Compact, Interpact and Masterpact Source changeover system

Catalogue

2007

To ensure a continuous supply of electrical power, certain installations are connected to two sources: b a normal source N b a replacement source R used to supply the installation when the normal source is unavailable. A source-changeover system switches the load between these two sources. It can be automated to manage transfers according to external conditions. A source-changeover system includes two or three circuit breakers or switch-disconnectors. With Interpact INS, Compact NS and Masterpact NT and NW, new installation solutions are available to optimise the size of the switchboard and simplify installation.

PB100839

Interlocking of two Interpact switch-disconnectors via rotary handles.

PB100840

Complete source-changeover assembly with two Interpact switch-disconnectors.

PB100930-68

Interlocking of two Compact NS circuit breakers on a base plate.

PB100842

Interlocking of two Masterpact NT and NW circuit breakers using cables.

Source-changeover systems

General content

Presentation

Functions and characteristics

Dimensions

37

Electrical diagrams

59

Catalogue numbers and order forms

95

Presentation

For maximum continuity of service ...

Manual source-changeover system


This is the most simple type. It is controlled manually by an operator and consequently the time required to switch from the normal to the replacement source can vary. A manual source-changeover system is made up of two or three mechanically interlocked manually-operated circuit breakers or switch-disconnectors.
PB100843

Remote-operated source-changeover system


This is the most commonly employed system for devices with high ratings (above 400 A). No human intervention is required. Transfer from the normal to the replacement source is controlled electrically. A remote-controlled source-changeover system is made up of two or three circuit breakers or switch-disconnectors linked by an electrical interlocking system that may have different configurations. In addition, a mechanical interlocking system protects against electrical malfunctions or incorrect manual operations.

Automatic source-changeover systems


PB100844

An automatic controller may be added to a remote-operated source-changeover system for automatic source control according to programmable operating modes. This solution ensures optimum energy management: b transfer to a replacement source according to external requirements b management of power sources b regulation b emergency source replacement, etc. The automatic controller may be fitted with an option for communication with a supervisor.
Commercial and service sector: b operating rooms in hospitals b safety systems for tall buildings b computer rooms (banks, insurance companies, etc.) b lighting systems in shopping centres

PB100845

Industry: b assembly lines b engine rooms on ships b critical auxiliaries in thermal power stations

PB100847

PB100846

Infrastructures: b port and railway installations b runway lighting systems b control systems on military sites

Presentation

... in a wide range of applications

PB100839

Interlocking of two Interpact switch-disconnectors via rotary handles.

PB100840

PB100842

Interlocking of two Masterpact NT and NW circuit breakers using cables.

PB100849

Complete source-changeover assembly with two Interpact switch-disconnectors.

PB100957-62

Interlocking of two Compact NS circuit breakers on a base plate.

Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

PB100850

Interlocking of three Masterpact NW circuit breakers using cables.

Other source-changeover systems: Telemecanique products


PB100848 PB100851

See LC2-D series.

See LC2-F series.

Presentation

For maximum continuity of service...

Incoming feeders and main LV switchboards


DB101543 PB100853

Currents
From 630 to 6300 A.

Power distribution
PB100852

Currents
From 250 to 3200 A.

Loads
PB100854

Currents
From 40 to 400 A.

Presentation

... in a wide range of applications

1 normal source 1 replacement source


DB101538 DB101539

2 sources with coupler on busbars


DB101540

2 normal sources 1 replacement source

QN
0 1 0

QR
0 0 1

QS1

QC

QS2

QN1
0 1 0 1 0

QN2
0 1 0 0 1

QR
0 0 1 0 0

0 0 0 1 0 1 1 1 0 0 1 1 1 0 0 (1) 0 0 1 (1) (1) possible by forcing operation.

Generator or permanent source QN


0 1 0
DB101541

QR
0 0 1

Typical applications: b continuous production processes b operating rooms b computer rooms...

Generator or permanent source


DB101541

Generator or permanent source QN


0 1 0
DB101544

QR
0 0 1

Typical applications b large electrical installations (e.g. airports) b refrigeration units b special electricity tariffs b pumping stations...

Source-changeover systems

Functions and characteristics

Presentation

Overview of solutions Manual source-changeover systems Interpact INS and Compact NS 40 A to 630 A Overview of solutions Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A Overview of solutions Remote-operated source-changeover systems Compact NS100/1600 100 A to 1600 A Overview of solutions Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A Manual source-changeover systems
Possible combinations

10

11 12
12

Remote-operated source-changeover systems


Mechanical interlocking General characteristics Mechanical and electrical durability

16
16 18 20

Connection and insulation accessories for Compact NS and INS y 630 A


Electrical interlocking Standard configurations

21
22 23

Associated controllers
Controller selection Controller installation BA controller BA controller - Operating sequences

24
24 25 26 27

Associated controllers
UA controller UA controller - Operating sequences

28
28 29

Operating sequences COM communications option


Dimensions Electrical diagrams Catalogue numbers and order forms

32 34
37 59 95

Functions and characteristics

Overview of solutions Manual source-changeover systems Interpact INS and Compact NS 40 A to 630 A
Interpact
INS40 to INS80 NS100 to INS160 40 to 160 Switch-disconnectors with extended handles INS250 to INS630 INV250 to INV630 100 to 630 Switch-disconnectors

Range
Models Rating (A) Type of device

Compact
NS100 to NS250 NS400 to NS630 100 to 630 N/H/L circuit breakers NA switch-disconnectors

Manual source-changeover systems


Interlocking via toggles
DB101768 DB101545

2 devices side-by-side

3 devices side-by-side

Interlocking via rotary handles


DB101769 DB101546 DB101547 DB101548
N
.4 2

ON I

ON I O OFF

2 devices side-by-side

O OFF

Interlocking via keylocks with captive keys


DB101770 DB101549 DB101550 DB101551

A number of different devices

Interlocking on a base plate


DB101771

2 devices side-by-side

Complete source-changeover assemblies


DB101772 DB101552

2 devices side-by-side

Functions and characteristics

Overview of solutions Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A
Compact
NS630b to NS1600 630 to 1600 N/H/L circuit breakers NA switch-disconnectors

Range
Models Rating (A) Type of device

Masterpact
NT06 to NT16 630 to 1600 H1/L1 circuit breakers HA switch-disconnectors NW08 to NW63 800 to 6300 N1/H1/H2/H3/L1 circuit breakers NA/HA/HF switchdisconnectors

Manual source-changeover systems


Interlocking via extended rotary handles
DB101769 DB101553

2 devices side-by-side

Interlocking via keylocks with captive keys


DB101770 DB101554 DB101555 DB101556 DB101562 DB101559

I O
push push OFF

ON

discharged

O OFF

I O
push push OFF

ON

discharged

O OFF

A number of different devices

Mechanical interlocking using connecting rods


DB101773 DB101557 DB101558 DB101561

FFO hsup

NO h sup

FFO

O
degr ahcs id

FFO hsup

NO h sup

FFO

O
degr ahcs id

2 devices one above the other


(1)

Mechanical interlocking using cables


DB101774 DB101560

2 or 3 devices one above the other

DB101775

(1)

2 or 3 devices side-by-side

(2)

For this case and other cases, please consult us


DB101916

(1) Implemented with NS630b to NS1600 electrically-operated devices only. (2) For source-changeover systems using cables, always respect the installation conditions specified on page 19.

Functions and characteristics

Overview of solutions Remote-operated sourcechangeover systems Compact NS100/1600 100 A to 1600 A


Compact
NS100 to NS630 100 to 630 N/H/L circuit breakers NA switch-disconnectors NS630b to NS1600 630 to 1600 N/H/L circuit breakers NA switch-disconnectors

Range
Models Rating (A) Type of device

Remote-operated source-changeover system


Mechanical interlocking on base plate + electrical interlocking
DB101771 DB101563

2 electrically-operated devices side-by-side combined with an electrical interlocking system

Mechanical interlocking using connecting rods + electrical interlocking


DB101773 DB101557

FFO hsup

NO h sup

FFO

O
degr ahcs id

FFO hsup

NO h sup

FFO

O
degr ahcs id

2 electrically-operated devices one above the other combined with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking


DB101777 DB101560

2 electrically-operated devices one above the other combined with an electrical interlocking system
DB101776

2 electrically-operated devices side-by-side combined with an electrical interlocking system


(2)

Automatic source-changeover systems


Remote-operated source-changeover system combined with an automatic-control system
DB101777 DB101564

The automatic controller operates the devices depending on external parameters. BA: Simple controller that manages the changeover function. UA: Controller that also manages engine generator sets. UA150 : UA controller with a communication option.

DB101776

BA controller

DB101565

UA and UA150 controller

(2) For source-changeover systems using cables, always respect the installation conditions specified on page 19.

10

Functions and characteristics

Overview of solutions Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A


Masterpact
NT06 to NT16 630 to 1600 H1/L1 circuit breakers HA switch-disconnectors NW08 to NW63 800 to 6300 N1/H1/H2/H3/L1 circuit breakers NA/HA/HF switch-disconnectors

Range
Models Rating (A) Type of device

Remote-operated source-changeover system


Mechanical interlocking using connecting rods + electrical interlocking
DB101773 DB101558 DB101559 DB101562

2 electrically-operated devices side-by-side combined with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking


DB101774 DB101561

2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1)

DB101775

2 or 3 electrically-operated devices side-by-side combined with an electrical interlocking system (1)


(2)

Automatic source-changeover systems


Remote-operated source-changeover system combined with an automatic-control system
DB101777 DB101564

The automatic controller operates the devices depending on external parameters. BA: Simple controller that manages the changeover function. UA: Controller that also manages engine generator sets. UA150: UA controller with a communication option.

DB101776

BA controller

DB101565

UA and UA150 controller

(1) Three devices with Masterpact NW only. (2) For source-changeover systems using cables, always respect the installation conditions specified on page 19. For other cases, please consult us.

11

Functions and characteristics

Manual source-changeover systems Possible combinations


All possibilities for manual source-changeover systems
Type of device Type of interlocking for two devices
Keylock Direct rotary handle Extended rotary handle Complete assembly Interpact switch-disconnectors INS40 to INS160 INS250-100 to INS630 INV100 to 630

A manual source-changeover system can be installed on two or three manuallyoperated and mechanically interlocked circuit breakers or switch-disconnectors. Interlocks prevent connection to both sources at the same time, even momentarily.

b b b b b b
r r

b b

r rr

INS/INV630b to 2500 b Legend: r Possible but visible break function disabled. r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Type of device

Type of interlocking for two devices


Toggle Keylock Direct rotary handle Extended rotary handle On base plate On base plate (toggle or direct extended (motor mechanism) rotary control)

Compact fixed or withdrawable circuit breakers NS100 to 250 NS400 to NS630 NS100 to 630

b b

b b

b b b

bp bp bp

b b b

b b b p

b b b b

b b b p b

b b b

bb bb b b p

b b b

bb bb b b p

NS630b to 1600 with b bp bb rotary handle Legend: b Fixed devices only. b Fixed or withdrawable devices. b Devices must be either both fixed or both withdrawable. p With NS400/630 rotary handle interlocking system. p Possible with NS400/630 base plate + NS100-250 adaptation kit. p Devices equipped with rotary handles.

Type of device

Type of interlocking for either all fixed or all withdrawable devices


Keylock Cable-type, 3 devices one above another Rod-type, 3 devices one above another

Cable-type, Cable-type, Cable-type, 2 devices side-by3 devices side-by2 devices one side side above the other Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism

NS630b to 1600 b b b Masterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism NT06 to 16 NW08 to 63 NT06 to NW63

b b

b b b

b b b b

b b b b

12

Functions and characteristics

Manual source-changeover systems Possible combinations

All possibilities for manual source-changeover systems


DB101571

Complete source-changeover assembly for two switchdisconnectors


These assemblies provide an easy way to implement source changeover functions with: b a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON) b a smaller size, taking up less room in the switchboard. A complete source changeover assembly can be ordered with a single catalogue number.

Complete source-changeover assembly for two Interpact INS switch-disconnectors.

"Normal N"
INS250-100 Ratings 100 A INS250-160 Ratings 160 A INS200-200 Ratings 200 A INS250-250 Ratings 250 A INS320 Ratings 320 A INS400 Ratings 400 A INS500 Ratings 500 A INS630 Ratings 630 A

"Replacement" R
INS250-100 b b b b b b b b INS250-160 INS200-200 INS250-250 INS320 INS400 INS500 INS630

Possible combinations of Normal and Replacement source circuit breakers

Interlocking of two or three toggle-controlled devices


Two devices can be interlocked using this system. Two identical interlocking systems can be used to interlock three devices installed side by side, in which case one device is in the ON position and the two others are in the OFF position. Devices must all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout. The system is locked using one or two padlocks (shackle diameter 5 to 8 mm). Two interlocking system models are available for: b Compact NS100 to 250 b Compact NS400 to 630.
DB101566

"Normal N"
Interlocking of two toggle-controlled devices. NS100 Ratings 16... 100 A NS160 Ratings 80...160 A NS250 Ratings 125...250 A NS400 Ratings 150... 400 A NS630 Ratings 630 A

"Replacement" R
NS100 b b b b b NS160 b b b b b NS250 b b b b b NS400 b b b b b NS630 b b b b b

13

Functions and characteristics

Manual source-changeover systems Possible combinations

Combination of Normal and Replacement devices

All Interpact, Compact and Masterpact circuit breakers and switch-disconnectors from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.

DB101569

Interlocking of a number of devices using keylocks (captive keys)


Interlocking is based on two identical keylocks with a single key and a keylock adapter (different for each device). This solution enables interlocking between two devices that are physically distant or that have very different characteristics, for example between a low and a medium-voltage device, or between Compact NS circuit breakers and switch-disconnectors. A system of wall-mounted captive key boxes makes possible a large number of combinations between many devices.

