Esr-1153 - Tji
Esr-1153 - Tji
ESR-1153*
Reissued May 1, 2011 This report is subject to renewal on May 1, 2013.
3.2.3 Adhesives: Adhesives are of the types specified in the quality control manual that contains Weyerhaeuser manufacturing standards. 4.0 DESIGN AND INSTALLATION 4.1 General: The design and installation of TJI joists described in this report must comply with Sections 4.2 through 4.16. Additionally, design of TJI joists is governed by the applicable code and corresponding editions of ANSI/AF&PA NDS, National Design Specification for Wood Construction (NDS). 4.2 Design Values: Table 3 specifies reference design moments, reactions, vertical shear forces, and joist stiffness (EI). Reference design reactions are based on minimum bearing lengths of 3 1 1 1 /4 inches, 2 /2 inches and 3 /2 inches (45, 64 and 89 mm),
Properties evaluated: Structural Sound ratings Fire-resistance ratings 2.0 USES TJI joists are prefabricated wood I-joists used as floor joists, roof rafters, blocking panels and rim joists, to support code-required loads. Prefabricated wood I-joists described in this report comply with Section 2303.1.2 of the IBC, for allowable stress design; and Section R502.1.4 of the IRC.
Copyright 2013
Page 1 of 24
ESR-1153 | Most Widely Accepted and Trusted for simple spans; and 31/2, 51/4 and 7 inches (89, 133 and 178 mm) at intermediate support points for continuous spans. When joists are used as multiple span members, the calculated shear, used for design at the intermediate support, may be reduced by the percentage determined from the following formula and limited to the depths shown in Table 4: R = W K red 18% where: Kred = V12 100. R = The percent reduction. V12 = The reference design shear for an 7 11 /8-inch-deep (302 mm) joist (pounds). W = The uniform load (plf). The reference design shear at the interior supports of multiple-span-member TJI joists up to 12 inches (305 mm) deep, used in residential floor construction, is permitted to be increased by 10 percent. This increase in reference design shear does not apply to the design shear at the ends of the joists. 4.3 Fasteners: Reference lateral and withdrawal design loads for fasteners, installed parallel or perpendicular to Microllam LVL or TimberStrand LSL flange glue lines, must be determined in accordance with ESR-1387 and the applicable code. Reference lateral and withdrawal design loads for fasteners installed into TJI joist sawn lumber flanges must be designed using the applicable code and a specific gravity of 0.42, such as for spruce-pine-fir. Allowable nail spacings for TJI joist diaphragm applications must be as specified in Sections 4.14 and 4.15, and Table 2. For nondiaphragm applications: 1. The spacing of fasteners installed into the face grain of Microllam LVL or TimberStrand LSL flanges must be greater than or equal to the closest permitted on-center spacing prescribed by the code for fasteners installed in sawn lumber. The spacing of fasteners installed into the edge grain of Microllam LVL or TimberStrand LSL flanges must be greater than or equal to the closest permitted on-center spacing requirements detailed in ESR-1387. 2. The spacing of fasteners installed into TJI joist sawn lumber flanges must be as prescribed by the code for fasteners installed in sawn lumber. The allowable lateral load capacity of 10d by 1 1 /2-inch-long (38 mm) common nails used to connect minimum No. 18 gage [0.048 inch (1.2 mm) base-metal thickness] metal straps or tension-ties, recognized in a current ICC-ES evaluation report, to TJI joist flanges, in conformance with Figure 6 of this report, is 112 pounds-force (498 N) per nail. The connections with the structural composite lumber flanges may be used for out-of-plane wall anchorage 1 to flexible diaphragms in lieu of the minimum 2 /2-inch (63.5 mm) wood element thickness specified in Item 5 of Section 1633.2.8.1 of the UBC. 4.4 Web Stiffeners: Web stiffener requirements for reactions and concentrated loads are noted in Table 3 and Figure 1. 4.5 Lateral Support: TJI joist compression flanges with widths less than 2.3 inches (58 mm) require lateral support every 18 inches (457 mm) on center. TJI joist compression flanges with
Page 2 of 24 widths equal to or greater than 2.3 inches (58 mm) require lateral support every 24 inches (610 mm) on center. Each connection must be capable of transmitting a 75-poundforce (334 N) horizontal load. All TJI joist ends require restraint to prevent rollover. Code prescribed methods of lateral restraint specified for sawn lumber are acceptable. Bridging is not required for floor and roof TJI joist applications. 4.6 Holes in TJI Joist Web: The tables in Figures 2 and 3 specify allowable sizes and location of round, square and rectangular holes in the TJI joist webs. TJI joists with holes located in the web in accordance with Figures 2 and 3 are permitted to be used in the fire-resistive-rated Assemblies B, C, D, E, F, G and H described in Figures 4B through 4H. 4.7 Duration of Load: Adjustments for duration of load, in accordance with Part 2.3.2 of the NDS or Item 6 of Section 2316.2 of the UBC, apply to the TJI joists and their fastenings. 4.8 In-service Moisture Conditions: TJI joists must be installed in dry service conditions, where the moisture content in-service is less than 16 percent, as in most covered structures. 4.9 Repetitive-member Use: The repetitive-member use factor applicable to the resistive moment capacities listed in Table 3 is limited to 1.0. 4.10 Member Spans: TJI joist spans must be determined in accordance with Part 3.2.1 of the NDS. Vertical shear calculations must include all loads within the span from face to face of supports. 4.11 Deflection: Deflection of simple span TJI joists with either uniform load or a concentrated load at midspan is determined using the formulas in the footnotes to Table 3. 4.12 Blocking Panels: Bearing walls perpendicular to and supported by TJI joists at the end or intermediate supports, or both, require full-depth blocking. TJI joists up to and including 16 inches (406 mm) in depth, when used as blocking panels, have a maximum vertical load transfer capacity of 2,100 plf (30 645 N/m). TJI joists over 16 inches (406 mm) and up to and including 20 inches (508 mm) in depth, when used as blocking panels, have a maximum vertical load transfer capacity of 1,550 plf (22 620 N/m). 4.13 Rim Joists: TJI joists having depths of up to and including 16 inches (406 mm) may be used as rim joists and boundary members of horizontal wood structural diaphragms. The joists have a maximum vertical load transfer capacity of 2,100 plf (30,645 N/m). TJI joists used as rim joists must be laterally supported at the top and continuously supported at the bottom, and the gravity loads must be uniformly applied along the top. Other loading and support conditions must be investigated and approved by a design professional. 4.14 TJI Joists as Prescriptive Diaphragm Framing Members: TJI joists are permitted as framing members in prescriptive floor and roof diaphragm construction in accordance with Section 2308 of the IBC or Chapters 5 and 8 of the IRC. When TJI 110, TJI 210 or TJI 230 series I-joists are used in floor diaphragm construction, the thickness of the 19 sheathing must be /32 inch (15.1 mm) or greater.
ESR-1153 | Most Widely Accepted and Trusted 4.15 TJI Joists as Engineered Diaphragm Framing Members: TJI 110, TJI 210, TJI 230, TJI 360, TJI 560, TJI 560D, TJI s31, TJI s33, TJI s47, TJI 100C and TJI 300C joists may be used as framing members in blocked and unblocked engineered diaphragms designed using Table 2306.2.1(1) of the IBC, or Tables 4.2A and 4.2C of the SDPWS, subject to the limitations specified in Table 2 of this report. TJI L65, TJI L90, TJI H90, TJI HD90 and TJI HS90 joists may be used as framing members in diaphragms designed in accordance with the applicable code. The closest permitted sheathing nail spacing in a single row is 3 inches (76 mm) on center for 10d common nails or 2 inches (51 mm) on center for 8d common nails. 4.16 Cantilevered TJI Joists: TJI joists are permitted to be installed with cantilevered ends, provided the cantilevers have a maximum length equal to one-third of the adjacent span and support uniform loads only, unless designed by a design professional. 4.17 TJI Joists with Flak Jacket Protection Used in IRC Section R501.3 Fire Protected Floors: TJI Joists with Flak Jacket protection applied to both sides of the web and vertical sides of the bottom flange are an alternative to the 2-by-10 dimension lumber, prescribed in the 2012 IRC Section R501.3 Exception 4, and have met the requirements of a floor assembly demonstrating equivalent floor performance. TJI Joists with Flak Jacket protection are identified in the field by a Flak Jacket Protection stamp or label placed on the web of the I-joist member. Flak Jacket protection is applied in accordance Joist with Flak Jacket Protection with the TJI Manufacturing Standard and quality control program. The TJI Joist Flak Jacket protection is limited to TJI 210, 230, 360, 560 and 560D I-joists which have a 3 minimum flange depth of 1 /8-inches (34.9 mm). The flooring attachment to the I-joists must include the application of construction adhesive complying with ASTM D3498. 4.18 Fire-resistance-rated Roof-ceiling or Floor-ceiling Assemblies: Refer to Figures 4A through 4F, and 4H, for details on onehour fire-resistance-rated roof-ceiling or floor-ceiling assemblies. Refer to Figure 4G for details on two-hour fireresistance-rated roof-ceiling or floor-ceiling assemblies. When assemblies A, B, C, D, E, and F are used as floorceiling assemblies over unusable crawl spaces, it is permitted to omit the ceiling membrane. Additionally, flooring is permitted to be omitted where unusable attic space occurs above, provided the lateral support requirements of Section 4.5 are met. Alternate floor or roof systems using lightweight concrete or gypsum concrete are permitted in accordance with Table 5
Page 3 of 24 4.19 Sound Ratings: Fire-resistance-rated assemblies B, D and G, as described in Figures 4B, 4D and 4G, have sound transmission class (STC) and impact insulation class (IIC) ratings as given in Table 6, provided they are constructed with the additional assembly components and floor coverings specified in Table 6. 5.0 CONDITIONS OF USE The TJI Prefabricated Wood I-joists described in this report comply with or are suitable alternatives to joists and rafters specified in the codes specifically listed in Section 1.0, subject to the following conditions: 5.1 TJI joists are designed in accordance with this report. 5.2 Drawings and design details verifying compliance with this report are submitted to the code official for approval. 5.3 Reference design values for TJI joists and their fasteners are permitted to be increased for duration of load in accordance with the applicable code. 5.4 Where one-hour or two-hour fire-resistance-rated construction is required, construction complies with this report. 5.5 No cutting or notching of TJI joist flanges is permitted. 5.6 Sound rated assemblies described in Table 6, with STC and or IIC ratings of less than 50, are only applicable in jurisdictions using the IRC. 5.7 TJI joists are produced at the Weyerhaeuser plants located in Castleberry, Alabama; Eugene, Oregon; and Natchitoches, Louisiana; and at the RedBuilt LLC plant located in Stayton, Oregon; and the Anthony-Domtar plant located in Sault Ste. Marie, Ontario, Canada; and at the Pacific Woodtech plant located in Burlington, Washington; under a quality control program with inspections by PFS Corporation (AA-652), or APAThe Engineered Wood Association (AA-649). 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Prefabricated Wood I-joists (AC14), dated February 2012. 6.2 Reports of fire tests conducted in accordance with ASTM E119. 6.3 Reports of sound transmission tests conducted in accordance with ASTM E90, ASTM E413 and ASTM E492. 7.0 IDENTIFICATION TJI prefabricated wood I-joists are identified by a stamp that includes the product designation, evaluation report number (ICC-ES ESR-1153), manufacturer's name or logo (iLevel, Weyerhaeuser), plant number, production date, and the name or logo of the inspection agency (PFS Corporation or APA).
Page 4 of 24
TABLE 1TJI JOIST DESCRIPTION TJI JOIST SERIES TJI 110 TJI 210 TJI 230 TJI 360 TJI 560 TJI 560D TJI s31 TJI s33 TJI s47 TJI L65 (or TJI L460) TJI L90 (or TJI L560) TJI H90 (or TJI H560) TJI HD90 (or TJI HD560) TJI HS90 (or TJI HS560) TJI 100C TJI 300C For SI: 1 inch = 25.4 mm.
FLANGE SIZE, DEPTH WIDTH (inches) Minimum 1.25 x 1.75 Minimum 1.25 x 2.08 Minimum 1.25 x 2.3 1.375 x 2.3 1.375 x 3.5 1.5 x 3.5 1.5 x 2.5 1.5 x 2.5 1.5 x 3.5 1.5 x 2.5 1.5 x 3.5 1.75 x 3.5 2.125 x 3.5 2.5 x 3.5 1.5 x 2.5 1.5 x 2.5
/8 /8 /8 /8
/16 /16 /8 /8
3 3 7 7 7 7
1 1 3 3
TABLE 2TJI JOIST ENGINEERED DIAPHRAGM FRAMING DESIGN INFORMATION TJI JOIST SERIES EQUIVALENT NOMINAL FRAMING WIDTH 2 in. 3 in. 3 in. EQUIVALENT SPECIFIC GRAVITY CLOSEST PERMITTED NAIL 2 SPACING (inches) 6d common 4 4 3 8d common 4 4 3 10d common 4 4 4
MAXIMUM PERMITTED SEISMIC DESIGN CAPACITY 1,3 (plf) Blocked 425 480 720 Unblocked Case 1 285 320 320 Unblocked Case 3 215 240 240 Unblocked Cases 2, 4, 5, 6 185 205
4
TJI 110 TJI 210 TJI 230 TJI 360 TJI 560 TJI 560D TJI s31 TJI s33 TJI s47 TJI 100C TJI 300C
1
240
3 in. 3 in.
