Exaopc GS36J02A10-01E PDF
Exaopc GS36J02A10-01E PDF
General Specications
GS 36J02A10-01E
GENERAL
As data sharing between information systems increases, the requirement to efciently access and use plant information to meet business needs in a timely manner also increases. Within the process industry, the control room contains valuable information that has previously been inaccessible. Exaopc was created to provide an open OPC (Open Product Connectivity) interface bridge between the control room and the outside world. Exaopc is an OPC server running on a Microsoft Windows platform which can be connected to a variety of PCSs (Process Control Systems) providing OPC clients with process data and alarm events. This GS contains the specication for the Exaopc OPC Server Interface Package.
FUNCTIONAL SPECIFICATIONS
Data Access (DA) Server Function
The DA Server reads and writes process data using item IDs as identiers.
GENERAL CONFIGURATION
OPC Client Exaopc <Server Common> Exaopc DA Server Exaopc DA Server Common Exaopc HDA Server Historical Database Exaopc A&E Server Exaopc A&E Server Common Exaopc Batch Server Exaopc Batch Server Common
PCS OPC Interface Event Process Data Batch Data/Batch Information Engineering Data PCS: Process Control System
F01E.ai
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-6375 Fax.: 81-422-52-5994
GS 36J02A10-01E Copyright June 1999 (YK) 31st Edition Nov. 30, 2012 (YK)
<<Contents>> <<Index>>
FEATURES
Major Applications
The Exaopc OPC Interface can be used in a wide variety of OPC client applications. - Yokogawa packages, including Exaquantum PIMS and Exapilot (Operation Efciency Improvement Package) - OPC standard compliant general-purpose applications - User applications created using VB or VC++
Trafc Control
When an OPC client attempts to access a large volume of data from a CENTUM CS system loading problems may occur (load concentration on control stations and control buses, in particular). To prevent problems, access from OPC clients are restricted to avoid the maximum accessible data rate being exceeded.
Exaopc supports Compliance Test Tool (CTT) [CENTUM VP/CS 3000/CS 1000]
Exaopc supports Compliance Test Tool (CTT) provided by the OPC Foundation. (Custom Interface for DA3.0, DA2.05a, A&E1.10, or HDA1.20)
Note: On CTT Compliance mode, some functions of Exaopc R3.21 or earlier version may not operate. If OPC client is Exaquantum, Exapilot, Exasmoc, or Exarqe, the conventional mode should be used. When use DA3.0, the CTT Compliance mode should be used.
Automatic Backup
The process data acquired by the DA server is automatically saved and stored in the historical database as backup data. Access to the stored data is enabled by the HDA server function.
IT Security support
A user can select suitable security level out from standard and legacy types. This IT security level is common through Yokogawa system products, and Exaopc is able to have the same IT security as CENTUM system.
<<Contents>> <<Index>>
3
Connection Method Vnet/IP or V net (*1) V net V net V net VL net
CONNECTED SYSTEMS
System CENTUM VP (Including Entry Class) R5.01 or later CENTUM VP (Including Entry Class) R4 CENTUM CS 3000 CENTUM CS CENTUM CS 1000 *1: Vnet/IP is supported on Exaopc R3.70 or later.
SYSTEM CONFIGURATION
Server/Client Composition
The following two client/server congurations can be used: - The OPC client exists on a PC with Exaopc installed. - The OPC client exists on a supervisory computer (Windows PC).
Multiple Clients
A single Exaopc can be accessed from multiple OPC clients.
Multiple Servers
Users can access multiple Exaopcs from a single OPC client.
