Fire Damper 5

The document provides information about fire dampers including their description, construction, dimensions, correct use, installation details, and order details. Fire dampers automatically shut to prevent the spread of fire and smoke through ductwork. They are tested according to standards and require proper approved installation and regular maintenance to function reliably in the event of a fire.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
362 views

Fire Damper 5

The document provides information about fire dampers including their description, construction, dimensions, correct use, installation details, and order details. Fire dampers automatically shut to prevent the spread of fire and smoke through ductwork. They are tested according to standards and require proper approved installation and regular maintenance to function reliably in the event of a fire.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

4/2/EN/9

Fire dampers
Type FK-K90
with general building inspectorate licence Z-41.3-321

The art of handling air

Contents Description
Description __________________________________ 2 Correct use __________________________________ 4 Construction Dimensions ______________________ 6 Attachments For dry mortarless installation in solid walls ________ 8 Cover grille ________________________________12 Circular spigot plate __________________________13 Flexible connectors __________________________14 Extension piece ____________________________15 Accessories Limit switch ________________________________16 Spring return actuator ________________________17 TROXNETCOM ____________________________20 Smoke detectors ____________________________22 Quick selection ______________________________23 Technical selection data Differential pressure __________________________24 Sound power level __________________________25 Free cross sectional area, resistance coefficient and correction values ____________________________26 Installation details In solid walls, ceiling slabs and gypsum wallboards__27 In solid walls with difficult access or multiple fire dampers ________________________28 Directly on the face of solid walls and ceiling slabs __31 Adjacent to solid walls and ceiling slabs __________32 Suspension systems ________________________33 Remote from solid walls ______________________34 In lightweight partition walls ____________________36 In lightweight fire walls ________________________42 Order Details ________________________________44

FK-K90-LD with fusible link Combinations of width and height up to B H = 800 mm 400 mm

FK-K90 with fusible link

Fire dampers shut automatically to prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments. FK-K90 fire dampers are tested according to DIN 4102 and EN 1366-2. Local requirements and building inspectorate approvals are essential. Correct approved installation locations are directly in solid walls, ceiling slabs, gypsum wall boards, lightweight partitions and lightweight fire walls, directly on the face of solid walls and ceiling slabs, adjacent to solid walls and ceiling slabs and remote from solid walls. Installation in vertical or horizontal ducts. Air flow direction is not critical. When installed in walls or ceiling slabs combustible ventilation ducting may be connected directly to the fire damper. In the case of fire, the damper is triggered at 72 C or 95 C (for use in warm air ventilation) either by a fusible link or thermoelectrically with a spring return actuator. The release mechanism is accessible and can be tested from the outside. The fire dampers have two inspection panels. The fire resistance class of fire dampers type FK-K90 is dependent on the application.

Special characteristics
Tested for fire resistance properties according to DIN 4102 and EN 1366-2 Construction (LD) has lower sound power level and differential pressure Equipped with spring return actuator, accessory ZEX1 approved for explosion-hazard areas Easy dry mortarless installation can be achieved with an installation kit Integration into the centralised BMS with TROXNETCOM

General building inspectorate licence: Z-41.3-321


Further, current information in particular licence and operating manual and installation instructions can be found on our website. Our Easy Product Finder design programme is also available on the Internet for the design and selection of our products.

Description

FK-K90-LD with spring return actuator Combinations of width and height up to B H = 800 mm 400 mm

FK-K90 with spring return actuator

FK-K90-LD with blade bead seal


Combinations of width and height up to B H = 800 mm 400 mm Release mechanisms: Fusible link 72 C or 95 C for use in warm air ventilation. Spring return actuator Type BLF or ExMax. Combinations of width and height up to B H = 800 mm 400 mm are supplied as standard construction for type FK-K90-LD.

FK-K90 with landing angles with bead seals


All combinations of width and height, except widths 200 mm and 250 mm which only have a height of up to 500 mm. Release mechanisms: Fusible link 72 C or 95 C for use in warm air ventilation. Spring return actuator Type BLF, BF or ExMax. Combinations of width and height up to B H = 800 mm 400 mm are supplied as standard construction for type FK-K90-LD. Construction in this dimensional range can be supplied with landing angles with bead seals on request.

Correct use
Fire dampers are products that require approval. The general and specific regulations of the general building inspectorate and the operating manual and installation instructions must be complied with. The general guidelines of DIN 31051 and EN 13306 are also applicable. The functional reliability of fire dampers must be tested at least at six-monthly intervals. If two consecutive tests are successful, the next test can be conducted one year later. In general, it is sufficient to close and reopen, fire dampers with spring return actuator, this can be by remote control. Fire dampers must be included in the regular cleaning schedule of the ventilation system.

Design information
The fire resistance class of FK-K90 for the following applications is K90. Installation in solid walls, ceiling slabs and lightweight partition walls with metal support structure and clad both sides and a fire resistance class lower than F90 is approved. In this case the fire damper has the same rating as the structure it is mounted in (e.g. wall F60 then fire damper K60) FK-K90 fire dampers are approved only for use in ventilation systems. Ducts must be connected at both ends or a duct on one end and a cover grille on the other end. Installation of fire dampers must be carried out in compliance with provisions of federal state law and the generally recognised codes of practice. In cases where fire dampers are installed outside Germany it is essential that local requirements and building inspectorate approvals are obtained. Ducting must be installed in such a manner that it does not impose any loads on the fire damper in the case of a fire. Flexible connectors must be used to connect solid ducting to the fire damper for particular applications.

Mounting location

Construction and building material

Minimum thickness in mm

Mortar based installation Casing length in mm L = 375 L = 500

Dry mortarless installation Casing length in mm L = 375 L = 500

Installation details Page

Solid walls and ceilings

Solid walls of concrete, aerated concrete or made of brickwork

100

Solid ceiling slabs of concrete or aerated concrete

125

27 to 30 Wallboards Gypsum wallboards to DIN 18163

100

Directly on the face of solid walls and ceiling slabs

Solid walls of concrete, aerated concrete or made of brickwork

100

31 Solid ceiling slabs of concrete or aerated concrete

125

Adjacent to solid walls and ceiling slabs

Solid walls of concrete, aerated concrete or made of brickwork

100

32 Solid ceiling slabs of concrete or aerated concrete

125

with installation kit

Correct use

Mounting location

Construction and building material

Minimum thickness in mm

Mortar based installation Casing length in mm L = 375 L = 500

Dry mortarless installation Casing length in mm L = 375 L = 500

Installation details Page

Remote from solid walls

In fire-resistant ventilation ducting

34 to 35

Lightweight partition walls with metal support structure and clad on both sides

Lightweight partition walls with mineral wool, to DIN 4102-4, Table 48 or with general appraisal certificate 100 36 to 38

Lightweight partition walls with metal support structure and clad on both sides and with flexible ceiling joint

Lightweight partition walls to DIN 4102-4, Table 48 or with general appraisal certificate

100

39

Lightweight partition walls with metal support structure and clad on one side

Shaft walls

90

40

Lightweight partition walls without metal support structure and clad on one side

Shaft walls

40

41

In lightweight fire walls with metal support structure and clad on both sides

Fire walls with general appraisal certificate

110

42 to 43

with installation kit

Wall thickness = 100 mm

Construction Dimensions
Characteristics
Fire resistance class according to DIN 4102-6, K90 Two casing lengths to allow for wall and ceiling slabs of various thicknesses Air flow in either direction Construction variant with damper bead seal (LD) has lower sound power level and differential pressure for combinations of width and weight up to B H = 800 mm 400 mm Release temperature 72 C or 95 C for use in warm air ventilation Installation orientation for horizontal ducts

Construction features
Rectangular construction, rigid frame Connecting flanges drilled both ends, suitable for duct connection Two inspection panels Width and height in intermediate dimensions are available in increments of 1mm

Release mechanism

FK-K90 with fusible link


311 260
10

35

35

9
35

3
10

4
H

5 1
35

L = 375 or 500

70 y

FK-K90 with spring return actuator


311 260
10

x 94 mm for B < 251 mm 115 mm for all other dimensions y approx. 175 mm for fusible link, or spring return actuator types BLF and BF approx. 220 mm for spring return actuator type ExMax

Keep clear to provide access to release mechanism or spring return actuator 7 1 2 3 4 5 6 7 8 9


10

Casing Damper blade Release mechanism Handle Interlock Fusible link Thermoelectric release mechanism Spring return actuator Inspection panel Travel stop (only LD)

L = 375 or 500

Construction Dimensions
The construction variants with stainless steel or powder-coated casing to meet more critical requirements for corrosion protection. Detailed listing on request.
Construction variant 1 Casing Galvanised Powder-coated Stainless steel Galvanised Galvanised Powder-coated Powder-coated Stainless steel Stainless steel Damper blade Standard Standard Standard Galvanised sheet steel clad Coated Stainless sheet steel clad Coated Stainless sheet steel clad Coated -1 -2 -6 -7 -1-6 -1-7 -2-6 -2-7 Order code

Materials
Casing in galvanised sheet steel, with powder-coating RAL 7001 (-1) or in stainless steel 1.4301 (-2) Damper blade from special insulation material Damper blade clad in galvanised sheet steel or stainless steel Lacquer coating of damper blade RAL 7001 Damper blade shafts and drive linkage in galvanised steel or stainless steel (-1, -2) Brass or stainless steel bearings Seals in polyurethane or elastomer

Construction variant 2 Release temperature 95 C with blade bead seal (not in combination with -6, -1-6, -2-6)