Keylock-type interlocking of two circuit breakers with rotary handles or motor mechanisms.

Possible combinations of Normal and Replacement source circuit breakers

Interlocking of two devices with rotary handles


The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.
ON I

DB101568

(1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking system.

ON I O OFF

O OFF

"Normal N" "Replacement" R NS160 Compact NS100/630 (1) NS100

NS250

NS400

NS630

Interlocking of two Compact NS circuit breakers with rotary handles.

NS100 Ratings 16... 100 A b b b v v NS160 Ratings 80...160 A b b b v v NS250 Ratings 125...250 A b b b v v NS400 Ratings 160... 400 A v v v b b NS630 Ratings 630 A v v v b b v 250 A and 630 A ratings can be mixed by using NS400/630 rotary handle interlocking system.

"Normal N" "Replacement" R NS800 Compact NS630/1600(1) NS630b

NS1000

NS1200

NS1600

NS630b Ratings 250... 630 A b b b b b NS800 Ratings 320... 800 A b b b b b NS1000 Ratings 400... 1000 A b b b b b NS1200 Ratings 480... 1200 A b b b b b NS1600 Ratings 640... 1600 A b b b b b (1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking system.

14

Functions and characteristics

Manual source-changeover systems Possible combinations

Possible combinations of Normal and Replacement source switch-disconnectors

Interlocking of two devices with rotary handles


The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.
INS40 INS63 INS80 INS100 INS40 Ratings 40 A b b b b INS63 Ratings 63 A b b b b INS80 Ratings 80 A b b b b INS100 Ratings 100 A b b b b INS125 Ratings 125 A b b b b INS160 Ratings 160 A b b b b (1) With extended rotary handles only. (2) Possible with INV, but visible-break function is significantly impaired.
DB107742

"Normal N" Interpact INS (1)

"Replacement" R
INS125 b b b b b b INS160 b b b b b b

Interlocking of two Interpact switch-disconnectors with direct rotary handles.

"Normal N" Interpact INS /INV (2)

"Replacement" R
INS250-100/ INV100 INS250-160/ INV160 INS250-200/ INV200 INS250-250/ INV250 INS320/ INV320 v INS400/ INV400 v INS500/ INV500 v INS630/ INV630

INS250-100/INV100 Ratings 100 A b b b b INS250-160/INV160 Ratings 160 A b b b b INS250-200/INV200 Ratings 200 A b b b b INS250-250/INV250 Ratings 250 A b b b b INS320/INV320 Ratings 320 A v v INS400/INV400 Ratings 400 A INS500/INV500 Ratings 500 A INS630/INV630 Ratings 630 A v v v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system. Possible combinations of Compact Normal and Replacement source circuit breakers

v b b b b b b b b b b b b

v b b b b

Interlocking of two devices on a base plate


A base plate is available for mechanical interlocking of two manually-operated Compact circuit breakers or switch-disconnectors. "Normal N" "Replacement" R
NS100 NS100 Ratings 16... 100 A NS160 Ratings 80... 160 A NS250 Ratings 125... 250 A NS400 Ratings 150... 400 A NS630 Ratings 630 A b b b b b NS160 b b b b b NS250 b b b b b NS400 b b b b b NS630 b b b b b
DB101570

push to trip

push to trip

Interlocking of two manually-operated Compact NS devices on a base plate. Combination of Masterpact devices

DB101903

Interlocking of a number of devices using keylocks (captive keys)


Interlocking uses two identical keylocks with a single key. This solution enables interlocking between two devices that are physically distant or that have significantly different characteristics.

15

Functions and characteristics

Remote-operated source-changeover systems Mechanical interlocking

Electrical interlocking of two or three devices is used to create a remote-operated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation.
PB100930-67

Interlocking of two Compact NS100 to 630 devices using a base plate


A base plate designed for two Compact circuit breakers can be installed horizontally or vertically on a mounting rail. Interlocking is carried out on the base plate by a mechanism located behind the breakers. Access to the circuit breaker controls and trip units is conserved. Circuit breakers must be fixed or plug-in versions, with or without earth-leakage protection or measurement modules. The base plate and the circuit breakers are supplied separately. b base plate for Compact NS100 to 250 devices This base plate is intended for two Compact NS100 to 250 devices. b base plate for Compact NS400 to 630 devices This base plate is intended for two Compact NS400 to 630 devices. It may also be used, without any modifications, to interlock a fixed Compact NS100 to 250 with a Compact NS400 or 630 device. An adapter kit is required for plug-in versions of the Compact NS100 to 250 devices. Compact NS100 to 250 devices, in both fixed and plug-in versions, may be equipped with spreaders.
Possible combinations of Normal and Replacement Compact source circuit breakers

"Normal N"
NS100 Ratings 12,5... 100 A NS160 Ratings 12,5...160 A NS250 Ratings 12,5...250 A NS400 Ratings 160... 400 A NS630 Ratings 250... 630 A

"Replacement" R
NS100 NS160 b b b b b NS250 b b b b b NS400 b b b b b NS630 b b b b b

Interlocking of two electrically-operated Compact NS circuit breakers using a base plate.

b b b b b

DB101572

Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rods
The two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices). Combinations are possible between Compact NS630b to NS1600 devices and between Masterpact NT and Masterpact NW devices. Installation This function requires: b an adaptation fixture on the right side of each circuit breaker or switchdisconnector b a set of connecting rods with no-slip adjustments. The adaptation fixtures, connecting rods and circuit breakers or switchdisconnectors are supplied separately, ready for assembly by the customer. The maximum vertical distance between the fixing planes is 900 mm.
Possible combinations of Normal and Replacement source circuit breakers

"Normal N"

"Replacement" R
NS630b to NS1600 NT06 to NT16 NW08 to NW40 NW40b to NW63

Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

NS630b to NS1600 Ratings 250... 1600 A NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A

b b b b b b b b b b

16

Functions and characteristics

Remote-operated source-changeover systems Mechanical interlocking


Interlocking of two Compact NS630b to 1600 or two Masterpact NT/NW or up to three Masterpact NW devices using cables

PB100842-a

For cable interlocking, the circuit breakers may be mounted one above the other or side-by-side. The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes. Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW) This function requires: b an adaptation fixture on the right side of each device b a set of cables with no-slip adjustments. The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm. Interlocking between three devices (Masterpact NW only) This function requires: b a specific adaptation fixture for each type of interlocking, installed on the right side of each device b two or three sets of cables with no-slip adjustments. The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm. Installation The adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer. Installation conditions for cable interlocking systems: b cable length: 2.5 m b radius of curvature: 100 mm b maximum number of curves: 3.
Possible combinations of Normal and Replacement source circuit breakers

Interlocking of two Masterpact circuit breakers using cables.

"Normal N"

"Replacement" R
NS630b to NS1600 NT06 to NT16 NW08 to NW40 NW40b to NW63

NS630b to NS1600 Ratings 250... 1600 A NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A

b b b b b b b b b b

It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW) devices. All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.
Possible combinations of three device NS630b to NS1600 NS630b to NS1600 Ratings 250... 1600 A NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A NT06 to NT16 NW08 to NW40 NW40b to NW63

b b

b b

Only Masterpact NW may be used for three-device combinations.

Types of mechanical interlocking and combinations


See page 10 to page 15.

17

Functions and characteristics

Remote-operated source-changeover systems General characteristics


Compact
NS100 to NS250 N/H/L NA all devices NS100 to NS250 N/H/L/NA fixed or plug-in 15 to 250 A 750 b 3, 4 See page 20 25 C to +70 C (50 C for 440 V - 60 Hz) AC DC AC DC 48 to 415 V - 50/60 Hz 440 V - 60 Hz 24-250 V 500 VA 500 W 800 ms NS400 to NS630 N/H/L NA all devices NS100 to NS630 N/H/L/NA fixed or plug-in 15 to 630 A 750 b

Range
Types of devices Types of circuit breakers Switch-disconnector version Mixing possibilities

Electrical characteristics Rating Insulating voltage Ui (V AC) Positive break indication Number of poles (N and R devices must have the same number of poles) Electrical durability Operating temperature Control characteristics Control voltage

Maximum consumption

Minimum switching time Interlocking Mechanical (see page ...) Electrical by diagram (without IVE) with IVE unit auxiliary contacts used by circuit breaker Protection and measurement Overload protection long time Short-circuit protection short time instantaneous Earth-fault protection Zone selective interlocking (ZSI) Earth-leakage protection by Vigi module by control unit by add-on Vigirex relay Current measurements Voltage, frequency, power measurements, etc. Indication and control auxiliaries Available auxiliary indication contacts Voltage releases MX shunt MN undervoltage Voltage presence indicator Voltage transformer Ammeter module Insulation monitoring module Source-changeover controller With permanent replacement source With standby generator set Remote communication via bus Device status indications Device remote control Transmission of settings Indication and identification of protection status and alarms Transmission of measurements Installation and connection Fixed front connected Fixed rear connected Withdrawable, plug-in or drawout Installation and connection accessories Downstream coupling accessory Bare-cable connectors Terminal extensions Terminal shields and inter-phase barriers Locking by padlock by keylock Front panel escutcheons

500 VA 500 W 800 ms

b b 1 OF + 1 SDE b b b

b b 1 OF + 1 SDE b b b b b b b

b b

OF + SD (+ SDV) b b b b b b b BA controller b UA controller b

2 OF + SD (+ SDV) b b b b b b

b (long rear connections) b (plug-in on base) b b b b b b

b (long rear connections) b (plug-in on base) b b b b b b b

18

Functions and characteristics

Remote-operated source-changeover systems General characteristics


Masterpact

NS630b to NS1600 N/H/L NA all devices NS630b to 1600 N/H/L/NA fixed or plug-in 250 to 1600 A 750 b

NT06 to 16 N1 / H1 / H2 / H3 / L1 NA / HA / HF all mixing possibilities (fixed, drawout or fixed + drawout) N1/H1/H2/H3/L1/NA/HA/HF

NW08 to 63 N1 / H1 / H2 / H3 / L1 NA / HA / HF all mixing possibilities (fixed, drawout or fixed + drawout) N1/H1/H2/H3/L1/NA/HA/HF

600 to 1600 A 1000 b 3, 4

800 to 6300 A 1000 b

See page 20 25 C to +70 C (50 C for 440 V - 60 Hz) 48 to 415 V - 50/60 Hz 440 V - 60 Hz 24-250 V 180 VA 180 W 800 ms

180 VA 180 W 800 ms

180 VA 180 W 800 ms

b b 1 OF + 1 CE (+ SDE) b b b b b b b b

b only with UA or BA 1 OF + 1 CE + 1 PF b b b b b b b b b 2 OF + SD b b b b b b b BA controller b UA controller

b only with UA or BA 1 OF + 1 CE + 1 PF b b b b b b b b b 2 OF + SD b b b b b b

2 OF + SD b b

b b b b

b b b b

b b b b

b (vertical or horizontal) b (drawout)

b (vertical or horizontal) b (drawout)

b (vertical or horizontal) b (drawout)

b b b b b

b b b

b b b

19

Functions and characteristics

Remote-operated source-changeover systems Mechanical and electrical durability


Interpact INS switch-disconnectors INS250-100 INS250-160 INS250-200

INS250
3, 4 250 AC22A 250 250 15000 AC22A 1500 1500 AC23A 250 250 AC23A 1500 1500

Number of poles Conventional thermal current (A) Rated operational current (A)

lth Ie

Durability (category A) (ON-CR-OR-CN cycles)

3, 4 At 60 C 100 Electrical AC, 50/60 Hz AC22A 440-480 V 100 660-690 V 100 Mechanical 15000 Electrical AC, 50/60 Hz AC22A 440-480 V 1500 660-690 V 1500

AC23A 100 100 AC23A 1500 1500

3, 4 160 AC22A 160 160 15000 AC22A 1500 1500

AC23A 160 160 AC23A 1500 1500

3, 4 200 AC22A 200 200 15000 AC22A 1500 1500

AC23A 200 200 AC23A 1500 1500

INS320
Number of poles Conventional thermal current (A) Rated operational current (A) lth Ie 3, 4 at 60 C 320 Electrical AC, 50/60 Hz AC22A 440-480 V 320 660-690 V 320 Mechanical 10000 Electrical AC, 50/60 Hz AC22A 440-480 V 1500 660-690 V 1500 AC23A 320 320 AC23A 1500 1500

INS400
3, 4 400 AC22A 400 400 10000 AC22A 1500 1500 AC23A 400 400 AC23A 1500 1500

INS500
3, 4 500 AC22A 500 500 10000 AC22A 1500 1500 AC23A 500 500 AC23A 1500 1500

INS630
3, 4 630 AC22A 630 630 10000 AC22A 1500 1500 AC23A 630 630 AC23A 1500 1500

Durability (category A) (ON-CR-OR-CN cycles)

Compact NS100-NS1600 NS100-250


Number of poles Rated current In (A) Mechanical durability (ON-CR-OR-CN cycles) Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2) Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2) 3, 4 100 to 250 10000 10000

NS400-630
3, 4 400 to 630 8000 3000

NS630bNS1600
3, 4 630 to 1600 8000 2000

1500

1500

1500

Masterpact NT06-NT16/NW08-NW63 (1) NT06- NT12- NW08- NW20 NW25- NW50NT10 NT16 NW16 NW40 NW63
Number of poles Rated current In (A) 3, 4 630 to 1600 8000 3, 4 1250 to 1600 8000 3, 4 800 to 1600 10000 3, 4 2000 3, 4 2500 to 4000 10000 3, 4 5000 to 6300 5000

Mechanical durability 10000 (ON-CR-OR-CN cycles) 6000 10000 8000 5000 1500 Electrical durability at In 6000 NT16: (ON-CR-OR-CN cycles) 3000 for y 440 V and 480 V NEMA (2) Electrical durability at In 3000 2000 10000 6000 2500 1500 (ON-CR-OR-CN cycles) NT16: for U = 500 V to 690 V (2) 1000 (1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions. (2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2. Note: ON: opening of Normal source CR: closing of Replacement source OR: opening of Replacement source CN: closing of Normal source

20

Functions and characteristics

Connection and insulation accessories for Compact NS and INS y 630 A


Downstream coupling accessory
This accessory simplifies connection to bars and cables with lugs. It may be used to couple two circuit breakers (Compact NS100 to 630) or switchdisconnectors (Interpact INS/INV100 to 630) of the same size. Pitch between outgoing terminals: b Interpact INS250 and INV100 to 250: 35 mm b Interpact INS/INV320 to 630: 52.5 mm b Compact NS100 to 250: 35 mm b Compact NS400 to 630: 52.5 mm. For Compact NS circuit-breakers, the downstream coupling accessory can be used only with fixed versions.

