Collector Test Method Under Quasi-Dynamic Conditions According To The European Standard EN 12975-2
Collector Test Method Under Quasi-Dynamic Conditions According To The European Standard EN 12975-2
]
0
15
30
45
60
75
90
i
n
c
i
d
e
n
t
a
n
g
l
e
[
]
time period
steady-state
measurements
time period for quasi-dynamic measurements
0
200
400
600
800
1000
1200
1400
9.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00
hour of the day [h]
g
l
o
b
a
l
i
r
r
a
d
i
a
n
c
e
[
W
/
m
]
0
10
20
30
40
50
60
70
i
n
d
i
c
e
n
t
a
n
g
l
e
[
]
Collector test under quasi-dynamic conditions Fischer
ISES 2001 Solar World Congress 5
4. THE PARAMETER IDENTIFICATION TOOL
The mathematical tool proposed for identification of the collector parameters, is denoted Multiple Linear
Regression or MLR. However, also very good experience have been made using the dynamic parameter
identification. For a detailed mathematical description of the MLR method see (Draper 1981) and (Wiesberg
1985), for the dynamic parameter identification see (Spirkl 1990).
4.1. The standard MLR Method
The standard MLR method is the same mathematical tool as used for the evaluation of data in the steady-state
standard (the least squares method). Linear means, that the model has to be written as a sum of terms where the
parameters has to be a multiplier in front of the terms.
The equations behind the individual terms can therefore still be highly non-linear in spite of the description
linear of the MLR method. In the collector parameter identification phase the collector model for the thermal
power output, as in equation 3, is used. Therefore the derived parameter set will minimise the error in useful
power output and not efficiency, as in steady-state testing. This is an important improvement of the method that is
not so visible. This gives the best accuracy when later using the parameters and preferably also the same collector
model in a simulation tool for prediction of the power and energy output of the collector.
The MLR-method allows for a free selection of data from the test data base, according to any test specification,
before applying the MLR parameter identification. This selection can be made afterwards from measurements
from a few test days. Using common spreadsheet software, e.g. EXCEL and LOTUS, even for an extensive
database, the parameter identification will need only a few seconds of computer time, making MLR very versatile
also for development and research.
4.2. The Extended MLR Method
Since several years, a special MLR method has also been developed for this application based on MLR with
dummy variables (Weisberg 1995). This makes it possible to identify the same parameter in different subsets or
ranges of the database. This offers the possibility to identify for example the zero loss efficiency angle by angle
without the need to have an equation. Even in two axis directions
L
and
t
. K
b
(
i
) in eq. (3) is then generalised
and replaced by K
b
(
L
,
t
).
Both the new and remaining other parameters can still be identified with a standard MLR software in the same
run and at almost the same calculation time. This widens the range of collectors that can be tested accurately with
this method and is especially useful for collectors as ETC (Evacuated Tube Collectors), CPC (Compound
Parabolic Concentrator) or unglazed collectors with round separate absorber tubes. They can not be modelled
accurately with the standard IAM equations. The derived IAM results can often be used directly in simulation
programmes, as in the case of TRNSYS or WATSUN.
4.3. The dynamic parameter identification
Dynamic parameter identification is a method to find the best fit of a given parameterized model to a real system
based on a time sequence of some measurable output. For a given set of forcing functions, e(t) = (e
1
, e
2
, ...), the
modelled output, y
mod
(p,t), is a function of time and a set of parameter values, p = (p
1
, p
2
, ...). The best fit is given
by the set of parameter values, which minimize the objective function c(p), which, in principle, is the integral of
the root mean square of the residual r(p,t) = y
mod
(p,t) - y
exp
(t). However, before calculating c(p), the high
frequency components of the residual may be dampened using a low pass filter with the time constant
F
. The
purpose being to weaken the impact of measurement noise and imperfect transient modelling. Further, a period
[0,t
skip
], long enough to let the influence of the initial state fade away is excluded from the calculation of c(p). In
this way the problem to determine the initial state is bypassed. The minimum of the objective function , c(p), is
searched in an iterative process. The method is attractive because it neither imposes any severe restrictions on the
model nor on the time sequence of measured data, and the model can also used in simulations. The IEA Dynamic
Collector test under quasi-dynamic conditions Fischer
ISES 2001 Solar World Congress 6
System Testing Group has already demonstrated the feasibility of the dynamic parameter identification for tests
of the performance of Solar Domestic Hot Water Systems and hot water stores.
The dynamic parameter identification method is especially useful for the identification of the collector
parameters of collector with a asymmetrical incident angle behaviour as described in section 4.2.