Order code ...-W ...-LD

Dimensions
FK-K90 with fusible link Dimensions in mm / Weight in kg
H 200 250 300 350 400 450 500 550 600 650 700 750 800 B 200 10 11 12 13 15 16 17 250 11 12 13 15 16 17 18 300 12 13 14 16 17 18 19 21 23 24 25 26 27 350 13 15 16 17 18 20 22 23 25 26 27 28 29 400 15 16 17 18 20 22 24 26 27 28 28 30 32 450 16 17 18 20 22 24 26 28 29 29 31 32 34 500 17 18 19 22 24 26 28 29 30 31 33 34 36 550 18 19 21 23 26 28 29 30 31 33 35 37 38 600 19 21 23 25 27 29 30 32 34 35 37 39 42 650 20 22 24 26 28 29 31 34 36 37 40 42 45 700 22 24 25 27 30 31 33 35 37 40 43 45 47 750 23 25 26 29 31 32 34 37 39 42 45 48 50 800 24 26 28 30 32 34 36 38 42 45 48 50 52 900 26 28 30 32 35 37 39 43 46 49 52 55 57 1000 28 30 31 34 38 40 45 47 50 53 56 59 62 1100 30 32 34 37 40 44 47 50 54 57 60 63 65 1200 31 34 36 39 43 47 50 54 57 61 64 66 68 1300 33 36 38 41 46 49 53 57 61 64 67 69 71 1400 35 38 40 44 48 52 56 60 64 68 71 73 75 1500 38 41 44 48 52 57 62 67 71 75 78 81 84

FK-K90 with spring return actuator: weight + 3 kg.

FK-K90-LD with blade bead seal in combinations of width and height up to B H = 800 mm 400 mm identified in the table by the blue box

Flange drilling Odd number of holes


300 300 35

Even number of holes


10 35 300 300

Detail A - Corner holes A


11
R4.5
R6 .5

10

17,5

35

35

17,5

35

35

17,5

Dimensions in mm
B or H No. of holes per B-side* No. of holes per H-side* 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500 * excluding corner holes

1 1

1 1

1 1

2 2

2 2

17,5

35

,5

Attachments
For dry mortarless installation in solid walls
An installation subframe and an installation kit are required for installation without mortar (dry installation) in solid walls. Fire damper, installation subframe and installation kit are supplied loose. Assembly and installation by others. Fire dampers with installation subframe and installation kit only in casing length L = 500 mm. The installation subframe is fixed in the wall with mortar-mix. The fire damper is assembled with the installation kit to form a unit, pushed into the installation subframe and fixed with screws. In case of fire an intumescent seal closes the remaining gap. Fire dampers installed in this manner can be easily installed and also be removed.

Installation subframe and installation kit for dry mortarless installation in solid walls L1 in mm 115 240 L in mm 500 500

Order code

44 45

Materials
Installation subframe in galvanised steel with intumescent seal Installation kit from special insulation material and mineral wool strips Fixing elements in galvanised steel

FK-K90 with Installation subframe and installation kit


8 7 2 6 1

Solid wall

8 4 5 3 8 7 2 6

Assembled installation subframe and installation kit


L = 500

Installation subframe and installation kit consisting of: 1 Installation subframe 2 Filler strip B-side (2 pieces) 3 Filler strip H-side (2 pieces) 4 Mineral wool B-side (2 pieces) 5 Mineral wool H-side (2 pieces) 6 Screw (8 pieces) 7 Clamp (4 16 pieces*) 8 Screw (4 16 pieces*)
* Number of depends on size

L1

Attachments
For dry mortarless installation directly on the face of solid walls and ceiling slabs
A face subframe with panel cladding is required for installation without mortar (dry installation) directly on the face of solid walls and ceiling slabs. Fire damper and face subframe are supplied loose. Assembly and installation by others. The face subframe is fixed with plugs and screws directly on the face of the wall or ceiling slab. The fire damper is fixed to the face subframe and clad with the panels. Rigid ducts must be connected with a flexible connector at the operating side.
Face subframe with panel cladding for installation without mortar directly on the face of solid walls and ceiling slabs Flexible connectors FK-K90 FK-K90-6 FK-K90-7 at the operating side at the operating side FK-K90-1 FK-K90-2 375 375 500 500 72 73 91 92 L in mm 375 375 500 500 22 23 41 42

Order code

Materials
Face subframe in galvanised steel (it is also powder coated silver-grey (RAL 7001) when used with powder coated (-1) and stainless steel (-2) dampers) Panel cladding using special insulation material Fixing elements in galvanised steel

at the operating side at the operating side

FK-K90 with face subframe and panel cladding

Operating side 3 1 2

8 5 4

B/H

85

Solid wall

9
10

Assembled face subframe with panel cladding


L = 375 or 500

Face subframe and panel cladding consisting of: 1 Face frame 2 Strip (4 pieces) 3 Screw M8 with washer and nut (4 16 pieces*) 4 Panel cladding (4 pieces) 5 Sheet metal angle bracket (4 14 pieces*) 6 Insulation (4 pieces) 7 Sheet metal strip (8 pieces) 8 Retainer (4 14 pieces*) 9 Screw (4 14 pieces*) 10 Washer (4 14 pieces*)
* Number of depends on size

Attachments
For dry mortarless installation in lightweight partition walls and lightweight fire walls
An installation kit is required for installation without mortar (dry installation) in lightweight partition walls and fire walls. Fire damper and installation kit are supplied loose. Assembly and installation by others. The fire damper is assembled with the installation kit to form a unit, pushed into the installation subframe and fixed with screws. In case of fire an intumescent seal closes the remaining gap. Rigid ducts must be connected with flexible connectors at the operating and installation side. Fire dampers with installation kit only in casing length L = 500 mm.

Installation kit for dry mortarless installation in lightweight partition walls and lightweight fire walls Flexible connectors L in mm FK-K90 FK-K90-1 FK-K90-2 FK-K90-6 FK-K90-7 FK-K90 FK-K90-6 FK-K90-7 at the operating and installation sides FK-K90-1 FK-K90-2 at the operating and installation sides 500 500 500

Order code

24 58 A8

Materials
Installation kit from special insulation material with intumescent seal and mineral wool strip Fixing elements in galvanised steel

FK-K90 with installation kit


7 6 1 5
90

Lightweight partition wall or lightweight fire wall

4 2
190

B + 95 H + 95

Assembled installation kit


L = 500

Installation kit consisting of: 1 Filler strip with intumescent seal B-side (2 pieces) 2 Filler strip with intumescent seal H-side (2 pieces) 3 Mineral wool B-side (2 pieces) 4 Mineral wool H-side (2 pieces) 5 Screw (8 pieces) 6 Clamp (4 6 pieces*) 7 Dry wall screw (4 6 pieces*)
* Number of depends on size

10

Attachments
For dry mortarless installation in lightweight partition walls with flexible ceiling joint
An installation kit is required for installation without mortar (dry installation) in lightweight partition walls with flexible ceiling joint directly underneath solid ceiling slabs. The installation kit allows for subsidence of the slab whilst maintaining the sealing continuity around the fire damper. Installation kit, extension piece and cross member underneath the installation kit are assembled at the factory to form a unit. The fire damper is fixed with the fixing elements of the installation kit to the ceiling slab by others. Rigid ducts must be connected with flexible connectors at the operating and installation side.

Installation kit for lightweight partition walls with flexible ceiling joint Flexible connectors FK-K90 FK-K90-6 FK-K90-7 at the operating and installation sides FK-K90-1 FK-K90-2 at the operating and installation sides L in mm 500 500 500 500

Order code

B1 B3 B2 B4

Materials
Installation subframe from special insulation material Cross members in galvanised steel Threaded rods in galvanised steel Fixing elements in galvanised steel Extension piece in galvanised steel

FK-K90 with installation kit for flexible ceiling joint


Ceiling slab 5 2

B + 83

4 Lightweight partition wall

Assembled installation kit


L = 500 260

Installation kit consisting of: 1 Installation subframe with cross member (1 piece) 2 Extension piece (1 piece) 3 Cross member (1 piece) 4 Threaded rod (4 pieces) 5 Screw, washer and nut (4 pieces of each)

11

Attachments
Cover grille
Cover grille
If only one end is ducted on site, the other end must have a cover grille. Due to the construction certain heights require an extension piece, see table. Fire damper, cover grille and, if applicable, extension piece are assembled at the factory to form a unit. The free cross sectional area of the cover grille is approx. 70%. The fixing holes in the cover grilles and extension pieces match those in the fire damper flanges. Cover grilles can also be supplied separately. Further information about extension piece see page 15. Cover grilles both ends are only approved for air transfer application with type FK-K90 to general building inspectorate licence Z-6.50-2031.
Cover grille Operating side Cover grille FK-K90-1 FK-K90-2 Cover grille Installation side Cover grille Cover grille Location and length of extension pieces Dimensions in mm
H Operating side Installation side L Order code

Order code

FK-K90 FK-K90-6 FK-K90-7 17 43 67 93

Materials
Cover grille in galvanised steel (it is also powder coated silver-grey (RAL 7001) when used with powder coated (-1) and stainless steel (-2) dampers)

200 500 550 800 200 300 350 500 550 800

120 120

120 260

375 / 500 375 / 500 500 500 500

17 17 43 43 43

67 67 93 93 93

Cover grille
Operating side Installation side

Note! Extension pieces and cover grilles are supplied factory assembled. Minimum distance Between the open damper blade edge and the cover grille should be a distance of a approx. 50 mm.