DB101605

Connection and insulation accessories


The coupling accessory can be fitted with the same connection and insulation accessories as the circuit breakers and switch-disconnectors.

Possible uses
Manual source-changeover systems
INS250 (100 to 250 A) with rotary handle NS100/250 with rotary handle NS100/250 on base plate with toggle control INS400/630 (320 to 630 A) with rotary handle NS400/630 with rotary handle NS400/630 on base plate with toggle control

Downstream coupling
Possible Outgoing pitch (mm) 35 35 35 52.5 52.5 52.5 35 52.5 35 52.5

b b b b b b b b b b

Complete source-changeover assembly


INS250 (100 to 250 A) INS400/630 (320 to 630 A)

Remote-operated source-changeover systems


NS100/250 NS400/630

21

Functions and characteristics

Remote-operated source-changeover systems Electrical interlocking


Electrical interlocking is carried out by an electrical control device. For Compact NS up to 630 A, electrical interlocking is implemented by the IVE unit integrating control circuits and an external terminal block. The integrated control circuits implement the time delays required for correct source transfer. For Compact NS630b to 1600 and Masterpact, this function can be implemented in one of two ways: b using the IVE unit b by an electrician based on the diagrams presented in the Electrical diagrams part of this catalogue.

Electrical interlocking is used with the mechanical interlocking system. It electrically interlocks the two circuit breakers and implements the time delays required for proper operation of the system. An automatic controller may be added to take into account information from the distribution system.

Characteristics of the IVE unit


b external connection terminal block: v inputs: circuit breaker control signals v outputs: status of the SDE contacts on the Normal and Replacement source circuit breakers b 2 connectors for the two Normal and Replacement source circuit breakers: v inputs: - status of the OF contacts on each circuit breaker (ON or OFF) - status of the SDE contacts on the Normal and Replacement source circuit breakers v outputs: power supply for operating mechanisms b control voltage: v 24 to 250 V DC v 48 to 415 V 50/60 Hz - 440 V 60 Hz. The IVE unit control voltage must be same as that of the circuit breaker operating mechanisms.

DB101573

IVE unit.

Necessary equipment
For Compact NS100 to 630, each circuit breaker must be equipped with: b a motor mechanism b an OF contact b an SDE contact. The components are supplied ready for assembly and the circuit breakers prewired. The prewiring must not be modified. For Compact NS630b to 1600, each circuit breaker must be equipped with: b a motor mechanism b an available OF contact b a CE connected-position contact (carriage switch) on withdrawable circuit breakers b an SDE contact. For Masterpact NT and NW, each circuit breaker must be equipped with: b a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF ready to close contact b an available OF contact b one to three CE connected-position contacts (carriage switches) on drawout circuit breakers (depending on the installation).

22

Functions and characteristics

Remote-operated source-changeover systems Standard configurations

Compact NS, Masterpact NT and NW


Types of mechanical interlocking
2 devices QN 0 1 0 QR 0 0 1 Compact NS100 to 630: b electrical interlocking without emergency power off (EPO) auxiliaries: v with EPO by MN v with EPO by MX Compact NS630b to 1600: b electrical interlocking with lockout after fault: v permanent replacement source (without IVE) v with EPO by MX (without IVE) v with EPO by MN (without IVE) v permanent replacement source (with IVE) v with EPO by MX (with IVE) v with EPO by MN (with IVE) b automatic control without lockout after fault: v permanent replacement source (without IVE) v engine generator set (without IVE) Masterpact NT and NW: b electrical interlocking with lockout after fault: v permanent replacement source (without IVE) v with EPO by MX (without IVE) v with EPO by MN (without IVE) v permanent replacement source (with IVE) v with EPO by MX (with IVE) v with EPO by MN (with IVE) b automatic control without lockout after fault: v permanent replacement source (without IVE) v engine generator set (without IVE) b automatic control with lockout after fault: v permanent replacement source (with IVE) v engine generator set (with IVE) b BA/UA controller (with IVE)
DB101574

Possible combinations Typical electrical diagrams

Diagram no.

51201177 51201178 51201179

51201180 51201181 51201182 51201183 51201184 51201185 51201186 51201187

51201139 51201140 51201141 51201142 51201143 51201144 51156226 51156227 51156904 51156905 51156903

Masterpact NW only
Types of mechanical interlocking
3 devices: 2 Normal sources and 1 Replacement source QN1 0 1 0 QN2 0 1 0 QR 0 0 1
DB101575

Possible combinations Typical electrical diagrams


b electrical interlocking: v without lockout after fault v with lockout after fault

Diagram no.

51156906 51156907

3 devices: 2 Normal sources and 1 Replacement source with source selection QN1 QN2 QR 0 0 0 1 0 0 0 0 1 1 1 0 0 1 0 3 devices: 3 sources, only one device QS1 0 1 0 0 3 devices: 2 sources + 1 coupling QS2 0 0 1 0 QS3 0 0 0 1

DB101576

b automatic control with engine generator set: v without lockout after fault (with MN) v with lockout after fault (with MN)

51156908 51156909

DB101577

b electrical interlocking: v without lockout after fault v with lockout after fault

51156910 51156911

QS1 QC QS2 b electrical interlocking: 0 0 0 v without lockout after fault 1 0 1 v with lockout after fault 1 1 0 b automatic control with lockout after fault 0 1 1 (1) 1 0 0 (1) 0 0 1 (1) possible by forcing operation Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.

51156912 51156913 51156914

DB101578

23

Functions and characteristics

Associated controllers Controller selection

By combining a remote-operated sourcechangeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences. These controllers can be used on sourcechangeover systems comprising 2 circuit breakers. For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the electrical diagrams section of this catalogue.
PB100855

Controller
Compatible circuit breakers

BA

UA

All Compact NS and Masterpact circuit breakers b b b b b b b b b b b b b b

4-position switch
Automatic operation Forced operation on Normal source Forced operation on Replacement source Stop (both Normal and Replacement sources off)

Automatic operation
Monitoring of the Normal source and automatic transfer Generator set startup control Delayed shutdown (adjustable) of generator set Load shedding and reconnection of non-priority circuits Transfer to the Replacement source if one of the phases of the Normal phase is absent

Test
By opening the P25M circuit breaker supplying the controller By pressing the test button on the front of the controller b b b b b b b b b b b b b

Indications
Circuit breaker status indication on the front of the controller: on, off, fault trip Automatic mode indicating contact

Other functions
Selection of type of Normal source (single-phase or three-phase)
(1)

BA controller.

Voluntary transfer to Replacement source (e.g. energy management commands) During peak-tariff periods (energy management commands) forced operation on Normal sourceif Replacement source not operational Additional contact (not part of controller). Transfer to Replacement source only if contact is closed. (e.g. used to test the frequency of UR). Setting of maximum startup time for the replacement source

Options
Communication option
PB100856

Power supply
Control voltages (2) 110 V 220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz and 440 V 60 Hz 0.35 Un y voltage y 0.7 Un 0.5 Un y voltage y 0.7 Un voltage u 0.85 Un b b b b b b

Operating thresholds
Undervoltage Phase failure Voltage presence b b b b b

IP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)
Front Side Connectors UA controller. Front IP40 IP30 IP20 IK07 b b b b b b b b

Characteristics of output contacts (dry, volt-free contacts)


Rated thermal current (A) 8 Minimum load 10 mA at 12 V Output contacts: Position of the Auto/Stop switch b b Load shedding and reconnection order b Generator set start order. b AC DC Utilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13 Operational current (A) 24 V 8 7 5 5 8 2 48 V 8 7 5 5 2 110 V 8 6 4 4 0.6 220/240 V 8 6 4 3 250 V 0.4 380/415 V 5 440 V 4 660/690 V (1) For example, 220 V single-phase or 220 V three-phase. (2) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this voltage is the same as the source voltage, then the Normal and Replacement sources can be used directly for the power supply. If not, an isolation transformer must be used.

24

Functions and characteristics

Associated controllers Controller installation

ACP auxiliaries control plate


The auxiliaries control plate provides in a single unit: b protection for the BA or UA controller with two highly limiting P25M circuit breakers (infinite breaking capacity) for power drawn from the AC source b control of circuit-breaker ON and OFF functions via two relay contactors b connection of the circuit breakers to the BA or UA controller via a built-in terminal block. Control voltages b 110 V 50/60 Hz b 220 to 240 V 50/60 Hz b 380 to 415 V 50/60 Hz and 440 V 60 Hz. The same voltage must be used for the ACP plate, the controller and the circuitbreaker operating mechanisms. Installation Connection between the ACP auxiliaries control plate and the IVE electricalinterlocking unit may use: b wiring done by the installer b prefabricated wiring (optional).
PB100857

Installation of the BA and UA controllers


The BA and UA controllers may be installed in one of two manners: b directly mounted on the ACP auxiliaries control plate b mounted on the front panel of the switchboard. The length of the connection between the ACP plate and the controller must not exceed two metres. Wiring is done by the installer.

ACP auxiliaries control plate.

DB101579

Mounting on the ACP plate.

DB101580

Mounting on the front panel of the switchboard.

25

Functions and characteristics

Associated controllers BA controller

The BA controller is used to create simple source-changeover systems that switch from one source to another depending on the presence of voltage UN on the Normal source. It is generally used to manage two permanent sources and can control Compact NS and Masterpact NT/NW circuit breakers and switch-disconnectors.
PB100858

Operating modes
A four-position switch may be used to select: b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off).

Setting the time delays


Time delays are set on the front of the controller. t1. delay between detection that the Normal source has failed and the transmission of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30 seconds). t2. delay between detection that the Normal source has returned and the transmission of the order to open the Replacement source circuit breaker (adjustable from 0.1 to 240 seconds).

Circuit breaker commands and status indications


The status of the circuit breakers is indicated on the front of the controller. b ON, OFF, fault. A built-in terminal block may be used to connect the following input/output signals: b inputs: v voluntary order to transfer to source R (e.g. for special tariffs, etc.) v additional control contact (not part of the controller). Transfer to the Replacement source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.) b outputs: indication of operation in automatic or stop mode via changeover contacts.

Test
It is possible to test the operation of the BA controller by turning OFF (opening) the P25M circuit breaker for the Normal source and thus simulating a failure of voltage UN.

DB101779

Front of the BA controller.

26

Functions and characteristics

Associated controllers BA controller Operating sequences


Switch set to the N position (forced operation on the Normal source)
DB101584

Switch set to Auto (automatic operation and special-tariff mode)

DB101582

Switch set to the R position (forced operation on the Replacement source)


DB101586 DB101588

Switch set to the Stop position

Key UN : Normal source voltage UR : Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker

WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

The number sends to the indicated step when the condition is true.

27

Functions and characteristics

Associated controllers UA controller

The UA controller is used to create a sourcechangeover system integrating the following automatic functions: b transfer from one source to another depending on the presence of voltage UN on the Normal source b startup of an engine generator set b shedding and reconnection of non-priority circuits b transfer to the Replacement source if one of the phases on the Normal source fails. The UA controller can control Compact NS and Masterpact NT/NW devices.
PB100858

Operating modes
A four-position switch may be used to select: b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off, then manual operation).

Setting the time delays


Time delays are set on the front of the controller. t1. delay between detection that the Normal source has failed and the transmission of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30 seconds). t2. delay between detection that the Normal source has returned and the transmission of the order to open the Replacement source circuit breaker (adjustable from 0.1 to 240 seconds). t3. delay following opening of QN with load shedding and before closing of QR (adjustable from 0.5 to 30 seconds). t4. delay following opening of QR with load reconnection and before closing of QN (adjustable from 0.5 to 30 seconds). t5. delay for confirmation that UN is present before shutting down the engine generator set (adjustable from 60 to 600 seconds). t6. delay before startup of the engine generator set (120 or 180 seconds).

Commands and indications


Circuit breaker status indications on the front of the controller: b ON, OFF, fault. A built-in terminal block may be used to connect the following input/output signals: b inputs: v voluntary order to transfer to source R (e.g. for special tariffs, etc.) v additional control contact (not part of the controller). Transfer to the Replacement source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.) b outputs: v control of an engine generator set (ON / OFF) v shedding of non-priority circuits v indication of operation in automatic mode via changeover contacts.

Distribution-system settings
Three switches are used to: b select the type of Normal source, whether single-phase or three-phase (e.g. 240 V single-phase or 240 V three-phase) b select whether to remain (or not) on the Normal source if the Replacement source is not operational during operation on special tariffs b select the maximum permissible startup time for the engine generator set during operation on special tariffs (120 or 180 seconds).

DB101778

Test
A pushbutton on the front of the controller may be used to test transfer from the Normal source to the Replacement source, then the return to the Normal source. The test lasts approximately three minutes.

COM communications option


Using the internal bus protocol, this option may be used to remote the following information: b circuit breaker status (ON, OFF, fault trip) b presence of the Normal and Replacement voltages b presence of an order for forced operation (e.g. special tariffs) b settings and configuration information b status of non-priority circuits (loads shed or not) b position of the switch (stop, auto, forced operation on the Normal source, forced operation on the Replacement source).

