Source Changeover
Source Changeover
Catalogue
2007
To ensure a continuous supply of electrical power, certain installations are connected to two sources: b a normal source N b a replacement source R used to supply the installation when the normal source is unavailable. A source-changeover system switches the load between these two sources. It can be automated to manage transfers according to external conditions. A source-changeover system includes two or three circuit breakers or switch-disconnectors. With Interpact INS, Compact NS and Masterpact NT and NW, new installation solutions are available to optimise the size of the switchboard and simplify installation.
PB100839
PB100840
PB100930-68
PB100842
Source-changeover systems
General content
Presentation
Dimensions
37
Electrical diagrams
59
95
Presentation
An automatic controller may be added to a remote-operated source-changeover system for automatic source control according to programmable operating modes. This solution ensures optimum energy management: b transfer to a replacement source according to external requirements b management of power sources b regulation b emergency source replacement, etc. The automatic controller may be fitted with an option for communication with a supervisor.
Commercial and service sector: b operating rooms in hospitals b safety systems for tall buildings b computer rooms (banks, insurance companies, etc.) b lighting systems in shopping centres
PB100845
Industry: b assembly lines b engine rooms on ships b critical auxiliaries in thermal power stations
PB100847
PB100846
Infrastructures: b port and railway installations b runway lighting systems b control systems on military sites
Presentation
PB100839
PB100840
PB100842
PB100849
PB100957-62
PB100850
Presentation
Currents
From 630 to 6300 A.
Power distribution
PB100852
Currents
From 250 to 3200 A.
Loads
PB100854
Currents
From 40 to 400 A.
Presentation
QN
0 1 0
QR
0 0 1
QS1
QC
QS2
QN1
0 1 0 1 0
QN2
0 1 0 0 1
QR
0 0 1 0 0
QR
0 0 1
QR
0 0 1
Typical applications b large electrical installations (e.g. airports) b refrigeration units b special electricity tariffs b pumping stations...
Source-changeover systems
Presentation
Overview of solutions Manual source-changeover systems Interpact INS and Compact NS 40 A to 630 A Overview of solutions Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A Overview of solutions Remote-operated source-changeover systems Compact NS100/1600 100 A to 1600 A Overview of solutions Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A Manual source-changeover systems
Possible combinations
10
11 12
12
16
16 18 20
21
22 23
Associated controllers
Controller selection Controller installation BA controller BA controller - Operating sequences
24
24 25 26 27
Associated controllers
UA controller UA controller - Operating sequences
28
28 29
32 34
37 59 95
Overview of solutions Manual source-changeover systems Interpact INS and Compact NS 40 A to 630 A
Interpact
INS40 to INS80 NS100 to INS160 40 to 160 Switch-disconnectors with extended handles INS250 to INS630 INV250 to INV630 100 to 630 Switch-disconnectors
Range
Models Rating (A) Type of device
Compact
NS100 to NS250 NS400 to NS630 100 to 630 N/H/L circuit breakers NA switch-disconnectors
2 devices side-by-side
3 devices side-by-side
ON I
ON I O OFF
2 devices side-by-side
O OFF
2 devices side-by-side
2 devices side-by-side
Overview of solutions Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A
Compact
NS630b to NS1600 630 to 1600 N/H/L circuit breakers NA switch-disconnectors
Range
Models Rating (A) Type of device
Masterpact
NT06 to NT16 630 to 1600 H1/L1 circuit breakers HA switch-disconnectors NW08 to NW63 800 to 6300 N1/H1/H2/H3/L1 circuit breakers NA/HA/HF switchdisconnectors
2 devices side-by-side
I O
push push OFF
ON
discharged
O OFF
I O
push push OFF
ON
discharged
O OFF
FFO hsup
NO h sup
FFO
O
degr ahcs id
FFO hsup
NO h sup
FFO
O
degr ahcs id
DB101775
(1)
2 or 3 devices side-by-side
(2)
(1) Implemented with NS630b to NS1600 electrically-operated devices only. (2) For source-changeover systems using cables, always respect the installation conditions specified on page 19.
Range
Models Rating (A) Type of device
FFO hsup
NO h sup
FFO
O
degr ahcs id
FFO hsup
NO h sup
FFO
O
degr ahcs id
2 electrically-operated devices one above the other combined with an electrical interlocking system
2 electrically-operated devices one above the other combined with an electrical interlocking system
DB101776
The automatic controller operates the devices depending on external parameters. BA: Simple controller that manages the changeover function. UA: Controller that also manages engine generator sets. UA150 : UA controller with a communication option.
DB101776
BA controller
DB101565
(2) For source-changeover systems using cables, always respect the installation conditions specified on page 19.
10
Range
Models Rating (A) Type of device
2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1)
DB101775
The automatic controller operates the devices depending on external parameters. BA: Simple controller that manages the changeover function. UA: Controller that also manages engine generator sets. UA150: UA controller with a communication option.
DB101776
BA controller
DB101565
(1) Three devices with Masterpact NW only. (2) For source-changeover systems using cables, always respect the installation conditions specified on page 19. For other cases, please consult us.
11
A manual source-changeover system can be installed on two or three manuallyoperated and mechanically interlocked circuit breakers or switch-disconnectors. Interlocks prevent connection to both sources at the same time, even momentarily.
b b b b b b
r r
b b
r rr
INS/INV630b to 2500 b Legend: r Possible but visible break function disabled. r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
Type of device
Compact fixed or withdrawable circuit breakers NS100 to 250 NS400 to NS630 NS100 to 630
b b
b b
b b b
bp bp bp
b b b
b b b p
b b b b
b b b p b
b b b
bb bb b b p
b b b
bb bb b b p
NS630b to 1600 with b bp bb rotary handle Legend: b Fixed devices only. b Fixed or withdrawable devices. b Devices must be either both fixed or both withdrawable. p With NS400/630 rotary handle interlocking system. p Possible with NS400/630 base plate + NS100-250 adaptation kit. p Devices equipped with rotary handles.
Type of device
Cable-type, Cable-type, Cable-type, 2 devices side-by3 devices side-by2 devices one side side above the other Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism
NS630b to 1600 b b b Masterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism NT06 to 16 NW08 to 63 NT06 to NW63
b b
b b b
b b b b
b b b b
12
"Normal N"
INS250-100 Ratings 100 A INS250-160 Ratings 160 A INS200-200 Ratings 200 A INS250-250 Ratings 250 A INS320 Ratings 320 A INS400 Ratings 400 A INS500 Ratings 500 A INS630 Ratings 630 A
"Replacement" R
INS250-100 b b b b b b b b INS250-160 INS200-200 INS250-250 INS320 INS400 INS500 INS630
"Normal N"
Interlocking of two toggle-controlled devices. NS100 Ratings 16... 100 A NS160 Ratings 80...160 A NS250 Ratings 125...250 A NS400 Ratings 150... 400 A NS630 Ratings 630 A
"Replacement" R
NS100 b b b b b NS160 b b b b b NS250 b b b b b NS400 b b b b b NS630 b b b b b
13
All Interpact, Compact and Masterpact circuit breakers and switch-disconnectors from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.
DB101569
Keylock-type interlocking of two circuit breakers with rotary handles or motor mechanisms.
DB101568
(1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking system.
ON I O OFF
O OFF
NS250
NS400
NS630
NS100 Ratings 16... 100 A b b b v v NS160 Ratings 80...160 A b b b v v NS250 Ratings 125...250 A b b b v v NS400 Ratings 160... 400 A v v v b b NS630 Ratings 630 A v v v b b v 250 A and 630 A ratings can be mixed by using NS400/630 rotary handle interlocking system.