A V A V A

Cover grille, mesh size 10 mm 10 mm, wire width 2 mm Extension piece

Without extension piece

With one extension piece Operating or installation side

With two extension pieces Operating and installation side


a a

a a a
A

a
A A A

H/B

H/B

V A

120

120

H/B

120

260

12

Attachments
Circular spigot plate
Circular spigot plate
Use of circular spigot plates facilitate the direct connection of circular ventilation ducting. Due to the construction certain heights require an extension piece, see table. Fire damper, spigot plate(s) and, if applicable, extension piece(s) are factory assembled to form a unit. The fixing holes in the spigot plates and extension pieces match those in the fire damper flanges. Spigot plates can also be supplied separately. Further information about extension piece see page 15.
Circular spigot Operating side Spigot plate Spigot plate FK-K90-1 FK-K90-2 Spigot plate Spigot plate Installation side Spigot plate Spigot plate Location and length of extension pieces Dimensions in mm
H Operating side Installation side L Order code

Order code

FK-K90 FK-K90-6 FK-K90-7 11 12 61 62

Materials
Circular spigot plate in galvanised steel (it is also powder coated silver-grey (RAL 7001) when used with powder coated (-1) and stainless steel (-2) dampers)

200 500 550 800 200 300 350 500 550 800

120 120

120 260

375 / 500 375 / 500 500 500 500

11 11 12 12 12

61 61 62 62 62

Circular spigot plate


Operating side Installation side

Note! Extension pieces and spigot plates are supplied factory assembled. Minimum distance Between the open damper blade edge and the spigot plate should be a distance of a approx. 50 mm.

R V

Circular spigot plate Extension piece

Without extension piece

With one extension piece Operating or installation side

With two extension pieces Operating and installation side


a a

a a a
R

a
R R R

H/B D

H/B D

V R

H/B D

120

120

120

260

Dimensions in mm
Nominal size BH D 200 250 300 350 400 450 500 550 600 650 700 750 800 200 200 250 250 300 300 350 350 400 400 450 450 500 500 550 550 600 600 650 650 700 700 750 750 800 800 198 248 298 348 398 448 498 548 598 648 698 748 798

13

Attachments
Flexible connectors
Flexible connectors
Ducting must be installed in such a manner that it does not impose any loads on the fire damper in the case of a fire. If fire dampers are installed in the following applications connection of rigid ducting can only be made using flexible connectors. The applications are, firstly partial mortaring into solid walls or ceiling slabs, secondly directly on the face of or adjacent to solid walls or ceiling slabs, thirdly remote from solid walls and finally in gypsum wall boards, lightweight partitions or fire walls. Flexible ducting may connected directly to the fire damper. Due to the construction certain heights require an extension piece, see table. The fixing holes in the flexible connectors and extension pieces match those in the fire damper flanges. Flexible connectors can also be supplied separately. Further information about extension piece see page 15.
Flexible connectors Operating side Flexible connectors Flexible connectors FK-K90-1 FK-K90-2 Flexible connectors Flexible connectors Installation side Flexible connectors Flexible connectors 19 20 69 70 FK-K90 FK-K90-6 FK-K90-7 Order code

Location and length of extension pieces Dimensions in mm


H Operating side Installation side L Order code

Materials
Flexible connectors in galvanised steel and fibre-reinforced plastic

200 500 550 800 200 300 350 500 550 800

120 120

120 260

375 / 500 375 / 500 500 500 500

19 19 20 20 20

69 69 70 70 70

Flexible connectors
Operating side Installation side

Note! Extension pieces are supplied factory assembled. Flexible connectors are supplied loose, connection materials are supplied by others. Minimum distance Between the open damper blade edge and the flexible connector should be a distance of a approx. 50 mm.

S V

Flexible connectors Extension piece

160* 185

* flexible range 100 mm in installed state

Without extension piece

With one extension piece Operating or installation side

With two extension pieces Operating and installation side


a a

a a a
S

a
S S S

H/B

H/B

V S

H/B

120

120

120

260

14

Attachments
Extension piece
Extension piece
When using cover grilles, circular spigot plates or flexible connectors an extension piece is required for certain heights. Fire dampers with these attachments are supplied with extension piece. Flexible connectors can also be supplied separately.
H x y L = 375 23 48 73 -52 98 -27 123 148 173 198 223 248 273 298 323 -2 23 48 73 98 123 148 173 198

Dimensions in mm
200 250 300 350 400 450 500 550 600 650 700 750 800 -224 -199 -174 -149 -124 -99 -74 -49 -24 1 26 51 76

Minimum distance
Between the open damper blade edge and the cover grille, circular spigot plate or flexible connector should be a distance of approx. a = 50 mm. Further information about cover grilles, circular spigot plates and flexible connectors see pages 12 to 14.

L = 500 -102 -77

= extension piece required

Materials
Extension piece in galvanised steel (it is also powder coated silver-grey (RAL 7001) when used with powder coated (-1) and stainless steel (-2) dampers)

FK-K90
L = 375 mm Operating side
x

FK-K90
L = 500 mm Installation side
y

Operating side
x

Installation side
y

-x

-x

-y

H/B

H/B

H/B

L = 375

L = 500

L = 375

H/B

L = 500

With one extension piece Operating side

With one extension piece Installation side

With two extension pieces Operating and installation side


a a

H/B

H/B

H/B

120

L = 375 or 500

L = 500

120

120

L = 500

260

Flexible connector, on operating and/or installation side

15

Accessories
Limit switch
FK-K90 with fusible link
Limit switches with potential-free contacts enable the damper blade position indication. Within the range of the switch rating, relays or indication lights for fire alarm systems can be used. One limit switch each is required for damper blade positions OPEN and CLOSED. Fire dampers with a fusible link can be supplied with one or two limit switches or they can be installed later.
Accessories Limit switch damper blade position CLOSED Limit switch damper blade position OPEN Limit switches damper blade position CLOSED and OPEN Order code Z01 Z02 Z03

Limit switch Connecting cable length / cross section Protection level Type of contact Max. switching current Max. switching voltage Contact resistance 1 m / 3 x 0.34 mm IP 66 1 change-over contact, galv. gold-plated 0.5 A 30 V DC, 250 V AC approx. 30 m

Limit switch

Wiring Examples
Limit switch not actuated Limit switch actuated

3 to 30 V DC 230 V AC N(-) L(+)

3 to 30 V DC 230 V AC N(-) L(+)

1 green

brown white 1 Indicator light or relay, supplied by others white

FK-K90 in OPEN position


Damper blade position indicator OPEN CLOSED

FK-K90 in CLOSED position


Damper blade position indicator OPEN CLOSED

Limit switch

Limit switch

actuated non-actuated

non-actuated actuated

16

Accessories
Spring return actuator
FK-K90 with spring return actuator type BLF
for combinations of width and height up to B H = 800 mm 400 mm Operation of the fire damper with a spring return actuator allows remote control and/or release by a suitable smoke detector. If the supply voltage fails or with thermoelectric release the damper closes (power off to close). Fire dampers with spring return actuators can be functionally checked OPEN/CLOSED/OPEN. Two limit switches are integrated into the actuator. The connecting cables of the BLF24-T-ST TR are fitted with plugs. The connection to the TROX AS-i bus system can be quickly made. A conversion kit is available for adding an actuator.
Accessories BLF230-T TR BLF24-T-ST TR Spring return actuator type BLF 230-T TR
230 V AC 14 % 50/60 Hz Spring compression Hold position Rating Motor / spring return Type of contact Switching voltage Switching current Contact resistance

Order code Z43 Z45 24-T-ST TR

Supply voltage

Power rating Run time Limit switch

IEC protection class Protection level Connecting cable Length / Cross section

24 V AC 20 % 50/60 Hz or 24 V DC -10 % / +20 % 6W 5W 3W 2.5 W 7 VA 40 to 75 s / 20 s 2 change-over contacts 5 120 V DC / 5 250 V AC 1 mA 3 A < 100 m II III IP54 1 m / 2 x 0.75 mm

Spring return actuator Type BLF...

Wiring example CLOSED position


230 V AC 24 V N(-) L(+) 110 230 V AC 24 48 V DC N(-) L(+)

1 2 3 CLOSED 3 OPEN

1 2 N L BLF...

S1 S2 S3 S4 S5 S6
<5 <80

1 Switch for opening and closing, supplied by others 2 Optional release mechanism, e.g. TROX smoke detector Type RM-O-3-D or RM-O-VS-D 3 Indicator light or relay, supplied by others

17

Accessories
Spring return actuator
FK-K90 with spring return actuator type BF
Operation of the fire damper with a spring return actuator allows remote control and/or release by a suitable smoke detector. If the supply voltage fails or with thermoelectric release the damper closes (power off to close). Fire dampers with spring return actuators can be functionally checked OPEN/CLOSED/OPEN. Two limit switches are integrated into the actuator. The connecting cables of the BF24-T-ST TR are fitted with plugs. The connection to the TROX AS-i bus system can be quickly made. A conversion kit is available for adding an actuator.
Accessories BF230-T TR BF24-T-ST TR Spring return actuator type BF 230-T TR
230 V AC 14 % 50/60 Hz Spring compression Hold position Rating Motor / spring return Type of contact Switching voltage Switching current Contact resistance

Order code Z43 Z45 24-T-ST TR

Supply voltage

Power rating Run time Limit switch

IEC protection class Protection level Connecting cable Length / Cross section

24 V AC 20 % 50/60 Hz or 24 V DC -10 % / +20 % 8W 7W 3W 2W 12.5 VA 10 VA approx. 140 s / approx. 16 s 2 change-over contacts 5 120 V DC / 5 250 V AC 1 mA 6 A < 100 m II III IP54 1 m / 2 x 0.75 mm

Spring return actuator type BF...

