0% found this document useful (2 votes)
324 views

Open and Short Circuit Test On Transformer - Electrical Engineering

The document summarizes open and short circuit tests performed on transformers. The open circuit test is used to determine core losses and the shunt branch parameters of the equivalent circuit by applying voltage to the low voltage side with the high voltage side open. The short circuit test is used to determine copper losses and the approximate equivalent circuit by applying current to the high voltage side with the low voltage side short circuited. Both tests determine losses and parameters needed to analyze the transformer's equivalent circuit and efficiency.

Uploaded by

Rajesh Aggarwal
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (2 votes)
324 views

Open and Short Circuit Test On Transformer - Electrical Engineering

The document summarizes open and short circuit tests performed on transformers. The open circuit test is used to determine core losses and the shunt branch parameters of the equivalent circuit by applying voltage to the low voltage side with the high voltage side open. The short circuit test is used to determine copper losses and the approximate equivalent circuit by applying current to the high voltage side with the low voltage side short circuited. Both tests determine losses and parameters needed to analyze the transformer's equivalent circuit and efficiency.

Uploaded by

Rajesh Aggarwal
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Electrical Engineering

Online Electrical Engineering Study Site


Search

Like

5,742 people like this. Be the first of your friends.

Open and Short Circuit Test on Transformer


Eddy Current Testing
www.ethernde.com The experts in supplying eddy current NDT solutions. Contact us!
Electrical Power Transformer Working Principle of Transformer Ideal Transformer Theory of Transformer EMF Equation of Transformer Leakage Reactance of Transformer Equivalent Circuit of Transformer Voltage Regulation of Transformer Losses in Transformer Open & Short Circuit Test on Transformer Auto Transformer Tertiary Winding of Transformer Parallel operation of Transformers Transformer Cooling System Core of Transformer Transformer Insulating Oil Transformer Accessories Dissolved Gas Analysis of Transformer Oil Over Fluxing in Transformer Three phase transformer Current Transformer Voltage Transformer Accuracy Limit & Instrument Security Factor Knee Point Voltage of Current Transformer Earthing or Grounding Transformer External & Internal Faults in Transformer Backup Protection of Transformer Differential Protection of Transformer Restricted Earth Fault Protection More.........
The connection diagram for open circuit test on transformer is shown in the figure. A voltmeter, wattmeter, and an ammeter are connected in LV side of the transformer as shown. The voltage at rated frequency is applied to that LV side with the help of a variac of variable ratio auto transformer. The HV side of the transformer is kept open. Now with help of variac applied voltage is slowly increase until the voltmeter gives reading equal to the rated voltage of the LV side. After reaching at rated LV side voltage, all three instruments reading (Voltmeter, Ammeter and Wattmeter readings) are recorded. The ammeter reading gives the no load current Ie. As no load current Ie is quite small compared to rated current of the transformer, the voltage drops due to this electric current then can be taken as negligible. Since, voltmeter reading V1 can be considered The input equal to secondary is induced voltage of the transformer. power during test indicated by watt-meter reading. As the transformer is open circuited, there is no output hence the input power here consists of core losses in transformer and copper loss in transformer during no load condition. But as said earlier, the no load current in the transformer is quite small compared to full load current so copper loss due to the small no load current can be These two tests are performed on a transformer to determine (i) equivalent circuit of transformer (ii) voltage regulation of transformer (iii) efficiency of transformer. The power required for these Open Circuit test and Short Circuit test on transformer is equal to the power loss occurring in the transformer.

Open Circuit Test on Transformer

Buchholz Relay in Transformer neglected. Hence the wattmeter reading can be taken as equal to core losses in transformer. Let us consider wattmeter reading is Po.
Po = V1 2/Rm Where Rm is shunt branch resistance of transformer. If, Zm is shunt branch impedance of transformer. Then, Zm = V1/ Ie. Therefore, if shunt branch reactance of transformer is X m Then, (1/ X m)2 = (1/ Zm)2 - (1/ Rm)2

Power Transformer
www.Alibaba.com Find Quality Products from Verified Suppliers. Get a Live Quote Now!
These values are referred to the LV side of transformer as because the test is conduced on LV side of transformer. These values could easily be referred to HV side by multiplying these values with square of transformation ratio. Therefore it is seen that the open circuit test on transformer is used to determine core losses in transformer and parameters of shunt branch of the equivalent circuit of transformer.

Short Circuit Test on Transformer


The connection diagram for short circuit test on transformer is shown in the figure. A voltmeter, wattmeter, and an ammeter are connected in HV side of the transformer as shown. The voltage at rated frequency is applied to that HV side with the help of a variac of variable ratio auto transformer. The LV side of the transformer is short circuited . Now with help of variac applied voltage is slowly increase until the ammeter gives reading equal to the rated current of the HV side. After reaching at rated current of HV side, all three instruments reading (Voltmeter, Ammeter and Watt-meter readings) are recorded. The ammeter reading gives the primary equivalent of full load current IL. As the voltage, applied for full load current in short circuit test on transformer, is quite small compared to rated primary voltage of the transformer, the core losses in transformer can be taken as negligible here. Lets, voltmeter reading is Vsc. The input power during test is indicated by watt-meter reading. As the transformer is short circuited, there is no output hence the input power here consists of copper losses in transformer. Since, the applied voltage Vsc is short circuit voltage in the transformer and hence it is quite small compared to rated voltage so core loss due to the small applied volate can be neglected. Hence the wattmeter reading can be taken as equal to copper losses in transformer. Let us consider wattmeter reading is Psc. Psc = Re.IL2 Where Re is equivalent resistance of transformer. If, Ze is equivalent impedance of transformer. Then, Ze = Vsc/ IL. Therefore, if equivalent reactance of transformer is X e Then, X e2 = Ze2 - Re2 These values are referred to the HV side of transformer as because the test is conduced on HV side of transformer. These values could easily be referred to LV side by dividing these values with square of transformation ratio. Therefore it is seen that the Short Circuit test on transformer is used to determine copper loss in transformer at full load and parameters of approximate equivalent circuit of transformer.

Search

You might also like