NS1000
NS1200
NS1600
NS630b Ratings 250... 630 A b b b b b NS800 Ratings 320... 800 A b b b b b NS1000 Ratings 400... 1000 A b b b b b NS1200 Ratings 480... 1200 A b b b b b NS1600 Ratings 640... 1600 A b b b b b (1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking system.
14
"Replacement" R
INS125 b b b b b b INS160 b b b b b b
"Replacement" R
INS250-100/ INV100 INS250-160/ INV160 INS250-200/ INV200 INS250-250/ INV250 INS320/ INV320 v INS400/ INV400 v INS500/ INV500 v INS630/ INV630
INS250-100/INV100 Ratings 100 A b b b b INS250-160/INV160 Ratings 160 A b b b b INS250-200/INV200 Ratings 200 A b b b b INS250-250/INV250 Ratings 250 A b b b b INS320/INV320 Ratings 320 A v v INS400/INV400 Ratings 400 A INS500/INV500 Ratings 500 A INS630/INV630 Ratings 630 A v v v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system. Possible combinations of Compact Normal and Replacement source circuit breakers
v b b b b b b b b b b b b
v b b b b
push to trip
push to trip
Interlocking of two manually-operated Compact NS devices on a base plate. Combination of Masterpact devices
DB101903
15
Electrical interlocking of two or three devices is used to create a remote-operated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation.
PB100930-67
"Normal N"
NS100 Ratings 12,5... 100 A NS160 Ratings 12,5...160 A NS250 Ratings 12,5...250 A NS400 Ratings 160... 400 A NS630 Ratings 250... 630 A
"Replacement" R
NS100 NS160 b b b b b NS250 b b b b b NS400 b b b b b NS630 b b b b b
b b b b b
DB101572
Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rods
The two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices). Combinations are possible between Compact NS630b to NS1600 devices and between Masterpact NT and Masterpact NW devices. Installation This function requires: b an adaptation fixture on the right side of each circuit breaker or switchdisconnector b a set of connecting rods with no-slip adjustments. The adaptation fixtures, connecting rods and circuit breakers or switchdisconnectors are supplied separately, ready for assembly by the customer. The maximum vertical distance between the fixing planes is 900 mm.
Possible combinations of Normal and Replacement source circuit breakers
"Normal N"
"Replacement" R
NS630b to NS1600 NT06 to NT16 NW08 to NW40 NW40b to NW63
NS630b to NS1600 Ratings 250... 1600 A NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A
b b b b b b b b b b
16
PB100842-a
For cable interlocking, the circuit breakers may be mounted one above the other or side-by-side. The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes. Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW) This function requires: b an adaptation fixture on the right side of each device b a set of cables with no-slip adjustments. The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm. Interlocking between three devices (Masterpact NW only) This function requires: b a specific adaptation fixture for each type of interlocking, installed on the right side of each device b two or three sets of cables with no-slip adjustments. The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm. Installation The adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer. Installation conditions for cable interlocking systems: b cable length: 2.5 m b radius of curvature: 100 mm b maximum number of curves: 3.
Possible combinations of Normal and Replacement source circuit breakers
"Normal N"
"Replacement" R
NS630b to NS1600 NT06 to NT16 NW08 to NW40 NW40b to NW63
NS630b to NS1600 Ratings 250... 1600 A NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A
b b b b b b b b b b
It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW) devices. All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.
Possible combinations of three device NS630b to NS1600 NS630b to NS1600 Ratings 250... 1600 A NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A NT06 to NT16 NW08 to NW40 NW40b to NW63
b b
b b
17
Range
Types of devices Types of circuit breakers Switch-disconnector version Mixing possibilities
Electrical characteristics Rating Insulating voltage Ui (V AC) Positive break indication Number of poles (N and R devices must have the same number of poles) Electrical durability Operating temperature Control characteristics Control voltage
Maximum consumption
Minimum switching time Interlocking Mechanical (see page ...) Electrical by diagram (without IVE) with IVE unit auxiliary contacts used by circuit breaker Protection and measurement Overload protection long time Short-circuit protection short time instantaneous Earth-fault protection Zone selective interlocking (ZSI) Earth-leakage protection by Vigi module by control unit by add-on Vigirex relay Current measurements Voltage, frequency, power measurements, etc. Indication and control auxiliaries Available auxiliary indication contacts Voltage releases MX shunt MN undervoltage Voltage presence indicator Voltage transformer Ammeter module Insulation monitoring module Source-changeover controller With permanent replacement source With standby generator set Remote communication via bus Device status indications Device remote control Transmission of settings Indication and identification of protection status and alarms Transmission of measurements Installation and connection Fixed front connected Fixed rear connected Withdrawable, plug-in or drawout Installation and connection accessories Downstream coupling accessory Bare-cable connectors Terminal extensions Terminal shields and inter-phase barriers Locking by padlock by keylock Front panel escutcheons
b b 1 OF + 1 SDE b b b
b b 1 OF + 1 SDE b b b b b b b
b b
2 OF + SD (+ SDV) b b b b b b
18
NS630b to NS1600 N/H/L NA all devices NS630b to 1600 N/H/L/NA fixed or plug-in 250 to 1600 A 750 b
See page 20 25 C to +70 C (50 C for 440 V - 60 Hz) 48 to 415 V - 50/60 Hz 440 V - 60 Hz 24-250 V 180 VA 180 W 800 ms
b b 1 OF + 1 CE (+ SDE) b b b b b b b b
b only with UA or BA 1 OF + 1 CE + 1 PF b b b b b b b b b 2 OF + SD b b b b b b
2 OF + SD b b
b b b b
b b b b
b b b b
b b b b b
b b b
b b b
19
INS250
3, 4 250 AC22A 250 250 15000 AC22A 1500 1500 AC23A 250 250 AC23A 1500 1500
Number of poles Conventional thermal current (A) Rated operational current (A)
lth Ie
3, 4 At 60 C 100 Electrical AC, 50/60 Hz AC22A 440-480 V 100 660-690 V 100 Mechanical 15000 Electrical AC, 50/60 Hz AC22A 440-480 V 1500 660-690 V 1500
INS320
Number of poles Conventional thermal current (A) Rated operational current (A) lth Ie 3, 4 at 60 C 320 Electrical AC, 50/60 Hz AC22A 440-480 V 320 660-690 V 320 Mechanical 10000 Electrical AC, 50/60 Hz AC22A 440-480 V 1500 660-690 V 1500 AC23A 320 320 AC23A 1500 1500
INS400
3, 4 400 AC22A 400 400 10000 AC22A 1500 1500 AC23A 400 400 AC23A 1500 1500
INS500
3, 4 500 AC22A 500 500 10000 AC22A 1500 1500 AC23A 500 500 AC23A 1500 1500
INS630
3, 4 630 AC22A 630 630 10000 AC22A 1500 1500 AC23A 630 630 AC23A 1500 1500
NS400-630
3, 4 400 to 630 8000 3000
NS630bNS1600
3, 4 630 to 1600 8000 2000
1500
1500
1500
Masterpact NT06-NT16/NW08-NW63 (1) NT06- NT12- NW08- NW20 NW25- NW50NT10 NT16 NW16 NW40 NW63
Number of poles Rated current In (A) 3, 4 630 to 1600 8000 3, 4 1250 to 1600 8000 3, 4 800 to 1600 10000 3, 4 2000 3, 4 2500 to 4000 10000 3, 4 5000 to 6300 5000
Mechanical durability 10000 (ON-CR-OR-CN cycles) 6000 10000 8000 5000 1500 Electrical durability at In 6000 NT16: (ON-CR-OR-CN cycles) 3000 for y 440 V and 480 V NEMA (2) Electrical durability at In 3000 2000 10000 6000 2500 1500 (ON-CR-OR-CN cycles) NT16: for U = 500 V to 690 V (2) 1000 (1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions. (2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2. Note: ON: opening of Normal source CR: closing of Replacement source OR: opening of Replacement source CN: closing of Normal source
20
DB101605
Possible uses
Manual source-changeover systems
INS250 (100 to 250 A) with rotary handle NS100/250 with rotary handle NS100/250 on base plate with toggle control INS400/630 (320 to 630 A) with rotary handle NS400/630 with rotary handle NS400/630 on base plate with toggle control
Downstream coupling
Possible Outgoing pitch (mm) 35 35 35 52.5 52.5 52.5 35 52.5 35 52.5
b b b b b b b b b b
21
Electrical interlocking is used with the mechanical interlocking system. It electrically interlocks the two circuit breakers and implements the time delays required for proper operation of the system. An automatic controller may be added to take into account information from the distribution system.