Wiring example CLOSED position


230 V AC 24 V N(-) L(+) 110 230 V AC 24 48 V DC N(-) L(+)

1 2 3 CLOSED 3 OPEN

1 N BF...

2 L

S1 S2 S3 S4 S5 S6
<5 <80

1 Switch for opening and closing, supplied by others 2 Optional release mechanism, e.g. TROX smoke detector Type RM-O-3-D or RM-O-VS-D 3 Indicator light or relay, supplied by others

18

Accessories
Spring return actuator (Ex)
FK-K90 with spring return actuator type ExMax
Operation of the fire damper with a spring return actuator allows remote control and/or release by a suitable smoke detector. If the supply voltage fails or with thermoelectric release the damper closes (power off to close). Fire dampers with spring return actuators can be functionally checked OPEN/CLOSED/OPEN. Two limit switches are integrated into the actuator. The electrical connection is carried out in the terminal box. Release temperature of the spring return actuator 72 C. ATEX-certified to guideline 94/9/EG by Electrosuisse SEV certification number SEV 05 ATEX 0112.
Accessories ExMax-15-BF-TR Spring return actuator type ExMax-15-BF-TR
Supply voltage Power rating Switch on current (< 1 s) Run time Motor / spring return Type of contact Limit switch Switching voltage Switching current IEC protection class Protection level 24 230 V AC/DC, each 10 %, actuator self adjusting 50 60 Hz 20 % 16 W / 15 VA 2A approx. 30 s / approx. 10 s 2 change-over contacts 230 V AC / 24 V DC 0.5 A / 3 A I (earthed) IP66
Gases Zones 1 / 2 Dusts Zone 22 II2D Ex tD A21 [iaD] IP66 T80C II3D IP65 T80C II2D IP66 T85C

Order code ZEX1

ATEX marking

Spring return actuator FireSafe Terminal box

II2G Ex d[ia] IIC T6/T5 II2G EEx d ia IIC T6 II2G EEx e IIC T6

Spring return actuator type ExMax

Wiring example CLOSED position


230 V AC 24 V N(-) L(+) 110 230 V AC 24 48 V DC N(-) L(+)

1 2 4 1 2 N L ExMax-15-BF-TR 3
5

CLOSED 3

OPEN

6
85

1 Switch for opening and closing, supplied by others 2 Optional release mechanism, e.g. TROX smoke detector Type RM-O-3-D or RM-O-VS-D 3 Indicator light or relay, supplied by others 4 Terminal for potential equalisation 4 mm

19

Accessories
TROXNETCOM
FK-K90 with spring return actuator and TROXNETCOM
The fire dampers with spring return actuator BLF24-T-ST TR or BF24-T-ST TR and the modules shown here as attached accessories form a functional unit ready for operation by an automatic fire damper controller. The components are factoryassembled and wired. Only the bus line and the supply voltage (LON only) are to be connected by the customer. The AS interface is a world-standard bus system according to EN 50295 and IEC 62026-2. It enables the integration of different components (modules) in a network regardless of the manufacturer and the design. The modules control actuators and/or receive signals from sensors.
Accessories AS-EM/B and BLF24-T-ST TR* or BF24-T-ST TR Order code ZA03 Order code ZL06 ZL07 ZL08

Accessories LON-WA1/B2 and BLF24-T-ST TR* or BF24-T-ST TR LON-WA1/B2-AD and BLF24-T-ST TR* or BF24-T-ST TR LON-WA1/B2-AD230 and BLF24-T-ST TR* or BF24-T-ST TR
* for combinations of dimensions up to B x H = 800 mm 400 mm

LON and LONMARK are a standardised local operating network system with manufacturer-independent communications. Data is transferred by a microprocessor supplied by Echelon Corporation using a unified protocol. Standards are defined in accordance with LONMARK to ensure that products are compatible.

AS-EM/B module
Controller and power unit FK-K90 with AS-EM/B

Module LON-WA1/...
230 V AC

FK-K90 with LON-WA1/B2

FK-K90 with AS-EM/B Flat cable insulation displacement connector

FK-K90 with LON-WA1/B2-AD230 LON FTT10A twisted pair

The module sends the control signals between the spring return actuator and the controller and power unit. This enables the actuator to be controlled and the monitoring of run time during functional testing. The supply voltage (24 V DC) for the module and the actuator is transmitted using the AS-i flat cable. Function display: operation 4 inputs 2 outputs

LON-WA1/B2 For the control of 1 or 2 fire dampers LON-WA1/B2-AD Connection box for the second fire damper with 24 V AC supply voltage LON-WA1/B2-AD230 Connection box for the second fire damper with 230 V AC supply voltage

Further information can be found on our website. 20

Accessories
TROXNETCOM (Ex)
FK-K90 with spring return actuator (Ex) and TROXNETCOM
The fire dampers with spring return actuator ExMax-15-BF-TR and module AS-EM/C as attached accessories form a functional unit ready for operation by an automatic fire damper controller. Installation outside of the Ex-zone by others. The AS interface is a world-standard bus system according to EN 50295 and IEC 62026-2. It enables the integration of different components (modules) in a network regardless of the manufacturer and the design. The modules control actuators and/or receive signals from sensors.
Accessories AS-interface module Order code ZEX2

AS-EM/C module
Controller
24 V AC / DC 230 V AC

FK-K90

AS-EM/C

AS-EM/C

FK-K90 Outside Ex-zone Inside Ex-zone

The module sends the control signals between the spring return actuator and the controller and power unit. This enables the actuator to be controlled and the monitoring of run time during functional testing. The supply voltage (24 V DC) for the module and the actuator is transmitted using the AS-i flat cable. Function display: operation 4 inputs 2 outputs

Further information can be found on our website. 21

Accessories
Smoke detectors
To prevent smoke from spreading in buildings through the ventilation system, it is extremely important that the smoke is detected at an early stage. Smoke detectors types RM-O-3-D and RM-O-VS-D operate on the principle of light scattering and detect the smoke regardless of its temperature so that the fire dampers close before the release temperature is reached. If the air contains suspended particles, as is the case with smoke, beams of light are deflected off these. A sensor (photodiode), which does not receive light in clear air, is illuminated by the scattered light. The release of the fire or smoke control damper is activated when the brightness of the scattered light exceeds a certain threshold.
Accessories Smoke detector Smoke detector with air flow monitor Order code RM-O-3-D RM-O-VS-D

Smoke detectors are accessories and to be ordered separately.

Smoke detector type RM-O-3-D

Smoke detector for fire and smoke control dampers General building inspectorate licence: Z-78.6-125 For air velocities from 1 to 20 m/s Independent of the air flow direction Supply voltage 230 V AC, 50/60 Hz Potential-free signal and alarm relays Integrated signal lights Contamination level indicator Automatic adjustment of alarm threshold Long service life Correct use and further technical data see leaflet 4/6.3/EN/..

Smoke detector type RM-O-VS-D with air flow monitor

Smoke detector for fire and smoke control dampers General building inspectorate licence Z-78.6-67 For air velocities from 1 to 20 m/s Independent of the air flow direction Air flow monitoring with lower warning limit 2 m/s Supply voltage 230 V AC, 50/60 Hz Potential-free signal and alarm relays Integrated signal lights Contamination level indicator Automatic adjustment of alarm threshold Long service life Correct use and further technical data see leaflet 4/6.2/EN/..

22

Quick selection
Nomenclature
B H A V vA pt in mm in mm in m in m/h in m/s in Pa : : : : : : Width Height Free cross sectional area Flow rate Air velocity based on B x H Total pressure differential (duct installation) pt = 2 vA fm LWA LW LWNC : Resistance coefficient (fully ducted) in kg/m : Air density (approx. 1.2 at 20 C) in Hz : Octave band centre frequency in dB(A) : Sound power level of the air-regenerated noise in the duct in dB : Octave band sound power level LW = LWA + correction value to obtain octave level (see tables 4 and 5) : NC rating of the sound power level LWNC LWA 5 K : Correction value for damper width B 450 mm or 600 mm (see table 6)

All sound power levels are based on 1 pW. All noise levels determined in a reverberation chamber. The sound power data is determined and corrected according to EN ISO 5135, February 1999. Selecting fire dampers using the quick selection table leads rapidly to optimum results. Ensures that normal limits of aerodynamic and acoustic performance are achieved. Air velocity Total pressure differential Sound power level FK-K90-LD with blade bead seal in combinations of width and height up to B H = 800 mm 400 mm identified in the table by the blue box