OPC Server Redundancy Function (Redundant DA, Redundant A&E, Redundant HDA)
Ethernet OPC Server 1 Exaopc (DA, A&E, HDA) Redundant Ethernet OPC Server 2 Exaopc (DA, A&E, HDA) Control Network
Master
Standby
CENTUM
F04E.ai
*1:
<<Contents>> <<Index>>
<<Contents>> <<Index>>
APPLICATION CAPACITY
OPC Server function Item A number of clients (A number of server objects) A number of groups (A number of group objects) DA Server A number of Item IDs Cache update period (Data gathering period) Max. throughput of data access (*1) A number of clients (A number of server objects) Max. number of event-registered objects (Max. number of event subscription objects) A number of clients (A number of server objects) A number of browser (A number of browser objects) A number of item IDs Max. historical data save period (*4) A number of clients (A number of server objects) A number of groups (A number of group objects) A number of item IDs *1: *2: *3: *4: *5: Application capacity 100 clients 1000 groups 10000 item IDs/group 100000 item IDs/all groups 1 to 3600 sec 2000 item IDs/sec or 4000 item IDs/sec (*5) 100 clients 1000 objects 100 clients 100 browser/server object 10000 browser/all server objects 100000 item IDs/server object Not restricted (Depends on disk capacity, its area is dened with a Record parameter) 100 clients 1000 groups 10000 item IDs/group 100000 item IDs/all groups
Batch Server
It depends on the conditions of the project and the application. On Exaopc, process alarms are treated as condition events. A table is provided to manage process alarm occurrence, ACK and recovery events. In case of overow on the table due to numerous process alarms, the OPC client will receive the process alarm occurrence events only. DCS will receive a system alarm to notify the overow situation on the table. If the data requests for a HDA are more than 20000 ItemIDs (2880 default recodes per each ItemIDs), the response may take a long time. It may be necessary to use one or more Exaopc. (Example: the phenomenon may occur when using the catch up function of Exaquantum.) The PC performance may be inuenced when the number of records increases from the default value. In order to achieve 4000 item ID/sec throughput, all of the following conditions must be met. - The system uses CENTUM VP R5.01 or later and Exaopc R3.70 or later. - All the FCS in the domain must be congured only with FFCS-V (models: AFV30/AFV40). Even if a UGS is deployed in the conguration, throughput ratio of 4000 item-ID/second can be realized. [Supplement] In case any one or more of SCS, AVR10D, SIOS, or GSGW are included in the conguration, the throughput ratio becomes 2000 item-ID/second. In case there are multiple domains in a CENTUM project, all the domains must meet the environmental conditions of CENTUM station deployment as described above to fulll 4000 item-ID/second. (If in case any of the domains in the project does not fulll the above mentioned conditions, the throughput ratio becomes 2000 item-ID/second for all the domains.) UGS : Unied Gateway Station SCS : Safety Control Station AVR10D : Duplexed Vnet Router SIOS : System Integration OPC Station GSGW : Generic Subsystem Gateway
<<Contents>> <<Index>>
OPERATING ENVIRONMENT
Hardware
Machine: IBM PC/AT Compatible (DOS/V)
OS (As for detail, refer to the Software Operating Environment.) Specication Item Required CPU Main memory Disk capacity Drive *1: Recommended Required Required Recommended Required Windows Vista, Windows Server 2008 (32bit) Pentium 4 2.84 GHz or faster Core 2 Duo 2.66 GHz or faster 2 GB or more (*1) 10 GB or more 40 GB or more DVD-ROM Drive 40 GB or more Windows 7 (64bit) Core 2 Duo 2.13 GHz or faster Xeon Dual Core 2.0 GHz or faster Windows Server 2008 R2 (64bit) Xeon Dual Core 2.93 GHz or faster
1 GB of main memory is supported for revision up from R3.60 or earlier versions of Exaopc.
Specication Item
Communication device:
System OPC clients (Including SBP product) CENTUM VP/CS 3000/CS 1000/CENTUM CS CENTUM VP R5.01 or later Compatibility of communication device Ethernet-ready network card VF702/VF701 Control Bus Interface Card VF702/VF701 Control Bus Interface Card, and VI702 Vnet/IP Interface Card
<<Contents>> <<Index>>
Software
The following lists the software requirements for Exaopc and the OPC Client connected to Exaopc according to the Exaopc release numbers.