DB101573
IVE unit.
Necessary equipment
For Compact NS100 to 630, each circuit breaker must be equipped with: b a motor mechanism b an OF contact b an SDE contact. The components are supplied ready for assembly and the circuit breakers prewired. The prewiring must not be modified. For Compact NS630b to 1600, each circuit breaker must be equipped with: b a motor mechanism b an available OF contact b a CE connected-position contact (carriage switch) on withdrawable circuit breakers b an SDE contact. For Masterpact NT and NW, each circuit breaker must be equipped with: b a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF ready to close contact b an available OF contact b one to three CE connected-position contacts (carriage switches) on drawout circuit breakers (depending on the installation).
22
Diagram no.
51201139 51201140 51201141 51201142 51201143 51201144 51156226 51156227 51156904 51156905 51156903
Masterpact NW only
Types of mechanical interlocking
3 devices: 2 Normal sources and 1 Replacement source QN1 0 1 0 QN2 0 1 0 QR 0 0 1
DB101575
Diagram no.
51156906 51156907
3 devices: 2 Normal sources and 1 Replacement source with source selection QN1 QN2 QR 0 0 0 1 0 0 0 0 1 1 1 0 0 1 0 3 devices: 3 sources, only one device QS1 0 1 0 0 3 devices: 2 sources + 1 coupling QS2 0 0 1 0 QS3 0 0 0 1
DB101576
b automatic control with engine generator set: v without lockout after fault (with MN) v with lockout after fault (with MN)
51156908 51156909
DB101577
b electrical interlocking: v without lockout after fault v with lockout after fault
51156910 51156911
QS1 QC QS2 b electrical interlocking: 0 0 0 v without lockout after fault 1 0 1 v with lockout after fault 1 1 0 b automatic control with lockout after fault 0 1 1 (1) 1 0 0 (1) 0 0 1 (1) possible by forcing operation Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.
DB101578
23
By combining a remote-operated sourcechangeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences. These controllers can be used on sourcechangeover systems comprising 2 circuit breakers. For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the electrical diagrams section of this catalogue.
PB100855
Controller
Compatible circuit breakers
BA
UA
4-position switch
Automatic operation Forced operation on Normal source Forced operation on Replacement source Stop (both Normal and Replacement sources off)
Automatic operation
Monitoring of the Normal source and automatic transfer Generator set startup control Delayed shutdown (adjustable) of generator set Load shedding and reconnection of non-priority circuits Transfer to the Replacement source if one of the phases of the Normal phase is absent
Test
By opening the P25M circuit breaker supplying the controller By pressing the test button on the front of the controller b b b b b b b b b b b b b
Indications
Circuit breaker status indication on the front of the controller: on, off, fault trip Automatic mode indicating contact
Other functions
Selection of type of Normal source (single-phase or three-phase)
(1)
BA controller.
Voluntary transfer to Replacement source (e.g. energy management commands) During peak-tariff periods (energy management commands) forced operation on Normal sourceif Replacement source not operational Additional contact (not part of controller). Transfer to Replacement source only if contact is closed. (e.g. used to test the frequency of UR). Setting of maximum startup time for the replacement source
Options
Communication option
PB100856
Power supply
Control voltages (2) 110 V 220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz and 440 V 60 Hz 0.35 Un y voltage y 0.7 Un 0.5 Un y voltage y 0.7 Un voltage u 0.85 Un b b b b b b
Operating thresholds
Undervoltage Phase failure Voltage presence b b b b b
IP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)
Front Side Connectors UA controller. Front IP40 IP30 IP20 IK07 b b b b b b b b
24
DB101579
DB101580
25
The BA controller is used to create simple source-changeover systems that switch from one source to another depending on the presence of voltage UN on the Normal source. It is generally used to manage two permanent sources and can control Compact NS and Masterpact NT/NW circuit breakers and switch-disconnectors.
PB100858
Operating modes
A four-position switch may be used to select: b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off).
Test
It is possible to test the operation of the BA controller by turning OFF (opening) the P25M circuit breaker for the Normal source and thus simulating a failure of voltage UN.
DB101779
26
DB101582
Key UN : Normal source voltage UR : Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).
The number sends to the indicated step when the condition is true.
27
The UA controller is used to create a sourcechangeover system integrating the following automatic functions: b transfer from one source to another depending on the presence of voltage UN on the Normal source b startup of an engine generator set b shedding and reconnection of non-priority circuits b transfer to the Replacement source if one of the phases on the Normal source fails. The UA controller can control Compact NS and Masterpact NT/NW devices.
PB100858
Operating modes
A four-position switch may be used to select: b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off, then manual operation).
Distribution-system settings
Three switches are used to: b select the type of Normal source, whether single-phase or three-phase (e.g. 240 V single-phase or 240 V three-phase) b select whether to remain (or not) on the Normal source if the Replacement source is not operational during operation on special tariffs b select the maximum permissible startup time for the engine generator set during operation on special tariffs (120 or 180 seconds).
DB101778
Test
A pushbutton on the front of the controller may be used to test transfer from the Normal source to the Replacement source, then the return to the Normal source. The test lasts approximately three minutes.
28
DB101590
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN). When the UA controller is not energised, the output for generator set startup is activated).
Key UN : Normal source voltage UR : Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker
29
Switch set to the Auto position (special-tariff mode) WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN). When the UA controller is not energised, the output for generator set startup is activated).
DB101596
Key UN : Normal source voltage UR : Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker B : Penalties accepted (N ON), i.e. B = 1
The number sends to the indicated step when the condition is true.
30
Switch set to the Auto position (automatic operation and test mode).
DB101598
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN). When the UA controller is not energised, the output for generator set startup is activated).
Key UN : Normal source voltage UR : "Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker B : Penalties accepted (N ON), i.e. B = 1 (*) The test lasts 180 seconds.
The number sends to the indicated step when the condition is true.