Flow rate in m/h for pt < 35 Pa


H in mm LWA in dB(A) 35 200 45 35 250 45 35 300 45 35 350 45 35 400 45 35 450 45 35 500 45 35 550 45 35 600 45 35 650 45 35 700 45 35 750 45 35 800 45
5050 6050 7050 8000 9000 9950 10950 11900 12900 13850 14850 16750 18700 20600 22550 24450 26400 28300 4700 3550 5650 4250 6550 4950 7450 5650 8400 6350 9300 7000 10200 11100 12000 12900 13800 15650 17450 19250 21050 22800 24600 26400 7700 8400 9050 9750 10450 11800 13150 14500 15850 17200 18550 19900 4350 3300 5200 3950 6050 4600 6900 5250 7750 5900 8600 6550 9450 7200 10300 11150 12000 12800 14500 16150 17850 19500 21150 22850 24500 7800 8450 9100 9700 11000 12250 13550 14800 16050 17300 18600 4000 3050 4800 3650 5600 4250 6350 4850 7150 5450 7950 6050 8700 6650 9500 7250 10250 11050 11800 13350 14900 16450 17950 19500 21050 22600 7850 8450 9000 10200 11350 12550 13700 14900 16050 17250 3650 2850 4400 3400 5100 3950 5800 4500 6550 5050 7250 5600 7950 6150 8650 6650 9400 7200 10100 10800 12200 13600 15050 16450 17850 19250 20650 7750 8300 9400 10500 11550 12650 13750 14800 15900 3300 2600 3950 3100 4600 3600 5250 4100 5900 4600 6550 5100 7200 5600 7850 6100 8500 6600 9150 7100 9800 7600 11050 12350 13600 14900 16200 17450 18750 8600 9600 10550 11550 12550 13550 14550 2200 2950 2950 2350 3550 2800 4150 3250 4700 3700 5300 4150 5850 4600 6450 5050 7050 5500 7600 5950 8200 6450 8750 6900 9900 7800 11050 12200 13350 14500 15650 16800 8700 9600 10500 11400 12300 13150 1800 1550 2400 2100 2600 2100 3150 2500 3650 2900 4150 3300 4650 3700 5200 4150 5700 4550 6200 4950 6700 5350 7200 5750 7750 6150 8750 6950 9750 7800 10800 11800 12800 13800 14850 8600 9400 10200 11000 11800 2250 1250 2850 1650 3450 1850 4000 2200 4550 2550 5100 2950 5650 3300 6150 3650 6700 4000 7200 4350 7700 4700 8250 5100 8750 5450 7600 6150 8450 6850 9350 7600 10200 11100 12000 12850 8300 9000 9700 10450 1950 1600 2450 2050 2950 2450 3450 2850 3950 3250 4400 3650 4850 4050 5350 4400 5800 4800 6250 5150 6700 5500 7150 5900 7550 6250 6400 5350 7150 5950 7900 6550 8650 7200 9400 7800 10100 10850 8450 9050 1600 1400 2050 1750 2500 2100 2900 2450 3300 2800 3700 3150 4100 3500 4500 3800 4850 4150 5250 4450 5650 4800 6000 5100 6400 5400 5200 4500 5800 5050 6400 5550 7050 6050 7650 6600 8250 7100 8850 7650 1300 1150 1650 1450 2000 1750 2300 2050 2650 2350 3000 2650 3300 2950 3600 3200 3950 3500 4250 3750 4550 4050 4850 4300 5150 4550 4000 3650 4450 4100 4950 4500 5400 4950 5850 5350 6350 5800 6800 6200 950 900 1200 1150 1450 1400 1750 1650 2000 1900 2250 2150 2500 2350 2700 2600 2950 2800 3200 3050 3450 3250 3650 3450 3900 3700 2750 2800 3100 3150 3400 3450 3750 3800 4050 4150 4400 4450 4700 4800

B in mm 200
650

250
850

300
1050

350
1250

400
1400

450
1600

500
1750

550
1950

600
2100

650
2300

700
2450

750
2600

800
2800

900
1950

1000 1100 1200 1300 1400 1500


2150 2400 2650 2850 3100 3300

23

Technical selection data


Differential pressure
Example 1
Given Flow rate: Maximum width: Required sound power level: 1250 l/s (4500 m/h) 600 mm 35 dB(A) Result of selection vA = 4500 m/h (0.6 m 0.4 m 3600) = 5.2 m/s pt = 5 Pa (from table 1, for B = 450 mm) Correction for B = 600 from table 2 pt = 5 Pa 0.8 4 Pa LWA = 31 dB(A) (from table 3, for B = 450 mm) Correction for B = 600 from table 6 LWA = 31 dB(A) + 0.5 32 dB(A)
Sound power level spectrum
fm in Hz LWA in dB(A) Correction from table 4 LW in dB
13 45 5 37 2 34 4 28

Quick selection FK-K90-LD / 600 400 500 (with blade bead seal)

63

125

250

500
32

1000

2000

4000

8000

6 26

11 21

17 15

24 8

Table 1: Differential pressue pt in Pa for damper B = 450 mm or 600 mm


H in mm 200 250 300 350 400 FK-K90 with landing angles with bead seals 450 500 550 600 600 650 700 750 800 450 B in mm vA in m/s Type 2
<

3
< < < < < < < < < < < < <

4
6 5 < < < 6 5 5 < < < < <

5
9 7 6 5 5 9 8 7 7 6 6 5 5

6
13 10 9 8 7 13 12 10 10 9 8 8 7

7
18 14 12 11 10 18 16 14 13 12 11 11 10

8
23 18 16 14 13 23 21 19 17 16 15 14 13

9
29 23 20 18 16 30 26 24 22 20 19 18 17

10
36 29 25 22 20 37 32 29 27 25 23 22 21

11
43 35 30 26 24 44 39 35 32 30 28 26 25

12
51 42 36 31 28 53 47 42 38 35 33 31 30

FK-K90-LD with blade bead seal

< < < < < < < < < < < <

Air velocities 8 m/s are only allowed for fire dampers with spring return actuators.

Table 2: Corrections based on other damper widths B


B in mm 450 600 B in mm Type
FK-K90LD FK-K90

200
1.9 2,4

250
1.6 1.9

300
1.3 1.6

350
1.2 1.4

400
1.1 1.3

450
1.0 1.2

500
0.9 1.1

550
0.9 1.0

600
0.8 1.0

650
0.8 1.0

700
0.7 0.9

750
0.7 0.9

800
0.7 0.9

900

1000 1100 1200 1300 1400 1500

0.8

0.8

0.8

0.8

0.8

0.7

0.7

24

Technical selection data


Sound power level
Example 2
Given Flow rate: Maximum width: Required sound power level: 4250 l/s (15300 m/h) 1000 mm 45 dB(A) Result of selection vA = 15300 m/h (1.0 m 0.7 m 3600) = 6.1 m/s pt = 8 Pa (from table 1, for B = 600 mm) Correction for B = 1000 from table 2 pt = 8 Pa 0.8 7 Pa LWA = 44 dB(A) (from table 3, for B = 600 mm) Correction for B = 1000 from table 6 LWA = 44 dB(A) 1 = 43 dB(A)
Sound power level spectrum
fm in Hz LWA in dB(A) Correction from table 5 LW in dB
4 47 6 49 1 44 3 40

Quick selection FK-K90 / 1000 700 500 (with landing angles with bead seals)

63

125

250

500
43

1000

2000

4000

8000

6 37

9 34

17 26

25 18

Table 3: Sound power level LWA in dB(A) for damper width B = 450 mm or 600 mm
H in mm 200 250 300 350 400 FK-K90 with landing angles with bead seals 450 500 550 600 600 650 700 750 800 450 B in mm vA in m/s Type 2
<15

3
20 18 17 17 16 26 25 25 25 24 24 24 24

4
29 27 26 25 25 34 34 33 33 33 32 32 32

5
35 33 32 32 31 41 40 40 39 39 39 38 38

6
41 39 38 37 37 46 45 45 44 44 44 44 43

7
45 44 42 42 42 50 50 49 49 48 48 48 48

8
49 48 46 46 46 54 53 53 53 52 52 52 52

9
53 51 50 49 49 57 57 56 56 56 55 55 55

10
56 54 53 53 52 60 60 59 59 59 58 58 58

11
59 57 56 55 55 63 62 62 62 61 61 61 61

12
62 60 59 58 58 65 65 64 64 64 64 63 63

FK-K90-LD with blade bead seal

<15 <15 <15 <15 <15 <15 <15 <15 <15 <15 <15 <15

Air velocities 8 m/s are only allowed for fire dampers with spring return actuators.

Table 4: Correction values for FK-K90-LD with blade bead seal to obtain octave levels in dB/Oct.
vA in m/s 2 4 6 8 10 63
17 15 10 7 5

Table 5: Correction values for FK-K90 with landing angles with bead seals to obtain octave levels in dB/Oct.
vA in m/s 2 4 6 8 10 63
10 8 4 2 1

125
8 5 4 3 2

250
3 2 2 1 1

fm in Hz 500 1000
2 3 4 4 5 8 7 6 6 5

2000
17 12 10 8 6

4000
26 19 16 13 11

8000
33 26 22 19 17

125
13 10 6 4 2

250
3 3 1 1 3

fm in Hz 500 1000
3 3 3 3 4 15 7 6 4 4

2000
17 11 9 7 7

4000
28 21 17 14 12

8000
36 29 25 22 20

25

Technical selection data


Free cross sectional area, resistance coefficient and correction values

Table 6: Free cross sectional area, resistance coefficient and correction values
H in mm B in mm 200 A in m 0.020 200 K
1.12 1

250
0.027 0.94 1 0.039 0.77 1 0.050 0.66 1 0.062 0.58 1 0.073 0.53 1 0.067 1.13 3,5 0.076 1.03 3,5

300
0.034 0.77 0 0.048 0.62 0 0.062 0.53 0 0.076 0.47 0 0.090 0.43 0 0.084 0.98 2 0.096 0.86 2 0.108 0.78 2 0.12 0.70 2 0.132 0.66 2 0.144 0.61 2 0.156 0.58 2 0.168 0.54 2

350
0.041 0.71 0 0.058 0.58 0 0.074 0.49 0 0.091 0.43 0 0.107 0.40 0 0.102 0.85 2 0.116 0.76 2 0.131 0.69 2 0.145 0.62 2 0.16 0.57 2 0.174 0.53 2 0.189 0.50 2 0.203 0.48 2