0.42 0.42
3 3
3 3
4 4
660 660
295 295
220 220
220 220
For SI: 1 inch = 25.4 mm, 1 plf = 14.59 N/m. Allowable shear loads for wood structural panel diaphragms with TJI joist framing must be determined in accordance with Tables 4.2A and 4.2C of the SDPWS or Table 2306.2.1(1) of the 2009 IBC, using the equivalent nominal framing width and specific gravities specified in Table 2, and must not exceed the maximum permitted design capacity given in Table 2. 2 One row of nails is permitted along each sheathing panel end and edge. When nail spacing is less than 6 inches on center, adjacent nails within a row must be offset (staggered). The closest permitted nail spacing in Table 2 must not be exceeded. Solid sawn framing members must be used in lieu of TJI joist framing members where the fastener spacing required in SDPWS Tables 4.2A and 4.2C or 2009 IBC Table 2306.2.1(1) is closer than the closest permitted nail spacing given in Table 2 of this report. 3 The maximum allowable seismic design capacities of Table 2 may be increased by a factor of 1.4 for wind design applications. 4 The design capacity of an unblocked diaphragm framed with TJI 110, TJI 210 or TJI 230 joists may be multiplied by a factor of 1.18 if a nonpolyurethane sub-floor adhesive is used in combination with mechanical fasteners for sheathing attachment. Continuous special inspection is not required for this adhesive application.
Page 5 of 24
TABLE 3REFERENCE DESIGN VALUES FOR TJI JOISTS Joist Joist (8) Depth Weight (plf) (in.) REFERENCE DESIGN VALUES Moment MR (10, (ft.-lbs.)
12)
1,2,3
Shear vR (lbs.)
EI 6 x 10 2 bs.-in.
K
1
4,5,6
4,5,6
3 /2 Bearing Length Web Stiffeners NO 1220 1375 1375 1330 1460 1460 1460 1330 1485 1485 1485 1425 1505 1505 1505 1505 1505 YES NA 1560 1735 NA 1655 1815 1815 NA 1655 1840 1840 NA 1705 1865 1865 1865 1865
5 /4 7
(7)
Bearing Length Web Stiffeners NO YES NA 2295 2295 NA 2505 2505 2505 NA 2765 2765 2765 NA 2815 2815 2815 2815 2815
Bearing Length Web Stiffeners NO 2350 2350 2350 2565 2565 2565 2565 2790 2790 2790 2790 3000 3000 3000 3000 3000 3000 YES NA 2705 2705 NA 2925 2925 2925 NA 3150 3150 3150 NA 3360 3360 3360 3360 3360
YES NA 1225 1225 NA 1365 1365 1365 NA 1420 1420 1420 NA 1440 1440 1440 1440 1440
TJI 110 2.3 2.5 2.8 2.6 2.8 3.1 3.3 2.7 3.0 3.3 3.5 2.7 3.0 3.3 3.5 3.7 4.0 2500 3160 3740 3000 3795 4490 5140 3330 4215 4990 5710 4790 6180 7335 8405 9465 10515 1220 1560 1860 1330 1655 1945 2190 1330 1655 1945 2190 1425 1705 1955 2190 2425 2660 157 267 392 186 315 462 629 206 347 509 691 249 419 612 830 1085 1376 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 910 910 910 1005 1005 1005 1005 1060 1060 1060 1060 1080 1080 1080 1080 1080 1080 NA 3-8d 3-8d NA 3-8d 3-8d 3-8d NA 3-8d 3-8d 3-8d NA 3-8d 3-8d 3-8d 3-8d 3-8d 1935 1935 1935 2145 2145 2145 2145 2410 2410 2410 2410 2460 2460 2460 2460 2460 2460 NA 3-8d 3-8d NA 3-8d 3-8d 3-8d NA 3-8d 3-8d 3-8d NA 3-8d 3-8d 3-8d 3-8d 3-8d
TJI 210
TJI 230
TJI 360
Page 6 of 24
(Continued)
Shear vR (lbs.)
EI 6 x 10 2 bs.-in.
K
1
4,5,6
4,5,6
3 /2 Bearing Length Web Stiffeners NO 1670 1725 1725 1725 1725 1725 1740 1885 1885 1885 1885 1885 NA NA NA NA NA 1205 1470 1470 1470 1205 1470 1470 1470 1490 1490 1490 1490 1490 1675 1885 1885 1885 1885 NA NA NA NA NA NA YES NA 2050 2200 2200 2200 2200 NA 2255 2355 2515 2515 2675 2830 2830 2990 3145 3145 NA 1530 1820 1825 NA 1530 1820 1825 1925 1965 1965 1965 1965 NA 1925 2125 2330 2535 2740 2935 3060 2900 2900 2900
5 /4 7
(7)
Bearing Length Web Stiffeners NO YES NA 3475 3475 3475 3475 3475 NA 3825 3825 3980 3980 4140 5090 5405 6180 6335 6655 NA 3110 3110 3110 NA 3110 3110 3110 3235 3495 3675 3675 3675 NA 3120 3365 3490 3615 3740 3860 3875 4725 4850 4975
(7) (7) (7) (7) (7) (7)
Bearing Length Web Stiffeners NO 3455 3455 3455 3455 3455 3455 3965 3965 3965 3965 3965 3965 NA NA NA NA NA 3120 3185 3185 3185 3120 3185 3185 3185 3195 3385 3550 3595 3595 3365 3365 3365 3365 3365 NA NA NA NA NA NA YES NA 3930 3930 3930 3930 3930 NA 4440 4440 4600 4600 4755 5705 6020 6795 6800 6800 NA 3540 3540 3540 NA 3540 3540 3540 3670 3860 4025 4070 4070 NA 3735 3985 4105 4230 4355 4480 4605 5345 5470 5590
(7) (7) (7) (7) (7) (7)
YES NA 1740 1740 1740 1740 1740 NA 1875 1875 2030 2030 2190 2345 2345 2450 2450 2450 NA 1530 1555 1555 NA 1530 1555 1555 1755 1755 1755 1755 1755 NA 1745 1750 1750 1750 1750 1750 1750 1750 1750 1750
TJI 560 3.6 4.0 4.2 4.5 4.8 5.1 3.8 4.2 4.5 4.7 5.0 5.3 5.6 5.8 6.1 6.4 6.6 2.6 2.9 3.1 3.4 2.6 2.9 3.1 3.4 3.6 3.8 4.0 4.3 4.5 3.0 3.3 3.6 3.9 4.2 4.4 4.7 5.0 5.3 5.5 5.8 7355 9500 11275 12925 14550 16165 7415 9605 11430 13115 14785 16435 18075 19700 21315 22915 24510 3000 3795 4490 5140 3805 4925 5930 6880 6970 8395 9735 11005 12180 5215 6750 8030 9210 10380 11540 12690 13830 14960 16085 17205 1670 2050 2390 2710 3030 3345 1740 2255 2540 2810 3080 3345 3615 3400 3400 3400 3400 1205 1530 1820 2065 1205 1530 1820 2065 1925 2125 2330 2535 2740 1675 1925 2125 2330 2535 2740 2935 3060 2900 2900 2900 378 636 926 1252 1631 2064 381 643 940 1273 1661 2105 2606 3165 3783 4463 5205 205 348 511 696 242 411 602 818 574 840 1140 1489 1889 263 450 666 913 1205 1545 1934 2374 2868 3417 4025 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 1265 1265 1265 1265 1265 1265 1400 1400 1400 1400 1400 1400 NA NA NA NA NA 1080 1200 1200 1200 1080 1200 1200 1200 1280 1280 1280 1280 1280 1375 1375 1375 1375 1375 NA NA NA NA NA NA NA 3-16d 3-16d 3-16d 3-16d 3-16d NA 3-16d 3-16d 4-16d 4-16d 5-16d 6-16d 6-16d 7-16d 8-16d 8-16d NA 3-8d 3-8d 3-8d NA 3-8d 3-8d 3-8d 3-16d 3-16d 3-16d 3-16d 3-16d NA 3-8d 5-8d 6-8d 7-8d 8-8d 9-8d 10-8d 11-8d 12-8d 13-8d 3000 3000 3000 3000 3000 3000 3350 3350 3350 3350 3350 3350 NA NA NA NA NA 2755 2755 2755 2755 2755 2755 2755 2755 2760 3020 3200 3200 3200 2745 2745 2745 2745 2745 NA NA NA NA NA NA NA 3-16d 3-16d 3-16d 3-16d 3-16d NA 3-16d 3-16d 4-16d 4-16d 5-16d 11-16d 13-16d 14-16d 15-16d 17-16d NA 3-8d 3-8d 3-8d NA 3-8d 3-8d 3-8d 3-16d 3-16d 3-16d 3-16d 3-16d NA 3-8d 5-8d 6-8d 7-8d 8-8d 9-8d 10-8d 11-8d 12-8d 13-8d
TJI 560D
TJI s31
TJI s33
TJI s47
TJI L65
Page 7 of 24
(Continued)
4,5,6
4,5,6
3 /2 Bearing Length Web Stiffeners NO 1675 1885 1885 1885 1885 NA NA NA NA NA NA 1885 1885 1885 1885 NA NA NA NA NA NA 2150 2150 2150 2150 NA NA NA NA NA NA NA 2150 2150 2150 2150 NA NA NA NA NA NA NA YES NA 1925 2125 2330 2515 2675 2830 2830 2900 2900 2900 1925 2125 2330 2515 2675 2830 2830 2900 2900 2900 2320 2565 2790 3020 3250 3480 3710 3940 4165 4375 4375 2320 2565 2790 3020 3250 3480 3710 3940 4165 4375 4375
5 /4 7
(7)
Bearing Length Web Stiffeners NO YES NA 3665 3825 3980 3980 4140 5090 5405 5800 5800 5800
(7) (7) (7)
Bearing Length Web Stiffeners NO 3965 3965 3965 3965 3965 NA NA NA NA NA NA 4100 4100 4100 4100 NA NA NA NA NA NA 4690 4690 4690 4690 NA NA NA NA NA NA NA 4690 4690 4690 4690 NA NA NA NA NA NA NA YES NA 4285 4440 4600 4600 4755 5705 6020 5800 5800 5800
(7) (7) (7)
YES NA 1715 1875 2030 2030 2190 2345 2345 2450 2450 2450 1715 1875 2030 2030 2190 2345 2345 2450 2450 2450
(9) (9) (9) (9)
TJI L90 3.8 4.2 4.5 4.7 5.0 5.3 5.6 5.8 6.1 6.4 6.6 4.6 4.9 5.2 5.4 5.7 6.0 6.3 6.5 6.8 7.1 5.4 5.7 6.0 6.3 6.7 7.0 7.3 7.6 7.9 8.2 8.5 6.0 6.3 6.6 7.0 7.3 7.6 7.9 8.2 8.5 8.8 9.1 7415 9605 11430 13115 14785 16435 18075 19700 21315 22915 24510 10960 13090 15065 17010 18945 20855 22755 24645 26520 28380 14075 16920 19550 22150 24725 27280 29815 32330 34830 37310 39785 16050 19425 22550 25640 28695 31725 34730 37715 40680 43630 46560 1675 1925 2125 2330 2535 2740 2935 3060 2900 2900 2900 1925 2125 2330 2535 2740 2935 3060 2900 2900 2900 2320 2565 2790 3020 3250 3480 3710 3940 4165 4375 4375 2320 2565 2790 3020 3250 3480 3710 3940 4165 4375 4375 365 621 913 1246 1635 2085 2597 3172 3814 4525 5306 687 1015 1389 1827 2331 2904 3549 4266 5059 5930 826 1232 1695 2239 2866 3579 4380 5272 6258 7339 8519 900 1355 1876 2488 3195 3998 4901 5905 7014 8230 9555 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 1400 1400 1400 1400 1400 NA NA NA NA NA NA 1400 1400 1400 1400 NA NA NA NA NA NA 1835 1835 1835 1835 NA NA NA NA NA NA NA 1835 1835 1835 1835 NA NA NA NA NA NA NA
(9) (9) (9) (9)
NA 2-16d 3-16d 4-16d 4-16d 5-16d 6-16d 6-16d 7-16d 8-16d 8-16d 2-16d 3-16d 4-16d 4-16d 5-16d 6-16d 6-16d 7-16d 8-16d 8-16d 4-16d 6-16d 6-16d 8-16d 10-16d 10-16d 12-16d 14-16d 14-16d 16-16d 18-16d 4-16d 6-16d 6-16d 8-16d 10-16d 10-16d 12-16d 14-16d 14-16d 16-16d 18-16d
3350 3350 3350 3350 3350 NA NA NA NA NA NA 3495 3495 3495 3495 NA NA NA NA NA NA 3995 3995 3995 3995 NA NA NA NA NA NA NA 3995 3995 3995 3995 NA NA NA NA NA NA NA
NA 2-16d 3-16d 4-16d 4-16d 5-16d 11-16d 13-16d 14-16d 15-16d 17-16d 2-16d 3-16d 4-16d 4-16d 5-16d 11-16d 13-16d 14-16d 15-16d 17-16d 4-16d 6-16d 6-16d 8-16d 10-16d 10-16d 12-16d 14-16d 14-16d 16-16d 18-16d 4-16d 6-16d 6-16d 8-16d 10-16d 10-16d 12-16d 14-16d 14-16d 16-16d 18-16d
TJI H90 3810 3970 4130 4130 4285 5235 5425 5800 5800 5800
(7) (7) (7)
4420 4575 4735 4735 4890 5840 6155 5800 5800 5800
(7) (7) (7)
TJI HD90 2320 2565 2790 3020 3250 3475 3500 3500 3500 3500 3500
(9) (9) (9) (9) (9) (9)
4650 4980 4980 5310 5425 5425 5425 6985 6985 7310 7640
(7) (7) (7) (7)
5345 5670 5670 6000 6330 6330 6655 7675 7675 8005 8335
(7) (7) (7) (7)
TJI HS90 2320 2565 2790 3020 3250 3475 3500 3500 3500 3500 3500
(9) (9) (9) (9) (9) (9)
4650 4980 4980 5310 5425 5425 5425 6985 6985 7310 7640
(7) (7) (7) (7)
5345 5670 5670 6000 6330 6330 6655 7675 7675 8005 8335
(7) (7) (7) (7)
Page 8 of 24
(Continued)
4,5,6
4,5,6
3 /2
Web Stiffeners NO 1120 1405 1405 1405 1405 1405 1405 YES NA 1420 1710 1760 1420 1710 1760
2
5 /4 7
(7)
Bearing Length Web Stiffeners NO YES NA 2640 2640 2640 2950 2950 2950
Bearing Length Web Stiffeners NO 2795 2795 2795 2795 3175 3175 3175 YES NA 3155 3155 3155 3535 3535 3535
TJI 100C 2.5 2.7 3.0 3.2 2.7 3.0 3.2 2605 3350 3915 4430 4470 5355 6085 1120 1420 1710 1970 1420 1710 1970 184 314 461 628 372 545 742 4.5 4.5 4.5 4.5 4.5 4.5 4.5 1120 1125 1125 1125 1125 1125 1125 NA 3-8d 3-8d 3-8d 3-8d 3-8d 3-8d 2285 2285 2285 2285 2595 2595 2595 NA 3-8d 3-8d 3-8d 3-8d 3-8d 3-8d
TJI 300C
For SI: 1 inch = 25.4 mm, 1 plf = 14 59 N/m, 1 ft.-lb. = 1.356 N-m, 1 lb.-in. = 2.87 kN-mm. FOOTNOTES FOR TABLE 3: 1 Refer to Figure 1 for web stiffener details
2
Uniform load : =
Where: P = Concentrated load, pounds. W = Uniform load in pounds per lineal foot.