31
Operating sequences
IVE unit
DB101600
Symbols QN : Normal Compact C circuit breaker equipped for remote operation (motor mechanism) QR : Replacement Compact C circuit breaker equipped for remote operation (motor mechanism) ON : Circuit breaker QN opening order OR : Circuit breaker QR opening order IN : Circuit breaker QN closing order IR : Circuit breaker QR closing order L1 : Faulty Normal indication LED L2 : Faulty Replacement indication LED
Note: Following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on the front of the motor mechanism is required.
32
Operating sequences
BA controller
DB101602
Inputs UN : Normal source voltage UR : Replacement source voltage KT : order for forced-operation on R KR : additional check before transfer Outputs QN : Normal source circuit breaker QR : Replacement source circuit breaker
UA controller
DB101604
Inputs UN : Normal source voltage UR : Replacement source voltage KT : order for forced-operation on R KR : additional check before transfer Outputs KG : order to the genset SH : load-shedding order QN : Normal source circuit breaker QR : Replacement source circuit breaker
Important If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out. If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is carried out later when KR status becomes I.
33
DB101928
Digipact
Modbus
Measurement Current A P H A P H Voltages, frequency, power, etc. P H P H Power quality: fundamental, harmonics H Programming of demand metering P H Fault readings Type of fault A P H Interrupted current P H Waveform capture On faults H On demand or programmed H Histories and logs Trip history P H Alarm history P H Event logs P H Indicators Counter operation A P H A P H Contact wear P H Maintenance register P H Note: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators.
34
Status indications
Normal source ON / OFF Circuit breaker ON Fault trip (SDE) Voltage presence Replacement source Circuit breaker ON Fault trip (SDE) Voltage presence Status of R voltage contact Controller Automatic mode Normal mode Replacement mode Stop mode Testing Replacement engine generator set Genset failure Genset OFF Genset ON Shedding of non-priority circuits Reconnection of non-priority circuits b b b b b b b b b b b b b b b b b b b b b b b b b
Settings
Time delay t1 for validation of UN absence Time delay t2 for validation of UN return Time delay t3 for wait between opening of N and closing of R Time delay t4 for wait between opening of R and closing of N Time delay t5 for wait between return of UN and order for genset shutdown Time delay t6 for wait before declaring genset failure Penalties accepted to avoid special tariff transfer
35
36
Source-changeover systems
Dimensions
2 7
39
39 40 42 43 44
46
46 50 52 57 59 95
37
38
Dimensions
Front-panel cut-out
Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L A 325 416 B 90 115 C 87.5 100 D 175 200 F 156 210 G 133 157 H 9.25 5 J 9 24.6 K 295 386 L 75.5 100 M 150 175 N 75 74.5 P 155 179
Front-panel cut-out
Dimensions (mm)
Type A B C INS/INV250 100/160/250 A 325 90 87.5 INS/INV320/400/500/630 416 115 100 Note: X et Y are the symmetry planes for a 3-pole device. D 175 200 F 156 210 G 106 130 H 17.5 22.5 K 295 386 L 75.5 100 M 150 175 N 75 74.5 P 131 160.4
39
Dimensions
Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L A 325 416 B 90 115 C 87.5 100 D 175 200 F 156 210 G min 185 204 G max 600 600 H 9.25 5 J 9 24.6 P 25.5 30.8 Q 25.5 30.8
Front-panel cut-out
Dimensions (mm)
Type INS40/63/80 INS100/125/160 INS/INV250 100/160/250 A INS320/400/500/630 A 325 325 325 416 B 90 90 90 115 C 87.5 87.5 87.5 100 D 175 175 175 200 F 156 156 156 210 G min 155 200 185 204 G max 396 441 600 600 H 0 0 17.5 22.5 P 25.5 25.5 25.5 30.8 Q 25.5 25.5 25.5 30.8
40
Dimensions
Front-panel cut-out
DB101619
Dimensions (mm)
Type NS630b/800/1000/1200/1600 A 411 B 63.5 C 98 D 175 F 280 G min 218 G max 605 H 25 J 24 P 25.5 Q 25.5 R 64
41
Dimensions
3 poles
DB101622
4 poles
Front-panel cut-out
DB101623
3 poles on left
DB101624
4 poles on left
Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L C2 54 92.5 C3 108 184 L 52.5 70 L16 140 185 L17 245 325 L18 280 370 R2 54 71.5 R18 89 116.5 R19 140 185 P5 83 107 P 115 144
42
Dimensions
Front-panel cut-out
DB101627
Dimensions (mm)
Type INS250 INS320/630 A 60.4 82.5 B 130.4 175 C 296 395 D 68 102.5 E 136 205 F 131 155 G 61.8 87 H 279.3 383.7 I 42 64 J 84 128 K 156 210 L 186.5 213 M 5.5 8 N 50 50
Dimensions (mm)
Type INS250 INV100/250 INS320/630 INV320/630
DB107743
A 60.4 82.5
B 130.4 175
C 295 395
E 136 205
K 156 210
L 138.5 162.5
M 631 658
N 50 75
Dimensions (mm)
Type INS250 INV100/250 INS320/630 INV320/630 P 100 150 Mmax 567.5 593 Mmin 195 220.5 Q 64 64
Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.
43
Dimensions
Dimensions
DB101630 DB101631
Connection
Dimensions (mm)
Type NS100/160/250 NS400/630 G2 118 165.9 G3 181.5 265.7 G28 238 339.5 G29 96 143.5 G30 140 188.5 G52 156 227.5 K1 35 45 K2 35 52.5 K3 51 75 K4 156 210 K8 70 113.5 K9 170 250.7 K16 8 3.75
Dimensions (mm)
Type NS100/160/250 NS400/630 L28 320 420 L29 99.5 127.5 L30 300 400 L31 89.5 117.5 L32 1 11.2 L33 123 187.5 L34 139.5 L35 74.5 96.5 L36 19.5 26 L37 87.5 115 L39 9.5 22.5 L40 140 210 T 6 6
Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.
44
Dimensions
Dimensions
DB101901 DB101902
Connection
Dimensions (mm)
Type INS250-100/160/200/250 NS320/400/500/630 G2 105.5 141 G3 169 240.7 G28 225.5 315 G29 83.5 119 G30 127.5 163.5 G52 143.5 202.5 K1 35 45 K2 35 52.5 K3 51 75 K4 156 210 K8 57.5 88.5 K9 157.5 225.7 K16 25.5 26.25
Dimensions (mm)
Type INS250-100/160/200/250 NS320/400/500/630 L28 320 420 L29 82 105 L30 300 400 L31 72 95 L32 16.5 11.2 L33 123 187.5 L34 139.5 L35 74.5 98.5 L36 21.5 26 L37 70 92.5 L39 8.5 0 L40 140 210 T 6 6
45
Dimensions
Fixed device
DB101636
Withdrawable device
Vertical mounting
DB101637 DB101638
Horizontal mounting
Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L G50 137.5 180 G51 285 360 H20 62.5 100 H21 97 152 H22 45.5 83 H23 73 123 H42 60 60 H43 120 120 H44 144.5 189 H45 300 378 H46 37 77 K25 156 210 K35 210.5 282.5 K36 300 400
Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L L31 110.5 150.5 L32 354 466 P7 25 25 P8 45 45 P9 75 100 P32 178 250 P33 143 215 P50 25 25 P52 99.5 123 P54 21 21 T9 9 9 T10 6 6 U y 32 y 32
Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.
46
Dimensions
Fixed device
Withdrawable device
DB101641
Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.
Horizontal mounting
47
Dimensions
Front-panel cut-out
Front-panel cut-out
Note for Compact NS: For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.