400
0.048 0.65 0 0.067 0.53 0 0.086 0.45 0 0.105 0.40 0 0.124 0.36 0 0.119 0.79 1 0.136 0.70 1 0.153 0.64 1 0.17 0.57 1 0.187 0.53 1 0.204 0.49 1 0.221 0.47 1 0.238 0.44 1

450
0.055 0.59 0 0.077 0.48 0 0.098 0.41 0 0.12 0.36 0 0.141 0.33 0 0.137 0.73 1 0.156 0.65 1 0.176 0.59 1 0.195 0.53 1 0.215 0.49 1 0.234 0.46 1 0.254 0.43 1 0.273 0.41 1

500
0.062 0.53 0 0.086 0.43 0 0.11 0.37 0 0.134 0.32 0 0.158 0.30 0 0.154 0.67 0 0.176 0.59 0 0.198 0.54 0 0.22 0.48 0 0.242 0.45 0 0.264 0.42 0 0.286 0.40 0 0.308 0.37 0

550
0.069 0.53 0 0.096 0.43 0 0.122 0.37 0 0.149 0.32 0 0.175 0.30 0 0.172 0.61 0 0.196 0.54 0 0.221 0.49 0 0.245 0.44 0 0.27 0.41 0 0.294 0.38 0 0.319 0.36 0 0.343 0.34 0

600
0.076 0.47 0.5 0.105 0.38 0.5 0.134 0.33 0.5 0.163 0.29 0.5 0.192 0.26 0.5 0.189 0.61 0 0.216 0.54 0 0.243 0.49 0 0.27 0.44 0 0.297 0.41 0 0.324 0.38 0 0.351 0.36 0 0.378 0.34 0

650
0.083 0.47 0.5 0.115 0.38 0.5 0.146 0.33 0.5 0.178 0.29 0.5 0.209 0.26 0.5 0.207 0.61 0 0.236 0.54 0 0.266 0.49 0 0.295 0.44 0 0.325 0.41 0 0.354 0.38 0 0.384 0.36 0 0.413 0.34 0

700
0.090 0.41 1 0.124 0.34 1 0.158 0.29 1 0.192 0.25 1 0.226 0.23 1 0.224 0.55 0 0.256 0.49 0 0.288 0.44 0 0.32 0.40 0 0.352 0.37 0 0.384 0.34 0 0.416 0.32 0 0.448 0.31 0

750
0.097 0.41 1 0.134 0.34 1 0.17 0.29 1 0.207 0.25 1 0.243 0.23 1 0.242 0.55 0 0.276 0.49 0 0.311 0.44 0 0.345 0.40 0 0.38 0.37 0 0.414 0.34 0 0.449 0.32 0 0.483 0.31 0

800
0.104 0.41 1 0.143 0.34 1 0.182 0.29 1 0.221 0.25 1 0.26 0.23 1 0.259 0.55 -1 0.296 0.49 -1 0.333 0.44 -1 0.37 0.40 -1 0.407 0.37 -1 0.444 0.34 -1 0.481 0.32 -1 0.518 0.31 -1

900
0.084 2,18 -1 0.126 1.26 -1 0.168 0.89 -1 0.21 0.69 -1 0.252 0.57 -1 0.294 0.49 -1 0.336 0.43 -1 0.378 0.39 -1 0.42 0.35 -1 0.462 0.33 -1 0.504 0.31 -1 0.546 0.29 -1 0.588 0.27 -1

1000 1100 1200 1300 1400 1500


0.094 2,18 -1 0.141 1.26 -1 0.188 0.89 -1 0.235 0.69 -1 0.282 0.57 -1 0.329 0.49 -1 0.376 0.43 -1 0.423 0.39 -1 0.47 0.35 -1 0.517 0.33 -1 0.564 0.31 -1 0.611 0.29 -1 0.658 0.27 -1 0.104 2,18 -1 0.156 1.26 -1 0.208 0.89 -1 0.26 0.69 -1 0.312 0.57 -1 0.364 0.49 -1 0.416 0.43 -1 0.468 0.39 -1 0.52 0.35 -1 0.572 0.33 -1 0.624 0.31 -1 0.676 0.29 -1 0.728 0.27 -1 0.114 2,18 -1 0.171 1.26 -1 0.228 0.89 -1 0.285 0.69 -1 0.342 0.57 -1 0.399 0.49 -1 0.456 0.43 -1 0.513 0.39 -1 0.57 0.35 -1 0.627 0.33 -1 0.684 0.31 -1 0.741 0.29 -1 0.798 0.27 -1 0.124 2,18 -1 0.186 1.26 -1 0.248 0.89 -1 0.31 0.69 -1 0.372 0.57 -1 0.434 0.49 -1 0.496 0.43 -1 0.558 0.39 -1 0.62 0.35 -1 0.682 0.33 -1 0.744 0.31 -1 0.806 0.29 -1 0.868 0.27 -1 0.134 1.90 -1 0.201 1.11 -1 0.268 0.78 -1 0.335 0.60 -1 0.402 0.50 -1 0.469 0.43 -1 0.536 0.38 -1 0.603 0.34 -1 0.67 0.31 -1 0.737 0.29 -1 0.804 0.27 -1 0.871 0.25 -1 0.938 0.24 -1 0.144 1.90 -1 0.216 1.11 -1 0.288 0.78 -1 0.36 0.60 -1 0.432 0.50 -1 0.504 0.43 -1 0.576 0.38 -1 0.648 0.34 -1 0.72 0.31 -1 0.792 0.29 -1 0.864 0.27 -1 0.936 0.25 -1 1.008 0.24 -1

A in m 0.029 250 K
0.91 1

A in m 0.038 300 K
0.78 1

A in m 0.047 350 K
0.68 1

A in m 0.056 400 K
0.63 1

A in m 0.049 450 K
1.48 5,5

A in m 0.056 500 K A in m 550 K A in m 600 K A in m 650 K A in m 700 K A in m 750 K A in m 800 K


1.35 5,5

26

Installation details
In solid walls and ceiling slabs and also gypsum wallboards
Mortar based installation
Installation of the fire damper is approved in solid walls and ceiling slabs and also in gypsum wallboards with perimeter mortar in fill (wet installation). Installation in horizontal or vertical ducts. Air flow direction is not critical. Requirements Solid walls of concrete, aerated concrete or made of brickwork or gypsum wallboards with minimum thickness 100 mm Solid ceiling slabs of concrete or aerated concrete with minimum thickness 125 mm 75 mm minimum distance to load bearing structural elements 200 mm minimum distance between two fire dampers when installed in ceiling slabs Connection of rigid ducts using a flexible connector when installed in gypsum wallboards to DIN 18163 Recommendations Casing length L = 500 mm, if the wall is thicker than 100 mm or the ceiling slab is thicker than 125 mm Installation details An opening or a cut hole with a minimum B + 80 mm and H + 80 mm is required or the fire damper is concreted into the wall or ceiling slab during construction Perimeter gap s is completely sealed with mortar. The mortar bed depth must not be less than 100 mm. Mortar that conforms to DIN 1053, Groups II, IIa, III or IIIa, concrete or plaster are approved for use.

Wall installation W 240 mm


260 W

Ceiling slab installation, upright

260 s 40

Mortar, concrete or plaster

Mortar, concrete or plaster

s 40

W > 240 mm
W 100

Ceiling slab installation, suspended

Extension piece

Mortar, concrete or plaster

s 40 L = 375 or 500 D 260

L = 375 or 500

L = 375 or 500

27

Installation details
In solid walls with difficult access
Installation of the fire damper is approved in solid walls with perimeter mortar in fill (wet installation) or without mortar (dry installation). Mortar based installation with partial mortaring Mortar based installation of multiple dampers flange to flange Dry mortarless installation with installation subframe and installation kit Installation in horizontal ducts. Air flow direction is not critical.

Mortar based installation with partial mortaring


Requirements Solid walls of concrete, aerated concrete or made of brickwork with minimum thickness 100 mm Connection of rigid ducts using flexible connectors Installation details Difficult to access gaps are sealed with metal profiles and mineral wool Gaps x are completely sealed with mineral wool, to DIN 4102, fire rating class A1, non-combustible, gross density approx. 100 kg/m Gaps s are completely sealed with mortar. The mortar bed depth must not be less than 100 mm. Mortar that conforms to DIN 1053, Groups II, IIa, III or IIIa, concrete or plaster are approved for use.

Installation with partial mortaring Difficult to access gap on one side, Wall joint
Ceiling slab Solid wall
L = 375 or 500

Difficult to access gap on one side, Ceiling joint


Ceiling slab
L = 375 or 500
x 40

Mortar, concrete or plaster, three sides Mineral wool and metal profile

Mineral wool and metal profile

s 40

Mortar, concrete or plaster, three sides


x 40

s4

Solid wall

Difficult to access gap on two sides, Wall and ceiling joint


Ceiling slab
x 40

x 40
L = 375 or 500

Mineral wool and metal profile


s 40

Solid wall

Mortar, concrete or plaster, two sides

28

Installation details
Multiple fire dampers in solid walls
Mortar based installation of multiple dampers flange to flange
Requirements Solid walls of concrete, aerated concrete or made of brickwork with minimum thickness 100 mm Installation details An opening or a cut hole with a minimum 2 B + 150 mm and H + 80 mm or B + 80 mm and 2 H + 150 mm is required or the fire damper is concreted into the wall slab during construction The flanges of the horizontal or vertical arranged fire dampers are next to one another, the spacing between the casings is a = 70 mm Gaps s and a are completely sealed with mortar. The mortar bed depth must not be less than 100 mm. Mortar that conforms to DIN 1053, Groups II, IIa, III or IIIa, concrete or plaster are approved for use.