Front of the UA controller.

28

Functions and characteristics

Associated controllers UA controller Operating sequences

Switch set to the R position (forced operation on the Replacement source)

Switch set to the N position (forced operation on the Normal source)


DB101592

DB101590

Switch set to the Stop position


DB101594

WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN). When the UA controller is not energised, the output for generator set startup is activated).
Key UN : Normal source voltage UR : Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker

29

Functions and characteristics

Associated controllers UA controller Operating sequences

Switch set to the Auto position (special-tariff mode) WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN). When the UA controller is not energised, the output for generator set startup is activated).
DB101596

Key UN : Normal source voltage UR : Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker B : Penalties accepted (N ON), i.e. B = 1

The number sends to the indicated step when the condition is true.

30

Functions and characteristics

Associated controllers UA controller Operating sequences

Switch set to the Auto position (automatic operation and test mode).
DB101598

WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN). When the UA controller is not energised, the output for generator set startup is activated).
Key UN : Normal source voltage UR : "Replacement source voltage N : Normal source circuit breaker R : Replacement source circuit breaker B : Penalties accepted (N ON), i.e. B = 1 (*) The test lasts 180 seconds.

The number sends to the indicated step when the condition is true.

31

Functions and characteristics

Operating sequences

IVE unit
DB101600

Symbols QN : Normal Compact C circuit breaker equipped for remote operation (motor mechanism) QR : Replacement Compact C circuit breaker equipped for remote operation (motor mechanism) ON : Circuit breaker QN opening order OR : Circuit breaker QR opening order IN : Circuit breaker QN closing order IR : Circuit breaker QR closing order L1 : Faulty Normal indication LED L2 : Faulty Replacement indication LED

Key O: OFF (circuit open) I: ON (circuit closed : either ON or OFF.

Note: Following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on the front of the motor mechanism is required.

32

Functions and characteristics

Operating sequences

BA controller
DB101602

Inputs UN : Normal source voltage UR : Replacement source voltage KT : order for forced-operation on R KR : additional check before transfer Outputs QN : Normal source circuit breaker QR : Replacement source circuit breaker

UA controller
DB101604

Inputs UN : Normal source voltage UR : Replacement source voltage KT : order for forced-operation on R KR : additional check before transfer Outputs KG : order to the genset SH : load-shedding order QN : Normal source circuit breaker QR : Replacement source circuit breaker

Key O: OFF (circuit open) I: ON (circuit closed : either ON or OFF.

Important If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out. If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is carried out later when KR status becomes I.

33

Functions and characteristics

COM communications option

DB101928

Communications option for Compact NS and Masterpact NT/NW


The COM communications option is compatible with all the source-changeover systems for Compact NS100 to 1600 and Masterpact NT/NW circuit breakers and switch-disconnectors. It can be used to remote status information. It may not be used to operate the circuit breakers (only possible locally on the front of the UA150 controller). Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors are compatible with the Modbus ECO COM option. Depending on the trip units or control units used, the COM option may also be used to analyse distribution-system parameters required for the operating and maintenance assistance.

Circuit breaker communication


SwitchCircuit disconnector breaker

Compact NS100/1600 status indications


ON / OFF Fault trip Connected / disconnected position b b b b b b b b b b

Masterpact NT/NW status indications


ON / OFF Fault trip Connected / disconnected position

Operating and maintenance assistance


STR53UE trip unit for Compact NS400/630
Current readings Phase and neutral rms currents Current on the most heavily loaded phase Alarm readings Overload Tripping cause (overload, short-circuit, etc.) Positions of setting dials b b b b b

Operating and maintenance aids

Digipact

Modbus

Measurement Current A P H A P H Voltages, frequency, power, etc. P H P H Power quality: fundamental, harmonics H Programming of demand metering P H Fault readings Type of fault A P H Interrupted current P H Waveform capture On faults H On demand or programmed H Histories and logs Trip history P H Alarm history P H Event logs P H Indicators Counter operation A P H A P H Contact wear P H Maintenance register P H Note: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators.

34

Functions and characteristics

COM communications option

Automatic source-changeover controller


UA150

Status indications
Normal source ON / OFF Circuit breaker ON Fault trip (SDE) Voltage presence Replacement source Circuit breaker ON Fault trip (SDE) Voltage presence Status of R voltage contact Controller Automatic mode Normal mode Replacement mode Stop mode Testing Replacement engine generator set Genset failure Genset OFF Genset ON Shedding of non-priority circuits Reconnection of non-priority circuits b b b b b b b b b b b b b b b b b b b b b b b b b

Settings
Time delay t1 for validation of UN absence Time delay t2 for validation of UN return Time delay t3 for wait between opening of N and closing of R Time delay t4 for wait between opening of R and closing of N Time delay t5 for wait between return of UN and order for genset shutdown Time delay t6 for wait before declaring genset failure Penalties accepted to avoid special tariff transfer

35

36

Source-changeover systems

Dimensions

Presentation Functions and characteristics

2 7

Manual source-changeover systems


Interlocking of direct rotary handles Interlocking of extended rotary handles Interlocking of toggles Complete source-changeover assembly Downstream coupling accessory

39
39 40 42 43 44

Remote-operated source-changeover systems


Interlocking on a base plate Interlocking using connecting rods Interlocking using cables IVE electrical-interlocking unit BA and UA automatic controllers Electrical diagrams Catalogue numbers and order forms

46
46 50 52 57 59 95

37

38

Dimensions

Manual source-changeover systems Interlocking of direct rotary handles

Compact NS100 to 1600


Dimensions
DB101606 DB101607 DB101608

Front-panel cut-out

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L A 325 416 B 90 115 C 87.5 100 D 175 200 F 156 210 G 133 157 H 9.25 5 J 9 24.6 K 295 386 L 75.5 100 M 150 175 N 75 74.5 P 155 179

Interpact INS/INV250 100 to 250 A / Interpact INS/INV320/400/500/630


Dimensions
DB101609 DB101610 DB101611

Front-panel cut-out

Dimensions (mm)
Type A B C INS/INV250 100/160/250 A 325 90 87.5 INS/INV320/400/500/630 416 115 100 Note: X et Y are the symmetry planes for a 3-pole device. D 175 200 F 156 210 G 106 130 H 17.5 22.5 K 295 386 L 75.5 100 M 150 175 N 75 74.5 P 131 160.4

39

Dimensions

Manual source-changeover systems Interlocking of extended rotary handles


Front-panel cut-out
DB101607 DB107757

Compact NS100 to 630


Dimensions
DB101612

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L A 325 416 B 90 115 C 87.5 100 D 175 200 F 156 210 G min 185 204 G max 600 600 H 9.25 5 J 9 24.6 P 25.5 30.8 Q 25.5 30.8

Interpact INS40/63/80/100/125/160 / Interpact INS/INV250 100 to 250 A / Interpact INS/INV320/400/500/630


Dimensions
DB101614 DB101615 DB107756

Front-panel cut-out

Dimensions (mm)
Type INS40/63/80 INS100/125/160 INS/INV250 100/160/250 A INS320/400/500/630 A 325 325 325 416 B 90 90 90 115 C 87.5 87.5 87.5 100 D 175 175 175 200 F 156 156 156 210 G min 155 200 185 204 G max 396 441 600 600 H 0 0 17.5 22.5 P 25.5 25.5 25.5 30.8 Q 25.5 25.5 25.5 30.8

40

Dimensions

Manual source-changeover systems Interlocking of extended rotary handles

Compact NS630b to 1600


Dimensions
DB101617 DB101618

Front-panel cut-out
DB101619

Dimensions (mm)
Type NS630b/800/1000/1200/1600 A 411 B 63.5 C 98 D 175 F 280 G min 218 G max 605 H 25 J 24 P 25.5 Q 25.5 R 64

41

Dimensions

Manual source-changeover systems Interlocking of toggles

Compact NS100 to 630


Dimensions
DB101620 DB101621

3 poles
DB101622

4 poles

Front-panel cut-out
DB101623

3 poles on left
DB101624

4 poles on left

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L C2 54 92.5 C3 108 184 L 52.5 70 L16 140 185 L17 245 325 L18 280 370 R2 54 71.5 R18 89 116.5 R19 140 185 P5 83 107 P 115 144

42

Dimensions

Manual source-changeover systems Complete source-changeover assembly

Assembly for INS250 100 to 250 A / Assembly for INS320/400/500/630


Dimensions
DB101625 DB101626

Front-panel cut-out
DB101627

Dimensions (mm)
Type INS250 INS320/630 A 60.4 82.5 B 130.4 175 C 296 395 D 68 102.5 E 136 205 F 131 155 G 61.8 87 H 279.3 383.7 I 42 64 J 84 128 K 156 210 L 186.5 213 M 5.5 8 N 50 50

Dimensions of the complete source-changeover assembly with an extended handle


DB101650 DB101651

Dimensions (mm)
Type INS250 INV100/250 INS320/630 INV320/630
DB107743

A 60.4 82.5

B 130.4 175

C 295 395

E 136 205

K 156 210

L 138.5 162.5

M 631 658

N 50 75

Dimensions (mm)
Type INS250 INV100/250 INS320/630 INV320/630 P 100 150 Mmax 567.5 593 Mmin 195 220.5 Q 64 64

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

43

Dimensions

Manual source-changeover systems Downstream coupling accessory

Compact NS100 to NS630 (only for Compact NS fixed devices)


Dimensions
DB101628 DB101629

Dimensions
DB101630 DB101631

Connection

Dimensions (mm)
Type NS100/160/250 NS400/630 G2 118 165.9 G3 181.5 265.7 G28 238 339.5 G29 96 143.5 G30 140 188.5 G52 156 227.5 K1 35 45 K2 35 52.5 K3 51 75 K4 156 210 K8 70 113.5 K9 170 250.7 K16 8 3.75

Dimensions (mm)
Type NS100/160/250 NS400/630 L28 320 420 L29 99.5 127.5 L30 300 400 L31 89.5 117.5 L32 1 11.2 L33 123 187.5 L34 139.5 L35 74.5 96.5 L36 19.5 26 L37 87.5 115 L39 9.5 22.5 L40 140 210 T 6 6

Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.

44

Dimensions

Manual source-changeover systems Downstream coupling accessory

Interpact INS250 100 to 250 A / Interpact INS320/400/500/630


Dimensions
DB101632 DB101633

Dimensions
DB101901 DB101902

Connection

Dimensions (mm)
Type INS250-100/160/200/250 NS320/400/500/630 G2 105.5 141 G3 169 240.7 G28 225.5 315 G29 83.5 119 G30 127.5 163.5 G52 143.5 202.5 K1 35 45 K2 35 52.5 K3 51 75 K4 156 210 K8 57.5 88.5 K9 157.5 225.7 K16 25.5 26.25

Dimensions (mm)
Type INS250-100/160/200/250 NS320/400/500/630 L28 320 420 L29 82 105 L30 300 400 L31 72 95 L32 16.5 11.2 L33 123 187.5 L34 139.5 L35 74.5 98.5 L36 21.5 26 L37 70 92.5 L39 8.5 0 L40 140 210 T 6 6

45

Dimensions

Remote-operated source-changeover systems Interlocking on a base plate

Compact NS100 to 250


Dimensions, 3 or 4 poles
DB101634 DB101635

Fixed device
DB101636

Withdrawable device

(*) Short terminal shields are mandatory.

Vertical mounting
DB101637 DB101638

Horizontal mounting

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L G50 137.5 180 G51 285 360 H20 62.5 100 H21 97 152 H22 45.5 83 H23 73 123 H42 60 60 H43 120 120 H44 144.5 189 H45 300 378 H46 37 77 K25 156 210 K35 210.5 282.5 K36 300 400

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L L31 110.5 150.5 L32 354 466 P7 25 25 P8 45 45 P9 75 100 P32 178 250 P33 143 215 P50 25 25 P52 99.5 123 P54 21 21 T9 9 9 T10 6 6 U y 32 y 32

Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.

46

Dimensions

Remote-operated source-changeover systems Interlocking on a base plate

Compact NS400 to 630


Dimensions, 3 or 4 poles
DB101639 DB101640

Fixed device

Withdrawable device
DB101641

Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.

(*) Short terminal shields are mandatory.

Dimensions Vertical mounting


DB101637 DB101638

Horizontal mounting

Note: dimensions see page 46.

47

Dimensions

Remote-operated source-changeover systems Interlocking on a base plate

"Normal" and "Replacement" source devices: NS100 to NS250


Dimensions
DB101642 DB107744

Front-panel cut-out

"Normal" and "Replacement" source devices: NS400 to NS630


Dimensions
DB101644 DB107745

Front-panel cut-out

Note for Compact NS: For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.