Exaopc release number R3.01 R3.10, R3.11, R3.20 Windows (Exaopc, OPC Client) Windows 2000 Professional or Windows 2000 Server Windows XP Professional Windows 2000 Professional or Windows 2000 Server Windows XP Professional Windows Server 2003 Standard Edition Windows 2000 Professional or Windows 2000 Server Windows XP Professional Windows Server 2003 Standard Edition Windows Server 2003 R2 Standard Edition Windows Vista Business Edition Windows XP Professional Windows Server 2003 Standard Edition Windows Server 2003 R2 Standard Edition Windows Vista Business Edition Windows XP Professional Windows Server 2003 Standard Edition Windows Server 2003 R2 Standard Edition Windows Server 2008 Standard Edition Windows 7 Professional (64 bit) (*1) Windows Vista Business Edition (32 bit) Windows Server 2008 Standard Edition (32 bit) Windows Server 2008 R2 Standard Edition (64 bit) Service Pack (Exaopc) 4 1, 2 4 1, 2 1 4 2 1, 2 2 1 2, 3 2 2 1, 2 2, 3 2 2 2 1 2 2 1
R3.21
R3.50
R3.60
R3.70, R3.71
Note: Only the latest version of Exaopc is available for sale. Exaopc package and its Windows operating system (OS) must share the same language environment. Exaopc for OPC server redundancy function (Exaopc-RD) is operable on Windows Server 2008/2008 R2. *1: 32-bit OS is supported only for OPC client connected to Exaopc R3.71.
Connecting with CENTUM Systems The table below shows the software connectability between Exaopc revisions and CENTUM VP/CENTUM CS 3000/ CS1000 versions/revisions.
CENTUM CS 1000/CENTUM CS 3000 Exaopc R3.01 R3.10 R3.11 R3.20 R3.21 R3.50 R3.60 R3.70 R3.71 XX: X: NC: *1: *2: *3: *4: *5: *6: R3.01 R3.02 R3.03 XX (*3) XX (*4) XX (*4) XX (*4) XX (*4) XX (*5) XX (*5) XX (*5) XX (*5) R3.04 R3.05 X (*2) XX (*4) XX (*4) XX (*4) XX (*4) XX (*5) XX (*5) XX (*5) XX (*5) R3.06 X (*2) X (*2) XX (*4) XX (*4) XX (*4) XX (*5) XX (*5) XX (*5) XX (*5) R3.07 X (*2) X (*2) X (*2) XX (*4) XX (*4) XX (*5) XX (*5) XX (*5) XX (*5) R3.08 X (*2) X (*2) X (*2) X (*2) XX (*4) XX (*5) XX (*5) XX (*5) XX (*5) R3.09 X (*2) X (*2) X (*2) X (*2) X (*2) X (*2) (*5) XX (*5) XX (*5) XX (*5) R4.01 NC NC NC NC NC XX XX XX XX CENTUM VP (*1) R4.02 NC NC NC NC NC X (*2) XX XX XX R4.03 NC NC NC NC NC X (*2) X (*6) XX XX R5.01 NC NC NC NC NC X (*2) X (*2) (*6) XX XX R5.02 NC NC NC NC NC X (*2) X (*2) (*6) X (*2) XX
Connectable. Exaopcs Expanded Test Functions can be used only with this combination. Connectable but without Exaopcs Expanded Test Functions. Not Connectable CENTUM VP R4.01 or later Some of the CENTUM new functions are not available because the release of these Exaopc was preceded to the CENTUM systems. Install Windows XP SP2 for Exaopc when the Exaopc extended test function is operated on Windows XP environment. Install the latest service packs that each Exaopc release number requires when the Exaopc extended test function works is operated on Windows Server 2003 or Windows XP. User Account setting is required on CENTUM HIS. Install Exaopc R3.60.06 patch version when the Windows user authentication mode is applied for authentication setting.
GS 36J02A10-01E Nov. 30, 2012-00
<<Contents>> <<Index>> Connecting with CENTUM CS The table below shows the software connectability between Exaopc revisions and CENTUM CS revisions.
Exaopc R3.01, R3.10, R3.11, R3.20, R3.21 R3.50, R3.60, R3.70, R3.71 X: -: NC: Connectable Connectable but with limitations Not Connectable CENTUM CS R2.09 R2.10 or later X NC X
Connectability between Exaopc Batch Server and VP Batch/CS Batch 3000/CS Batch 1000 The table below shows the software connectability between Exaopc/Batch revisions and Vp Batch/CS Batch 3000/CS Batch 1000 versions/revisions.
Exaopc/Batch R3.01 R3.10 R3.11 R3.20 R3.21 R3.50 R3.60 R3.70 R3.71 X: -: NC: Note: CENTUM CS Batch 3000/CS Batch 1000 R3.01 R3.02 NC NC NC NC NC NC NC NC NC R3.03 R3.04 X R3.05 X R3.06 R3.07 X R3.08 X X R3.09 X X X R4.01 X X X R4.02 NC NC NC NC NC X X X VP Batch R5.01 R4.03 R5.02 NC NC NC NC NC NC NC NC NC NC NC X X X X X
Connectable Connectable but with limitations Not Connectable Exaopc Batch Server does not support multiple project connection function.