Flange to flange Arrangement horizontal


260 W

Arrangement vertical
260 W

A
L = 375 or 500

W 100 mm
L = 375 or 500

Mortar
a=7 0 s4

View A
a = 70

Mortar

Mortar

a = 70

29

Installation details
In solid walls
Dry mortarless installation with installation subframe and installation kit
Requirements Solid walls of concrete, aerated concrete or made of brickwork with minimum thickness 100 mm Casing length L = 500 mm Installation details An opening or cut hole with a minimum B + 185 mm and H + 185 mm is required Fire damper is fitted with the installation kit and pushed into the installation subframe Perimeter gap s is completely sealed with mortar. The mortar bed depth must not be less than 100 mm. Mortar that conforms to DIN 1053, Groups II, IIa, III or IIIa, concrete or plaster are approved for use. Further information about installation subframe and installation kit see page 8.

Dry mortarless installation with installation subframe and installation kit


L = 500 260

290

5/ B + 18 5 H + 18

L1 = 115 or 240

Installation kit

Installation subframe

Mortar, concrete or plaster Solid wall


s4 0

Detail A
W

Solid wall
s 40

Mortar, concrete or plaster Installation subframe Installation kit

30

Installation details
Directly on the face of solid walls and ceiling slabs
Dry mortarless installation
Installation of the fire damper is approved directly on the face of solid walls and ceiling slabs with a face frame and panel cladding. Installation in horizontal and vertical ducts. Air flow direction is not critical. Requirements Solid walls of concrete, aerated concrete or made of brickwork with minimum thickness 100 mm Solid ceiling slabs of concrete or aerated concrete with minimum thickness 125 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using a flexible connector Installation details Perimeter fire resistant insulation with panel cladding is required (Accessory or by others) Unevenness of the hole in the wall or ceiling slab is scimmed to form a smooth surface to enable effective sealing of the subframe. Face subframe is fixed only with suitable plugs and screws. Further information about face subframe with panel cladding see page 9.

Installation to wall
Face subframe
L = 375 or 500 260

Solid wall

Panel cladding

B/H
60

Upright ceiling installation

Suspended ceiling installation

Face subframe Panel cladding Ceiling slab Panel cladding

Face subframe

Ceiling slab

31

Installation details
Adjacent to solid walls and ceiling slabs
Dry mortarless installation
Installation of the fire damper is approved directly adjacent to solid walls and ceiling slabs when connecting to an existing fire damper that requires refurbishment, to sheet steel duct with angled profile and perimeter mortaring or to an intermediate frame and/or angle frame with perimeter mortaring. In all cases additional suspension support of the new fire damper is not required. Installation in horizontal or vertical ducts. Air flow direction is not critical. Requirements Maximum 260 mm duct with approved fire resistance without any opening between the fire damper and the wall Solid walls of concrete, aerated concrete or made of brickwork with minimum thickness 100 mm Solid ceiling slabs of concrete or aerated concrete with minimum thickness 125 mm Connection of rigid ducts using a flexible connector Installation details Existing fire damper, duct or intermediate frame is clad with 40 mm mineral wool or calcium silicate and then additional L90 cladding Panel cladding ends 10 mm from the wall, ceiling or angle profile, the gap is filled with mineral wool Mineral wool, to DIN 4102, fire rating class A1, non-combustible, gross density approx. 100 kg/m

Installation adjacent to wall with existing fire damper casing


4
260

Installation adjacent to wall to duct with intermediate frame and/or angle frame
1 Solid wall
260

7 3

Solid wall

L = 375 or 500

260

L = 375 or 500

260

Installation adjacent to wall to duct with angle profile


4
260

Solid wall

1 2 3 4 5 6 7 8

Existing fire damper casing Existing duct Mineral wool Mineral wool or calcium silicate Cladding L90 Angle profile Intermediate frame Angle frame

L = 375 or 500

260

32

Installation details
Suspension systems
Installation remote from a solid wall suspension supports are required. To support heavy loads a fixing plate can be used. Steel plug anchors Plug anchors with general building inspectorate licence (ABZ) or European technical approval (ETA) with certified fire protection qualification: Plugs are installed and must have loads that do not exceed those in the approval certificate. Plug anchors with general building inspectorate licence (ABZ) or European technical approval (ETA) without certified fire protection qualification: Plug in minimum M8 is installed to a depth twice as reqired in the approval-certificate, however the depth must be at least 60 mm, and loaded with a maximum of 50 kg. If the maximum load is exceeded a fixing plate is required Threaded rod Threaded rods > 1.5 m need fire resistant cladding
Thread diameter Maximum tensile load per threaded rod in kg * Weight of the fire damper, see page 7 M8 22* M10 35* M12 52* M14 70* M16 96* M20 150*

1 2 3 4 5 6 7 8

Threaded rod, M8 to M20. galvanised steel Washer, M8 to M20. galvanised steel Hexagonal nut, M8 to M20. galvanised steel Spacer tube, 30 33, galvanised steel Fixing plate, min. 10 mm thick, galvanised or coated steel Steel plug anchor, galvanised steel Threaded bush, galvanised steel Cross member, U50 to DIN 1026, 50 mm 38 mm 5 mm, galvanised or coated steel

Suspension
Ceiling slab

Fixing plate A
M8 to M16 M20 5
>9

5
>9
50

M8 M16 80 120 M20 100 150

B/

B
H

Detail A Ceiling slab fixing


without plug 3 2
60

Detail B Cross member


with plug M8 to M14 M16 to M20

6 7 1

1 2 3 8

1 4 8 2 3

with plug anchor and fixing plate

10

6 5 3 1

33

Installation details
Remote from solid walls
Dry mortarless installation
The fire damper installation remote from a solid wall is approved when the intermediate duct has an external fire resistant cladding between the plane of the fire damper blade and the solid wall. Requirements Sheet steel ventilation ducting with fire resistant cladding L90 Ducting made from L90 boards Sheet steel ventilation ducting with outer mineral wool insulation L90 No openings in the insulated ducts between the fire damper and the solid wall Openings in the ducts on the non-insulated side of the fire damper must be at least 1.5 times dimension B or H which ever is larger from the fire damper or must be protected with a cover grille made of non-combustible material Connection of rigid ducts to the non-insulated side using a flexible connector Installation details Construction details of suspension systems see page 33 Maximum distance between two suspension assemblies should not exceed 1 m Suspensions require adequate sized threaded rods. Suspensions measuring > 1.5 m in lenght require fire resistant insulation. A fixing plate with multiple plugs and screws can be used to support heavy loads Suspensions can be fixed on top of the ceiling slab using nuts and washers made of galvanised steel Thickness of insulation according to the particulars of the mineral wool manufacturer

In sheet steel ventilation ducting with fire resistant cladding L90


4
260

Solid wall 6
L = 375 or 500

Flexible connectors

In L90 board ventilation ducting


42
260

Solid wall 6
L = 375 or 500 100

Flexible connectors

34

Installation details
Remote from solid walls

1 Sheet steel ventilation ducting with fire resistant cladding L90 2 Ducting made of L90 boards 3 Sheet steel ventilation ducting with outer mineral wool insulation L90 to DIN 4102-4 (Edition March 1994) 4 Mineral wool, to DIN 4102, fire rating class A1, non-combustible, gross density approx. 100 kg/m, thickness approx. 40 mm 5 Cover plate, by others (only required with outer mineral wool insulation) 6 Cross member U50 to DIN 1026, 50 mm 38 mm 5 mm, galvanised or coated steel; Suspension can be outside of the cladding (but inside of mineral wool insulation) 7 Suspension according to the particulars of the ducting manufacturer; however the maximum distance between two suspension assemblies should not exceed 1m 8 Board staples or dry wall screws, steel

In sheet steel ventilation ducting with outer mineral wool insulation L90
5
260

Solid wall 6
L = 375 or 500

Flexible connectors

35

Installation details
In lightweight partition walls with metal support structure and clad on both sides
Installation of fire dampers in lightweight partition walls with metal support structure and clad both sides is approved with perimeter mortar in fill (wet installation) or without mortar (dry installation). Mortar based installation Dry mortarless installation with installation kit Dry mortarless installation during construction of the wall Dry mortarless installation with installation kit for flexible ceiling joint Installation in horizontal ducts. Air flow direction is not critical.

Mortar based installation


Requirements Lightweight partition walls with metal support structure and mineral wool, minimum thickness 100 mm, to DIN 4102-4, Table 48 or with general appraisal certificate 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Installation details An opening or cut hole with B + 80...120 mm and H + 80...120 mm is required Perimeter gap s is completely sealed with mortar. The mortar bed depth must not be less than 100 mm. Mortar that conforms to DIN 1053, Groups II, IIa, III or IIIa, or preferably plaster are approved for use. Optional plaster board trim panels

Mortar based installation


260 W 260 W

A
L = 375 or 500 L = 375 or 500

Mortar or plaster

Mortar or plaster

Perimeter metal profile

Perimeter metal profile

Dry wall screw


s 40

Dry wall screw Trim panel, option

s = 40

...60

Detail A
W

Metal support structure for mortar based installation

Perimeter metal profile Trim panel, option

Mortar or plaster

625

x = H + 80...120 mm z = B + 80...120 mm

36

Installation details
In lightweight partition walls with metal support structure and clad on both sides
Dry mortarless installation with installation kit
Requirements Lightweight partition walls with metal support structure and mineral wool, minimum thickness 100 mm, to DIN 4102-4, Table 48 or with general appraisal certificate Casing length L = 500 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Installation details An opening with a minimum B + 95 mm and H + 95 mm is required Fire damper is assembled with the installation kit and pushed into the ready made lightweight partition wall. Fixing is carried out with clamps and screws to the perimeter metal profile. Further information about installation kit see page 10.

