |w| rale poWer supp|y |s
N0T a||oWed)
E|eclr|ca| correcl|or d|arar For rore dela||s p|ease c|ec| l|e W|r|r d|arar ol eac| ur|l.
3lardard parls
0uT000R uNlT
83 uNlT 83 uNlT
lN000R uNlT
PoWer supp|y
F1-F2
correcl|or
F1-F2
correcl|or
X1V: F1-F2
T0 0uT/0 uNlT
X1V: F1-F2
T0 lN/0 uNlT
2
c
o
re
c
o
r
r
u
r
|c
a
l|o
r
x1V: 1-2
T0 lN/0 uNlT
X1r: F1-F2
X1V: L-N-earl|
X1V: L1-L2-L3-N-earl|
F1-F2
correcl|or
F1-F2
correcl|or
F1-F2
correcl|or
PoWer supp|y PoWer supp|y PoWer supp|y PoWer supp|y
Reler lo pae 2 lor rore dela||s
lN000R uNlT lN000R uNlT lN000R uNlT
lN000R uNlT
(lXl0)
lN000R uNlT
(Coo||r or|y)
83 uNlT P0wER 3uPPLY
0NLY F0R 0TA111A1
Vu|l|-lerarl poWer supp|y:
220v - 210v = aerl|
5 core
3 core
2 core
380v - 115v earl|
3
8
VRV Systems HXHD-A 15
Indoor Unit HXHD-A
8 External connection diagrams
HXHD-A
REYAQ-P
2TW60656-1(2)
,QGRRU XQLW SRZHU VXSSO\
5RRP
WKHUPRVWDW
Poss|o|||ly 1: 2QO\ IRU QRUPDO SRZHU VXSSO\ LQVWDOODWLRQ
Poss|o|||ly 1
Poss|o|||ly 2
Poss|o|||ly 2: 2QO\ IRU EHQHW N:K UDWH SRZHU VXSSO\ LQVWDOODWLRQ
220v - 210v earl|
8erell |w| rale poWer supp|y:
220v - 210v earl|
8erell |w| rale poWer supp|y corlacl
Norra| |w| rale poWer supp|y:
220v - 210v earl|
0pl|ora| ru|l|-|erarl poWer supp|y:
21v
0pl|ora| parls
P2T - T|err|slor
Waler lerperalure
0lwrode
or/oll oulpul
Coo||r/|eal|r
or/oll oulpul
A|arroulpul
lrpul ru|l|p|e selpo|rl 1
lrpul ru|l|p|e selpo|rl 2
Exlerra| sersor
(loor ol aro|erl)
K13 (W|er EKlT3 |s |rsla||ed)
se|ecl|or dorel|c |ol Waler - |eal|r
0oresl|c |ol
Waler lar|
user |rlerlace user |rlerlace
3Way va|ve
0r|y lor EKlT3 / EKlwP
0r|y lor EKRP1AlTA
0r|y lor lXl0
0r|y lor EKRTET3
0r|y lor EKRTw(W|red roorl|erroslal)
0r|y lor EKRTR (W|re|ess roorl|erroslal)
0r|y lor EKRP1l8AA
0pl|ora| poWer supp|y:
coo||r/|eal|r or/oll oulpul
0pl|ora| poWer supp|y:
a|arroulpul
F|e|d supp|y
0pl|ora| parls
2 core (3r|rc|uded)
0r|y lor EKRuAlT
s|ra|
s|ra|
s|ra|
s|ra|
s|ra|
s|ra|
corrur|calor
2 core
2 core
2 core
2 core
2 core
2 core
2 core
2 core
2 core
2 core
1 core
1 core
1 core
1 core
2 core
2 core
2
c
o
r
e
2
c
o
r
e
c
o
r
r
u
r
|c
a
l|o
r
c
o
r
r
u
r
|c
a
l|o
r
3 core
3 core
3 core
220v- 210v
220v- 210v
220v- 210v
220v- 210v
220v- 210v
220v- 210v
220v- 210v
220v- 210v
220v- 210v
3 core
earl|
earl|
Rerove
W|re or|des
lN000R uNlT
Indoor Unit HXHD-A
9
VRV Systems HXHD-A 16
9 Sound data
9 - 1 Sound Power Spectrum
HXHD-A
3TW59917-2A
Sound Power Lw per Octave band (dB) Total
(dBA)
125 250 500 1000 2000 4000 8000 LwA
HXHD125A 39 50 51 45 45 43 41 55
NOTES
- Measured according to ISO 3744
- Reference acoustic pressure 0dB = 10e-6 W/m
2
- dBA = A-weighted sound power level
- Unit condition: Ta = 7/6C - heating setpoint 55/65C - maximum compressor frequency
- If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reections.
Choos the installation location carefully and do not install in a sound sensitive environment (e.g. living room, bedroom, ...).
3
9
VRV Systems HXHD-A 17
Indoor Unit HXHD-A