5. COMPARISON OF THE RESULTS GAINED USING THE STEADY-STATE AND
THE QUASI-DYNAMIC TEST METHOD
An essential qualification for an alternative test method is the compatibility of the gained results to the long
established test method. The quasi-dynamic test method is build on a far more detailed collector model than the
steady-state model, taking into account e.g. the incident angle behaviour of the thermal collectors. Due to these
correction terms in equation (3) it is possible to predict the collector output power for any possible environment
conditions, including the strict conditions demanded by the steady-state method.
The results gained by the two test methods can not be compared without the adjustment of the collector
parameters found using the quasi-dynamic test method.
To conform these results with the presentation of the steady-state test the test results are presented in the form of
a efficiency function and an efficiency curve which is calculated from the efficiency function using a global
irradiance G = 800 W/m and a diffuse fraction of 15%. The parameter dt
m
/dt is set to zero and the incident
angle to 15 to adjust to steady-state conditions at around solar noon. If the wind speed dependence of the heat
losses and the zero loss efficiency are used in the collector model for glazed collectors the wind speed u = 3 m/s
is used in the equation. If the sky temperature dependence of the heat loss coefficient is used in the collector
model then (E
L
-T
a
4
) = -100 W/m is used for the calculation. Equation 4 shows the described modification of
equation (3) shown as an efficiency function.
= F( )
en
K
b
(15) 0.85 + F( )
en
K
d
0.15 - c
6
3 1 - c
1
(t
m
-t
a
)
-c
2
(t
m
-t
a
)
- c
3
3 (t
m
-t
a
) - c
4
100/800
- c
5
0 (4)
Table 2 shows the test results of two flat plate collectors tested according the steady-state as well as according to
the quasi-dynamic test method. To achieve the listed collector parameters of the quasi-dynamic test the above
described procedure was applied. The efficiency curves of collector A are shown in Figure 3.
Table 2: Comparison of the test results according the steady-state and the quasi-dynamic test method
collector method
0
[-]
c
1
[W/(mK)]
c
2
[W/(mK)]
yearly energy gain
[kWh/(myear)]
steady-state 0.792 3.578 0.018 491
A
quasi-dynamic 0.794 3.489 0.018 495
steady-state 0.776 3.823 0.012 485
B
quasi-dynamic 0.787 3.749 0.013 484
steady-state 0.762 3.531 0.013 468
C
quasi-dynamic 0.767 3.531 0.012 479
steady-state 0.729 3.289 0.010 454
D
quasi-dynamic 0.736 3.184 0.013 466
steady-state 0.785 3.864 0.010 470
E
quasi-dynamic 0.785 3.794 0.011 478
steady-state 0.765 2.938 0.014 496
F
quasi-dynamic 0.774 3.084 0.013 502
steady-state 0.780 3.010 0.011 500
G
quasi-dynamic 0.785 3.042 0.011 509
steady-state 0.724 3.464 0.008 430
H
quasi-dynamic 0.727 3.179 0.013 456
steady-state 0.761 3.017 0.015 480
I
quasi-dynamic 0.766 3.321 0.012 480
Table 2 shows that the zero heat loss efficiency
0
determined by the steady-state method is always slightly
smaller than the one determined by the quasi-dynamic method. This is due to the fact that the mean incident angle
as well as the diffuse fraction during the test have been greater than the 15 and 15% respectively.
Collector test under quasi-dynamic conditions Fischer
ISES 2001 Solar World Congress 7
The difference in the heat loss coefficients c
1
and c
2
between the two test methods can be neglected. If there is a
significant difference in c
1
(e.g. collector I) it is compensated by the opposite difference in c
2
.
To allow a more detailed comparison of the test results Table 2 shows, apart from the zero heat loss efficiency
0
and the heat loss coefficients c
1
and c
2
, the yearly energy gain of the collector. The yearly energy gain is
predicted by a system simulation according BMWI (1995) using the simulation tool TRNSYS. The system
simulation takes into account all identified collector parameters. This bears the advantage that a comparison of
the thermal performance of different collector type can be done by using only one number: the yearly energy
gain.
The used system is build up of a 300 liter thermal store, 135 liter are kept at a constant temperature of 60C by
the auxiliary heater, and an collector aperture area of 5m. The hot water load (200 l/day) is drawn at a
temperature of 45C and the reference weather data of Wuerzburg (Germany) is used.