Dry mortarless installation with installation kit


W

L = 500 260

B + 95 / H + 95

Lightweight partition wall

Perimeter metal profile

Detail B
W

Metal support structure for dry mortarless installation with installation kit

Perimeter metal profile

Installation kit

625

x = H + 95 mm z = B + 95 mm

37

Installation details
In lightweight partition walls with metal support structure and clad on both sides
Dry mortarless installation during construction of the wall
Requirements Lightweight partition walls with metal support structure and mineral wool, minimum thickness 100 mm, to DIN 4102-4, Table 48 or with general appraisal certificate Casing length L = 500 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Installation details A perimeter metal profile frame with a minimum B + 75 mm and H + 75 mm is required Fire damper is assembled with perimeter plaster-board strips by others. For fixing reinforcing boards are used on both sides of the partition wall.

Dry mortarless installation during construction of the wall


260 W
W

A
L = 500

Reinforcing board

Filler strips, 3 pieces Perimeter metal profile Dry wall screw Reinforcing board
100

Lightweight partition wall


140

Dry wall screw

Detail A
W

Metal support structure for dry mortarless installation during construction of the wall

Reinforcing board

Reinforcing board

Perimeter metal profile

Mineral wool

Filler strips, 3 pieces x = H + minimum 75 mm z = B + minimum 75 mm

625

38

Installation details
In lightweight partition walls with metal support structure and clad on both sides
Flexible ceiling joint with installation kit
Requirements Lightweight partition walls with metal support structure and mineral wool, thickness 100 mm, to DIN 4102-4, Table 48 or with general appraisal certificate Maximum subsidence of the ceiling slab a = 40 mm Casing length L = 500 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Installation details Fire damper is fixed to the wall using the factory installed installation kit Cladding of the lightweight partition wall can only be carried out after installation of the fire damper A three-side metal profile frame with B + 305 mm and H + a + 186 mm is required Further information about installation kit see page 11.

Flexible ceiling joint with installation kit


Ceiling slab

260

Reinforcing board

Metal profile

Lightweight partition wall


W

Detail A

Metal support structure for flexible ceiling joint


Ceiling slab Reinforcing board Drywall steel profile UW Drywall steel profile CW
x

Installation kit

625

x = H + a + 186 mm z = B + 305 mm

39

Installation details
In lightweight partition walls with metal support structure and clad on one side
Dry mortarless installation with installation kit
Installation of fire dampers in lightweight partition walls with metal support structure and clad on one side is approved without mortar (dry installation). Dry mortarless installation in an existing lightweight partition wall is carried out using an installation kit. Installation in horizontal ducts. Air flow direction is not critical. Requirements Lightweight partition walls with metal support structure with minimum thickness 90 mm Wall height maximum 5000 mm Casing length L = 500 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Further conditions according to general appraisal certificate P-3254/1449 Installation details An opening with a minimum B + 95 mm and H + 95 mm is required Further information about installation kit see page 10.

Dry mortarless installation with installation kit


B + 95 / H + 95
W

L = 500 260

Lightweight partition wall

Reinforcing board

Perimeter metal profile


100

Detail A
W

Metal support structure for dry mortarless installation with installation kit

Perimeter metal profile

Installation kit

625

x = H + 95 mm z = B + 95 mm

40

Installation details
In lightweight partition walls without metal support structure and clad on one side
Dry mortarless installation with installation kit
Installation of fire dampers in lightweight partition walls without metal support structure and clad on one side is approved without mortar (dry installation). Dry mortarless installation in an existing lightweight partition wall is carried out using an installation kit. Installation in horizontal ducts. Air flow direction is not critical. Requirements Lightweight partition walls without metal support structure with minimum thickness 40 mm Wall width maximum 2000 mm Wall height maximum 5000 mm Casing length L = 500 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Further conditions according to general appraisal certificate P-3160/0967 or P-3586/8692 Installation details An opening with a minimum B + 95 mm and H + 95 mm is required Further information about installation kit see page 10.

Dry mortarless installation with installation kit


B + 95 / H + 95
W

L = 500 260

Lightweight partition wall

Reinforcing board

Perimeter metal profile


100

Detail B
W

Metal support structure for dry mortarless installation with installation kit

Perimeter metal profile

Installation kit x = H + 95 mm z = B + 95 mm

41

Installation details
In lightweight fire walls with metal support structure and clad on both sides
Installation of fire dampers in lightweight fire walls with metal support structure and clad on both sides is approved with perimeter mortar in fill (wet installation) or without mortar (dry installation). Mortar based installation Dry mortarless installation with installation kit Installation in horizontal ducts. Air flow direction is not critical.

Mortar based installation


Requirements Lightweight fire walls with metal support structure according to general appraisal certificate and minimum thickness 110 mm Knauf ABP P-3391/170/08, Rigips ABP P-3020/0109 Lafarge ABP P-3391/0890, Promat ABP P-3796/7968 Wall height maximum 5000 mm 200 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Installation details An opening or cut hole with B + 80...120 mm and H + 80...120 mm is required Perimeter gap s is completely sealed with mortar. The mortar bed depth must not be less than 100 mm. Mortar that conforms to DIN 1053, Groups II, IIa, III or IIIa, or preferably plaster are approved for use. Optional plaster board trim panels

Mortar based installation


260 W 260 W

A
L = 375 or 500

A
L = 375 or 500

Mortar or plaster

Mortar or plaster

Perimeter metal profile

Perimeter metal profile

s 40

Trim panel, option

s = 40

...60

Detail A
W

Metal support structure for mortar based installation

Drywall steel profile UW Drywall steel profile UA Trim panel, option


z x

Mortar or plaster
312,5

x = H + 80...120 mm z = B + 80...120 mm

42

Installation details
In lightweight fire walls with metal support structure and clad on both sides
Dry mortarless installation with installation kit
Requirements Lightweight fire walls with metal support structure according to general appraisal certificate and minimum thickness 110 mm Knauf ABP P-3391/170/08, Rigips ABP P-3020/0109 Lafarge ABP P-3391/0890, Promat ABP P-3796/7968 Wall height maximum 5000 mm Casing length L = 500 mm 180 mm minimum distance between two fire dampers Connection of rigid ducts using flexible connectors Installation details An opening with a minimum B + 95 mm and H + 95 mm is required Further information about installation kit see page 10.

Dry mortarless installation with installation kit


W

L = 500 260

B + 95 / H + 95

Lightweight fire wall

Perimeter metal profile

Detail B
W

Metal support structure for dry mortarless installation with installation kit

Drywall steel profile UW Drywall steel profile UA


z x

Installation kit
312,5

x = H + 95 mm z = B + 95 mm

43

Order Details

Specification text *
Square or rectangular fire dampers in many dimensional combinations for the isolation of duct penetrations between fire compartments. Ready-for-operation unit contains a fire-resistant damper blade and a release mechanism. Fire resistance class: K90. Tested for fire resistance properties according to DIN 4102 and EN 1366-2, with general building inspectorate licence Z-41.3-321 of the Deutsches Institut fr Bautechnik, Berlin. For installation directly in solid walls, ceiling slabs, gypsum wall boards, lightweight partitions and lightweight fire walls, on the face of solid walls and ceiling slabs, adjacent to solid walls and ceiling slabs and remote from solid walls. Special characteristics: Tested for fire resistance properties according to DIN 4102 and EN 1366-2 Construction (LD) has lower sound power level and differential pressure Integration into the centralised BMS with TROXNETCOM

Fire damper model with: Spring return actuator with thermoelectric release mechanism. Two limit switches integrated into actuator for damper blade position indication OPEN and CLOSED. Casing made of galvanised sheet steel, damper blade made of special insulating material, blade mounting shaft and drive linkage of stainless steel, plain brass bearings, seals from polyurethane or elastomer.
* Text for a FK-K90 with fusible link Text for construction variants, attachments and accessories see design programme or our home page

Order code
FK-K90 / 600 400 500 / 17 / Z43

ype Construction variant 1 Galvanised casing, no entry required -1 Powder-coated casing -2 Stainless steel casing -6 Sheet steel clad damper blade -7 Coated damper blade -1-6 Powder-coated casing and sheet steel clad damper blade -1-7 Powder-coated casing and coated damper blade -2-6 Stainless steel casing and sheet steel clad damper blade -2-7 Stainless steel casing and coated damper blade

Construction variant 2 ...-W Release temperature 95 C ...-LD With blade bead seal Nominal size BHL ttachments None, no entry required 11 to B4 ccessories None, no entry required Z01 to ZEX2

Combinations of width and height up to B H = 800 mm 400 mm as a standard construction FK-K90-LD is supplied. Construction with landing angles with bead seals on request.

Subject to change All rights reserved TROX GmbH (11/2010)

Order example FK-K90 with blade bead seal and fusible link
Make: Type: TROX FK-K90-LD / 600 400 500

Order example FK-K90, with landing angles with bead seals, powder-coated, with operating side cover grille and spring return actuator 230 V AC
Make: Type: TROX FK-K90 - 1 / 1000 700 500 / 17 / Z43

44