Worcester Bosch 28i RSF Combi Installation Manual
Worcester Bosch 28i RSF Combi Installation Manual
WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER
Cat I2H
GC NUMBER N.G. 47 311 54
BOILER OUTPUT
To Domestic Hot Water Modulated Control Minimum 8.5 kW Maximum 27.5 kW To Central Heating Modulated Control Minimum 10.5 kW Maximum 27.5 kW
THESE INSTRUCTIONS APPLY IN THE UK ONLY AND MUST BE LEFT WITH THE USER OR AT THE GAS METER. READ THE INSTRUCTIONS BEFORE STARTING WORK - THEY HAVE BEEN WRITTEN TO MAKE THE INSTALLATION EASIER AND PREVENT HOLD-UPS. This appliance must be installed by a competent person in accordance with the Gas Safety (Installation and Use) Regulations 1998
Contents
1. Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5. Siting the Flue. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6. Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8. Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9. Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10. Gas Suppy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 2 4 6 7 7 8 8 9 9 11. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10 12. Installing the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13 13. Commissioning the Appliance . . . . . . . . . . . . . . . . . . . . Page 18 14. Handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20 15. Inspection and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21 16. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22 17. Operational Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . Page 27 18. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 29 19. Component Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 37
1. Installation Regulations
1.1 Gas Safety (Installation and Use) Regulations, October 1998 All gas appliances must be installed by a competent person in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. 1.2 The manufacturers notes must not be taken, in any way, as overriding statutory obligations. 1.3 The compliance with a British Standard does not, of itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following; Gas Safety (Installation and Use) Regulations 1998 as amended. Current IEE Wiring Regulations BS 7671. Local Building Regulations. Building Standards (Scotland)(Consolidation). Bylaws of the local Water Company. Health and Safety Document No. 635 (Electricity at Work Regulations). The British Gas Material and Installation Specification for central heating and hot water It should be in accordance with the relevant recommendations of the following British Standards. BS6798:1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60 kW. BS5449:1990 Central Heating for Domestic Premises. BS5546:1990 Installation of gas hot water supplies for domestic purposes. BS5440:1:2000 Flues and Ventilation for gas appliances of rated input not exceeding 60 kW: Flues. BS5440:2:2000 Flues and Ventilation for gas appliances of rated input not exceeding 70kW: Air Supply. BS6891:1988 Installation of low pressure gas pipework installations up to 28mm (R1). BS7593:1993 Central Heating system cleansing and flushing. 1.4 To ensure that the installation will perform to the highest standards, the system and components should conform to any other relevant British Standards in addition to those mentioned in the instructions. 1.5 The appliance complies with the Essential Requirements of the Gas Appliance Directive and other Directives currently applicable. 1.6 This appliance contains no asbestos products. There is no potential hazard due to the appliance being electrically unsafe. There are no substances used that are a potential hazard in relation to the COSHH Regulations 1988. 1.7 The advice and instructions given in this document covers, as far as possible, the foreseeable situations which may arise. Contact Worcester Heat Systems Technical Helpline for advice on specific installations. 1.8 Product Liability regulations indicate that, in certain circumstances, the installer can be held responsible, not only for mistakes on his part but also for damage resulting from the use of faulty materials. We advise that, to avoid any risk, only quality approved branded fittings be used.