The yearly energy gain based on the quasi-dynamic method is up two 2% higher that the one based on the steady-
state method. This is basically due to the missing handling of the diffuse irradiance within the simulation of the
steady-state results. Collector G denotes a difference of 6% in the yearly collector gain due to very pour incident
angle dependence.
Figure 3: Comparison of the efficiency curves gained using the steady-state and the quasi-dynamic test
method
6. CONCLUSIONS
The quasi-dynamic test method offers a much more complete characterisation of the collector and a much wider
range of collectors can be tested within the same method, compared to the steady-state test methods.
At the same time, less restrictions in the test requirements makes it easier to find periods outdoors for testing:
This leads to easier and cheaper tests, especially for places with varying climate conditions like middle and
northern Europe.
These varying climate conditions, thus embedded in the test results, will also better reflect operating conditions
encountered by the collectors in real service. This will improve the accuracy of collector performance predictions
for application areas as design, research and collector development.
With the European Standard EN 12975:2000 there is now a guideline available that allows the test institute all
over Europe to perform the collector test according to their very own weather conditions leading to comparable
results. This is an important step towards the harmonization of the European solar market.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
(t
m
- t
a
)/G [(mK)/W]
e
f
f
i
c
i
e
n
c
y
[
-
]
steady-state
quasi-dynamic
Collector test under quasi-dynamic conditions Fischer
ISES 2001 Solar World Congress 8
7. NOMENCLATURE
b
0
[-] parameter for the characterization of the incident angle modifier of the beam irradiance
c
1
[W/(mK)] heat loss coefficient at (t
m
t
a
) = 0
c
2
[W/(mK)] temperature dependence of the heat loss coefficient
c
3
[J/(mK)] wind speed dependence of the heat loss coefficient
c
4
[W/(mK)] sky temperature dependence of the heat loss coefficient
c
5
[kJ/(mK)] effective thermal capacity
c
6
[s/m] wind speed dependence of the zero heat loss efficiency
dt
m
/dt [K/s] time derivative of the mean fluid temperature
E
L
[W/m] longwave irradiance
F( )
en
[-] zero loss efficiency
G [W/m] global solar irradiance
G
b
[W/m] beam irradiance
G
d
[W/m] diffuse solar irradiance
K
( ) [-] incident angle modifier
K
b
( ) [-] incident angle modifier for beam irradiance
K
d
[-] incident angle modifier for diffuse irradiance
Q [W/m] useful output power
u [m/s] surrounding air speed
[-] efficiency
a
[C] surrounding air temperature
m
[C] mean fluid temperature
[] incident angle of the beam irradiance
[W/(mK
4
)] Stefan-Boltzmann constant
8. REFERENCES
ASHRAE 93-77 (1978), Methods for Testing to Determine The Thermal Performance of Solar Collectors.
BMWI (1995) Richtlinien zur Frderung von Manahmen zur Nutzung erneuerbarer Energien, Juni 1995
CEN (2000) European Standard prEN 12975-2:2000. European Committee for Standardisation.
Draper, N.R. and Smith, H. (1981) Applied Regression Analysis. John Wiley & Sons. New York.
Hellstrm, B. and Perers, B. (1998) Comparison of two standard collector test methods. In Proceedings of
EuroSun98, the Second ISES Europe Solar Congress, 2, III.2.17.1-6.
ISO (1994), ISO 9806-1. Thermal Performance of Glazed Liquid Heating Collectors.
ISO (1995) ISO 9806-3. Thermal Performance of Unglazed Liquid Heating Collectors.
Perers, B. (1993) Dynamic method for solar collector array testing and evaluation with standard database and
simulation programmes. Solar Energy 50, 517-526.
Perers, B. (1995) Optical Modelling of Solar Collectors and Booster Reflectors under Non Stationary
Conditions. Application for Collector Testing, System Simulation and Evaluation. Doctoral Thesis, Uppsala
University, ISBN 91-554-3496-7.
Perers, B. (1997) An improved dynamic solar collector test method for determination of non linear optical and
thermal characteristics with multiple regression. Solar Energy 59, 163-178.
Spirkl, W. (1990) Dynamic solar domestic hot water testing. J. of Solar Energy Eng., Transaction of the ASME,
vol. 112, p.98-101.
Pauschinger, Th. and H. Drck (1995) VELS, Verfahren zur Ermittlung der Leistungsfhigkeit von Solaranlagen,
Phase II, Universitt Stuttgart, Institut fr Thermodynamik und Wrmetechnik, Stuttgart
Weisberg, S. (1985) Applied Linear Regression. John Wiley & Sons. New York.