9 Sound data
9 - 2 Sound Pressure Spectrum
HXHD-A
Position of microphones
Sound levels
3TW59917-1A
NOTES
- The above data is valid in free eld condition, because it is measured in a semi-anechoic room. If the
sound is measured under actual installation, the measured value will be higher due to environmental
noise and sound reections. Choose the installation location carefully and do not install the unit in a
sound sensitive environment (e.g. living room, bedroom, ...).
- dBA = A-weighted sound pressure level (A scale according to IEC).
- EW = entering water temperature - LW = Leaving water temperature
- Reference acoustic pressure 0dB = 20Pa
- Sound pressure level of low sound mode n2 and n3 is lower than n1
- (*) Does not occur simultanously on all sides.
Back
Right
Left
= microphone
Front
Sound pressure
[
dBA
]
HXHD
125
- EW/LW 55/65 C
Front
Left / Right / Back (*)
42
41
- EW/LW 70/80 C
Front
Left / Right / Back (*)
43
42
- EW/LW 55/65 C - Low sound mode n1
Front-Right (*)
38
Indoor Unit HXHD-A
10
VRV Systems HXHD-A 18
10 Operation range
HXHD-A
REYAQ-P
3TW60653-1A
Ta (CDB) Ta (CDB)
Corl|ruous |eal|r operal|or
Space heating mode Domestic hot water mode
LWT (C)
Tank temperature (C)
DHW operation
Continuous
heating
operation
Startup
area
0oresl|c |ol Waler operal|or
3larlup area
0peral|or poss|o|e, oul ro uararlee ol capac|ly
0peral|or poss|o|e, oul ro uararlee ol capac|ly
Car oe adjusled oy le|d sell|r
3
11
VRV Systems HXHD-A 19
Indoor Unit HXHD-A
11 Hydraulic performance
11 - 1 Static Pressure Drop Unit
HXHD-A
3TW60669-1
unit ESP without DHW 3way valve
unit ESP including DHW 3way valve
Note:
In case of stand alone tank, available ESP during DHW mode: to be conrmed
1. The ESP curves are the maximum ESP curve for different AT types (pump rpm = 4400 AT = 5C; pump rpm = 4000 for AT = 10C).
The pump of the indoor module is inverter controlled and controls to have a xed AT between return and leaving water temperature.
2. In case of installing a demestic hot water tank there is an additional pressure drop over the three way valve (delivered as accessory with the tank).
ESP: external static pressure
Flow: waterow through the unit
Warning:
1. Selecting a ow outside the curve can cause damage to or malfunction of the unit. See also minimum and maximum allowed water owrange
in the technical specications.
2. Water quality must be according to EN directive EC 98/83 EC.
E
S
P

[
k
P
a
]
Flow [l/min]
(heating)
(heating)
These products are not within the scope of
the Eurovent certification program
E
E
D
E
N
1
3
-
2
0
4




0
6
/
1
3


C
o
p
y
r
i
g
h
t

D
a
i
k
i
n

T
h
e

p
r
e
s
e
n
t

p
u
b
l
i
c
a
t
i
o
n

s
u
p
e
r
s
e
d
e
s

E
E
D
E
N
1
2
-
2
0
4
The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, re-
liability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or re-
lated to the use and/or interpretation of this leaflet. All content is copy-
righted by Daikin Europe N.V.