3
The stated reference design values are for loads of normal duration. Adjustments to the reference design values must be in accordance with the applicable code, with the exception noted in footnote 10 below. 4 Interpolation between bearing lengths and joist depths is permitted for reference design reactions. 5 The minimum bearing length is permitted to be reduced for joists supported by hangers if supplemental nail attachment is provided to the web stiffener. 6 Required bearing lengths have been determined based on Weyerhaeuser TJI Joist products. Allowable bearing stresses on supporting members must be checked. 7 1 Referenced design reactions require 5 /4-inch and 7-inch bearing lengths at intermediate supports. 8 Joist weights shown are calculated on a rational basis, are based on the heavier of eastern or western species products and are suitable for dead load calculation. Contact the producing plant for shipping weight information if needed. 9 1 Applicable to TJI HD90 and TJI HS90 joists only. Tabulated values indicate reference design bearing reactions for a 2 /2 inch bearing length at end supports. 3 1 /4 inch end bearing lengths are also permitted; with reference design reactions of 1600 lbs. without web stiffeners for depths up to and including 18 inches; 7 with web stiffeners the reference design reaction is 2255 lbs. for the 11 /8 inch depth and 2450 lbs. for all other depths. 10 The reference design moment values listed in Table 3 may not be increased by any code allowed repetitive-member use factor. 11 Applicable to TJI HD90 and TJI HS90 joists only. Reference design reaction values are based on applicable hanger seat length (interpolated as per note 4 above) may be increased 510 lbs when supported by Simpson Strong-Tie Co. HWI or WPU joist hangers with a minimum of 4 10d common nails installed through the joist hanger stirrups and into the joist web stiffener and web. 12 Use 90% of the published TJI 210, 230, 360, and 560 joist bending capacity for TJI joists with Flak Jacket protection when used in one-hour fireresistance-rated Assembly H described in Figure 4H of this report.
TABLE 4PROPERTIES FOR USE IN SECTION 4.2 TJI JOIST SERIES TJI 110 TJI 210, TJI 230 TJI 360 TJI 560 TJI 560D TJI s31, TJI s33 TJI s47 TJI 110C, TJI 300C TJI L65, TJI L90, TJI H90 TJI HD90, TJI HS90 For SI: 1 inch = 25.4 mm, 1 lb. = 4.448 N, 1 plf = 14.59 N/m.
V12 (lbs.) 1560 1655 1705 2050 2255 1530 1925 1420 1925 2320
Kred 15.60 16.55 17.05 20.50 20.50 15.30 19.25 14.20 19.25 23.20
Page 9 of 24
Web stiffeners must be installed at bearing points as required in Table 3. Web stiffeners must be installed at points of concentrated loads greater than 1500 pounds and are to be nailed in accordance with the intermediate reaction schedule in Table 3. 3 Web stiffeners are to be installed on each side of the web as shown, with nails equally spaced vertically. 4 A gap must be left at the top of web stiffeners as shown at all bearing conditions. In the case of concentrated loads, web stiffeners are required as shown and the gap must be at the bottom. 5 Web stiffener material must be sheathing meeting the requirements of PS-1 or PS-2 with the face grain parallel to the long axis of the stiffener. 6 Some hangers require web stiffeners to comply with nailing requirements through side plates. 7 If web stiffeners are not used in hanger support, the side of the hanger must extend up to laterally support the top flange. 8 See manufacturers published installation instructions for additional details and requirements for web stiffeners. Web stiffener specifications are as follows: TJI JOIST SERIES TJI 110 TJI 210 TJI 230, TJI 360, TJI L65 TJI s31, TJI s33, TJI 100C, TJI 300C TJI s47, TJI 560, TJI 560D, TJI L90, TJI H90 TJI HD90, TJI HS90
GRADE See Note 5 See Note 5 See Note 5 See Note 5 Construction Grade 2x4 1.3E minimum grade TimberStrand LSL
T (inches)
5
/8 /8
23/32
7
1.0 1 /2 1 /2
1 1
Page 10 of 24
Hole Factors and Locations Chart Round Hole Size (inches) Rectangular Hole Size inches) 11 /8 14 Joist depth (inches) 16 18 20 22 24 26 28 30
7
2 1 /4
1
3 1 /4
3
4 2 /4
1
5 3
6 3 /2
1
7 4
8 43 4
/
9 5 /4
1
10 6
11 6 /2
1
12 7
13 7 /4
3
14 8 /4
1
15 9
16 9 /2
1
17 10
18 10 /4
3
19 11 /4
1
20 12
A A A 4 4 4 4 4 4 4
C C B A A A A A 1-3 1-3
E C C B B A A A A 1-3 D C C B B A A A A E D C C B B B A A E D C C B B B A E E D C C B B B E D D C C B B E D D C C B E E D D C C E E D D C E D D C E E D D E E D E E E E E
Hole Locations Chart Joist Span (center to center of support, feet) 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Hole Factor A 1-3 1-3 1-3 1-6 1-6 1-9 1-9 2-0 2-0 2-0 2-3 2-3 2-3 2-6 2-6 2-6 2-9 3-0 3-0 3-0 3-0 3-3 3-3 B 2-0 2-0 2-3 2-9 3-0 3-0 3-0 3-0 3-0 3-3 3-3 3-6 3-9 3-9 4-0 4-0 4-3 4-3 4-6 4-9 5-0 5-0 5-0 C 2-6 3-0 3-3 3-9 4-3 4-3 4-3 4-3 4-3 4-3 4-6 4-9 4-9 5-0 5-3 5-6 5-9 5-9 6-0 6-3 6-6 6-6 6-9 D 3-9 4-0 4-6 5-0 5-6 5-6 5-6 5-9 5-9 5-9 5-9 5-9 6-0 6-3 6-6 6-9 7-0 7-3 7-6 7-9 8-0 8-3 8-6 E 5-0 5-3 5-9 6-3 6-9 7-0 7-0 7-3 7-3 7-6 7-6 7-9 7-9 7-9 8-0 8-3 8-6 8-9 9-3 9-6 9-9 10-0 10-3 Notes to Figure 2: Charts are based on simple spans and uniform load applications or applicable building code provisions for concentrated loads (2000 lbs. Over 2.5 square feet) with 25 psf dead load and 20 psf partition load. 2. For uniformly loaded multiple span applications holes must be located 1.0 inch farther from the support for each foot of joist span, than the values indicated in the Charts. 3. Holes are not allowed in cantilever areas unless specifically designed by a qualified design professional. 4. Where more than one hole is to be cut in the web, the clear distance between holes must be twice the length of the longest dimension of the largest adjacent hole. 5. Hole sizes shown are hole sizes, not duct sizes. 6. Rectangular hole sizes are based on measurement of the longest side. 7. Hole locations are measured from inside face of joist support to nearest edge of hole. See Figure 3. 1. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
FIGURE 2ALLOWABLE HOLE SIZE AND LOCATION FOR THE TJI L65, TJI L90, TJI H90, TJI HD90 AND TJI HS90 JOISTS ONLY
Page 11 of 24
TABLE AMINIMUM DISTANCE FROM INSIDE FACE OF END SUPPORT TO NEAREST EDGE OF HOLE JOIST DEPTH (inches)
1
ROUND HOLE SIZE (inches) 2 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 3 1-6 1-6 2-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 4 2-0 2-0 2-6 1-0 1-0 1-0 1-6 1-6 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 6 /2 5-0 5-0 5-6 2-6 2-6 3-0 4-6 5-0 1-0 1-0 1-6 2-6 2-6 1-0 1-0 1-0 1-0 5-0 5-6 6-0 7-0 8-0 2-6 3-0 3-6 5-6 6-0 1-6 2-0 3-0 3-0 5-0 6-0 6-6 8-0 9-0 3-6 4-0 6-0 6-6 6-0 6-6 9-0 10-0
1
SQUARE OR RECTANGULAR HOLE SIZE (inches) 13 2 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 3 1-6 2-0 2-0 1-0 1-0 1-0 1-0 2-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 4 2-6 2-6 3-0 1-6 2-0 2-0 2-6 3-6 1-0 1-0 1-0 1-0 1-6 1-0 1-0 1-0 1-0 6 /2 4-6 5-0 5-0 4-6 5-0 5-6 6-6 7-0 3-6 4-0 4-0 5-6 6-6 2-6 3-0 4-0 5-0 6-0 6-6 7-0 7-6 8-0 6-0 6-6 7-0 8-0 9-0 6-6 7-0 9-0 10-0 8-0 8-6 9-0 9-6 10-0 8-0 9-0 10-0 11-0 10-6 11-0 11-6 12-0
1
8 /8
11
8 /8
11
13
9 /2
11 /8
TJI 230 TJI 360 TJI 560 TJI 110 TJI 210
14
TJI 230 TJI 360 TJI 560 TJI 210 TJI 230 TJI 360
16
TABLE BMINIMUM DISTANCE FROM INSIDE FACE OF INTERMEDIATE OR CANTILEVER SUPPORT TO NEAREST EDGE OF HOLE JOIST DEPTH (inches)
1
ROUND HOLE SIZE (INCHES) 2 1 -6 2-0 2-6 1-0 1-0 1-0 2-0 1-6 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 3 2-6 2-6 3-0 1-0 1-0 2-0 3-0 3-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 4 3-0 3-6 4-0 1-6 2-0 2-6 4-0 4-6 1-0 1-0 1-0 2-0 1-6 1-0 1-0 1-0 1-0 6 /2 7-6 7-6 8-0 4-0 4-6 5-0 7-0 8-0 2-0 2-6 3-0 5-6 5-6 1-0 1-6 3-0 2-6 8-0 9-0 9-6 11-0 12-0 4-6 5-0 5-6 8-6 9-6 3-0 4-0 6-6 7-0 8-0 9-0 10-0 12-6 13-6 5-6 6-6 10-0 11-0 9-6 10-6 13-6 15-0
1
SQUARE OR RECTANGULAR HOLE SIZE (inches) 13 2 1-6 2-0 2-6 1-0 1-0 1-0 2-0 3-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 1-0 3 2-6 3-0 3-0 1-6 2-0 2-6 3-6 4-6 1-0 1-0 1-0 2-0 3-0 1-0 1-0 1-0 1-0 4 3-6 4-0 4-6 2-6 3-0 3-6 5-0 6-0 1-0 2-0 2-6 4-0 5-0 1-0 1-0 2-0 3-6 6 /2 6-6 7-0 7-6 6-6 7-6 8-0 9-6 10-6 5-0 6-0 6-0 9-0 10-0 4-6 5-0 7-6 9-0 9-0 10-0 10-0 11-0 12-0 9-0 10-0 10-6 12-0 13-6 9-6 10-6 13-0 14-6 12-0 12-6 13-0 14-0 15-0 12-6 13-0 14-6 16-0 15-6 16-0 17-0 18-0