<<Contents>> <<Index>>
Note: When Exaopc resides with other SBP products, all the IT Security models must be identical. Note: Please contact Yokogawa when Exaopc resides with other revisions. *1: *2: Set Exaopc IT Security to Legacy model. Exasmoc/Exarqe patch (Modication module) is required.
Remarks when connecting Exaopc with other SBP products via network
Please consider to set the IT security level of each SBP products as the same level as the security model when it is resided with Exaopc, even when it is connected via network.
Document Browser
Adobe Reader 9.5, 10.1 or later.
Note: It is necessary to install Adobe Reader to read document of Exaopc.
<<Contents>> <<Index>>
10
The Exaopc package provides the OPC client with an interface with the following specications:
- OPC Data Access Custom Interface Specication Version 2.05a/3.0 - OPC Data Access Automation Specication Version 2.0 - OPC Security Custom Interface Specication Version 1.0
A&E Server
- OPC Alarms and Events Version 1.10 (Exaopc R3.10 or later) (*1) - OPC Alarms and Events Automation Specication Version 1.0 (draft) - OPC Security Custom Interface Specication Version 1.0
*1: OPC Alarms and Events Version 1.0 had been supported by Exaopc R3.01.50 or earlier. The specication range of the severity for the SetFilter method is changed from 0 to 1000 (A&E1.0) to 1 to 1000 (A&E1.10). When severity=0 value is set for the SetFilter method to Exaopc A&E1.10 OPC server, an error code will be returned by Exaopc because it is out of range. Be sure to use A&E version compatible with both Exaopc and an OPC client accordingly.
HDA Server
- OPC Historical Data Access Custom Interface Version 1.2 - OPC Historical Data Access Automation Interface Version 1.0 (draft) - OPC Security Custom Interface Specication Version 1.0
Batch Server
- OPC Batch Custom Interface Specication Version 1.0 - OPC Batch Automation Specication Version 1.0 - OPC Security Custom Interface Specication Version 1.0 Visit the web site of OPC Foundation at http://www.opcfoundation.org for OPC interfaces. When OPC client program that accesses Exaopc DA/A&E/HDA Server is congured with the VB application, it is recommended to use the Exaopc Client Library of Yokogawa Solutions Corporation (model: NTPT900) for VB programmer. The Library provides OPC connection functionality with the ActiveX component.
The product is supplied without the manufacturers warranty costs. Users are required to enter into an annual maintenance contract to receive maintenance service from the rst year of the purchase onward. For more details of the maintenance service, please refer to Maintenance Services for Solution-Based Software Package [GS 36J20A10-01E].
<<Contents>> <<Index>>
11
Sufx Codes
Option Codes
Consult with Yokogawa to use this Sufx Code. Exclusively used for Exaquantum/Batch. Exclusively used for Exaquantum or Exapilot. AAASuite (Advanced Alarm Administrator) Alarm Rationalization Assistance Package is included. Description Maintenance Service for Exaopc Annual Contract For CENTUM VP/CENTUM CS 3000 For CENTUM CS 1000 For CENTUM CS For general-purpose system For CENTUM VP/CENTUM CS 3000 (Exaopc/Batch) For CENTUM CS 1000 (Exaopc/Batch) For OPC Server Redundancy (Exaopc-RD) Always 1
Sufx Codes
ORDERING INFORMATION
Specify model and sufx codes.
TRADEMARK
- Exaopc, Exapilot, Exaquantum, Exaplog, Exasmoc and Exarqe are registered trademarks of Yokogawa Electric Corporation. - CENTUM is a registered trademark of Yokogawa Electric Corporation. - Windows, ActiveX, Visual Basic, Visual C++ are registered trademarks of Microsoft Corporation. - Ethernet is a registered trademark of XEROX Corporation. - Pentium, Core 2 Duo and Xeon are registered trademarks of Intel Corporation. - Adobe Reader is either registered trademakrs or trademarks of Adobe Systems Incorporated in the United States and/or other countries. - All other company and product names in this GS are registered trademarks or trademarks of respective companies.