48

Dimensions

Remote-operated source-changeover systems Interlocking on a base plate

NS400 to NS630 as the "Normal" device, NS100 to NS250 as the "Replacement" device
Dimensions
DB101646 DB107746

Front-panel cut-out

49

Dimensions

Remote-operated source-changeover systems Interlocking using connecting rods

Two Compact NS630b to NS1600 devices one above the other


Fixed devices
DB107747 DB101655

Withdrawable devices

Two Masterpact NT devices one above the other


Fixed devices
DB101656 DB101655

Withdrawable devices

50

Dimensions

Remote-operated source-changeover systems Interlocking using connecting rods

Two Masterpact NW devices one above the other


Fixed devices
DB107748 DB107749

Withdrawable devices

51

Dimensions

Remote-operated source-changeover systems Interlocking using cables

Two Compact NS630b to NS1600 devices side-by-side


Fixed devices
DB101661 DB101662

Withdrawable devices

Two Masterpact NT devices side-by-side


Fixed devices
DB101663 DB101662

Drawout devices

Two Masterpact NT and NW devices side-by-side


Fixed devices
DB101664 DB101665

Drawout devices

52

Dimensions

Remote-operated source-changeover systems Interlocking using cables

Two Masterpact NW devices side-by-side


Fixed devices
DB101666 DB101667

Drawout devices

Three Masterpact NW devices side-by-side


Fixed devices
DB101668

Drawout devices
DB101669

53

Dimensions

Remote-operated source-changeover systems Interlocking using cables

Two Compact NS630b to NS1600 devices one above the other


Fixed devices
DB107750 DB101671

Withdrawable devices

Two Masterpact NT devices one above the other


Fixed devices
DB101672 DB101671

Drawout devices

54

Dimensions

Remote-operated source-changeover systems Interlocking using cables

Two Masterpact NW devices one above the other


Fixed devices
DB107751 DB107752

Drawout devices

Two Masterpact NT and NW devices one above the other


Fixed devices
DB107753 DB107752

Drawout devices

55

Dimensions

Remote-operated source-changeover systems Interlocking using cables

Three Masterpact NW devices one above the other


Fixed devices
DB107754 DB107755

Drawout devices

56

Dimensions

Remote-operated source-changeover systems IVE electrical-interlocking unit BA and UA automatic controllers

IVE electrical-interlocking unit


DB101679 DB101678

ACP auxiliaries control plate and BA/UA controller


DB101680 DB101681 DB101682

Door cut-out for BA/UA controllers


DB101683

(1) Cut-out according DIN 43700 standard.

57

58

Source-changeover systems

Electrical diagrams

Presentation Functions and characteristics Dimensions

2 7 37

Remote-operated source-changeover systems


2 Compact NS100/1600 or Masterpact NT/NW devices 2 Compact NS100/630 devices 2 Compact NS630b/1600 devices 2 Masterpact NT or NW devices 3 Masterpact NW devices

60
60 61 64 72 82

Source-changeover systems with automatic controllers


2 Compact NS100/1600 or Masterpact NT/NW devices 2 Masterpact NT or NW devices Catalogue numbers and order forms

91
91 94 95

59

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS100/1600 or Masterpact NT/NW devices

Electrical interlocking by the IVE unit


Recommended electrical control system
DB101689

(1) The normal and replacement source transfer orders must be interlocked electrically. (2) Operating diagram: the SDE fault-trip signals are transmitted to the IVE unit. The SDE auxiliary contacts are mounted in the circuit breakers.

Legends ON "Normal source opening order OR "Replacement source opening order FN "Normal source closing order FR Replacement source closing order L1 Normal source fault-trip signal L2 Replacement source fault-trip signal N Normal source auxiliary wiring connector R Replacement source auxiliary wiring connector

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

60

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS100/630 devices


Diagram no. 51201177

Source-changeover system without automatic-control system


Without auxiliaries for emergency off
DB101686 DB101659

Local reset

Voluntary remote reset


DB101660

Automatic reset

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, reverse the wires connected to terminals 82 and 84. Legends QN Normal source Compact NS equipped with motor mechanism QR Replacement source Compact NS equipped with motor mechanism SDE fault-trip indication contact IVE electrical interlocking and terminal block unit MT motor mechanism OF2 breaker ON/OFF indication contact RN reset order for breaker QN RR reset order for breaker QR

(1) Prefabricated wiring: cannot be modified.

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

61

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS100/630 devices


Diagram no. 51201178

Source-changeover system without automatic-control system


With emergency off by MN release and automatic reset
DB112553

Automatic reset

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, reverse the wires connected to terminals 82 and 84.

(1) Prefabricated wiring supplied. (2) Independent auxiliary source.

Legends QN Normal source Compact NS equipped with motor mechanism QR "Replacement source Compact NS equipped with motor mechanism MN undervoltage release OF2 breaker ON/OFF indication contact SDE fault-trip indication contact MT motor mechanism IVE electrical interlocking and terminal block unit BP emergency off button with latching KA3 auxiliary relay F1 auxiliary power supply circuit breaker

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

62

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS100/630 devices


Diagram no. 51201179

Source-changeover system without automatic-control system


With emergency off by MX release and automatic reset
DB101691

Automatic reset

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, reverse the wires connected to terminals 82 and 84.

(1) Prefabricated wiring supplied (2) This source can be: b the source present in the case of voltage monitoring b an independent source. In this case, the MX release must be protected. (3) The reset orders must be delayed by 0.3 seconds.

Legends QN Normal source Compact NS equipped with motor mechanism QR Replacement source Compact NS equipped with motor mechanism SDE fault-trip indication contact OF2 breaker ON/OFF indication contact MX shunt release MT motor mechanism IVE electrical interlocking and terminal block unit KA1 time-delayed auxiliary relays KA2 time-delayed auxiliary relays F1 auxiliary power supply circuit breaker F2 auxiliary power supply circuit breaker

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

63

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201180

Electrical interlocking
DB101693

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

States permitted by mechanical interlocking system


Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

64

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201181

Electrical interlocking with emergency off by shunt release


DB101695

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker MX shunt release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

65

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201182

Electrical interlocking with emergency off by undervoltage


DB101697

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker MN undervoltage release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR "Replacement source closing order (0.25 second delay) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

66

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201183

Electrical interlocking by IVE


DB112554

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired on fixed version. (2) Prefabricated wiring supplied.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker IVE electrical interlocking and terminal block unit ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

67

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201184

Electrical interlocking by IVE with emergency off by shunt release


DB112555

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired on fixed version. (2) Prefabricated wiring supplied.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker IVE electrical interlocking and terminal block unit MX shunt release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

68

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201185

Electrical interlocking by IVE with emergency off by undervoltage release


DB112556

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired on fixed version. (2) Prefabricated wiring supplied.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 MCH spring-charging motor MX standard opening release XF standard closing release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker IVE electrical interlocking and terminal block unit MN undervoltage release BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

69

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201186

Automatic-control system without IVE for permanent replacement source


DB101705

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

70

Electrical diagrams

Remote-operated source-changeover systems 2 Compact NS630b/1600 devices


Diagram no. 51201187

Automatic-control system for replacement source generator set


DB101707

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Compact NS630b to 1600 QR Replacement source Compact NS NS630b to 1600 OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact CE1 connected-position indication contact (carriage switch) F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KA3 auxiliary relays - generator set startup if UN absent KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source) MT Motor Mechanism

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

71

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51201139

Electrical interlocking with lockout after a fault


DB101709

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

72

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51201140

Electrical interlocking with lockout after a fault and emergency off by shunt release
DB101711

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends KA3 time delay for genset startup order to avoid starting the genset for transient UN disturbances QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker MX2 shunt release BP emergency off button with latching ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay) BP emergency off button with latching

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

73

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51201141

Electrical interlocking with lockout after a fault and emergency off by undervoltage release
DB101713

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker BP emergency off button with latching S1 control switches KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

74

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51201142

Electrical interlocking by IVE with lockout after a fault


DB101715

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.

Legends QN "Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

75

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51201143

Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release
DB101717

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker BP emergency off button with latching KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

76

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51201144

Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
DB101719

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker BP emergency off button with latching S1 control switches KA3 auxiliary relay ON Normal source opening order OR Replacement source opening order FN Normal source closing order (0.25 second delay) FR Replacement source closing order (0.25 second delay)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

77

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51156226

Automatic-control system without IVE for permanent replacement source with lockout after a fault
DB101721

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

78

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51156227

Automatic-control system for replacement source generator set with lockout after a fault
DB101723

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

(1) Not to be wired on fixed version.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays - UN presence detection KA2 auxiliary relays - UR presence detection KA3 auxiliary relays - generator set startup if UN absent KM1 contactors with 0.25 second delay (for transfer to Replacement source) KM2 contactors with 0.25 second delay (for transfer to Normal source)

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

79

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51156904

Automatic-control system for permanent replacement source with lockout after a fault (with MN)
DB112557

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker F2 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relays KA2 auxiliary relays KA3 auxiliary relays

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

80

Electrical diagrams

Remote-operated source-changeover systems 2 Masterpact NT or NW devices


Diagram no. 51156905

Automatic-control system for replacement source generator set with lockout after a fault (with MN)
DB112558

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breaker F2 circuit breaker (high breaking capacity) S1 control switches KA1 auxiliary relay KA2 time delay for genset startup order to avoid starting the genset for transient UN disturbances KA3 auxiliary relay

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

81

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156906

2 Normal sources and 1 Replacement source: electrical interlocking without lockout after a fault
DB101734

Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 order for transfer from R to N1 + N2 (QN1 and QN2 closing time delay = 0.25 sec. minimum) t2 order for transfer from N1 + N2to R (QR closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Normal 1 Normal 2 Replacement 0 0 0 1 1 0 0 0 1 1 0 0 0 1 0 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

82

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156907

2 Normal sources and 1 Replacement source: electrical interlocking with lockout after a fault
DB101766

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker S1 control switches S2 source selection switches t1 order for transfer from R to N1 + N2 (QN1 and QN2 closing time delay = 0.25 sec. minimum) t2 order for transfer from N1 + N2to R (QR closing time delay = 0.25 sec. minimumm)

States permitted by mechanical interlocking system


Normal 1 Normal 2 Replacement 0 0 0 1 1 0 0 0 1 1 0 0 0 1 0 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

83

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156908

2 Normal sources and 1 Replacement source: automatic-control system for generator set without lockout after a fault (with MN)
DB101737

Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches S2 source selection switches KA1 auxiliary relay KA2 auxiliary relays with 10 to 180 sec. time delay KA3 auxiliary relays with 0.1 to 30 sec. time delay KA4 auxiliary relay KA5 auxiliary relays with 0.25 sec. time delay KA6 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system and with associated automatism


Normal 1 Normal 2 Replacement 0 0 0 1 1 0 0 0 1 1 0 0 0 1 0 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

84

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156909

2 Normal sources and 1 Replacement source: automatic-control system for generator set with lockout after a fault (with MN)
DB101739

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

Legends QN... Normal source Masterpact NW QR Replacement source Masterpact NW MCH spring-charging motor XF standard closing voltage release MN undervoltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches S2 source selection switches KA1 auxiliary relay KA2 auxiliary relays with 10 to 180 sec. time delay KA3 auxiliary relays with 0.1 to 30 sec. time delay KA4 auxiliary relay KA5 auxiliary relays with 0.25 sec. time delay KA6 auxiliary relays with 0.25 sec. time delay KA7 auxiliary relay KA8 auxiliary relay

States permitted by mechanical interlocking system and with associated automatism


Normal 1 Normal 2 Replacement 0 0 0 1 1 0 0 0 1 1 0 0 0 1 0 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

85

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156910

3 sources with only 1 device closed: electrical interlocking without lockout after a fault
DB101741

Legends QS... Source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 order for transfer to Source 1 (QS1 closing time delay = 0.25 sec. minimum) t2 order for transfer to Source 2 (QS2 closing time delay = 0.25 sec. minimum) t3 order for transfer to Source 3 (QS3 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Source 1 Source 2 Source 3 0 0 0 1 0 0 0 1 0 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

86

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156911

3 sources with only 1 device closed: electrical interlocking with lockout after a fault
DB101743

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

Legends QS... Source Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 order for transfer to Source 1 (QS1 closing time delay = 0.25 sec. minimum) t2 order for transfer to Source 2 (QS2 closing time delay = 0.25 sec. minimum) t3 order for transfer to Source 3 (QS3 closing time delay = 0.25 sec. minimum) KA1 auxiliary relays KA2 auxiliary relays KA3 auxiliary relays

States permitted by mechanical interlocking system


Source 1 Source 2 Source 3 0 0 0 1 0 0 0 1 0 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

87

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156912

2 sources and 1 coupling: electrical interlocking without lockout after a fault


DB101745

Legends QS... Source Masterpact NW QC Coupling Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 coupling order for Source 1 failure (QC closing time delay = 0.25 sec. minimum) t2 coupling order for Source 2 failure (QC closing time delay = 0.25 sec. minimum) t3 coupling order for Source 1 restored (QS1 closing time delay = 0.25 sec. minimum) t4 coupling order for Source 2 restored (QS2 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Source 1 Source 2 Coupling 0 0 0 1 1 0 1 0 1 0 1 1 1 0 0 0 1 0 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

88

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156913

2 sources and 1 coupling: electrical interlocking with lockout after a fault


DB101747

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

Legends QS... Source Masterpact NW QC Coupling Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker t1 coupling order for Source 1 failure (QC closing time delay = 0.25 sec. minimum) t2 coupling order for Source 2 failure (QC closing time delay = 0.25 sec. minimum) t3 coupling order for Source 1 restored (QS1 closing time delay = 0.25 sec. minimum) t4 coupling order for Source 2 restored (QS2 closing time delay = 0.25 sec. minimum) KA1 auxiliary relays KA2 auxiliary relays KA3 auxiliary relays

States permitted by mechanical interlocking system


Source 1 Source 2 Coupling 0 0 0 1 1 0 1 0 1 0 1 1 1 0 0 0 1 0 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

89

Electrical diagrams

Remote-operated source-changeover systems 3 Masterpact NW devices


Diagram no. 51156914

2 sources and 1 coupling: automatic-control system with lockout after a fault


DB101749

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

Legends QS... Source Masterpact NW QC Coupling Masterpact NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault trip indication contact PF ready-to-close contact CE... connected-position indication contact (carriage switch) CH springs charged indication contact F1 auxiliary power supply circuit breaker F2/F3 circuit breaker (high breaking capacity) S1 control switches S2 source selection switches KA1 auxiliary relays with 10 to 180 sec. time delay KA2 auxiliary relays with 0.1 to 30 sec. time delay KA3 auxiliary relays with 10 to 180 sec. time delay KA4 auxiliary relays with 0.1 to 30 sec. time delay KA5 auxiliary relays with 0.25 sec. time delay KA6 auxiliary relays with 0.25 sec. time delay KA7 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system and with associated automatism


Source 1 Source 2 Coupling 0 0 0 1 1 0 1 0 1 0 1 1 1 0 0 0 1 0 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close. Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN...).