1
8 /8
11
8 /8
11
13
9 /2
11 /8
TJI 230 TJI 360 TJI 560 TJI 110 TJI 210
14
TJI 230 TJI 360 TJI 560 TJI 210 TJI 230 TJI 360
16
FIGURE 3ALLOWABLE HOLE SIZE AND LOCATION FOR THE TJI 110, TJI 210, TJI 230, TJI 360 AND TJI 560 JOISTS (TABLES A AND B)
TABLE CMINIMUM DISTANCE FROM INSIDE FACE OF END SUPPORT TO NEAREST EDGE OF HOLE ROUND HOLE SIZE (inches) 4 2'-6'' 3'-0'' 2'-0'' 1'-6'' 2'-0'' 1'-0'' 1'-0'' 1'-6'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 2'-0'' 6'-0'' 10'-0'' 1'-0'' 1'-0'' 2'-0'' 5'-6'' 9'-6'' 1'-0'' 1'-0'' 4'-0'' 7'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 3'-0'' 1'-0'' 5'-0'' 1'-0'' 1'-6'' 5'-6'' 9'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 2'-6'' 5'-0'' 8'-0'' 1'-0'' 1'-0'' 1'-0'' 2'-0'' 3'-6'' 6'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-6'' 3'-6'' 7'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 2'-6'' 5'-0'' 1'-0'' 1'-0'' 1'-0'' 3'-0'' 4'-0'' 2'-6'' 3'-0'' 3'-6'' 2'-0'' 2'-6'' 1'-6'' 1'-0'' 1'-0'' 4'-6'' 8'-6'' 1'-0'' 1'-0'' 1'-0'' 5'-0'' 2'-0'' 4'-6'' 8'-0'' 1'-0'' 1'-0'' 1'-0'' 4'-0'' 7'-0'' 8'-0'' 5'-0'' 6'-6'' 6'-0'' 7'-0'' 8'-6'' 5'-0'' 6'-6'' 6'-6'' 4'-6'' 1'-6'' 3'-0'' 6'-0'' 1'-0'' 1'-0'' 1'-0'' 3'-6'' 6'-0'' 3'-0'' 6'-6'' 1'-0'' 1'-0'' 2'-0'' 5'-0'' 6'-6'' 7'-6'' 8'-6'' 9'-6'' 6'-6'' 8'-0'' 7'-0'' 9'-0'' 10'-0'' 6'-6'' 8'-0'' 10'-6'' 10'-0'' 9'-6'' 10'-6'' 11'-0'' 8'-0'' 10'-0'' 12'-0'' 11'-6'' 2'-6'' 5'-0'' 1'-0'' 1'-0'' 1'-6'' 4'-0'' 5'-6'' 3'-6'' 7'-0'' 1'-0'' 1'-6'' 2'-6'' 6'-6'' 7'-6'' 3'-6'' 7'-0'' 1'-0'' 1'-0'' 2'-6'' 5'-6'' 7'-0'' 3'-0'' 6'-0'' 1'-0'' 1'-0'' 2'-0'' 4'-6'' 6'-0'' 5'-0'' 1'-0'' 1'-6'' 2'-6'' 4'-0'' 6'-0'' 1'-0'' 2'-0'' 3'-0'' 5'-0'' 5'-6'' 1'-0'' 1'-6'' 2'-6'' 4'-6'' 6 /4
1
12 /4
14 /4
16 /4
6 /4
8 /8
10 /4
12 /4
143/4
163/4
s31
1'-0''
2'-0''
9 /2
s33
1'-6''
2'-6''
100C
1'-0''
1'-6''
s31
1'-0''
1'-0''
s33
1'-0''
1'-0''
11 /8
s47
1'-0''
1'-0''
100C
1'-0''
1'-0''
300C
1'-0''
1'-0''
s31
1'-0''
1'-0''
s33
1'-0''
1'-0''
14
s47
1'-0''
1'-0''
100C
1'-0''
1'-0''
300C
1'-0''
1'-0''
s31
1'-0''
1'-0''
s33
1'-0''
1'-0''
16
s47
1'-0''
1'-0''
100C
1'-0''
1'-0''
300C
1'-0''
1'-0''
18
s47
1'-0''
1'-0''
20
s47
1'-0''
1'-0''
Page 12 of 24
TABLE DMINIMUM DISTANCE FROM INSIDE FACE OF INTERMEDIATE OR CANTILEVER SUPPORT TO NEAREST EDGE OF HOLE ROUND HOLE SIZE (inches) 4 4'-0'' 5'-0'' 3'-0'' 2'-6'' 3'-6'' 2'-0'' 2'-0'' 3'-0'' 1'-6'' 2'-0'' 1'-0'' 1'-0'' 1'-6'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 3'-6'' 7'-0'' 10'-6'' 1'-0'' 3'-0'' 6'-6'' 9'-6'' 14'-6'' 15'-0'' 2'-0'' 4'-0'' 6'-6'' 11'-0'' 1'-0'' 2'-6'' 4'-6'' 7'-6'' 2'-0'' 5'-6'' 9'-0'' 14'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 2'-6'' 5'-0'' 7'-6'' 12'-6'' 1'-0'' 2'-0'' 3'-6'' 5'-6'' 9'-6'' 1'-0'' 1'-0'' 1'-0'' 1'-6'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 3-6'' 6'-0'' 10'-6'' 1'-0'' 2'-0'' 2'-0'' 4'-6'' 8'-0'' 1'-0'' 1'-0'' 2'-0'' 3'-0'' 1'-6'' 2'-0'' 3'-0'' 1'-0'' 2'-0'' 1'-6'' 1'-0'' 4'-0'' 7'-6'' 12'-6'' 1'-0'' 2'-6'' 4'-0'' 4'-0'' 6'-6'' 12'-0'' 1'-0'' 2'-0'' 3'-6'' 3'-0'' 5'-0'' 9'-0'' 1'-0'' 1'-6'' 2'-6'' 5'-6'' 6'-6'' 8'-0'' 4'-6'' 6'-0'' 4'-6'' 5'-6'' 7'-0'' 3-6'' 5'-0'' 6'-0'' 4'-0'' 5'-0'' 10'-0'' 1'-6'' 3'-0'' 4'-0'' 7'-6'' 4'-0'' 8'-0'' 1'-0'' 2'-0'' 3'-0'' 6'-0'' 8'-0'' 9'-6'' 9'-0'' 11'-0'' 12'-0'' 8'-0'' 10'-0'' 9'-0'' 11'-0'' 13'-0'' 7'-6'' 10'-0'' 11'-0'' 9'-0'' 11'-6'' 13'-0'' 13'-6'' 10'-6'' 12'-0'' 11'-0'' 13'-6'' 15'-0'' 9'-6'' 12'-0'' 15'-6'' 15'-0'' 14'-0'' 15'-6'' 16'-6'' 12'-6'' 15'-0'' 17'-0'' 16'-6'' 18'-6'' 18'-0'' 19'-6'' 5'-6'' 11'-0'' 2'-0'' 3'-6'' 5'-0'' 9'-6'' 11'-0'' 5'-6'' 10'-6'' 2'-0'' 3'-0'' 4'-0'' 8'-6'' 10'-0'' 4'-6'' 9'-0'' 1'-6'' 2'-6'' 3'-6'' 7'-0'' 9'-0'' 7'-6'' 1'-6'' 2'-6'' 3'-6'' 6'-0'' 9'-0'' 2'-0'' 3'-6'' 4'-6'' 7'-6'' 8'-6'' 2'-0'' 3'-0'' 4'-0'' 6'-6'' 6 /4
1
12 /4
14 /4
16 /4
6 /4
8 /8
10 /4
12 /4
14 /4
16 /4
s31
2'-0''
3'-0''
9 /2
s33
2'-6''
3'-6''
100C
1'-6''
2'-6''
s31
1'-6''
2'-0''
s33
2'-0''
3'-0''
11 /8
s47
1'-0''
1'-0''
100C
1'-0''
1'-6''
300C
1'-6''
2'-6''
s31
1'-0''
1'-0''
s33
1'-0''
1'-0''
14
s47
1'-0''
1'-0''
100C
1'-0''
1'-0''
300C
1'-0''
1'-0''
s31
1'-0''
1'-0''
s33
1'-0''
1'-0''
16
s47
1'-0''
1'-0''
100C
1'-0''
1'-0''
300C
1'-0''
1'-0''
18
s47
1'-0''
1'-0''
20
s47
1'-0''
1'-0''
FIGURE 3ALLOWABLE HOLE SIZE AND LOCATION FOR THE TJI s31, TJI s33, TJI s47, TJI 100C AND 300C JOISTS (TABLES C AND D) (Continued)
Page 13 of 24
TABLE EMINIMUM DISTANCE FROM INSIDE FACE OF END SUPPORT TO NEAREST EDGE OF HOLE ROUND HOLE SIZE (inches) 6 6'-0'' 5'-0'' 4'-0'' 3'-0'' 1'-6'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 1'-6'' 1'-6'' 2'-6'' 3'-6'' 5'-0'' 7'-0'' 8'-0'' 9'-6'' 1'-0'' 2'-0'' 4'-0'' 6'-0'' 2'-6'' 4'-0'' 5'-0'' 7'-0'' 8'-6'' 10'-0'' 1'-0'' 2'-6'' 4'-0'' 6'-0'' 2'-6'' 3'-6'' 5'-0'' 7'-6'' 9'-0'' 11'-0'' 1'-0'' 2'-0'' 4'-0'' 6'-6'' 8'-6'' 8'-6'' 8'-0'' 2'-0'' 3'-6'' 5'-0'' 8'-0'' 10'-0'' 12'-6'' 1'-0'' 1'-6'' 4'-0'' 6'-6'' 9'-6'' 1'-6'' 3'-6'' 5'-0'' 8'-6'' 11'-6'' 1'-0'' 1'-0'' 3'-6'' 6'-6'' 14'-6'' 2'-6'' 4'-6'' 6'-0'' 10'-6'' 1'-0'' 2'-6'' 5'-0'' 7'-0'' 10'-0'' 12'-6'' 15'-0'' 15'-0'' 15'-6'' 11'-0'' 10'-0'' 3'-6'' 5'-6'' 7'-6'' 1'-0'' 3'-0'' 5'-6'' 8'-0'' 10'-6'' 11'-6'' 14'-6'' 16'-0'' 16'-0'' 16'-6'' 16'-6'' 16'-6'' 16'-6'' 16'-6'' 17'-0'' 17'-0'' 17'-0'' 17'-0'' 17'-0'' 17'-0'' 17'-6'' 5'-0'' 6'-6'' 9'-0'' 2'-0'' 4'-0'' 6'-0'' 8'-6'' 10'-0'' 11'-0'' 5'-6'' 8'-0'' 2'-0'' 4'-0'' 6'-6'' 8'-6'' 9'-0'' 6'-6'' 3'-0'' 4'-6'' 6'-6'' 7'-6'' 2'-0'' 4'-0'' 5'-6'' 8 10 12 16 18 20 2 4 6 8 10 12 16 18 SQUARE OR RECTANGULAR HOLE SIZE (inches) 20
1,2,3,4,5
9 /2
2'-0''
4'-0''
11 /8
1'-6''
3'-0''
14
1'-0''
2'-0''
16
1'-0''
1'-6''
18
1'-0''
1'-0''
20
560D
1'-0''
1'-0''
22
1'-0''
1'-0''
24
1'-0''
1'-0''
26
1'-0''
1'-0''
28
1'-0''
1'-0''
30
1'-0''
1'-0''
TABLE FMINIMUM DISTANCE FROM INSIDE FACE OF INTERMEDIATE OR CANTILEVER SUPPORT TO NEAREST EDGE OF HOLE ROUND HOLE SIZE (inches) 6 9'-6'' 7'-0'' 5'-6'' 3'-6'' 1'-0'' 1'-0'' 2'-6'' 4'-0'' 5'-6'' 5'-6'' 5'-6'' 6'-6'' 8'-0'' 9'-0'' 11'-6'' 6'-6'' 7'-6'' 9'-0'' 11'-6'' 6'-6'' 7'-6'' 9'-0'' 12'-0'' 5'-6'' 7'-0'' 8'-6'' 12'-6'' 15'-0'' 14'-0'' 13'-0'' 13'-0'' 4'-6'' 6'-6'' 8'-0'' 13'-0'' 16'-6'' 17'-6'' 16'-0'' 15'-0'' 14'-6'' 1'-0'' 4'-6'' 8'-6'' 16'-0'' 4'-6'' 7'-6'' 11'-0'' 6'-6'' 10'-0'' 13'-0'' 8'-6'' 11'-6'' 2'-6'' 1'-0'' 1'-0'' 1'-0'' 1'-0'' 2'-0'' 4'-0'' 4'-0'' 4'-0'' 10'-0'' 4'-0'' 4'-0'' 8 10 12 16 18 20 2 4 6'-6'' 6'-6'' 6'-0'' 5'-0'' 3'-0'' 1'-0'' 3'-6'' 5'-0'' 6'-0'' 6'-0'' 6'-0''
SQUARE OR RECTANGULAR HOLE SIZE (inches) 6 8'-0'' 10'-0'' 9'-0'' 8'-6'' 7'-6'' 5'-6'' 6'-6'' 7'-6'' 8'-0'' 8'-0'' 8'-0'' 10'-6'' 12'-0'' 12'-6'' 11'-6'' 10'-0'' 10'-0'' 10'-6'' 10'-6'' 10'-6'' 10'-6'' 13'-6'' 14'-6'' 16'-0'' 15'-0'' 19'-0'' 14'-0'' 13'-0'' 13'-0'' 12'-6'' 16'-0'' 17'-0'' 18'-0'' 20'-0'' 20'-0'' 20'-6'' 16'-0'' 15'-0'' 20'-0'' 21'-0'' 21'-0'' 21'-6'' 21'-6'' 21'-6'' 21'-6'' 21'-6'' 22'-0'' 22'-0'' 22'-0'' 22'-0'' 22'-0'' 22'-0'' 22'-6'' 8 10 12 16 18 20
9 /2
4'-0''
6'-0''
11 /8
2'-0''
4'-6''
14
1'-0''
3'-0''
16
1'-0''
1'-0''
18
1'-0''
1'-0''
20
560D
1'-0''
1'-0''
22
1'-0''
1'-0''
24
1'-0''
2'-6''
26
3'-0''
4'-0''
28
3'-0''
4'-0''
30
3'-0''
4'-0''
The clear distance between multiple holes must be twice the length of the longest dimension of the largest hole. 1 Holes may be located vertically anywhere within the web. Leave /8 inch of web minimum at top and bottom of hole. 3 Tables A, C and E (simple and continuous spans) and Tables B, D and F (continuous spans) are based on uniform load applications, within the limitations of the applicable Weyerhaeuser literature. 4 1 TJI joists are manufactured with 1 /2 inch diameter perforated knockouts in the web at approximately 12 inches on center along the length of the joist. 5 For simple span (5 foot minimum) uniformly loaded joists, one maximum size hole may be located in the web at the center of the joist span provided no other holes occur in the joist. FIGURE 3ALLOWABLE HOLE SIZE AND LOCATION FOR THE TJI 560D JOISTS (TABLES E AND F) (Continued)
Page 14 of 24
Page 15 of 24
10 minimum
Assembly Component
Component Specifications Subfloor of nominal 1-inch-thick, tongue-and-groove sheathing or 32/16 span-rated sheathing (Exposure 1) and a second layer of nominal 1-inch-thick, tongue-and-groove finish flooring.