48
Dimensions
NS400 to NS630 as the "Normal" device, NS100 to NS250 as the "Replacement" device
Dimensions
DB101646 DB107746
Front-panel cut-out
49
Dimensions
Withdrawable devices
Withdrawable devices
50
Dimensions
Withdrawable devices
51
Dimensions
Withdrawable devices
Drawout devices
Drawout devices
52
Dimensions
Drawout devices
Drawout devices
DB101669
53
Dimensions
Withdrawable devices
Drawout devices
54
Dimensions
Drawout devices
Drawout devices
55
Dimensions
Drawout devices
56
Dimensions
57
58
Source-changeover systems
Electrical diagrams
2 7 37
60
60 61 64 72 82
91
91 94 95
59
Electrical diagrams
(1) The normal and replacement source transfer orders must be interlocked electrically. (2) Operating diagram: the SDE fault-trip signals are transmitted to the IVE unit. The SDE auxiliary contacts are mounted in the circuit breakers.
Legends ON "Normal source opening order OR "Replacement source opening order FN "Normal source closing order FR Replacement source closing order L1 Normal source fault-trip signal L2 Replacement source fault-trip signal N Normal source auxiliary wiring connector R Replacement source auxiliary wiring connector
Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.
60
Electrical diagrams
Local reset
Automatic reset
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, reverse the wires connected to terminals 82 and 84. Legends QN Normal source Compact NS equipped with motor mechanism QR Replacement source Compact NS equipped with motor mechanism SDE fault-trip indication contact IVE electrical interlocking and terminal block unit MT motor mechanism OF2 breaker ON/OFF indication contact RN reset order for breaker QN RR reset order for breaker QR
61
Electrical diagrams
Automatic reset
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, reverse the wires connected to terminals 82 and 84.
Legends QN Normal source Compact NS equipped with motor mechanism QR "Replacement source Compact NS equipped with motor mechanism MN undervoltage release OF2 breaker ON/OFF indication contact SDE fault-trip indication contact MT motor mechanism IVE electrical interlocking and terminal block unit BP emergency off button with latching KA3 auxiliary relay F1 auxiliary power supply circuit breaker
62
Electrical diagrams
Automatic reset
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, reverse the wires connected to terminals 82 and 84.
(1) Prefabricated wiring supplied (2) This source can be: b the source present in the case of voltage monitoring b an independent source. In this case, the MX release must be protected. (3) The reset orders must be delayed by 0.3 seconds.
Legends QN Normal source Compact NS equipped with motor mechanism QR Replacement source Compact NS equipped with motor mechanism SDE fault-trip indication contact OF2 breaker ON/OFF indication contact MX shunt release MT motor mechanism IVE electrical interlocking and terminal block unit KA1 time-delayed auxiliary relays KA2 time-delayed auxiliary relays F1 auxiliary power supply circuit breaker F2 auxiliary power supply circuit breaker
63
Electrical diagrams
Electrical interlocking
DB101693
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
64
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker MX shunt release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism
65
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker MN undervoltage release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR "Replacement source closing order (0.25 second delay) MT Motor Mechanism
66
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker IVE electrical interlocking and terminal block unit ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism
67
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker IVE electrical interlocking and terminal block unit MX shunt release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism
68
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 MCH spring-charging motor MX standard opening release XF standard closing release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker IVE electrical interlocking and terminal block unit MN undervoltage release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism
69
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source) MT Motor Mechanism
70
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KA3 auxiliary relays - generator set startup if UN absent KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source) MT Motor Mechanism
71
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)
72
Electrical diagrams
Electrical interlocking with lockout after a fault and emergency off by shunt release
DB101711
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends KA3 time delay for genset startup order to avoid starting the genset for transient UN disturbances QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker MX2 shunt release BP emergency off button with latching ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) BP emergency off button with latching
73
Electrical diagrams
Electrical interlocking with lockout after a fault and emergency off by undervoltage release
DB101713
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker BP emergency off button with latching S1 control switches KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)
74
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.
Legends QN "Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)
75
Electrical diagrams
Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release
DB101717
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)
76
Electrical diagrams
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
DB101719
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker BP emergency off button with latching S1 control switches KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)
77
Electrical diagrams
Automatic-control system without IVE for permanent replacement source with lockout after a fault
DB101721
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source)
78
Electrical diagrams
Automatic-control system for replacement source generator set with lockout after a fault
DB101723
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KA3 auxiliary relays - generator set startup if UN absent KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source)
79
Electrical diagrams
Automatic-control system for permanent replacement source with lockout after a fault (with MN)
DB112557
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker F2 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays KA2 auxiliary relays KA3 auxiliary relays
80
Electrical diagrams
Automatic-control system for replacement source generator set with lockout after a fault (with MN)
DB112558
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker F2 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relay KA2 time delay for genset startup order to avoid starting the genset for transient UN disturbances KA3 auxiliary relay
81
Electrical diagrams
2 Normal sources and 1 Replacement source: electrical interlocking without lockout after a fault
DB101734
Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 order for transfer from R to N1 + N2 (QN1 and QN2 closing time delay = 0.25 sec. minimum) t2 order for transfer from N1 + N2to R (QR closing time delay = 0.25 sec. minimum)
82
Electrical diagrams
2 Normal sources and 1 Replacement source: electrical interlocking with lockout after a fault
DB101766
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker S1 control switches S2 source selection switches t1 order for transfer from R to N1 + N2 (QN1 and QN2 closing time delay = 0.25 sec. minimum) t2 order for transfer from N1 + N2to R (QR closing time delay = 0.25 sec. minimumm)
83
Electrical diagrams
2 Normal sources and 1 Replacement source: automatic-control system for generator set without lockout after a fault (with MN)
DB101737
Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches S2 source selection switches KA1 auxiliary relay KA2 auxiliary relays with 10 to 180 sec. time delay KA3 auxiliary relays with 0.1 to 30 sec. time delay KA4 auxiliary relay KA5 auxiliary relays with 0.25 sec. time delay KA6 auxiliary relays with 0.25 sec. time delay
84
Electrical diagrams
2 Normal sources and 1 Replacement source: automatic-control system for generator set with lockout after a fault (with MN)
DB101739
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches S2 source selection switches KA1 auxiliary relay KA2 auxiliary relays with 10 to 180 sec. time delay KA3 auxiliary relays with 0.1 to 30 sec. time delay KA4 auxiliary relay KA5 auxiliary relays with 0.25 sec. time delay KA6 auxiliary relays with 0.25 sec. time delay KA7 auxiliary relay KA8 auxiliary relay
85
Electrical diagrams
3 sources with only 1 device closed: electrical interlocking without lockout after a fault
DB101741
Legends QS... Source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 order for transfer to Source 1 (QS1 closing time delay = 0.25 sec. minimum) t2 order for transfer to Source 2 (QS2 closing time delay = 0.25 sec. minimum) t3 order for transfer to Source 3 (QS3 closing time delay = 0.25 sec. minimum)
86
Electrical diagrams
3 sources with only 1 device closed: electrical interlocking with lockout after a fault
DB101743
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QS... Source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 order for transfer to Source 1 (QS1 closing time delay = 0.25 sec. minimum) t2 order for transfer to Source 2 (QS2 closing time delay = 0.25 sec. minimum) t3 order for transfer to Source 3 (QS3 closing time delay = 0.25 sec. minimum) KA1 auxiliary relays KA2 auxiliary relays KA3 auxiliary relays
87
Electrical diagrams
Legends QS... Source Masterpact NW QC Coupling Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 coupling order for Source 1 failure (QC closing time delay = 0.25 sec. minimum) t2 coupling order for Source 2 failure (QC closing time delay = 0.25 sec. minimum) t3 coupling order for Source 1 restored (QS1 closing time delay = 0.25 sec. minimum) t4 coupling order for Source 2 restored (QS2 closing time delay = 0.25 sec. minimum)
88
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QS... Source Masterpact NW QC Coupling Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 coupling order for Source 1 failure (QC closing time delay = 0.25 sec. minimum) t2 coupling order for Source 2 failure (QC closing time delay = 0.25 sec. minimum) t3 coupling order for Source 1 restored (QS1 closing time delay = 0.25 sec. minimum) t4 coupling order for Source 2 restored (QS2 closing time delay = 0.25 sec. minimum) KA1 auxiliary relays KA2 auxiliary relays KA3 auxiliary relays
89
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.