90

Electrical diagrams

Source-changeover systems with automatic controllers 2 Compact NS100/1600 or Masterpact NT/NW devices
Coupling

Source-changeover system with BA controller

DB101751

DB101753

Transfer conditions
DB101755

Terminals 20 and 21: additional control contact (not part of controller).

Tests on Normal and Replacement source voltages The single-phase check for UN and UR is implemented across terminals 1 and 5 of circuit breakers Q1 and Q2.

Legends Q1 circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source Q2 circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source ACP auxiliaries control plate BA automatic controller IVE electrical interlocking and terminal block unit

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

91

Electrical diagrams

Source-changeover systems with automatic controllers 2 Compact NS100/1600 or Masterpact NT/NW devices
Load shedding and genset management

Source-changeover system with UA controller

DB101757

DB101758

Transfer conditions
DB101759

Terminals 20 and 21: additional control contact (not part of controller).

Tests on Normal and Replacement source voltages Normal source voltage UN test
DB101761

Replacement source voltage UR test The single-phase check for UR is implemented across terminals 1 and 5 of circuit breaker Q2.

Legends Q1 circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source Q2 circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source ACP auxiliaries control plate UA automatic controller IVE electrical interlocking and terminal block unit

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

92

Electrical diagrams

Source-changeover systems with automatic controllers 2 Compact NS100/1600 or Masterpact NT/NW devices
Using communication functions
DB101763

Controller settings
DB101762

Tests on Normal source voltage A = 0 single-phase test, A = 1 three-phase test. Voluntary transfert (e.g. for energy management) b action in the event of genset failure B = 0 circuit breaker N opens, B = 1 circuit breaker N remains closed. b maximum permissible genset startup time (T6) C = 0 T = 120 s, C = 1 T = 180 s. After this time has elapsed, the genset is considered to have failed.

The address of the UA controller is set using the two BBus dials.

93

Electrical diagrams

Source-changeover systems with automatic controllers 2 Masterpact NT or NW devices


Diagram no. 51156903

Electrical interlocking with lockout after a fault


DB101765

ATTENTION
The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution. (2) Not to be wired on fixed version. (3) Prefabricated wiring supplied.

Legends QN Normal source Masterpact NT or NW QR Replacement source Masterpact NT or NW MCH spring-charging motor MX standard opening voltage release XF standard closing voltage release OF... breaker ON/OFF indication contact SDE1 fault-trip indication contact PF ready-to-close contact CE1 connected-position indication contact (carriage switch) CH springs charged indication contact IVE electrical interlocking and terminal block unit

States permitted by mechanical interlocking system


Normal Replacement 0 0 1 0 0 1 Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.

Wiring colour codes


RD red GN green BK black VT violet YE GY yellow grey WH white BN brown

94

Source-changeover systems

Catalogue numbers and order forms

Presentation Functions and characteristics Dimensions Electrical diagrams

2 7 37 59

Source-changeover systems for 2 devices


Interpact INS40 to INS2500 Compact NS100 to NS630 Compact NS630b to NS1600 circuit breakers and switch-disconnectors Masterpact NT circuit breakers and switch-disconnectors

96
96 97 99 101

Source-changeover systems for 2 or 3 devices


Masterpact NW circuit breakers and switch-disconnectors

102
102

Source-changeover systems for 2 devices


Interpact INS40 to INS630 Switch-disconnectors Compact NS100 to NS630 / Circuit-breakers and switch-disconnectors Compact NS630b to NS1600 / Circuit-breakers and switch-disconnectors Masterpact NT or NW / Circuit-breakers and switch-disconnectors

104
104 106 108 110

Source-changeover systems for 3 devices


Masterpact NW / Circuit-breakers and switch-disconnectors

112
112

95

Catalogue numbers and order forms

Source-changeover systems for 2 devices Interpact INS40 to INS2500 and INV100 to INV2500

Manual source-changeover systems Interpact INS40 to INS630 and INV100 to INV630


Interlocking for rotary handle
Mechanical device for INS40 to INS160 equipped with an extended rotary handle 3/4P 28953

DB107710

5...8

Mechanical device for INS250-100 to INS250/INV100 to INV250 equipped with a direct or extended rotary handle Mechanical device for INS/INV320 to INS/INV630 equipped with a direct or extended rotary handle

31073 31074

E89624

Complete assembly source-changeover systems Interpact INS250 to INS630


3P With Interpact INS250-100A 31140 With Interpact INS250-160A 31144 With Interpact INS250-200A 31142 With Interpact INS250 31146 With Interpact INS320 31148 With Interpact INS400 31150 With Interpact INS500 31152 With Interpact INS630 31154 Locking for INS complete source changeover assembly Handle locking by 1 to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 1351B.500 keylock or + Profalux KS5 B24 D4Z keylock Rotary handle Extended front control for complete source changeover assembly 4P 31141 31145 31143 31147 31149 31151 31153 31155 Built in 31097 41940 42888

DB107711

E89638

E89617

31055

Manual source-changeover systems Interpact INS250 to INS2500 and INV250 to INV2500 by keylock
Interlocking
Locking device for Ronis/Profalux keylocks on INS250-100 to INS250/INV100 to INV250 Locking device for Ronis/Profalux keylocks on INS/INV320 to INS/INV630 3/4P 2x 31087 2x 31088

DB101549

E89626

Locking device for Ronis/Profalux keylocks on INS/INV630b to INS/INV2500

2x 31291

+ Ronis 1351B.500 keylock (2 keylocks / 1 key) or + Profalux KS5 B24 D4Z keylock (2 keylocks / 1 key)

41950 42878

Connection accessories
Downstream coupling accessories
Short terminal shields
DB101062

INS250 (1 pair) INS320 to INS630 (1 pair)

3P 29322 32563

4P 29322 32563

E50998

"Normal" source / "replacement" source

INS250 INS320 to INS630

29358 32619

29359 32620

Long terminal shields


DB101063

INS250 (1 pair) INS320 to INS630 (1 pair)

29324 32583

29324 32583

96

Catalogue numbers and order forms

Source-changeover systems for 2 devices (cont.) Compact NS100 to NS630

Manual source changeover


Mechanical interlocking
For toggle controlled circuit-breakers
E21288

NS100...250 NS400...630

29354 32614

For rotary handled circuit-breakers


E18780

NS100...250 NS400...630

29369 32621

Key lock interlocking


E23851

For rotary handled or remote controlled circuit breakers 2 locks, 1 key Ronis 1351B.500 Profalux KS5 B24 D4Z

41950 42878

Remote controlled source changeover


Plate + IVE
Source "normal"/source "replacement" (identical voltages)
E33419

24 to 250 V DC

48 to 415 V AC 50/60 Hz 440 V 60 Hz 29350 29349 29352 4 x 29450 29365


(2) (2)

NS100...250/NS100...250 Plate + IVE (1) Plate IVE Auxiliary switches 2 OF + 2 SDE Spare wiring system (device/IVE) Back sockets option add: Only long RC Plug in base option add: Plug in kit NS400...630/NS100...630 Plate + IVE (1) Plate IVE Auxiliary switches 2 OF + 2 SDE Spare wiring system (device/IVE) Back sockets option add: Only long RC Plug in base option add: Plug in kit Adaptator kit for NS100...250 110/127 V AC 50/60 Hz

29351 29349 29356 4 x 29450 29365


(2) (2)

32611 32609 29356 4 x 29450 29365


(2) (2)

32610 32609 29352 4 x 29450 29365


(2) (2)

1 x 32618 220/240 V AC 50/60 Hz 29470 29363 29376 29472 29363 29378 29474 29363 29379

1 x 32618 380/415 V AC 50/60 Hz 440 V 60 Hz 29471 29364 29377 29473 29364 29380 29475 29364 29381

Control unit option


E33420
GERIN MERLIN
multi P25M 9

0 . OFF

GERIN MERLIN
multi P25M 660V AC3-IEC292-1 9

0 . OFF

660V AC3-IEC292-1

Test

Test

ACP + control unit BA (1) Plate ACP Control unit BA ACP + control unit UA (1) 29448 Plate ACP 29447 Control unit UA 29446 ACP + control unit UA150 (1) (communication option) Plate ACP Control unit UA150

661.42 227.30 434.11

Wiring cable between BA/UA and ACP/IVE


29368 29368 (1) The supply voltages BA/UA control unit, ACP plate, IVE and the remote control must be identical whatever the source changeover type. (2) See products pages.

97

Catalogue numbers and order forms

Source-changeover systems for 2 devices (cont.) Compact NS100 to NS630 (cont.)

Connection accessories
Downstream coupling accessories
Short terminal shields (1 pair)
DB101062

NS100...250/NS100...250 NS400...630/NS400...630

3P 29321 32562

4P 29322 32563

E50998

Source "normal"/source "replacement"

NS100...250/ NS100...250 NS400...630/ NS400...630

250 A 630 A

29358 32619

29359 32620

Long terminal shields (1 pair)


DB101063

NS100...250/NS100...250 NS400...630/NS400...630

29324 32565

Typical composition of remote controlled source changeover


Remote controlled source changeover
1 normal device N (1) + 1 replacement device R (2) + 2 remote controls (3) + 1 plate with interlocking (4) with IVE (5) and its wiring (8) + 2 plug-in kits (if plug-in version) + 1 adaptor kit for NS100...250 plug-in (if NS400...630 with NS100...250) + auxilary switches (6) 2 x (1 OF + 1 SDE) for Compact NS100...630 + 1 downstream coupling accessory (7) for Compact NS100...630 (option) + long RC (if back connection)
E33422

IVE voltages and remote controls are identical.

Associated control unit


GERIN MERLIN
multi P25M 9

0 . OFF

GERIN MERLIN
multi P25M 660V AC3-IEC292-1 9

0 . OFF

660V AC3-IEC292-1

Test

Test

1 source changeover without associated control unit + 1 ACP (9) with BA control unit (10) Or + 1 ACP (9) with UA control unit (11) Or + 1 ACP (9) with UA150 control unit (11) + extension (12) for remote UA/BA connection on front of switchboard

E33423

IVE voltages + remote control + ACP + BA or UA are identical.

98

Catalogue numbers and order forms

Source-changeover systems for 2 devices (cont.)


Compact NS630b to NS1600 circuit breakers and switch-disconnectors

interlocking for source-changeover systems


Mechanical interlocking
For 2 devices with extended rotary handles
E70744

33890

Interlocking using connecting rods for Compact electrically-operated devices


Complete assembly with 2 adaptation fixtures + rods 2 Compact fixed devices 2 Compact withdrawable devices
FFO hsup

33910 33913

E72941

NO h sup

FFO

O
d e gr a h cs id

FFO hsup

NO h sup

FFO

O
d e gr a h cs id

Interlocking using cables for Compact electrically-operated devices


Complete assembly with 2 adaptation fixtures + cables 2 Compact fixed devices 2 Compact withdrawable devices 1 Compact fixed + 1 Compact withdrawable device
FFO hsup

33911 33914 33915

E72942

NO h sup

FFO

O
d e gr ahcs id

FFO hsup

NO h sup

FFO

O
d e gr ahcs id

99

Catalogue numbers and order forms

Source-changeover systems for 2 devices (cont.)


Compact NS630b to NS1600 circuit breakers and switch-disconnectors (cont.)

Associated controller
The automatic-control option includes: b an IVE electrical-interlocking unit b an ACP auxiliaries control plate b a BA or UA controller, depending on the required functions b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit


For 2 devices Wiring kit for connection of 2 fixed/withdrawable devices to the IVE unit

48/415 V AC 50/60 Hz 440 V 60 Hz


29352 54655

E88714

Control unit option

110/127 V AC 50/60 Hz

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz 440 V 60 Hz

ACP + control unit BA (1) 29470 29471 Plate ACP 29363 29364 Control unit BA 29376 29377 ACP + control unit UA (1) 29448 29472 29473 Plate ACP 29447 29363 29364 Control unit UA 29446 29378 29380 ACP + control unit UA150 (1) (communication option) 29474 29475 Plate ACP 29363 29364 Control unit UA150 29379 29381 (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.
E33420
GERIN MERLIN
multi 9

0 . OFF

P25M

GERIN

MERLIN
multi 9

0 . OFF

660V AC3-IEC292-1

P25M

660V AC3-IEC292-1

Test

Test

100

Catalogue numbers and order forms

Source-changeover systems for 2 devices (cont.) Masterpact NT circuit breakers and switch-disconnectors

interlocking for source-changeover systems


Interlocking using connecting rods
Complete assembly with 2 adaptation fixtures + rods 2 Masterpact NT fixed devices 2 Masterpact NT drawout devices 33912 33913
E47760

Interlocking using cables (*)


Choose 2 adaptation fixtures (1 for each breaker + 1 set of cables) 1 adaptation fixture for Masterpact NT fixed devices 1 adaptation fixture for Masterpact NT drawout devices 1 set of 2 cables (*) Can be used with any combination of NT or NW, fixed or drawout devices. 33200 33201 33209

Associated controller
The automatic-control option includes: b an IVE electrical-interlocking unit b an ACP auxiliaries control plate b a BA or UA controller, depending on the required functions b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit


for 2 devices wiring kit for connection of 2 fixed/drawout devices to the IVE unit

48/415 V AC 50/60 Hz 440 V 60 Hz


29352 54655

E88714

Control unit option

110/127 V AC 50/60 Hz

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz 440 V 60 Hz

ACP + control unit BA (1) 29470 29471 Plate ACP 29363 29364 Control unit BA 29376 29377 ACP + control unit UA (1) 29448 29472 29473 Plate ACP 29447 29363 29364 Control unit UA 29446 29378 29380 ACP + control unit UA150 (1) (communication option) 29474 29475 Plate ACP 29363 29364 Control unit UA150 29379 29381 (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.
E33420
GERIN MERLIN
multi 9