Installation
Alternatively, finish flooring is permitted to be 40/20 span-rated sheathing (Exposure 1), or Type-1 5 Grade-1 particleboard not less than /8-inch thick. When used as a roof-ceiling assembly, a single layer of square-edged span-rated sheathing (Exposure 1), complying with the code, is permitted to be used for roof sheathing.
All butt joints of the sheathing must be located over framing members.
2 3
Installed in accordance with this report, at a maximum spacing of 48 inches on center. See Recessed Light Fixture Installation. Installed in the ceiling. Must be protected by insulation as described below. A 24-inch-by-48-inch fixture is used as an example: A 2 /4-inch-by-48-inch, minimum 1 /4-inch-thick piece of minimum 4 pcf Thermafiber rigid mineral fiber board or Fibrex-FBX 1240 Industrial Board or Fibrex-IF 1240 Flex Batt light fixture protection, is laid along the long sides of the fixture, and against adjacent suspension members Two pieces of the same insulation, measuring 19- /2 inches by 48 inches, are laid over the top of the fixture, and A 4 /2-inch-by-24-inch piece of the same insulation is laid at each end and tied, at the corners of the fixture, to the top pieces using No. 18 SWG steel wire.
1 1 1 1
24 inch x 48 inch, maximum. The aggregate area of the lighting fixture may not exceed 12 square feet per 100 square feet of ceiling area.
See Figure 5 for details. 5 Channels Cold rolled. Air diffusers, up to a maximum of 12 inches in diameter, are permitted. The aggregate area must not exceed 113 square inches per 100 square feet of ceiling area. Minimum 1-inch-thick, 4 pcf minimum, Thermafiber Sound Attenuation Fire Blankets, or Fibrex -FBX 1240 industrial boards, or Fibrex -IF 1240 Flex Batts, or IIG MinWool -1240 Industrial Board, or IIG MinWool -1240 Flexible Batt.
Air Diffuser
Suspended Ceiling
Supported by an approved exposed fire-resistance-rated suspension system attached to joist bottom flange or to coldrolled channels. When TJI joists are spaced more than 24 inches on center, framing perpendicular to the joists must be installed at 24 inches on center to support the ceiling. The distance from the bottom of the TJI joists to the soffit of the ceiling must be a minimum of 10 inches.
Page 16 of 24
Optional resilient channels directly applied to joists or trusses at 16 inches on-center, supporting both layers of gypsum board, are necessary to achieve sound ratings.
Component Specifications Single layer of 48/24 span-rated, tongue-and-groove, sheathing (Exposure 1). When used as a roof-ceiling assembly, the decking is permitted to be any wood deck recognized in the code.
Installation
Nailed and glued to the top of the TJI joists. Construction adhesive conforming to ASTM D3498 must be applied to the top of the joists prior to placing sheathing. All butt joints of the sheathing must be located over framing members.
Two layers of /2-inch-thick NGC Gold Bond Fire-Shield C gypsum board, or Gypsum Board Two layers of /2-inch-thick USG SHEETROCK Brand FIRECODE C gypsum panels, or Two layers of /8-inch-thick, Type X gypsum board complying with ASTM C36.
5 1
For TJI joists spaced 24 inches on-center or less, attach ceiling to joist bottom flange. The first layer of gypsum board must be installed perpendicular to the 5 TJI joists and attached using 1 /8-inch-long, Type S screws spaced 12 inches on-center. The second layer must be installed with the joints staggered from the first layer. The second layer must be fastened to the TJI joists with 2-inch-long, Type S screws spaced 12 inches on-center in the field and 8 inches on-center at the butt joints. Type G screws, 1 /2 inches long, must be spaced 8 inches on-center and 6 inches from each side of the transverse joints of the second layer. The second layer must be finished with joint tape and compound. Installed in accordance with this report, with a maximum spacing of 24 inches on-center for floor-ceiling assemblies. When used in roof-ceiling assemblies, the joists are permitted to be spaced a maximum of 48 inches on-center. May be installed in the joist plenum when resilient channels are used. The insulation must be placed above the resilient channels between the joist bottom flanges. Fasten perpendicular to the TJI joists using 1-inch-long, Type S screws. When resilient channels are used, the first layer of the ceiling membrane must be installed perpendicular to the channels and attached to the resilient channels using 1-inch-long, Type S screws spaced 12 inches on-center. The second layer must be installed with the joints staggered from the 5 first layer and attached using 1 /8-inch-long, Type S screws. The screw spacing for the second layer of gypsum board must be a maximum of 12 inches on-center in the field and 8 inches on-center at the butt joints. Type G screws, 1 /2 inches long, must be spaced 8 inches on-center and 6 inches from each side of the transverse joints of the second layer. The second layer must be finished with joint tape and compound. In roof-ceiling assemblies in which the TJI joists are spaced more than 24 inches on-center, the ceiling, including the resilient channels, must be applied to stripping spaced 24 inches on-center. The attachment of the ceiling membrane to the stripping members must be similar to the attachment of the ceiling membrane to the TJI joists. Attached to the joist bottom flange using a minimum of two 10d box nails into each bottom flange. Stripping materials of equivalent strength and attachment are permitted when approved by the code official.
1 1
TJI Joist
TJI joist.
(not shown)
Minimum 3 /2-inch-thick glass fiber insulation or glass fiber insulation rated R-30 or less.
(not shown)
RC-1 resilient channels spaced 16 inches on-center (may be increased to 24 inches on-center if the joists are spaced 16 inches on-center).
(not shown)
Stripping
Minimum of nominal 2-by-4 construction-grade Douglas fir lumber for spans up to 5 feet.
Page 17 of 24
12 minimum
Assembly Component
Component Specifications Single layer of 48/24 span-rated, tongue-andgroove, sheathing (Exposure 1).
Sheathing
When used as a roof-ceiling assembly, a single layer of square-edged span-rated sheathing (Exposure 1), complying with the code, is permitted to be used for roof sheathing.
Construction adhesive conforming to ASTM D3498 must be applied to the top of the joists prior to placing sheathing. All butt joints of the sheathing must be located over framing members. Installed in accordance with this report, at a maximum spacing of 24 inches on center for floor-ceiling assemblies.
TJI Joist
TJI joist.
When used in roof-ceiling assemblies the joists are permitted to be spaced a maximum of 48 inches on center. When the joist spacing exceeds 24 inches on center, framing perpendicular to the joists must be installed at 24 inches on center to support the ceiling. Installed above the gypsum board, in the cavity between the joists. Installed on steel suspension grid. Light fixture protection must consist of 6-inch-wide pieces of ceiling grid panels that are 48 inches long for the sides, and 24 inches long for the ends, with a full grid panel placed on top. Attached to the joists, or to stripping spaced 24 inches oncenter or less. Installed perpendicular to the TJI joists or stripping. The gypsum board must be fastened using 1 /8-inch-long, Type S screws located 6 inches on-center at end joints and 8 inches on-center in the field. Protected with ceiling panels per Fixture Protection above.
5
Glass fiber batt insulation rated R-30 or less. 24 inch x 24 inch, /8-inch-thick, USG FIRECODE AURATONE ceiling panel.
5
Ceiling Panel
Fixture Protection
Gypsum Board
Single layer of, /2-inch-thick NGC Gold Bond Fire-Shield C gypsum board, or /8-inch-thick, Type X gypsum board complying with ASTM C36.
5
(not shown)
Galvanized steel duct. Maximum 6 inch x 12 inch opening per 200 square feet of ceiling. Steel diffuser without damper.
A duct is permitted for each 200 square feet of ceiling. Air return opening and steel diffuser are required. Required if steel duct is used.
Diffuser
Suspension Grid
Minimum distance between the suspended ceiling and the gypsum board ceiling membrane must be 12 inches. The grid system must be suspended with No. 12 SWG galvanized steel wire fastened to the stripping or joists using 3 inch long flathead hanger screws.
Page 18 of 24
Assembly Component
Component Specifications Single layer of 48/24 span-rated, tongueand-groove, sheathing (Exposure 1).
Installation
Sheathing
When used as a roof-ceiling assembly, a single layer of square-edged span-rated sheathing (Exposure 1), complying with the code, is permitted to be used for roof sheathing. Minimum flange depth of 1 /8 inches.
3
All butt joints of the sheathing must be located over framing members.
TJI Joist
Installed in accordance with this report, at a maximum spacing of 24 inches on-center. Installed perpendicular to joists. Furring channels spaced 24 inches on-center. Furring channels spaced 1 inches from, and on each side of, wallboard end joints, and 24 inches from end joints.
Channels
Attached and suspended from the joists using No. 24 gage proprietary attachment clips designated Simpson StrongTie CSC Support Clips. A CSC support clip must be located at each joist, to support the furring channel.
At channel splices, adjacent pieces are overlapped a minimum of 6 inches, and are tied with double-strand No. 18 SWG galvanized steel wire at each end of the overlap. Simpson Strong-Tie Co. Type CSC support clips. Support furring channels at the intersection with each joist with clips. Support clips nailed to side of joist bottom flange with 1 inch long No. 11 gauge nail. Used to prevent rotation of the support clips at wallboard end joints and along walls.
Clips
(not shown)
Stabilizer Strap
/4 inch x 6 inch No. 24 gauge galvanized steel strap. Single layer of 1-inch-thick, minimum 6 pcf Thermafiber Type CW 90 mineral-wool blanket, Fibrex-FBX 1280 Industrial Board, Fibrex-IF 1280 Flex Batt, IIG MinWool 1260 Industrial Board or IIG MinWool 1260 Flexible Batt. Alternatively, a layer of 2-inch-thick, Thermafiber mineral-wool blanket, having a density of 8 pcf, is permitted to be used. Single layer of /2-inch-thick, USG SHEETROCK Brand FIRECODE C gypsum board , or Single layer of /2-inch-thick, CertainTeed ProRoc Type C gypsum board.
1 1
Installed below the bottom flanges of the joists and on top of the furring channels.
Gypsum Board
Attached with screws to steel furring channels placed perpendicular to the joists.
Page 19 of 24
Assembly Component
Component Specifications Subfloor of nominal 1-inch-thick, tongue-andgroove sheathing or 32/16 span-rated sheathing (Exposure 1) and a second layer of nominal 1-inch-thick, tongue-and-groove finish flooring or 40/20 span-rated sheathing (Exposure 1), or Type-1 Grade-1 5 particleboard not less than /8-inch thick. Alternatively, a single layer of 48/24 spanrated, tongue-and-groove sheathing (Exposure 1) may be used. When used as a roof-ceiling assembly, a single layer of square-edged span-rated sheathing (Exposure 1), complying with the code, is permitted to be used for roof sheathing.
Installation
When a single-layer floor is used, a construction adhesive conforming to ASTM D3498 must be applied to the top of the joists prior to placing sheathing. All butt joints of the sheathing must be located over framing members.
TJI Joist
TJI joist.
Maximum spacing of 24 inches on-center for floor-ceiling assemblies, and a maximum spacing of 48 inches on-center for roof-ceiling assemblies. When the flooring consists of a double wood floor, the joists may be spaced a maximum of 48 inches on-center.
(not shown)
Channels
Resilient channels. Minimum of nominal 2-by-4, constructiongrade Douglas fir lumber for spans up to 5 feet. Stripping materials of equivalent strength and attachment are permitted when specifically approved by the code official. Any approved ceiling membrane that provides a minimum 40-minute finish rating must be used.