2. Introduction
The Benchmark initiative is the new code of practice to encourage the correct installation, commissioning and servicing of domestic central heating boilers and system equipment. The 'Log-book' is a vital document that must be completed by the installer at the time of installation. It confirms that the boiler has been installed and commissioned according to the manufacturers instructions. Without the completion of the Log-book, manufacturers may refuse to respond to a call-out from a householder, who will be advised that he or she must call back the installer, who has not fulfilled his obligations to record the information required by the initiative. It is important that: The services and the system are properly flushed as specified. The User is clearly instructed on the correct operation of the appliance. The benefits of regular servicing are explained - to maintain the efficiency and extend the life of the appliance. 2.1 General Information The appliance is set to give the maximum output of 27.5 kW to the domestic hot water and to the heating system. The hot water flow rate is limited to a nominal 10 l/min at a maximum temperature rise of 40C. The sanitary water section of the appliance is suitable for mains water pressure of up to 10bar. 2.2 Electrical Supply 230V - 50Hz. Load 180 watts. External fuse 3A, Internal fuses F1 - 2A, F2 - 1.0A (20mm). 2.3 Gas supply The appliance requires a maximum of 3.17 m3/h of natural gas (G20). The installation and the connection of the gas supply to the appliance must be in accordance with BS6891. The meter or regulator should deliver a dynamic pressure of 20 mbar (G20) at the appliance, which is equivalent to about 1919.5 mbar at the gas valve inlet pressure test point. 2.4 Installation The appliance is suitable for indoor installation only and for use with a sealed system only. Do not place anything on top of the appliance. It is a room sealed appliance and a separate combustion air supply is not required in any room or compartment in which the appliance is fitted. If the appliance is fitted in a cupboard or a compartment is built around it after installation, then the structure must conform to the requirements of BS6798 and BS5440 Part 2. However, because of the low casing losses, there is not a need for the cooling ventilation openings in the compartment. The spaces specified in Section 6.3 must be maintained. There is space for the service pipes to pass at the back of the appliance. 2.5 Flue The appliance has a multi-directional fanned flue system. The standard telescopic flue assembly length is from 330mm to 725mm. Extension flue kits are available for flue lengths up to 2500mm. 2
An optional vertical flue kit to provide for flue lengths up to 3400mm including vertical flue terminal. A terminal guard, Type K2, GC 393 553, is available from Tower Flue Components, Vale Rise, Tonbridge, TN9 1TB. Do not allow the flue terminal fitted to the outside wall to become obstructed or damaged. A kit for internal fixing of the flue is available separately. 2.6 Controls Central Heating Temperature control knob. A facia mounted programmer is provided. A room thermostat and/or an externally mounted programmer for mains voltage operation may be connected to the appliance.
When hot water is no longer required, the burner will extinguish. The fan and pump will continue to run for a short period to dissipate the residual heat from the appliance. Central Heating: With a demand for heating the burner will light at its minimum setting and gradually increase to give a controlled temperature rise. When the required heating temperature is achieved the output of the appliance is then automatically adjusted to maintain the temperature of the system. The output can reduce down to a minimum of 10.5 kW. If the system no longer requires even the minimum output to maintain the desired room temperature the burner will extinguish. The fan and pump will continue to run to dissipate the residual heat from the appliance. The appliance will remain off for a fixed period before re-lighting to automatically meet the system requirements. Domestic Hot Water and Central Heating: The appliance will supply heat to the central heating system as required. A demand for domestic hot water at a tap or shower will override the central heating requirement for the period of the domestic hot water demand. When hot water is no longer required the appliance will return to the central heating state and its normal mode of operation. The fan will continue to run to dissipate the residual heat from the appliance as necessary.
