DATA SHEET
This product is an on/off temperature alarm unit which inputs signals from a thermocouple or thermistor sensor and transmits a relay contact output when an input signal reaches the preset alarm level. This thermostat is most suited for overheat detection in machines, equipments, etc.
PAS3
FEATURES
1. Highly compact Front panel having a DIN size of 24 x 48 mm, as lightweight as 100 g and besides, depth just 85 mm, featuring a space saving design. 2. A variety of temperature sensors connectable Because thermocouples (5 types) and thermistors (0 to 100C) are connectable, measurement within a wide temperature range from low to high can be covered so as to match your equipment. 3. Measured and Alarm Temperatures Displayable Alarm set value and measured temperature value can be checked promptly using the front keys. 4. Alarm point settable in 1C steps Temperature can be set in 1C steps by key operation from the front. 5. Washable front structure The front display and operating section has an IP66 waterproof structure (corresponding to NEMA-4X). This design allows washing from the panel front. 6. 2 relay contact outputs available This thermostat is capable of issuing 2 relay contact outputs. Therefore, any output of high/low limit pair, 2 upper limits and 2 lower limits can be selected.
SPECIFICATIONS
Specification Number of inputs: 1 Input signal and measurable range: Refer to Table 1. Allowable signal source resistance: Thermocouple input 100 max. Measurement cycle: 2 sec. or less Burnout function: Thermocouple input; UUU display Thermistor input: LLL display (Upscale or downscale at burnout settable) Input impedance: Thermocouple input 1 M or higher Input filter: 0 to 90 sec. (settable in 1 sec. steps) Primary lag filter Input value compensation: Settable within 10% of measurable range Indication Indication means: LCD (without back light) Value/parameter indication: 4 digits of 7 segments each (However, at the 1st digit, only - or 1 is indicated within -999 to 1999.) Contents of indication: Measured value, alarm set value 1, alarm set value 2, various parameters Each indicator of alarms 1 and 2, C scale Operation Number of keys: 3 keys, sheet type keys (embossed) Alarm value setting resolution: 1C Key lock function: (Change of setting can be inhibited.) Accuracy Indication accuracy: Refer to Table 1. (However, error of a temperature sensor is not included.) Reference contact compensation error: 3C (at 23C) Alarm Number of outputs: 1 or 2 (as specified in CODE SYMBOLS) output Contact structure: 1a contact Alarm type: Refer to Table 2. Contact capacity: 220 V AC/30 V DC, 2 A (resistance load) 220 AC/30 DC, 1 A (inductive load) Mechanical life of contact: 20 million activations or more (100 activations/min.) Electrical life of contact: 100,000 activations or more (rated load) Output resetting cycle: 2 sec. or less Alarm value settable range: Settable within 0 to 100% of measurable range Hysteresis width settable range: 0 to 110% of measurable range (settable in 1C steps) Alarm action delay time: Settable within 1 to 120 sec. Item Input
Item Power supply Specification Power supply voltage: 100 V (15%) to 240 V (+10%) AC 50/60 Hz (10%) Power consumption: 3 VA max. (with 100 V AC), 6 VA max. (with 240 V AC) Operating Ambient temperature: 0 to 50C conditions Ambient humidity: 90% RH max. (condensation unallowable) Body Mounting method: Panel flush mounting Use of optional DIN rail-mounting adapter allows the instrument to be rail mounted or wall mounted. structure External dimensions (H x W x D): 24 x 48 x 85 mm Weight: Approx. 100 g Casing material: Plastic (corresponding to flame resistance grade UL94V-0) Front protective structure: IP66 (corresponding to NEMA-4X) when using Fujis genuine front waterproof packing part External terminals: Plug-in type (for bar terminals) Finish color: Ivory
Minimum resolution 1C 1C 4C 1C 1C 1C
Indication accuracy 3C 3C 4C 3C 3C 4C
Note 1) Correct indication is not ensured within a range from 0 to 500C for an R type thermocouple. Note 2) Switching between a thermistor and a thermocouple is not allowed. Thermocouple input type can be changed by front key operation.
EDS11-141a
Date Apr. 10, 2002
PAS3
Table 2 Alarm types
With Relay Code of Alarm Set value holding action PA1, 2 direction notation (Note 2) at alarm 0 1 2 3 4 5 6 7 8 No alarm Upper limit Absolute value No No Yes Yes No No Yes Yes Relay excitation Relay excitation Relay excitation Relay excitation Relay nonexcitation Relay nonexcitation Relay nonexcitation Relay nonexcitation Action diagram (Note 1)
CODE SYMBOLS
Input signal Temperature sensor Number of alarm Thermocouple Option 1 2 Thermistor Provided 1 2 Code symbols PAS3K1Y1 PAS3K1A1 PAS3H1Y1 PAS3H1A1
OPTIONAL DEVICE
DIN rail adapter (Model: ZZP*CTK368715P1)
SETTING at DELIVERY
Measurable range Alarm set value K thermocouple input (0 to 1200C) Thermistor input (0 to 100C) K thermocouple input: For 1-point alarm (upper limit 1200C) K thermocouple input: For 2-point alarm (upper limit 1200C, lower limit alarm 0C) Thermistor input: For 1-point alarm (upper limit 100C) Thermistor input: For 2-point alarm (upper limit 100C, lower limit alarm 0C) 1C 0 sec. Measured value Upscale at burnout 5 sec. 0%
(Note 1) How to read action area: A range in which ALM1 or ALM2 is indicated on LCD at the front. area: A range in which alarm relay is excited point: Alarm set value The horizontal axis represents measured values (PV). (Note 2) What is the hold function? Even if the process value is within the alarm range when turning on power, the alarm does not turn on immediately but only after it leaves and then returns to the alarm range.
PV (process value) Period where lower limit alarm is output Power ON Lower limit alarm Lower limit alarm (with hold) Power OFF
on off off off on
Alarm hysteresis width Alarm delay time Indication Burnout Input filter Input value compensation
Note 1) Switching between a thermistor and a thermocouple is not allowed. Note 2) Thermocouple input type can be changed by front key operation.
Power ON
on off off
SCOPE of DELIVERY
Thermostat unit, panel-mounting adapter, front waterproof packing, instruction manual Thermistor sensor added for thermistor input
(1C)
ON
20 MAX.
34.2
24
22
+0.3 0
22.2
50 MIN.
22.2
+0.3 0
This mounting does not meet NEMA-4X/IP66 (front waterproof specification). (Because the packing cannot be used in horizontally close mounting.)
57 MIN.
PV SET1 SET2
45.4
ALM1 ALM2
2-
.3
DIN rail
96.2 92.5
4 M
MFD. No.
36.8
PAS3...
PAS3
CONNECTION DIAGRAM
3
+
5 to 6 mm
Thermocouple input
Alarm output 1
Alarm output 2
Bar terminal Dimension of strip-off conductor section: 2 x 1.5 mm or smaller Length of strip-off conductor section: 5 to 6 mm
1.5MAX. 2MAX. 5 to 6 mm
Thermistor
CONNECTION METHOD
PAS3 Screw driver
Wires
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.