Over Fluxing in Transformer - Electrical Engineering
Over Fluxing in Transformer - Electrical Engineering
mentioned flux density as per its design limitations, the transformer is said to have faced over fluxing problem and consequent bad effects towards its operation and life. Depending upon the design and saturation flux densities and the thermal time constants of the heated component parts, a transformer has some over excitation specificat i o n transformer capacity. I.S. f o r elect rical power
time permissible over excitation, though in a round about way it does indicate that the maximum over fluxing in transformer shall not exceed 110%. The flux density in a transformer can be expressed by B = C V/f, where, C = A constant,
Effect of Over Fluxing in Transformers Stipulated Withstand-Duration of Over Fluxing in Transformers Protection Against Over fluxing (v/f - Protection) in Transformer
therefore, proportional to the quotient of voltage and frequency (V/f). Over fluxing can, therefore, occur either due to increase in voltage or decrease in-frequency of both. The probability of over fluxing is relatively high in step-up transformers in Power stations compared to step - down transformers in Sub-Stations, where voltage and frequency usually remain constant. However, under very abnormal system condition, over-fluxing trouble can arise in step-down Sub-Station transformers as well.
SL Component involved 1 Metallic support and surfaces structure for core and coils 2 Windings
Physical evidences
Consequences
Discoloration or metallic parts and adjacent insulation.Possible carbonized material in oil. Evolution of combustible gas.
Contamination of a oil and surfaces of insulation. Mechanical weakening of insulation Loosing of structure. Mechanical structure
Discoloration winding insulation evolution of Electrical and mechanical weakling of gas. winding insulation
Core lamination.
Discoloration of insulating material in contact with core. Discoloration and carbonization of organic/lamination insulation Evaluation of gas.
Electrical weakening of major insulation (winding to core) increased interlaminar eddy loss.
Tank
Blistering of paints
It may be seen that metallic support structures for core and coil, windings, lead conductors, core lamination, tank etc. may attain sufficient temperature with the evolution of combustible gas in each case due to over fluxing of transformer and the same gas may be collected in Buchholz Relay duration of time the transformer is subjected to over fluxing. Due to over fluxing in transformer its core becomes saturated as such induced voltage in the primary circuit becomes more or less constant. If the supply voltage to the primary is increased to abnormal high value, there must be high magnetising current in the primary circuit. Under such magnetic state of condition of transformer core linear relations between primary and secondary quantities (viz. for voltage and currents) are lost. So there may not be sufficient and appropriate reflection of this high primary magnetising current to secondary circuit as such mismatching of primary currents and secondary currents is likely to occur, causing differential relay to operate as we do not have overfluxing protection for sub-stn. transformers. with consequent Alarm/Trip depending upon the quantity of gas collected which again depends upon the
1.1 continuous
1.2 2
1.25 1
1.3 0.5
1.4 0
From the table above it may be seen that when over fluxing due to system hazards reaches such that the factor F attains a values 1.4, the transformer shall be tripped out of service instantaneously otherwise there may be a permanent damage.
Search