Installed at 24 inches on-center when joist spacing is more than 24 inches on-center. Stripping attached to the joist bottom flange using a minimum of two 10d box nails. Attachment of the ceiling membrane to the stripping must be similar to the attachment of the ceiling membrane to the TJI joists. Substantiating data, including a report of the fire-endurance testing conducted in accordance with ASTM E119, must be furnished to the local code official, and must verify that a particular ceiling system meets the 40-minute finish rating requirements. When the finish rating is to be determined, temperature performance of protective membranes must be in accordance with Section 47 of ASTM E119. The finish rating is defined in Section 48 of ASTM E119.
(not shown)
Stripping
Ceiling System
An example of an approved ceiling having a 40-minute finish rating is one that consists of two layers of inch-thick, Type X gypsum board complying with ASTM C36, a minimum of 4 feet wide, installed perpendicular to the TJI joists, as described in Figure 4B of this report (Assembly B).
Page 20 of 24
Assembly Component
Component Specifications Single layer of 48/24 span-rated, tongueand-groove, sheathing (Exposure 1).
Installation Attached to the TJI joist top flange with construction adhesive that meets ASTM D3498, and nailed using 8d common nails spaced a maximum of 6 inches on-center along the boundary and edges, and 12 inches on-center in the field. All butt joints of the sheathing must be located over framing members.
Sheathing
When used as a roof-ceiling assembly, a single layer of square-edged span-rated sheathing (Exposure 1), complying with the code, is permitted to be used for roof sheathing. Single layer of /8-inch-thick, USG SHEETROCK Brand FIRECODE C gypsum board, or Single layer of /8-inch-thick, CertainTeed ProRoc Type C gypsum board.
5 5
Gypsum Board
Fastened to the resilient channels with 1-inch-long, Type S screws spaced 12 inches on-center in the field and 8 inches on-center at the butt joints.
TJI Joist
When used in a floor-ceiling assembly, joist spacing must not exceed 24 inches on-center. When used in a roof-ceiling assembly, joist spacing is permitted to exceed 24 inches on-center. Installed perpendicular to joists. Spaced at 16 inches on-center. Attached to the joists with 1 /8-inch-long, Type S screws at each joist. Two channels must be provided at each gypsum-board butt joint, and extend to the next joist beyond the longitudinal joints. In roof-ceiling assemblies in which TJI joists are spaced more than 24 inches on-center, the ceiling, including the resilient channels, must be attached to stripping spaced 24 inches on-center. The attachment of the ceiling membrane to the stripping members is similar to the attachment of the ceiling membrane to the joists. Stripping must be attached to the bottom flanges of the joists using a minimum of two 10d box nails. Installed between the bottom flanges of the joists and on top of the resilient channels. Friction-fitted into place and supported by the resilient channels.
5
Channels
(not shown)
Stripping
Minimum of nominal 2-by-4, constructiongrade Douglas fir lumber for spans up to 5 feet. Stripping materials of equivalent strength and attachment are permitted when specifically approved by the code official.
Single layer of 1-inch-thick, minimum 2 pcf, Thermafiber Sound Attenuation Fire Blankets, Fibrex-SAFB (Sound Attenuation Fire Batts), or IIG MinWool 1200 Sound Attenuation Fire Batts.
Page 21 of 24
Assembly Component
Component Specifications Single layer of 48/24 span-rated, tongueand-groove, sheathing (Exposure 1).
Installation
Sheathing
When used as a roof-ceiling assembly, a single layer of square-edged span-rated sheathing (Exposure 1), complying with the code, is permitted to be used for roof sheathing. Minimum joist depth of 9 /4 inches. Glass-fiber insulation with unfaced batts that 1 are 24 inches wide by 48 inches long by 3 /2 inches thick.
1
All butt joints of the sheathing must be located over framing members. Flooring is permitted to be omitted where unusable attic space occurs above the system, provided the requirements of Section 4.5 are met. Installed in accordance with this report, at a maximum spacing of 24 inches on-center. Installed in the plenum and supported by stay wires spaced at 12 inches along the joist bottom flange. Base layer installed perpendicular to joists with end joints staggered, and attached directly to the bottom flange using 5 1 /8-inch-long Type S screws spaced 12 inches on-center along each joist. Resilient channels attached per 5 below. Middle layer of gypsum board installed perpendicular to the resilient channels, with end joints staggered, and attached to the resilient channels with 1-inch-long, Type S screws spaced 12 inches on-center. Finish layer of gypsum board installed with edges and end joints staggered from the middle layer, and must be 5 fastened to the resilient channels using 1 /8-inch-long, Type S screws spaced 8 inches on-center. Joints of the finish layer of gypsum board must be covered with joint compound and paper tape, and exposed screw heads must be covered with joint compound. Ceiling membrane may be omitted when used as a floorceiling assembly over unusable crawl spaces. Installed perpendicular to joists, under the first layer of gypsum board.
Gypsum Board
Channels
Spaced a maximum of 16 inches on-center. Attached to the bottom flange of each joist with 1 /8-inchlong, Type S screws.
5
Page 22 of 24
Assembly Component
Component Specifications Single layer 48/24 span-rated, tongue-and-groove sheathing (Exposure 1).
Installation
Construction adhesive conforming to ASTM D3498 must be applied to the top of the joists prior to placing sheathing. All butt joints of the sheathing must be located over framing members. The floor sheathing shall be installed in accordance with the applicable code.
Floor Sheathing
When used as a roof-ceiling assembly, the decking is permitted to be any wood deck recognized in the code. TJI 210, 230, 360 and 560 joists with Flak Jacket protection. Minimum flange depth is 1 /8 inches. Minimum joist depth is 9 inches.
3
TM
Installed in accordance with Weyerhaeuser recommendations, with a maximum spacing of 16 inches on-center. For TJI 230, 360 and 560 joists with a depth of 14 inches or deeper the maximum spacing is 24 inches on-center. Attach to resilient channels with 1 inch Type S drywall screws spaced at 6 inches on center. Tape and joint compound must be applied to all fastener heads and gypsum wallboard joints on exposed surfaces. Spaced at 16 inches on-center, installed perpendicular to the TJI joists and attached with 1 inch-long, Type W screws at each joist.
Gypsum Board
Resilient Channels
Two channels must be provided at each gypsum-board butt joint, and extend to the next joist beyond the longitudinal joints. Where splices are necessary, the resilient channels must overlap 6-inches and be fastened together with two screws.
Flak Jacket protection is applied to both sides of the web and the vertical sides of the bottom flange, in accordance with the
TJI Joist With Flak Jacket Protection Manufacturing Standard and quality control program.
Placed in I-joist cavity, between the I-joists and above the bottom flange.
(not shown)
Optional Insulation
**Load Limitation
For design with this assembly, use 90% of published TJI 210, 230, 360 and 560 bending moment capacity found in Table 3 of this report.
Page 23 of 24
Sheathing Required
1-inch-thick lightweight concrete or inch-thick gypsum concrete over the sheathing. Gypsum concrete must be recognized in a current ICC-ES evaluation report, and the report must include an evaluation for fire resistance that permits the replacement of the floor systems with the sheathing and gypsum concrete system.
TABLE 6SOUND RATINGS Assembly Assembly Figure STC Rating Assembly Components Required IIC Rating Floor Covering Required The floor covering must include a 40-ounceper-square-yard pad and a 56-ounce-persquare-yard carpet. Floor covering must consist of Tarkett Acoustiflor sheet vinyl, 51 Ceiling must consist of two layers of -inchthick, Type X gypsum board, and the Bottom of the floor cavity must contain 3-inch-thick glass-fiber insulation. The floor covering must include a 43.2ounce-per-square-yard, minimum 0.123inch-thick cushioned vinyl. The floor covering must include a 40-ounceper-square-yard pad and a 56-ounce-persquare-yard carpet. Floor covering must consist of Tarkett Acoustiflor sheet vinyl, 54 Ceiling must consist of two layers of -inchthick, Type X gypsum board, and the Bottom of the floor cavity must contain 3-inch-thick glass-fiber insulation. Floor covering must be either Armstrong VIOS or Armstrong Cambray sheet vinyl, 50 Ceiling must consist of two layers of -inchthick Type X gypsum board, and Bottom of the floor cavity must contain 3-inch-thick glass fiber insulation. Floor covering must include a 40-ounce-persquare-yard pad and a 56-ounce-persquare-yard carpet.
60
Assembly B Option 1
Figure 4B
50, minimum
Assembly B constructed with resilient channels spaced at 16 inches oncenter to separate the ceiling membrane from the structural framing.
45
54
Assembly B Option 2
Figure 4B
58, minimum
Assembly B constructed with resilient channels spaced at 16 inches on center to separate the ceiling membrane from the structural framing. -inch-thick floor topping of gypsum concrete recognized in a current ICC-ES evaluation report.
Assembly D Option 1
Figure 4D
47
Assembly D
54
Assembly D Option 2
Figure 4D
59
Assembly D constructed with a -inch-thick topping of gypsum concrete recognized in a current ICC-ES evaluation report. Assembly G, constructed 1 with 3 /2-inch-thick unfaced glass fiber insulation.
54
Assembly G
Figure 4G
50
64
The floor covering must include a 69-ounce3 per-square-yard, /8-inch-thick pad and 80ounce-per-square-yard carpet.
Page 24 of 24
FIGURE 5LIGHT FIXTURE PROTECTION (See Figure 4A, Items 4 and 7 for detailed description of mineral wool batts.) For SI: 1 inch = 25.4 mm.
Detail A:
Detail A is applicable to all TJI Joists with structural composite lumber flange widths of 2.5 inches or greater. Simpson Strong-Tie Co. MSTI or PAI straps, or other straps of the same minimum gauge, dimensions, grade of steel and nail patterns and recognized in a current ICC-ES Report or ICC-ES Legacy Report may be used.
Detail B:
Detail B is applicable to all TJI Joists with structural composite lumber flange widths of 3.5 inches or greater. Simpson Strong-Tie Co. LSTI or LTTI straps, or other straps of the same minimum gauge, dimensions, grade of steel and nail patterns and recognized in a current ICC-ES Report or ICC-ES Legacy Report may be used. General Notes: Connection capacity limited to a lateral nail design value of 112 lbs/nail with the following conditions. 1. All nails must be 10d short nails, 0.148 inches x 1.5 inches. 2. Minimum steel thickness must be 18 gauge (0.049 inches). 3. Total connection capacity must not exceed the code approved strap or tension-tie design value. 4. The connection capacity is permitted to be increased for duration of load in accordance with the code. 5. No additional reductions are necessary due to penetration. 6. The minimum required end distance must be 3 inches.
FIGURE 6METAL STRAP AND TENSION-TIE CONNECTION CAPACITIES AND DETAILS FOR TJI JOISTS For SI: 1 inch = 25.4 mm, 1 lbf. = 4.448 N.
Reissued August 1, 2012 This report is subject to renewal August 1, 2013. A Subsidiary of the International Code Council
Weyerhaeuser Framer Series Lumber Weyerhaeuser Pro Series Lumber Weyerhaeuser Lumber Weyerhaeuser Green Stud Weyerhaeuser Edge Engineered Wood Panels Weyerhaeuser Edge Gold Engineered Wood Panels Weyerhaeuser Radiant Barrier Sheathing Weyerhaeuser Sheathing Weyerhaeuser Plywood Building Optimization Software: Javelin Design Software NextPhase Site Solutions 1.0 EVALUATION SCOPE Compliance with the following evaluation guidelines: ICC-ES Environmental Criteria for Determination of Bio-based Material Content (EC102), dated March 2012 ICC-ES Evaluation Guideline for Determination of Regionally Extracted, Harvested or Manufactured Materials or Products (EG104), dated October 2008 ICC-ES Environmental Criteria for Determination of Formaldehyde Emissions of Composite Wood Products (EC108), dated March 2012 ICC-ES Environmental Criteria for Determination of Certified Wood and Certified Wood Content in Products (EC109), dated March 2012 Compliance eligibility with the applicable sections of the following codes, standards and green building rating systems: 2012 International Green Construction Code (IgCC) (see Table 2 for details) 2010 California Green Building Standards Code (CALGreen), Title 24, Part 11 (see Table 3 for details) National Green Building Standard (ICC 700-2008) (see Table 4 for details) LEED for Homes 2008 (see Table 5 for details) LEED 2009 for New Construction Renovations (see Table 6 for details) and Major
VAR-1008
Microllam , Parallam , TimberStrand , StrandGuard , Trus Joist , TJI , Framer Series , Javelin and NextPhase are registered trademarks, and Edge, Edge Gold and Pro Series are trademarks of Weyerhaeuser NR Company.
ICC-ES Verification of Attributes Reports are issued under the ICC-ES VAR Environmental Program. These reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report.
Copyright 2012
Page 1 of 12
VAR-1008 | Most Widely Accepted and Trusted LEED 2009 for Schools New Construction and Major Renovations (see Table 7 for details) LEED 2009 for Core and Shell Development (see Table 8 for details) LEED 2009 for Commercial Interiors (see Table 9 for details) LEED for Existing Buildings 2008 (see Table 10 for details) ANSI/GBI 01-2010 - Green Building Assessment Protocol for Commercial Buildings Construction (see Table 11 for details) ANSI/ASHRAE/USGBC/IES Standard 189.1-2009 Standard for the Design of High-Performance Green Buildings, Except Low-Rise Residential Buildings (see Table 12 for details) CSI GreenFormat (see Table 13 for details) 2.0 USES Weyerhaeuser and Trus Joist structural wood products are used for a variety of interior and exterior framing and sheathing applications.