0 . OFF

P25M

GERIN

MERLIN
multi 9

0 . OFF

660V AC3-IEC292-1

P25M

660V AC3-IEC292-1

Test

Test

101

Catalogue numbers and order forms

Source-changeover systems for 2 or 3 devices Masterpact NW circuit breakers and switch-disconnectors

interlocking for source-changeover systems for 2 devices


Interlocking of 2 devices using connecting rods
Complete assembly with 2 adaptation fixtures + rods 2 Masterpact NW fixed devices 2 Masterpact NW drawout devices Can be used with 1 NW fixed + 1 NW drawout. 48612 48612
E47762

Interlocking of 2 devices using cables (*)


Choose 2 adaptation fixtures (1 for each breaker + 1 set of cables) 1 adaptation fixture for Masterpact NW fixed devices 1 adaptation fixture for Masterpact NW drawout devices 1 set of 2 cables (*) Can be used with any combination of NT or NW, fixed or drawout devices. 47926 47926 33209

Associated controller for 2 devices


The automatic-control option includes: b an IVE electrical-interlocking unit b an ACP auxiliaries control plate b a BA or UA controller, depending on the required functions b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit


for 2 devices wiring kit for connection of 2 fixed/drawout devices to the IVE unit

48/415 V AC 50/60 Hz 440 V 60 Hz


29352 54655

E88714

Control unit option

110/127 V AC 50/60 Hz

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz 440 V 60 Hz

ACP + control unit BA (1) 29470 29471 Plate ACP 29363 29364 Control unit BA 29376 29377 ACP + control unit UA (1) 29448 29472 29473 Plate ACP 29447 29363 29364 Control unit UA 29446 29378 29380 ACP + control unit UA150 (1) (communication option) 29474 29475 Plate ACP 29363 29364 Control unit UA150 29379 29381 (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
E33420
GERIN MERLIN
multi 9

0 . OFF

P25M

GERIN

MERLIN
multi 9

0 . OFF

660V AC3-IEC292-1

P25M

660V AC3-IEC292-1

Test

Test

interlocking for source-changeover systems for 3 devices


Interlocking of 3 devices using cables
Choose 3 adaptation fixtures (1 complete set with 3 adaptation fixtures + cables) 3 sources, only 1 device closed, fixed or drawout devices 2 sources, 1 coupling, fixed or drawout devices 2 normal, 1 replacement source, fixed or drawout devices 48610 48609 48608

102

103

Catalogue numbers and order forms

Source-changeover systems for 2 devices Interpact INS40 to INS630 Switch-disconnectors


To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Mechanical interlocking of two INS40 to INS630 devices
Devices with front rotary handles, mounted side by side Two devices with direct rotary handles INS250 INS320/400/500/630 Two devices with extended rotary handles INS40/63/80 INS100/125/160 INS250 INS320/400/500/630 Downstream coupling accessory Long terminal shields INS250 INS250 INS250-100 A INS250-200 A INS320 INS500 INS320/400/500/630 INS320/400/500/630 INS250-160 A INS250-250 A INS400 INS630

and enter the

Complete source-changeover assembly

104

Catalogue numbers and order forms

Source-changeover systems for 2 devices Interpact INS40 to INS630 Switch-disconnectors


Indication and measurements
4P ammeter module For INS250 Rating 100 A 150 A 250 A 400 A 600 A 4P current-transformer module For INS250 Rating 100 A 150 A 250 A 400 A 600 A Standard Low level Standard Low level

To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)

Device identification: Q 1 - NORMAL SOURCE Q 2 - REPLACEMENT SOURCE Switch-disconnector


Interpact type INS40/63/80 INS100/125/160 INS250 INS320/400/500/630 A 3 or 4

Adaptation kit required for direct handles For INS320/630 Rating

For INS320/630 Auxiliary contact For INS40/160 For INS250/630

Rating 1OF/CAF/CAO 1 OF/CAM

Rating Number of poles

Connections
Front connection Standard

Rotary handles
Rear connection INS40/80 connectors INS100/160 connectors INS250 connectors 2 short 2 long Distribution 3x16v rigid/10v flexible Snap-on y 95v Distribution 4x25v rigid/16v flexible Snap-on 1.5v to 95v (< 160 A) Snap-on 10v to 185v (< 250 A) Voltage tap connector for 185v connector Clips for connectors Set of 10 Distribution 6x1.5v to 35v rigid with interphase barriers INS320/630 connectors 1 cable 35v to 300v 2 cables 35v to 240v Voltage tap connector for 185v connector Extended front handles INS40 to INS160 Black INS250 Black INS320 to INS630 Black For complete changeover assembly Red on yellow front Red on yellow front Red on yellow front INS250 INS320/630

Locking of rotary handles


Padlocking Keylocking 1 to 3 padlocks (in OFF position) Keylock adapter (keylock not included) Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z For switch-disconnectors For ammeter module, IP40

Installation accessories
Front-panel escutcheon

"Distribloc" 125 A 160 A Multi-stage 125 A 160 A "Polybloc" 160 A 250 A Rt-angle extension Set of 3 or 4 250 A 630 A Straight extension INS250 Edgewise ext. INS630 Spreader INS250 (45 mm) Front alignment base INS320/630 52.5 mm 70 mm One-piece INS250 INS630 CU cable lugs INS100/160 For 95v cable supplied with INS250 For 120v cable 2 or 3 inter-phase For 150v cable barriers For 185v cable INS320/630 For 240v cable For 300v cable AL cable lugs INS250 For 150v cable supplied with For 185v cable 2 or 3 inter-phase INS320/630 For 240v cable barriers For 300v cable Terminal shrouds INS40/63/80 INS100/125/160 Terminal shields INS40/63/80 INS100/125/160 INS250 Short Long INS320/630 Short Long Long for 52.5 mm spreaders Interphase INS100/160 Set of 6 barriers INS250 Set of 6 INS320/630 Set of 6

Distribution blocks

105

Catalogue numbers and order forms

Source-changeover systems for 2 devices Compact NS100 to NS630 / Circuitbreakers and switch-disconnectors
To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Diagram for two Compact NS devices
Without automatic control, without emergency off auxiliaries Without automatic control, with emergency off by MN Without automatic control, with emergency off by MX (no. 51201177) (no. 51201178) (no. 51201179)

and enter the

Mechanical interlocking of two NS100 to NS630 devices


(fixed, plug-in or withdrawable) Manually operated devices, mounted side by side: Two devices with toggles Two devices with rotary handles

Mechanical and electrical interlocking of two NS100 to NS630 devices


(fixed or plug-in) Electrically operated devices, mounted side by side: Select 1 base plate + IVE, the 4 auxiliary contacts and the options / accessories Base plate + IVE Identical voltages: 48 to 415 V AC 50/60 Hz 24 to 250 V DC 440/480 V AC 60 Hz "Normal" NS100/250 "Replacement" NS100/250 "Normal" NS400/630 "Replacement" NS400/630 "Normal" NS400/630 "Replacement" NS100/250 Adapter kit for NS400/630 with NS100/250 (plug-in) Auxiliary contacts 2 OF + 2 SDE (mandatory) Quantity Options Long rear connections Plug-in base Downstream coupling accessory 3P NS100/250 4P NS400/630 Prefabricated wiring Between device and IVE Quantity

Automatic-control option
Power supply 220/240 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller

106

Catalogue numbers and order forms

Source-changeover systems for 2 devices Compact NS100 to NS630 / Circuitbreakers and switch-disconnectors
Communication
Communicating OF, SD, SDE or SDV auxiliary contacts Connected/disconnected position indication contacts Motor mechanism + communicating OF, SD, SDE contacts

To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)

220-240 V 50/60 Hz 3P 3P 3P 3P Standard 4P 4P Low level 4P

Device identification: Q 1 - NORMAL SOURCE Q 2 - REPLACEMENT SOURCE Circuit breaker or switch-disconnector


Compact type Rating Circuit breaker Switch-disconnector NS100/160/250 NS400/630 A N, H, L NA

Indication and measurements


Ammeter module standard I max Current-transformer module Insulation-monitoring module Voltage-presence indicator Auxiliary contact OF, SD, SDE or SDV SDE adapter (TM or MA trip units)

Remote operation
Electrical operation Voltage releases Motor mechanism Instantaneous Delayed AC MX AC MN AC MN AC DC DC DC DC V V V V

Number of poles 2, 3 or 4 Number of poles tripped 2d, 3d, 3dN/2 or 4d Fixed device Front Long rear conn. connections Short rear conn. Plug-in/withdr. Plug-in Earth-leakage protection Mixed rear conn. Withdrawable ME, MH, MB, MHM Voltage V 4p MB option on 3p NS

Rotary handles
Direct Extended Indication auxiliary Black Red on yellow front MCC conversion access. CNOMO conversion access. Black Red on yellow front Telescopic handle for withdrawable device 1 early-break switch 2 early-break switches Wiring accessory for early-make switches

Thermal-magnetic or electronic trip unit


Thermalmag. Electronic TMD rating (16 250 A) TMG rating (16 63 A) MA rating (2.5 220 A) STR22 SE GE STR23 SE SV STR53 (basic) UE F STR53UE FT FI ZSI wiring Option T (rating 150630 A) STR43ME Option STDAM ME SV F FTI A

Locking
Toggle (1 to 3 padlocks) Removable Fixed Rotary handle Keylock adapter (keylock not included) Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z Motor mechanism Keylock adapter + Keylocks Ronis (special) NS100/250 Keylock adapter (keylock not included) NS400/630 Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z

Installation accessories
Front-panel escutcheon Toggle Rotary handle, motor mechanism, escutcheon collar; IP40 Vigi module or ammeter IP40 Vigi module Toggle cover Sealing accessories DIN rail adapter NS100/250

F FI 110/240 V AC/DC 24/48 V AC/24/72 V DC

COM wiring Spare battery for STR43 and STR53

Connections
Rearconnect. kit Short Mixed Vigicompact Vigicompact

Plug-in / withdrawable configuration accessories


Auxiliary connections 1 automatic connector fixed part with 9 wires (for base) 1 auto. conn. moving part with 9 wires (for circuit breaker) 1 support for 3 automatic connector moving parts 9-wire manual auxiliary connector (fixed + moving) Long insulated terminals Set of 3 Set of 4 2 IP4 shutters for base Escutcheon collar Toggle Vigi Locking kit (keylock not included) 2 carriage switches (conn./disconnected position indication) Plug-in base FC/RC 2P 3P 4P Set of two power connections Standard Vigi Safety trip for advanced opening For 3P/4P chassis Moving part Fixed part

Plug-in kit Compact Withdrawable Compact kit

Long terminal-shield kit for plug-in or withdr. NS400/630 Interphase-barrier kit for plug-in or withdr. NS400/630 NS100/250 connectors Snap-on 1.5v to 95v (< 160 A) Snap-on 10v to 185v (< 250 A) Distribution 6 x 1.5v to 35v NS1400/630 connectors 1 cable 35v to 300v 2 cables 35v to 240v Right-angle terminal extensions Straight extensions NS100/250 Edgewise extensions NS400/630 Spreader NS100/250 (one piece) (45 mm) NS400/630 (52.5 mm) (70 mm) CU cable lugs NS100/250 120v 150v 185v NS400/630 240v 300v AL cable lugs NS100/250 150v 185v NS400/630 240v 300v Voltage measurement input for lugs NS100/250 y 185v for connector for lugs NS400/630 Terminal NS100/250 Short Long shields NS400/630 Short Long Long for 52.5 mm spreaders Interphase barriers Set of 6 Insulation kit > 600 V Without spreaders NS400/630 With 52.5 mm spreaders 2 insulating NS100/250 screens: NS400/630 52.5 pitch 70 pitch

Plug-in base accessories Chassis accessories

Parts of plug-in

107

Catalogue numbers and order forms

Source-changeover systems for 2 devices Compact NS630b to NS1600 / Circuitbreakers and switch-disconnectors
0

To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Diagram for two Compact NS devices
Electrical interlocking with lockout after fault: Permanent replacement source (without IVE) With emergency off by MX (without IVE) With emergency off by MN (without IVE) Permanent replacement source (with IVE) With emergency off by MX (with IVE) With emergency off by MN (with IVE) Automatic control without lockout after fault: Permanent replacement source (without IVE) Engine generator set (without IVE)

and enter the

(no. 51201180) (no. 51201181) (no. 51201182) (no. 51201183) (no. 51201184) (no. 51201185) (no. 51201186) (no. 51201187)

Interlocking using connecting rods between two NS630b to NS1600 devices


Manually operated devices installed side-by-side: For two fixed NS devices with extended rotary handles Electrically operated devices installed one above the other: Select a complete set including two adaptation fixtures and the connecting rods Complete set for: 2 fixed NS devices 2 withdrawable NS devices

Interlocking using cables between two NS630b to NS1600 devices


Electrically operated devices installed one above the other or side-by-side: Select a complete set including two adaptation fixtures and the cables Complete set for: 2 fixed NS devices 2 withdrawable NS devices 1 fixed NS device + 1 withdrawable NS device

Electrical interlocking between two NS630b to NS1600 devices


1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz 1 wiring kit for connection between 2 fixed / withdrawable devices to the IVE unit

Automatic-control option
Power supply 110 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller Power supply 220/240 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller

108

Catalogue numbers and order forms

Source-changeover systems for 2 devices Compact NS630b to NS1600 / Circuitbreakers and switch-disconnectors
Indication contacts
SD trip indication (maximum 1) 6 A-240 V AC Low level SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices) 6 A-240 V AC Low level OF ON/OFF indication contacts (maximum 3) 6 A-240 V AC qty Low level qty Carriage switches (possible combinations: 3 CE, 2 CD, 1 CT) CE - "connected" position 6 A-240 V AC qty CD - "disconnected" position 6 A-240 V AC qty CT - "test" position 6 A-240 V AC qty Auxiliary terminals for chassis alone 3-wire terminal (30 parts) Low level qty Low level qty Low level qty Jumpers (set of 10) 6-wire terminal (10 parts) Communicating DC DC DC Adjustable