Legends QS... Source Masterpact NW QC Coupling Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches S2 source selection switches KA1 auxiliary relays with 10 to 180 sec. time delay KA2 auxiliary relays with 0.1 to 30 sec. time delay KA3 auxiliary relays with 10 to 180 sec. time delay KA4 auxiliary relays with 0.1 to 30 sec. time delay KA5 auxiliary relays with 0.25 sec. time delay KA6 auxiliary relays with 0.25 sec. time delay KA7 auxiliary relays with 0.25 sec. time delay
90
Electrical diagrams
Source-changeover systems with automatic controllers 2 Compact NS100/1600 or Masterpact NT/NW devices
Coupling
DB101751
DB101753
Transfer conditions
DB101755
Tests on Normal and Replacement source voltages The single-phase check for UN and UR is implemented across terminals 1 and 5 of circuit breakers Q1 and Q2.
Legends Q1 circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source Q2 circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source ACP auxiliaries control plate BA automatic controller IVE electrical interlocking and terminal block unit
Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.
91
Electrical diagrams
Source-changeover systems with automatic controllers 2 Compact NS100/1600 or Masterpact NT/NW devices
Load shedding and genset management
DB101757
DB101758
Transfer conditions
DB101759
Tests on Normal and Replacement source voltages Normal source voltage UN test
DB101761
Replacement source voltage UR test The single-phase check for UR is implemented across terminals 1 and 5 of circuit breaker Q2.
Legends Q1 circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source Q2 circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source ACP auxiliaries control plate UA automatic controller IVE electrical interlocking and terminal block unit
Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.
92
Electrical diagrams
Source-changeover systems with automatic controllers 2 Compact NS100/1600 or Masterpact NT/NW devices
Using communication functions
DB101763
Controller settings
DB101762
Tests on Normal source voltage A = 0 single-phase test, A = 1 three-phase test. Voluntary transfert (e.g. for energy management) b action in the event of genset failure B = 0 circuit breaker N opens, B = 1 circuit breaker N remains closed. b maximum permissible genset startup time (T6) C = 0 T = 120 s, C = 1 T = 180 s. After this time has elapsed, the genset is considered to have failed.
The address of the UA controller is set using the two BBus dials.
93
Electrical diagrams
ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.
Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit
94
Source-changeover systems
2 7 37 59
96
96 97 99 101
102
102
104
104 106 108 110
112
112
95
Source-changeover systems for 2 devices Interpact INS40 to INS2500 and INV100 to INV2500
DB107710
5...8
Mechanical device for INS250-100 to INS250/INV100 to INV250 equipped with a direct or extended rotary handle Mechanical device for INS/INV320 to INS/INV630 equipped with a direct or extended rotary handle
31073 31074
E89624
DB107711
E89638
E89617
31055
Manual source-changeover systems Interpact INS250 to INS2500 and INV250 to INV2500 by keylock
Interlocking
Locking device for Ronis/Profalux keylocks on INS250-100 to INS250/INV100 to INV250 Locking device for Ronis/Profalux keylocks on INS/INV320 to INS/INV630 3/4P 2x 31087 2x 31088
DB101549
E89626
2x 31291
+ Ronis 1351B.500 keylock (2 keylocks / 1 key) or + Profalux KS5 B24 D4Z keylock (2 keylocks / 1 key)
41950 42878
Connection accessories
Downstream coupling accessories
Short terminal shields
DB101062
3P 29322 32563
4P 29322 32563
E50998
29358 32619
29359 32620
29324 32583
29324 32583
96
NS100...250 NS400...630
29354 32614
NS100...250 NS400...630
29369 32621
For rotary handled or remote controlled circuit breakers 2 locks, 1 key Ronis 1351B.500 Profalux KS5 B24 D4Z
41950 42878
24 to 250 V DC
NS100...250/NS100...250 Plate + IVE (1) Plate IVE Auxiliary switches 2 OF + 2 SDE Spare wiring system (device/IVE) Back sockets option add: Only long RC Plug in base option add: Plug in kit NS400...630/NS100...630 Plate + IVE (1) Plate IVE Auxiliary switches 2 OF + 2 SDE Spare wiring system (device/IVE) Back sockets option add: Only long RC Plug in base option add: Plug in kit Adaptator kit for NS100...250 110/127 V AC 50/60 Hz
1 x 32618 220/240 V AC 50/60 Hz 29470 29363 29376 29472 29363 29378 29474 29363 29379
1 x 32618 380/415 V AC 50/60 Hz 440 V 60 Hz 29471 29364 29377 29473 29364 29380 29475 29364 29381
0 . OFF
GERIN MERLIN
multi P25M 660V AC3-IEC292-1 9
0 . OFF
660V AC3-IEC292-1
Test
Test
ACP + control unit BA (1) Plate ACP Control unit BA ACP + control unit UA (1) 29448 Plate ACP 29447 Control unit UA 29446 ACP + control unit UA150 (1) (communication option) Plate ACP Control unit UA150
97
Connection accessories
Downstream coupling accessories
Short terminal shields (1 pair)
DB101062
NS100...250/NS100...250 NS400...630/NS400...630
3P 29321 32562
4P 29322 32563
E50998
250 A 630 A
29358 32619
29359 32620
NS100...250/NS100...250 NS400...630/NS400...630
29324 32565
0 . OFF
GERIN MERLIN
multi P25M 660V AC3-IEC292-1 9
0 . OFF
660V AC3-IEC292-1
Test
Test
1 source changeover without associated control unit + 1 ACP (9) with BA control unit (10) Or + 1 ACP (9) with UA control unit (11) Or + 1 ACP (9) with UA150 control unit (11) + extension (12) for remote UA/BA connection on front of switchboard
E33423
98
33890
33910 33913
E72941
NO h sup
FFO
O
d e gr a h cs id
FFO hsup
NO h sup
FFO
O
d e gr a h cs id
E72942
NO h sup
FFO
O
d e gr ahcs id
FFO hsup
NO h sup
FFO
O
d e gr ahcs id
99
Associated controller
The automatic-control option includes: b an IVE electrical-interlocking unit b an ACP auxiliaries control plate b a BA or UA controller, depending on the required functions b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.
E88714
110/127 V AC 50/60 Hz
220/240 V AC 50/60 Hz
ACP + control unit BA (1) 29470 29471 Plate ACP 29363 29364 Control unit BA 29376 29377 ACP + control unit UA (1) 29448 29472 29473 Plate ACP 29447 29363 29364 Control unit UA 29446 29378 29380 ACP + control unit UA150 (1) (communication option) 29474 29475 Plate ACP 29363 29364 Control unit UA150 29379 29381 (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.