Javelin software and NextPhase Site Solutions are building optimization solutions consisting of a coordinated package of services, software, and fabrication equipment used for customized design and detailing of structural building products for individual projects, including complete framing plans and precut framing package options.
Page 2 of 12 (LCI) inputs that consist of aggregated data and the methodology contained in the documentation noted in Section 5.10 of this report. The acceptance of this LCA information rests with the end-user. See Appendix A of this report for additional discussion on LCA. The final interpretation of the specific requirements of the respective green building rating system and/or standard rests with the developer of that specific rating system or standard or the AHJ, as applicable. Decisions on compliance for those items noted as Eligible for Points in Tables 2 through 13 rests with the user of this report, and those items are subject to the conditions noted. The user is advised of the projectspecific provisions that may be contingent upon meeting specific conditions, and the verification of those conditions is outside the scope of this report. Rating systems or standards often provide supplemental information as guidance. Compliance for items noted as Verified Attribute are also subject to any conditions noted in the tables. 5.0 BASIS OF EVALUATION The information in this report, including the Verified Attribute, is based upon the following supporting documentation: 5.1 ICC-ES EC102. [Evaluation applies to IgCC Section 505.2.4; CALGreen Section A4.405.4 and A5.405.2; ICC 700 Section 606.1(2); ANSI/GBI 01-2010 Section 10.2.1.1; ASHRAE 189.1 Section 9.4.1.3.] 5.2 ICC-ES EG104. [Evaluation applies to IgCC Section 505.2.5; CALGreen Section A5.405.1; ICC 700 Section 608.1; LEED Homes MR2.2(c); LEED NC MR 5; LEED Schools MR 5; LEED C&S MR 5; LEED CI MR5; LEED EB MR 3; ANSI/GBI 01-2010 Section 10.1.4.1; ASHRAE 189.1 Section 9.4.1.2; CSI GreenFormat 3.2.1.] 5.3 ICC-ES EC108. [Evaluation applies to IgCC Section 806.1; ICC 700 Section 901.4(6); LEED NC Credit EQ 4.4; LEED Schools EQ 4.4; LEED C&S EQ 4.4; LEED CI EQ 4.4; LEED EB Credit MR3; ASHRAE 189.1 Section 8.4.2.4; CSI GreenFormat 2.3.6.] 5.4 ICC-ES EC109. [Evaluation applies to ICC 700 Section 606.2(2); ANSI/GBI 01-2010 Section 10.3.2.1; ASHRAE 189.1 Section 9.4.1.3.1.] 5.5 Documentation demonstrating conformance with HUD PATH and DOE recommendations for advanced framing techniques, as summarized in Table 12 of this report. Note that the TJ Shear Brace may be eligible when used to achieve a target reduction of 50 percent or more in square footage of wall bracing constructed on site. [Evaluation applies to ICC 700 Section 601.2; LEED Homes MR 1.4; CALGreen Section A5.404.1.] 5.6 Software output of the Javelin software with detailed framing or structural plans, material quantity lists and on-site cut lists for framing, structural materials, and sheathing materials, to assist with waste minimization. [Evaluation applies to ICC 700 Section 601.4; LEED Homes MR 1.2, 1.3 & 1.5, CALGreen Section A4.404.1] 5.7 Software output of the NextPhase Site Solutions software with detailed framing or structural plans, material quantity lists and precut framing packages to assist in waste minimization. [Evaluation applies to ICC 700 Section 601.5(1); LEED Homes MR 1.2, 1.3 & 1.5, CALGreen A4.404.1.]
3.0 DESCRIPTION Weyerhaeuser and Trus Joist structural wood products are manufactured from various wood species bonded with structural adhesives (where applicable) complying with applicable ICC-ES reports as indicated in Table 1. Javelin software ) specifies optimized combinations of residential engineered wood products and dimension lumber in layouts for floor, wall, and roof systems with detailed framing plan and material list outputs. NextPhase Site Solutions combine products, integrated design and fabrication software, fabrication equipment, support and training to enable precut or panelized framing packages to be delivered directly to a jobsite. 4.0 CONDITIONS 4.1 Code Compliance:
The Weyerhaeuser and Trus Joist structural products that have been evaluated for compliance with or otherwise deemed to comply with, the requirements of the International Building Code (IBC) and/or International Residential Code (IRC) are listed in Table 1 of this report.
The evaluation of the Javelin software and NextPhase Site Solutions building optimization solutions for compliance with the requirements of the IBC and/or IRC is outside the scope of this evaluation report. Compliance with all applicable code requirements must be demonstrated to the Authority Having Jurisdiction (AHJ). 4.2 Green Codes, Standards and Rating Systems Eligibility: The information presented in Tables 2 through 13 of this report provides a matrix of areas of evaluation and corresponding limitations and/or additional project-specific requirements, and offer benefit to individuals who are assessing eligibility for credits or points. The information on Life Cycle Assessment (LCA) is limited to the boundary conditions, the Life Cycle Inventory
VAR-1008 | Most Widely Accepted and Trusted 5.8 Evidence of compliance with AWPA Standard T1-09, Table 3. [Evaluation applies to ICC 700 Section 602.8.] 5.9 Documentation establishing and documenting all major sources of primary manufacturing energy. [Evaluation applies to ICC 700 Section 606.3.] 5.10 Consortium for Research on Renewable Industrial Materials (CORRIM) Phase 1 report (available at http://www.corrim.org/reports/2006/final_phase_1/ind ex.htm), containing an LCA analysis performed in accordance with ISO 14044. [Evaluation applies to ICC 700 Section 609.1; CALGreen Section A5.409.1; ASHRAE 189.1 Section 9.5.1.]
Page 3 of 12 5.11 Documentation establishing that the environmental management system conforms to the requirements of ISO 14001 or equivalent. [Evaluation applies to ICC 700 Section 610.1.] 6.0 IDENTIFICATION Weyerhaeuser and Trus Joist structural wood products are identified with a stamp noting the name or logo of the manufacturer (Weyerhaeuser), the plant number, the product trade name and the ICC-ES evaluation report number (if applicable), and the name or logo of the inspection or grading agency. The report subjects are also identified on the product and/or packaging with the VAR Environmental Report number (VAR-1008) and the ICC-ES SAVE Mark, as applicable.
TABLE 1REFERENCE STANDARD OR EVALUATION REPORT NUMBER FOR WEYERHAEUSER AND TRUS JOIST STRUCTURAL WOOD PRODUCTS PRODUCT TJI Joist TimberStrand LSL Parallam PSL Microllam LVL TJ Shear Brace StrandGuard TimberStrand LSL Framer Series Lumber Pro Series Lumber Weyerhaeuser Lumber Weyerhaeuser Green Stud Weyerhaeuser Edge panels Weyerhaeuser Edge Gold Weyerhaeuser RBS Weyerhaeuser Sheathing Weyerhaeuser Plywood
REPORT NUMBER/ REFERENCE STANDARD ESR-1153 ESR-1387 ESR-1387 ESR-1387 ESR-2652 ESR-1387 USDOC PS20 USDOC PS20 USDOC PS20 USDOC PS20 USDOC PS2 USDOC PS2 USDOC PS2 USDOC PS2 USDOC PS1
Page 4 of 12
TABLES 2 THROUGH 13
Strandguard TimberStrand LSL Parallam Plus PSL Edge Edge Gold Radiant Barrier Sheathing Sheathing Plywood NextPhase Site Solutions
TABLE 2SUMMARY OF AREAS OF ELIGIBILITY WITH THE 2012 INTERNATIONAL GREEN CONSTRUCTION CODE (IgCC)
505.2.4 Bio-based materials N/A Wood and wood products used to comply with this section, other than salvaged or reused wood products, shall be labeled in accordance with the SFI Standard, FSC STD-40-004 V2-1 EN, PEFC Council Technical Document or equivalent fiber procurement system. Products shall be recovered, harvested, extracted and manufactured within a 500 mile (800 km) radius of the building site. Where only a portion of a material or product is recovered, harvested, extracted and manufactured within 500 miles (800 km), only that portion shall be included. Where resources are transported by water or rail, the distance to the building site shall be determined by multiplying the distance that the resources are transported by water or rail by 0.25, and adding that number to the distance transported by means other than water or rail. Use regional distance calculator at www.woodbywy.com2 Weyerhaeuser structural plywood and structural panel products comply with US DOC PS-1 and US DOC PS-2, respectively (see Table 1 of this report) and are exempt from formaldehyde emissions testing. Weyerhaeuser I-joists comply with ASTM D5055 (see Table 1 of this report) and are exempt from formaldehyde emissions testing. Weyerhaeuser LSL, PSL and LVL products comply with ASTM D5456 (see Table 1 of this report) and are exempt from formaldehyde emissions testing.
10
10
10
10
10
505.2.5
Indigenous materials
N/A
N/A
806.1
Formaldehyde emissions
N/A
N/A
TABLE 3SUMMARY OF AREAS OF ELIGIBILITY WITH 2010 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN)
4.504.5, 5.504.4.5 4.505 A4.205.1 A4.404.1 Composite wood product emissions Moisture content of building materials Radiant roof barriers Proper beam, header and trimmer design Products containing fewer materials are used to achieve the same end-use requirements as conventional products Detailed cut list and material order Renewable sources Mandatory Mandatory Elective Elective EWP and lumber products do not apply to the composite wood product definition6 Moisture content of lumber may be measured with an appropriate handheld moisture meter7 Radiant barrier sheathing has been tested in accordance with ASTM C1371 Beams and headers and trimmers are the minimum size to adequately support the load Use premanufactured building systems as a substitute for solid lumber Material lists are included in the plans which specify material quantity and provide direction for on-site cuts. Materials from renewable sources (such as engineered wood and solid wood products) Advanced framing methods shall not conflict with structural framing methods or fire-rated assemblies required by the California Building Code. (See Table 14)
A4.404.3
Elective
Elective Elective
Elective
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
Page 5 of 12
TABLE 3SUMMARY OF AREAS OF ELIGIBILITY WITH 2010 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN) (Continued)
A5.405.1 Regional materials Elective Verify local products that are extracted, processed and manufactured within California or 500 miles (805 km) of the job site. Use regional distance calculator at www.woodbywy.com2 All Weyerhaeuser and Trus Joist wood products are qualified as biobased Under review by California Building Standards Commision
5
N/A
N/A
N/A
N/A
N/A
N/A
A5.405.2
Bio-based materials
Select materials or assemblies based on an LCA done in accordance with ISO 14044, such as that contained in the CORRIM report at www.corrim.org
TABLE 4SUMMARY OF AREAS OF ELIGIBILITY WITH THE NATIONAL GREEN BUILDING STANDARD (ICC 7002008)
601.2 Building-code-compliant structural systems or advanced framing techniques are implemented that optimize material usage Detailed framing or structural plans, material quantity lists and on-site cut lists for framing, structural materials, and sheathing materials are provided Precut or preassembled components, or panelized or precast assemblies are utilized for a minimum of 90 percent of the floor system Termite-resistant materials are used Two types of biobased materials are used, each for more than 1 percent of the projects projected building material cost Two certified wood-based products are used for major elements of the building, such as all walls, floors or roof Materials are used for major components of the building that are manufactured using a minimum of 33 percent of the primary manufacturing process energy derived from renewable sources, combustible waste sources, or renewable energy credits Products containing fewer materials are used to achieve the same end-use requirements as conventional products = Eligible for points = Verified attribute = This provision does not apply to this product/service Note: Footnotes are located after Table 13. 3 each 9 max To earn 3 points the framing methods listed in Table 14 must be used for floor, wall or roof framing. To earn 9 points they must be used for all floor, wall and roof framing
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
601.4
601.5(1)
To earn 4 points the precut package must be used for 90% or more of the floor system To earn 6 points all structural elements must be termite resistant in areas of heavy termite infestation. 2 or 4 points are available for areas with lower infestation probability To earn 6 points products must be at least 1% of the construction material cost AND another bio-based product at 1% of material cost must be used. 1 or 3 points are available for greater than 0.5% To earn 4 points a second certified wood product must also be used as a major element1
602.8
10
606.1(2)
10
10
10
10
10
606.2(2)
606.3
2 each 6 max
To earn 6 points the products must be used for at least 3 major components of the building. 2 points may be earned when used for each major component
607.1
3 each 9 max
To earn 3 points at least 80% of framing products used in the building are Weyerhaeuser or Trus Joist products
Page 6 of 12
TABLE 4 (Continued)
608.1 Indigenous materials 2 each 10 max To earn 2 points verify local products that are originated, produced, grow naturally or occur naturally within 500 miles (805 km) of the job site. This can be done by use of the regional distance calculator at www.woodbywy.com2
609.1
A more environmentally preferable product or assembly is selected for an application based upon the use of a Life Cycle Assessment (LCA) tool complying with ISO 14044 or other recognized standards that compare the environmental impact of building materials, assemblies, or the whole building Product manufacturers operations and business practices include environmental management system concepts, and the production facility is ISO 14001 certified or equivalent Structural plywood used for floor, wall, and/or roof sheathing complies with DOC PS 1 and/or DOC PS 2. OSB used for floor, wall, and/or roof sheathing complies with DOC PS 2. The panels are made with moisture-resistant adhesives and the trademark indicates the adhesives are Exposure 1 or Exterior (plywood) and Exposure 1 (OSB) Non-emitting products, which can include structural wood framing
3 each 15 max
To gain 15 points an ISO 14044-complaint LCA must be done on a whole building basis, such as that contained in the CORRIM report at www.corrim.org. 3 points may be earned where comparative LCA is done for individual products or systems
610.1
1 per % 10 max
1 point may be earned for each building products used that equals 1 percent or more of the estimated total building materials cost. Material cost breakdown to be verified and points adjusted to reflect actual percentage of all products from ISO 14001 facilities
Mandatory
901.4(1)
To meet this a minimum of 85% of OSB or plywood in the building must consist of Weyerhaeuser or Trus Joist products
901.4(6)
A minimum of 85% of product in the building are the identified Weyerhaeuser or Trus Joist products To earn 4 points the moisture content of lumber must be determined to not exceed 19%, such as measuring with a moisture meter, prior to enclosure7
The moisture content of lumber is sampled to ensure 903.4.1(3) it does not exceed 19 percent prior to the surface and/or wall cavity exposure = Eligible for points = Verified attribute = This provision does not apply to this product/service Note: Footnotes are located after Table 13.