To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)

Device identification: Q 1 - NORMAL SOURCE Q 2 - REPLACEMENT SOURCE Circuit breaker or switch-disconnector


Compact type Rating Circuit breaker Switch-disconnector Number of poles Device NS630b to NS1600 A N, H, L NA 3 or 4 Fixed Withdr. chassis Withdr. without chassis (moving part only) Chassis alone without connections

Remote operation
Electrical operation Voltage releases Standard Power supply MX MN MN delay unit AC AC AC V V V Nonadjustable

Micrologic control unit


Basic protection A - ammeter 2.0 5.0

Rotary handles for fixed and withdrawable device


Direct Extended Indication auxiliary Red on yellow front CNOMO conversion access. Black Red on yellow front Telescopic handle for withdrawable device 6 A-240 V AC 2 early-make switches 2 early-break switches Removable system OFF position Ronis 1351B.500 Fixed system ON and OFF positions Profalux KS5 B24 D4Z Black

2.0 5.0 6.0 7.0 AD - external power-supply module V TCE - external sensor (CT) for neutral protection Rectangular sensor 280 x 115 mm TCW - external sensor for SGR protection LR - long-time rating plug Standard 0.4 to 1 Ir Low setting 0.4 to 0.8 Ir High setting 0.8 to 1 Ir LT OFF

Locking
Toggle (1 to 3 padlocks) Rotary handle using a keylock For electrically operated devices

Communication
COM module Jbus/ Modbus Digipact Manual operation Electrical operation Manual operation Electrical operation

Modbus Eco COM module (for switchboard display units)

Connections
Horizontal rear connections Vertical rear connections Front connections 4x240v bare cable connectors + shields Long connection shields Vertical-connection adapters Cable-lug adapters Arc chute screen Interphase barriers Spreaders VO - safety shutters on chassis Top Top Top NS - FC fixed NS - FC fixed NS - FC fixed, withdr. VPEC - door interlock NS - FC fixed, withdr. NS - FC fixed NS - FC fixed, withdr. NS - FC fixed, withdr. NS - FC fixed VPOC - racking interlock VDC - mismatch protection Bottom Bottom Bottom

Keylock kit (without keylock) VBP - ON/OFF pushbutton locking OFF position locking: VCPO - by padlocks VSPO - by keylocks Keylock kit (w/o keylock) Profalux 1 keylock Profalux Profalux

Ronis Ronis Ronis

2 identical keylocks, 1 key Chassis locking in "disconnected" position: VSPD - by keylocks Keylock kit (w/o keylock)

Profalux Ronis Kirk Castell 1 keylock Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis 2 keylocks, different keys Profalux Ronis Optional connected/disconnected/test position locking On right-hand side of chassis On left-hand side of chassis

Accessories
CDM - mechanical operation counter CDP - escutcheon CP - transparent cover for escutcheon OP - blanking plate for escutcheon Mounting brackets for fixed NS Test kits Mini test kit

for mounting on horizontal plane Portable test kit

109

Catalogue numbers and order forms

Source-changeover systems for 2 devices Masterpact NT or NW / Circuitbreakers and switch-disconnectors


To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Diagram for 2 Masterpact NT/NW devices
Electrical interlocking with lockout after fault: Permanent replacement source (without IVE) With emergency off by MX (without IVE) With emergency off by MN (without IVE) Permanent replacement source (with IVE) With emergency off by MX (with IVE) With emergency off by MN (with IVE) Automatic control without lockout after fault: Permanent replacement source (without IVE) Engine generator set (without IVE) Automatic control with lockout after fault: Permanent replacement source (with IVE) Engine generator set (with IVE) BA/UA controller (with IVE) (no. 51201139) (no. 51201140) (no. 51201141) (no. 51201142) (no. 51201143) (no. 51201144) (no. 51156226) (no. 51156227) (no. 51156904) (no. 51156905) (no. 51156903)

and enter the

Interlocking using connecting rods (NT/NW devices one above the other)
Select a complete set including two adaptation fixtures and the connecting rods Complete set for: 2 drawout NT devices 2 fixed NT devices 2 drawout NW devices 2 fixed NW devices 1 fixed NT device + 1 fixed NW devices 1 drawout NT device + 1 drawout NW device

Interlocking using cables (NT/NW devices one above the other or side-by-side)
Select two adaptation fixtures (one for each device) and a set of two cables Adaptation fixture for: 1 fixed NT device (NT/NW fixed and drawout 1 drawout NT device devices may be mixed) 1 fixed NW device 1 drawout NW device 1 set of 2 cables (for two devices) qty qty qty qty

Electrical interlocking 2 appareils NT/NW


1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz 1 wiring kit for connection between 2 fixed / withdrawable devices to the IVE unit

Automatic-control option
Power supply 220/240 V - 50/60 Hz: ACP + BA controller ACP + UA controller ACP + UA150 controller ACP + BA controller ACP + UA controller ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

110

Catalogue numbers and order forms

Source-changeover systems for 2 devices Masterpact NT or NW / Circuitbreakers and switch-disconnectors


Indication contacts
OF - ON/OFF indication contacts Standard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW) Additional 1 block of 4 OF for NW max. 2 qty EF - combined "connected/closed" contacts 1 EF 6 A-240 V AC for NW 1 EF low-level for NW SDE - "fault-trip" indication contact NW Standard 1 SDE 6 A-240 V AC Additional 1 SDE 6 A-240 V AC 1 SDE Low level Programmable contacts 2 M2C contacts 6 M6C contacts Carriage switches 6 A-240 V AC Low level CE - "connected" position max. 3 for NW / NT CD - "disconnected" position max. 3 for NW, 2 for NT CT - "test" position max. 3 for NW, 1 for NT AC - NW actuator for 6 CE - 3 CD - 0 CT additionnal carriage switches max. 8 max. 8 qty qty

To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)

Device identification: Q 1 - NORMAL SOURCE Q 2 - REPLACEMENT SOURCE Circuit breaker or switch-disconnector


Masterpact type Rating Sensor rating Circuit breaker Switch-disconnector Number of poles Option: neutral on right side Device NT A A N1, H1, H2, H3, L1 NA, HA, HF, ES, HA10 (NW) 3 or 4 Fixed Withdr. chassis Withdr. without chassis (moving part only) Chassis alone without connections

qty qty qty qty V V V

Remote operation
Remote ON/OFF MCH - gear motor XF - closing voltage release MX - opening voltage release PF - "ready to close" contact

Micrologic control unit


A - ammeter 5.0 6.0 P - power meter 5.0 6.0 H - harmonic meter 5.0 6.0 AD - external power-supply module TCE - external sensor (CT) for neutral protection Rectangular sensor NT (280 x 115 mm) for earth-leakage protection NW (470 x 160 mm) LR - long-time rating plug 2.0 7.0 7.0 7.0 V

Low level 6 A-240 V AC V V

Remote tripping

BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option MN - undervoltage release R - delay unit (non-adjustable) Rr - adjustable delay unit 2nd MX - shunt release

Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks) OFF position locking: VCPO - by padlocks VSPO - by keylocks Keylock kit (w/o keylock) Profalux Kirk 1 keylock Profalux 2 identical keylocks, 1 key Profalux 2 keylocks, different keys (NW) Profalux Chassis locking in "disconnected" position: VSPD - by keylocks Keylock kit (w/o keylock) Profalux Kirk

Standard 0.4 to 1 Ir Low setting 0.4 to 0.8 Ir High setting 0.8 to 1 Ir LT OFF PTE - external voltage measurement input (required for reverse supply) BAT - battery module

Communication
Eco COM module Modbus (for switchboard display units)

Ronis Castell Ronis Ronis Ronis Ronis Castell

Connections
Horizontal Vertical Front Vertical-connection adapters Cable-lug adapters Arc chute screen Interphase barriers Spreaders Disconnectable front connection adapter Lugs for 240v or 300v cables VO - safety shutters on chassis VIVC - shutter position indication and locking Top Bottom Top Bottom Top Bottom NT - FC fixed, draw. NT - FC fixed, draw. NT - FC fixed NT, NW fixed, draw. NT fixed, drawout NW fixed NT fixed, draw. NT, NW NW

VPEC - door interlock

1 keylock Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis 2 keylocks, different keys Profalux Ronis Optional connected/disconnected/test position locking On right-hand side of chassis On left-hand side of chassis

VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection

Accessories
CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover for escutcheon OP - blanking plate for escutcheon Brackets for mounting NW fixed Test kits Mini test kit

on backplates Portable test kit

111

Catalogue numbers and order forms

Source-changeover systems for 3 devices Masterpact NW / Circuit-breakers and switch-disconnectors


To indicate your choices, check the applicable square boxes appropriate information in the rectangles . Diagram for 3 Masterpact NW devices
2 "Normal" sources + 1 "Replacement" source: Electrical interlocking without lockout after fault (no. 51156906) Electrical interlocking with lockout after fault (no. 51156907) 2 "Normal" sources + 1 "Replacement" source with source selection: Automatic control w/ engine generator set w/o lockout after fault (no. 51156908) Automatic control w/ engine generator set w/ lockout after fault (no. 51156909) 3 sources, only 1 device ON: Electrical interlocking without lockout after fault (no. 51156910) Electrical interlocking with lockout after fault (no. 51156911) 2 "Normal" sources + 1 coupling: Electrical interlocking without lockout after fault (no. 51156912) Electrical interlocking with lockout after fault (no. 51156913) Automatic control with lockout after fault: (no. 51156914)

and enter the

Interlocking using cables (NW devices one above the other or side-by-side)
Select a complete set including three adaptation fixtures and the cables 1 complete set for: 3 sources / 1 device ON, fixed or drawout 2 sources + 1 coupling, fixed or drawout 2 sources + 1 replacement source, fixed or drawout

112

Catalogue numbers and order forms

Source-changeover systems for 3 devices Masterpact NW / Circuit-breakers and switch-disconnectors


Indication contacts
OF - ON/OFF indication contacts Standard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level) Additional 1 block of 4 OF max. 2 EF - combined "connected/closed" contacts 1 EF 6 A-240 V AC 1 EF low-level SDE - "fault-trip" indication contact NW Standard 1 SDE 6 A-240 V AC Additional 1 SDE 6 A-240 V AC 1 SDE Low level Programmable contacts 2 M2C contacts 6 M6C contacts Carriage switches 6 A-240 V AC Low level CE - "connected" position max. 3 CD - "disconnected" position max. 3 CT - "test" position max. 3 AC - NW actuator for 6 CE - 3 CD - 0 CT additionnal carriage switches max. 8 max. 8

To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .
(one sheet per device, make copies if necessary)

qty qty qty

Device identification: Q 1 - NORMAL SOURCE Q 2 - REPLACEMENT SOURCE Circuit breaker or switch-disconnector


Masterpact type Rating Sensor rating Circuit breaker Switch-disconnector Number of poles Option: neutral on right side Device A A N1, H1, H2, H3, L1 NA, HA, HF 3 or 4 Fixed Drawout with chassis Drawout without chassis (moving part only) Chassis alone without connections

qty qty qty qty V V V

Remote operation
Remote ON/OFF MCH - gear motor XF - closing voltage release MX - opening voltage release PF - "ready to close" contact

Micrologic control unit


A - ammeter 5.0 6.0 P - power meter 5.0 6.0 H - harmonic meter 5.0 6.0 AD - external power-supply module TCE - external sensor (CT) for neutral protection Rectangular sensor 470 x 160 mm for earth-leakage protection TCW - external sensor for SGR protection Standard 0.4 to 1 Ir Low setting 0.4 to 0.8 Ir High setting 0.8 to 1 Ir LT OFF PTE - external voltage measurement input (required for reverse supply) BAT - battery module LR - long-time rating plug 2.0 7.0 7.0 7.0 V

Low level

Remote tripping

6 A-240 V AC BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option MN - undervoltage release R - delay unit (non-adjustable) Rr - adjustable delay unit 2eme MX - shunt release

V V

Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks) OFF position locking: VCPO - by padlocks VSPO - by keylocks Keylock kit (w/o keylock) Profalux Kirk 1 keylock Profalux 2 identical keylocks, 1 key Profalux 2 keylocks, different keys (NW) Profalux Chassis locking in "disconnected" position: VSPD - by keylocks Keylock kit (w/o keylock) Bottom Bottom Bottom VPEC - door interlock Profalux Kirk

Communication
Eco COM module Modbus (for switchboard display units)

Ronis Castell Ronis Ronis Ronis Ronis Castell

Connections
Horizontal Vertical Front Interphase barriers Disconnectable front connection adapter Top Top Top Fixed, drawout Fixed

1 keylock Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis 2 keylocks, different keys Profalux Ronis Optional connected/disconnected/test position locking On right-hand side of chassis On left-hand side of chassis

VO - safety shutters on chassis VIVC - shutter position indication and locking

VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection

Accessories
CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover for escutcheon OP - blanking plate for escutcheon Brackets for mounting NW fixed Test kits Mini test kit

on backplates Portable test kit

Schneider Electric Industries SAS


89, boulevard Franklin Roosevelt F - 92500 Rueil-Malmaison (France) Tel : +33 (0)1 41 29 85 00 http://www.schneider-electric.com http://www.merlin-gerin.com
http://www.schneider-electric.co

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Printed on recycled paper. Design: Schneider Electric Photos: Schneider Electric Printed: JPF - Imprimerie du Pont de Claix - Made in France

ABTED201149EN

09-2007

ART29770 2007 - Schneider Electric - All rights reserved