E33420
GERIN MERLIN
multi 9
0 . OFF
P25M
GERIN
MERLIN
multi 9
0 . OFF
660V AC3-IEC292-1
P25M
660V AC3-IEC292-1
Test
Test
100
Source-changeover systems for 2 devices (cont.) Masterpact NT circuit breakers and switch-disconnectors
Associated controller
The automatic-control option includes: b an IVE electrical-interlocking unit b an ACP auxiliaries control plate b a BA or UA controller, depending on the required functions b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.
E88714
110/127 V AC 50/60 Hz
220/240 V AC 50/60 Hz
ACP + control unit BA (1) 29470 29471 Plate ACP 29363 29364 Control unit BA 29376 29377 ACP + control unit UA (1) 29448 29472 29473 Plate ACP 29447 29363 29364 Control unit UA 29446 29378 29380 ACP + control unit UA150 (1) (communication option) 29474 29475 Plate ACP 29363 29364 Control unit UA150 29379 29381 (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.
E33420
GERIN MERLIN
multi 9
0 . OFF
P25M
GERIN
MERLIN
multi 9
0 . OFF
660V AC3-IEC292-1
P25M
660V AC3-IEC292-1
Test
Test
101
E88714
110/127 V AC 50/60 Hz
220/240 V AC 50/60 Hz
ACP + control unit BA (1) 29470 29471 Plate ACP 29363 29364 Control unit BA 29376 29377 ACP + control unit UA (1) 29448 29472 29473 Plate ACP 29447 29363 29364 Control unit UA 29446 29378 29380 ACP + control unit UA150 (1) (communication option) 29474 29475 Plate ACP 29363 29364 Control unit UA150 29379 29381 (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
E33420
GERIN MERLIN
multi 9
0 . OFF
P25M
GERIN
MERLIN
multi 9
0 . OFF
660V AC3-IEC292-1
P25M
660V AC3-IEC292-1
Test
Test
102
103
104
To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)
Connections
Front connection Standard
Rotary handles
Rear connection INS40/80 connectors INS100/160 connectors INS250 connectors 2 short 2 long Distribution 3x16v rigid/10v flexible Snap-on y 95v Distribution 4x25v rigid/16v flexible Snap-on 1.5v to 95v (< 160 A) Snap-on 10v to 185v (< 250 A) Voltage tap connector for 185v connector Clips for connectors Set of 10 Distribution 6x1.5v to 35v rigid with interphase barriers INS320/630 connectors 1 cable 35v to 300v 2 cables 35v to 240v Voltage tap connector for 185v connector Extended front handles INS40 to INS160 Black INS250 Black INS320 to INS630 Black For complete changeover assembly Red on yellow front Red on yellow front Red on yellow front INS250 INS320/630
Installation accessories
Front-panel escutcheon
"Distribloc" 125 A 160 A Multi-stage 125 A 160 A "Polybloc" 160 A 250 A Rt-angle extension Set of 3 or 4 250 A 630 A Straight extension INS250 Edgewise ext. INS630 Spreader INS250 (45 mm) Front alignment base INS320/630 52.5 mm 70 mm One-piece INS250 INS630 CU cable lugs INS100/160 For 95v cable supplied with INS250 For 120v cable 2 or 3 inter-phase For 150v cable barriers For 185v cable INS320/630 For 240v cable For 300v cable AL cable lugs INS250 For 150v cable supplied with For 185v cable 2 or 3 inter-phase INS320/630 For 240v cable barriers For 300v cable Terminal shrouds INS40/63/80 INS100/125/160 Terminal shields INS40/63/80 INS100/125/160 INS250 Short Long INS320/630 Short Long Long for 52.5 mm spreaders Interphase INS100/160 Set of 6 barriers INS250 Set of 6 INS320/630 Set of 6
Distribution blocks
105
Source-changeover systems for 2 devices Compact NS100 to NS630 / Circuitbreakers and switch-disconnectors
To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Diagram for two Compact NS devices
Without automatic control, without emergency off auxiliaries Without automatic control, with emergency off by MN Without automatic control, with emergency off by MX (no. 51201177) (no. 51201178) (no. 51201179)
Automatic-control option
Power supply 220/240 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller
106
Source-changeover systems for 2 devices Compact NS100 to NS630 / Circuitbreakers and switch-disconnectors
Communication
Communicating OF, SD, SDE or SDV auxiliary contacts Connected/disconnected position indication contacts Motor mechanism + communicating OF, SD, SDE contacts
To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)
Remote operation
Electrical operation Voltage releases Motor mechanism Instantaneous Delayed AC MX AC MN AC MN AC DC DC DC DC V V V V
Number of poles 2, 3 or 4 Number of poles tripped 2d, 3d, 3dN/2 or 4d Fixed device Front Long rear conn. connections Short rear conn. Plug-in/withdr. Plug-in Earth-leakage protection Mixed rear conn. Withdrawable ME, MH, MB, MHM Voltage V 4p MB option on 3p NS
Rotary handles
Direct Extended Indication auxiliary Black Red on yellow front MCC conversion access. CNOMO conversion access. Black Red on yellow front Telescopic handle for withdrawable device 1 early-break switch 2 early-break switches Wiring accessory for early-make switches
Locking
Toggle (1 to 3 padlocks) Removable Fixed Rotary handle Keylock adapter (keylock not included) Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z Motor mechanism Keylock adapter + Keylocks Ronis (special) NS100/250 Keylock adapter (keylock not included) NS400/630 Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z
Installation accessories
Front-panel escutcheon Toggle Rotary handle, motor mechanism, escutcheon collar; IP40 Vigi module or ammeter IP40 Vigi module Toggle cover Sealing accessories DIN rail adapter NS100/250
Connections
Rearconnect. kit Short Mixed Vigicompact Vigicompact
Long terminal-shield kit for plug-in or withdr. NS400/630 Interphase-barrier kit for plug-in or withdr. NS400/630 NS100/250 connectors Snap-on 1.5v to 95v (< 160 A) Snap-on 10v to 185v (< 250 A) Distribution 6 x 1.5v to 35v NS1400/630 connectors 1 cable 35v to 300v 2 cables 35v to 240v Right-angle terminal extensions Straight extensions NS100/250 Edgewise extensions NS400/630 Spreader NS100/250 (one piece) (45 mm) NS400/630 (52.5 mm) (70 mm) CU cable lugs NS100/250 120v 150v 185v NS400/630 240v 300v AL cable lugs NS100/250 150v 185v NS400/630 240v 300v Voltage measurement input for lugs NS100/250 y 185v for connector for lugs NS400/630 Terminal NS100/250 Short Long shields NS400/630 Short Long Long for 52.5 mm spreaders Interphase barriers Set of 6 Insulation kit > 600 V Without spreaders NS400/630 With 52.5 mm spreaders 2 insulating NS100/250 screens: NS400/630 52.5 pitch 70 pitch
Parts of plug-in
107
Source-changeover systems for 2 devices Compact NS630b to NS1600 / Circuitbreakers and switch-disconnectors
0
To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Diagram for two Compact NS devices
Electrical interlocking with lockout after fault: Permanent replacement source (without IVE) With emergency off by MX (without IVE) With emergency off by MN (without IVE) Permanent replacement source (with IVE) With emergency off by MX (with IVE) With emergency off by MN (with IVE) Automatic control without lockout after fault: Permanent replacement source (without IVE) Engine generator set (without IVE)
(no. 51201180) (no. 51201181) (no. 51201182) (no. 51201183) (no. 51201184) (no. 51201185) (no. 51201186) (no. 51201187)
Automatic-control option
Power supply 110 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller Power supply 220/240 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller
108
Source-changeover systems for 2 devices Compact NS630b to NS1600 / Circuitbreakers and switch-disconnectors