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
Page 7 of 12
TABLE 5SUMMARY OF AREAS OF ELIGIBILITY WITH USGBC'S LEED FOR HOMES 2008
MR 1.2 MR 1.3 MR 1.4 MR 1.5 MR 2.1 Detailed framing documents Detailed cut list and lumber order Framing efficiencies Off-site fabrication FSC certified tropical wood 1 1 3 max 4 0.5 each 8 max Visually verify detailed framing plans and/or scopes of work To earn 1 point verify that detailed framing cut list and lumber order are used To earn 1 point verify that advanced framing measures in Table 12 are used for floors, walls OR roof framing To earn 4 points use off-site panelized or modular, prefabricated construction3 To earn 0.5 point per component use FSC-certified tropical wood4 To earn points use products that are extracted, processed and manufactured within 500 miles (805 km) of the site for a minimum of 90% (by weight or volume of the component. Source distance can be done by use of the regional distance calculator at www.woodbywy.com2
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
MR 2.2(c)
Environmentally preferable products for roof, wall and floors; interior and exterior framing and sheathing
TABLE 6SUMMARY OF AREAS OF ELIGIBILITY WITH USGBC'S LEED 2009 FOR NEW CONSTRUCTION AND MAJOR RENOVATIONS
MR 5 (MR 5.1) MR 5 (MR 5.2) MR 7 EQ 4.4 Regional materials (10% of content) Regional materials (20% of content) Certified wood Low emitting materials 1 2 1 1 To earn 1 point use products that are extracted, processed and manufactured within 500 miles (805 km) of the site for a minimum of 10% (by cost) of total materials value. To earn 2 points use a minimum of 20%. Source distance can be done by use of the regional distance calculator at www.woodbywy.com2 To earn 1 point use a minimum 50% (based on cost) of wood-based materials/products certified to FSC requirements4 To earn 1 point use wood composite wood products containing no-added urea-formaldehyde resins
TABLE 7SUMMARY OF AREAS OF ELIGIBILITY WITH USGBC'S LEED 2009 FOR SCHOOLS NEW CONSTRUCTION AND MAJOR RENOVATIONS
MR 5 (MR 5.1) MR 5 (MR 5.2) MR 7 Regional materials (10% of content) Regional materials (20% of content) Certified wood 1 2 1 To earn 1 point use products that are extracted, processed and manufactured within 500 miles (805 km) of the site for a minimum of 10% (by cost) of total materials value. To earn 2 points use a minimum of 20%. Source distance can be done by use of the regional distance calculator at www.woodbywy.com2 To earn 1 point use a minimum 50% (based on cost) of wood-based materials/products certified to FSC requirements
4
EQ 4.4
Based on the LEED for Schools PIECAP, it is permissible to substitute LEED 2009 for New Construction EQ 4 Low-Emitting Materials credits in place of corresponding LEED 2009 for Schools EQ 4 Low-Emitting Materials credits.
= Eligible for points = Verified attribute = This provision does not apply to this product/service
Page 8 of 12
TABLE 8SUMMARY OF AREAS OF ELIGIBILITY WITH USGBC'S LEED 2009 FOR CORE AND SHELL DEVELOPMENT
MR 5 (MR 5.1) MR 5 (MR 5.2) MR 7 EQ 4.4 Regional materials (10% of content) Regional materials (20% of content) Certified wood Low emitting materials 1 2 1 1 To earn 1 point use products that are extracted, processed and manufactured within 500 miles (805 km) of the site for a minimum of 10% (by cost) of total materials value. To earn 2 points use a minimum of 20%. Source distance can be done by use of the regional distance calculator at www.woodbywy.com2 To earn 1 point use a minimum 50% (based on cost) of wood-based materials/products certified to FSC requirements4 To earn 1 point use wood composite wood products containing no-added urea-formaldehyde resins
TABLE 9SUMMARY OF AREAS OF ELIGIBILITY WITH USGBC'S LEED 2009 FOR COMMERCIAL INTERIORS
MR 5 Regional materials (20% of content) (Option 1) MR 5 Regional materials (Meet Option 1 + 10% of content) (Option 2) MR 7 Certified wood 1 2 To earn 1 point use products that are extracted, processed and manufactured within 500 miles (805 km) of the site for a minimum of 20% (by cost) of total materials value, including furniture. To earn 2 points use a minimum of 20% + 10%. Source distance can be done by use of the regional distance calculator at www.woodbywy.com To earn 1 point use a minimum 50% (based on cost) of wood-based materials/products certified to FSC requirements4. Furniture material value is also included in determination of certified wood content To earn 1 point use wood composite wood products containing no-added urea-formaldehyde resins
EQ 4.4
TABLE 10SUMMARY OF AREAS OF ELIGIBILITY WITH USGBC'S LEED FOR EXISTING BUILDINGS 2008
Maintain a sustainable purchasing program where the purchase of products contain a minimum of 50% materials (by cost) are extracted, processed and manufactured within 500 miles (805 km) of the site. Source distance can be done by use of the regional distance calculator at www.woodbywy.com2 1 Certified wood Maintain a sustainable purchasing program where the purchase of products contain a minimum 50% (by cost) of wood-based materials/products certified to FSC requirements4 Maintain a sustainable purchasing program where the purchase of wood composite wood products are those that contain no-added ureaformaldehyde resins
Regional materials
MR 3
= Eligible for points = Verified attribute = This provision does not apply to this product/service
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
Page 9 of 12
TABLE 11SUMMARY OF AREAS OF ELIGIBILITY WITH ANSI/GBI 01-2010GREEN BUILDING ASSESSMENT PROTOCOL FOR COMMERCIAL BUILDINGS
10.1.1.1 10.1.2.2 Life cycle impact - building assemblies Biobased Products - building assemblies 33 max 7 max Use Green Globes LCA Credit Calculator All Weyerhaeuser and Trus Joist wood products are qualified as biobased To earn credits use products that are extracted, processed and manufactured within 500 miles (805 km) of the site for a minimum of 90% (by weight or volume of the component). Source distance can be done by use of the regional distance calculator at www.woodbywy.com2 Between 10% and 60% or more of wood-based products used in the building are third party certified
10+A12
10
10
10
10
10
10.1.4.1
5 max
10.3.2.1
Certified wood
9.4.1.2
Regional materials
9.4.1.3
Biobased products
9.4.1.3.1
Prescriptive option
10
10
10
10
10
10
9.5.1
Life cycle assessment = Eligible for points = Verified attribute = This provision does not apply to this product/service
Performance Select materials or assemblies based on an LCA done in accordance with option ISO 14044, such as that contained in the CORRIM report at www.corrim.org
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
Page 10 of 12
3.3
Manufacturing = Eligible for points = Verified attribute = This provision does not apply to this product/service
N/A
Certification is required of the manufacturer only. Vendor Chain of Custody is not required to qualify for this point. 2 Distance calculator provides distance from source to mill and mill to site in a straight line.
3 Applicable only when a third-party prefabricates the framing package prior to arrival on the site. NextPhase Solutions allows for either prefabrication off-site or assembly on-site using materials labeled and cut to precision-end-trim dimensions offsite. 4 Forest certification credit currently resources FSC exclusively. Credit of other certification schemes is at the discretion of the verifier. 5 CGBSC recognizes importance of use of certified forest products however the specific requirements are currently under development. 6 This area is not be confused with the provisions of EQ 4.4 in LEED (Tables 4, 5, 6, 7, and 8) because the California Air Resources Board (CARB) does not regulate engineered wood product emissions and are exempt in ASHRAE 189.1.
Note that PS-20 lumber products with a moisture content >19% are shipped wet with fungicide protection. Engineered wood products and sheathing are shipped dry with MC < 10%. Per Section 5.5 of this report, TJ Shear Brace may be eligible when used to achieve a target reduction of 50 percent or more in square footage of wall bracing constructed on site. 9 Additional listees have not been evaluated for renewable energy or ISO 14001 EMS systems 10 Weyerhaeuser, Murphy and Pacific WoodTech locations are certified to either SFI certified sourcing or SFI chain of custody. RedBuilt and Anthony-Domtar locations are certified to FSC chain of custody. TJI joists or Microllam LVL from RedBuilt and Anthony-Domtar are not labeled as SFI certified, but these locations source materials following FSC procurement policies. N/A = Not applicable
8
Javelin Software
TJ Shear Brace
Section #
Section Intent
Possible Points
TJI Joist
Page 11 of 12
PERFORMANCE-BASED COMPLIANCE CRITERIA Optimized design per Wood Frame Construction Manual Optimized design per National Design Specification for Wood Construction Precut framing packages For SI: 1 inch = 25.4 mm.
1
represents that the criteria is deemed to comply when conditions are met.
In ICC-700 Section 601.2, 3 points may be gained for each advanced framing technique that exceeds 80% usage in the building up to 9 points maximum. See references in 601.2 commentary for additional details on prescriptive-based compliance criteria. 3 In LEED for Homes Section MR 1.4, Table 23, alternative measures to Table 23 are eligible for points if they save comparable amounts of framing material. 4 Other framing techniques as permitted by the U.S. Department of Energys Office of Building Technology, State and Community Programs, subject to approval by the AHJ.
VAR-1008 | Most Widely Accepted and Trusted Appendix A Discussion Related to Life-Cycle Assessment A1.0 GENERAL
Page 12 of 12
The following information is intended to provide some general background on LCA provisions in existing rating systems and standards. Users are advised that the science of LCA is still evolving and there are no standardized procedures for such an analysis. It must be noted that Section 609.1 of ICC 700, Section A5.409.1 of the California Green Building Standards Code (CALGreen), Section 9.5.1 of ASHRAE 189.1, and Section 10.1.1 of Green Globes encourage the use of comparative LCA as means of selecting preferable materials, systems or building assemblies. However, LCA results should not be interpreted beyond the scope of the boundary limits used in performing the LCA. This VAR indicates that iLevel and Weyerhaeuser products may be eligible for points related to LCA by use of the information contained in the documentation noted in Section 5.10 of this report. This appendix discusses additional information required by the user of this report related to achieving points or demonstrating compliance based on LCA output. A2.0 DISCUSSION RELATED TO ICC 700 As indicated in the ICC 700 Commentary, points can be obtained based on the results of an analysis based on an LCA. For the purpose of compliance with the intent of ICC 700, the following steps (as a minimum) are recommended: Fully define the benchmark material, product, assembly, or structure Fully define the product or assembly proposed as more environmentally friendly Fully define the endpoints or boundaries of the analysis (so-called cradle-to-gate, cradle-to-grave, cradle-to-cradle, gateto-gate, etc). For analyses that go beyond cradle-to-gate, a separate report is recommended for each application or use category. Such reports are also recommended to include a discussion of the sensitivity of the analysis to major assumptions for major parameters. Employ an LCA method complying with ISO 14044. Report all applicable attributes of the benchmark analysis and the proposed product/assembly analysis that are relevant to the LCA. The involvement of an individual with experience in the field of LCA and who is knowledgeable in the latest research and standards related to LCA, from the earliest planning stages through completion of the final assessment, is recommended. An independent peer review of the entire LCA methodology and its conclusions by an individual knowledgeable in LCA is recommended. Examples of an LCA that meets these requirements can be found in the series of CORRIM reports (www.corrim.org) that address a broad range of wood-based building materials. A3.0 DISCUSSION RELATED TO CALGREEN AND ASHRAE 189.1 Similar to the requirements of ICC 700, Section A5.409.1 of the CALGreen and Section 9.5.1 of ASHRAE 189.1 allows the use of selected materials or assemblies based on LCA done in accordance with ISO 14044. A4.0 DISCUSSION RELATED TO ANSI/GBI 01-2010 Although life-cycle assessment in its broad sense is too complex for standardization at this time, the use of a specific tool (e.g., Green Globes LCA Credit Calculator) in strict accordance with the rating system intent of comparative analysis of specific components of the building is reasonable. However, users are advised to consult with persons familiar with LCA tools when conducting this analysis. Additional guidance regarding the Green Globes LCA Credit Calculator is provided in Appendix N of the Green Globes document.