Indication contacts
SD trip indication (maximum 1) 6 A-240 V AC Low level SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices) 6 A-240 V AC Low level OF ON/OFF indication contacts (maximum 3) 6 A-240 V AC qty Low level qty Carriage switches (possible combinations: 3 CE, 2 CD, 1 CT) CE - "connected" position 6 A-240 V AC qty CD - "disconnected" position 6 A-240 V AC qty CT - "test" position 6 A-240 V AC qty Auxiliary terminals for chassis alone 3-wire terminal (30 parts) Low level qty Low level qty Low level qty Jumpers (set of 10) 6-wire terminal (10 parts) Communicating DC DC DC Adjustable
To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)
Remote operation
Electrical operation Voltage releases Standard Power supply MX MN MN delay unit AC AC AC V V V Nonadjustable
2.0 5.0 6.0 7.0 AD - external power-supply module V TCE - external sensor (CT) for neutral protection Rectangular sensor 280 x 115 mm TCW - external sensor for SGR protection LR - long-time rating plug Standard 0.4 to 1 Ir Low setting 0.4 to 0.8 Ir High setting 0.8 to 1 Ir LT OFF
Locking
Toggle (1 to 3 padlocks) Rotary handle using a keylock For electrically operated devices
Communication
COM module Jbus/ Modbus Digipact Manual operation Electrical operation Manual operation Electrical operation
Connections
Horizontal rear connections Vertical rear connections Front connections 4x240v bare cable connectors + shields Long connection shields Vertical-connection adapters Cable-lug adapters Arc chute screen Interphase barriers Spreaders VO - safety shutters on chassis Top Top Top NS - FC fixed NS - FC fixed NS - FC fixed, withdr. VPEC - door interlock NS - FC fixed, withdr. NS - FC fixed NS - FC fixed, withdr. NS - FC fixed, withdr. NS - FC fixed VPOC - racking interlock VDC - mismatch protection Bottom Bottom Bottom
Keylock kit (without keylock) VBP - ON/OFF pushbutton locking OFF position locking: VCPO - by padlocks VSPO - by keylocks Keylock kit (w/o keylock) Profalux 1 keylock Profalux Profalux
2 identical keylocks, 1 key Chassis locking in "disconnected" position: VSPD - by keylocks Keylock kit (w/o keylock)
Profalux Ronis Kirk Castell 1 keylock Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis 2 keylocks, different keys Profalux Ronis Optional connected/disconnected/test position locking On right-hand side of chassis On left-hand side of chassis
Accessories
CDM - mechanical operation counter CDP - escutcheon CP - transparent cover for escutcheon OP - blanking plate for escutcheon Mounting brackets for fixed NS Test kits Mini test kit
109
Interlocking using connecting rods (NT/NW devices one above the other)
Select a complete set including two adaptation fixtures and the connecting rods Complete set for: 2 drawout NT devices 2 fixed NT devices 2 drawout NW devices 2 fixed NW devices 1 fixed NT device + 1 fixed NW devices 1 drawout NT device + 1 drawout NW device
Interlocking using cables (NT/NW devices one above the other or side-by-side)
Select two adaptation fixtures (one for each device) and a set of two cables Adaptation fixture for: 1 fixed NT device (NT/NW fixed and drawout 1 drawout NT device devices may be mixed) 1 fixed NW device 1 drawout NW device 1 set of 2 cables (for two devices) qty qty qty qty
Automatic-control option
Power supply 220/240 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller ACP + BA controller ACP + UA controller ACP + UA150 controller
110
To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)
Remote operation
Remote ON/OFF MCH - gear motor XF - closing voltage release MX - opening voltage release PF - "ready to close" contact
Remote tripping
BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option MN - undervoltage release R - delay unit (non-adjustable) Rr - adjustable delay unit 2nd MX - shunt release
Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks) OFF position locking: VCPO - by padlocks VSPO - by keylocks Keylock kit (w/o keylock) Profalux Kirk 1 keylock Profalux 2 identical keylocks, 1 key Profalux 2 keylocks, different keys (NW) Profalux Chassis locking in "disconnected" position: VSPD - by keylocks Keylock kit (w/o keylock) Profalux Kirk
Standard 0.4 to 1 Ir Low setting 0.4 to 0.8 Ir High setting 0.8 to 1 Ir LT OFF PTE - external voltage measurement input (required for reverse supply) BAT - battery module
Communication
Eco COM module Modbus (for switchboard display units)
Connections
Horizontal Vertical Front Vertical-connection adapters Cable-lug adapters Arc chute screen Interphase barriers Spreaders Disconnectable front connection adapter Lugs for 240v or 300v cables VO - safety shutters on chassis VIVC - shutter position indication and locking Top Bottom Top Bottom Top Bottom NT - FC fixed, draw. NT - FC fixed, draw. NT - FC fixed NT, NW fixed, draw. NT fixed, drawout NW fixed NT fixed, draw. NT, NW NW
1 keylock Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis 2 keylocks, different keys Profalux Ronis Optional connected/disconnected/test position locking On right-hand side of chassis On left-hand side of chassis
VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection
Accessories
CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover for escutcheon OP - blanking plate for escutcheon Brackets for mounting NW fixed Test kits Mini test kit
111
Interlocking using cables (NW devices one above the other or side-by-side)
Select a complete set including three adaptation fixtures and the cables 1 complete set for: 3 sources / 1 device ON, fixed or drawout 2 sources + 1 coupling, fixed or drawout 2 sources + 1 replacement source, fixed or drawout
112
To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)
Remote operation
Remote ON/OFF MCH - gear motor XF - closing voltage release MX - opening voltage release PF - "ready to close" contact
Low level
Remote tripping
6 A-240 V AC BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option MN - undervoltage release R - delay unit (non-adjustable) Rr - adjustable delay unit 2eme MX - shunt release
V V
Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks) OFF position locking: VCPO - by padlocks VSPO - by keylocks Keylock kit (w/o keylock) Profalux Kirk 1 keylock Profalux 2 identical keylocks, 1 key Profalux 2 keylocks, different keys (NW) Profalux Chassis locking in "disconnected" position: VSPD - by keylocks Keylock kit (w/o keylock) Bottom Bottom Bottom VPEC - door interlock Profalux Kirk
Communication
Eco COM module Modbus (for switchboard display units)
Connections
Horizontal Vertical Front Interphase barriers Disconnectable front connection adapter Top Top Top Fixed, drawout Fixed
1 keylock Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis 2 keylocks, different keys Profalux Ronis Optional connected/disconnected/test position locking On right-hand side of chassis On left-hand side of chassis
VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection
Accessories
CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover for escutcheon OP - blanking plate for escutcheon Brackets for mounting NW fixed Test kits Mini test kit
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Printed on recycled paper. Design: Schneider Electric Photos: Schneider Electric Printed: JPF - Imprimerie du Pont de Claix - Made in France
ABTED201149EN
09-2007