2.7 System All dirt must be flushed from the system before operating the appliance. The connections in the system must withstand a pressure of upto 3 bar. Radiator valves must conform to BS2767: 10:1977. Table 3 gives the pump head available for the system and the required temperature differential. A drain cock must be fitted to the lowest point and an air vent to the highest point of the system. 2.8 Showers, Bidets, Taps and Mixing Valves All taps and mixing valves must be suitable for the available mains pressure and temperatures up to 55C. It may be necessary to fit a pressure reducing valve. Hot and cold mains fed water can be supplied to over-rim bidets but is subject to local water company requirements. The flow of water from individual outlets varies on all mains fed systems that are not fitted with flow balancing valves. If a pressure equalising valve is fitted then the domestic hot water temperature should be set to maximum. Thermostatically controlled shower valves give extra comfort and protection. 2.9 Safety The appliance must not be operated with the inner casing cover removed. The gas and electricity supplies must be turned off before working on the appliance. Temperature monitoring controls are fitted to prevent overheating. Automatic frost protection is provided together with automatic pump seizure protection. The gas valve solenoids are automatically checked for gas soundness. IMPORTANT: Where back-flow prevention devices, including water meters, are fitted the expansion of hot water into cold water main can be prevented. This can result in a pressure build-up that may cause damage to the boiler and household devices such as showers, washing machines etc. In these cases we recommend that a mini-expansion vessel be fitted adjacent to the boiler in the cold water pipe. 2.10 Operation Domestic Hot Water: With a demand for hot water the burner will light at its maximum setting and then automatically adjust its output to maintain the temperature of the delivered water. 3
8
11
12 6 3 1 1 2 3 4 5 6 7 8 2 4 5
Safety Discharge C.H. Flow Domestic Hot Water Out Domestic Cold Supply C.H. Return Fixed By-pass Circulating Pump Sealed System Expansion Vessel 9 Automatic Air Vent
10 Bi-thermal Gas to Water Heat Exchanger 11 Domestic Water Flow Turbine 12 Pressure Relief Valve
3. Technical Data
Table 1. NOMINAL BOILER RATINGS (10 Minutes After Lighting) BOILER ADJUSTED FOR G20 (Natural Gas) BURNER OUTPUT INPUT (Net) GAS RATE PRESSURE kW kW m bar. m3/h 8.5 10.5 1.0 1.11 10.5 13.5 1.5 1.38 27.5 30.0 13.5 3.17 Natural Gas: Net Input = Gross Input x 0.901 * Hot water setting - manual adjustment **Central heating setting - non adjustable Table 2. FLUE DETAILS HORIZONTAL FLUE WALL HOLE DIAMETER STANDARD FLUE EXTENDED FLUE FLUE ASSEMBLY DIAMETER * NOTE : Flue lengths between 330 and 425mm require the flue to be cut EXTERNAL FIX INTERNAL FIX MINIMUM LENGTH MAXIMUM LENGTH MAXIMUM LENGTH mm 110 150 330/425 * 725 2500 100
* **
Table 3 MAXIMUM AVAILABLE PUMP HEAD BOILER OUTPUT kW 10.5 27.5 HEAD Metres 4.19 2.0 MIN. FLOW RATE L/min. 13.7 27.5 FLOW/RETURN DIFFERENTIAL C 11 14
Table 4 MECHANICAL SPECIFICATIONS CENTRAL HEATING FLOW - COMPRESSION RETURN - COMPRESSION COLD WATER INLET - COMPRESSION DOMESTIC WATER FLOW - COMPRESSION GAS INLET RELIEF VALVE DISCHARGE (PUSH FIT) CASING HEIGHT CASING WIDTH CASING DEPTH WEIGHT - LIFT WEIGHT - UNPACKED (DRY) WEIGHT - PACKAGED 22mm 22mm 15mm 15mm Rp 1 2 15mm 800mm 450mm 360mm 42.3kg 45.8kg 52kg 4
Table 5 PERFORMANCE SPECIFICATIONS PRIMARY WATER CAPACITY MAXIMUM MAINS INLET PRESSURE MINIMUM MAINS INLET PRESSURE (WORKING) FOR MAXIMUM FLOW MINIMUM MAINS INLET PRESSURE (WORKING) FOR OPERATION MAXIMUM CENTRAL HEATING FLOW TEMPERATURE MAXIMUM CENTRAL HEATING SYSTEM PRESSURE (OPERATING) MINIMUM CENTRAL HEATING SYSTEM PRESSURE OUTPUT TO DOMESTIC HOT WATER OUTPUT TO CENTRAL HEATING kw kw litres bar bar bar C bar bar NATURAL GAS (G20) NATURAL GAS (G20) l/min l/min 3.0 10 0.9 0.1 82 (nom) 2.5 0.5 8.5 - 27.5 10.5 - 27.5 13.1 9.8 Class 2 78.1 D mm 4.5
DOMESTIC HOT WATER SPECIFIC RATE - D 30C RISE MAXIMUM DOMESTIC HOT WATER FLOW RATE - 40C RISE NOx CLASSIFICATION SEDBUK NUMBER SEDBUK BAND BURNER INJECTOR
Table 6 DISCHARGE RATE l/min TEMPERATURE RISE C Table 7 GAS SUPPLY SYSTEM Total length of gas supply pipe (metres) 3 6 9 12 Natural Gas 8.7 18.0 5.8 12.0 4.6 9.4 22 28 Pipe size (mm) DOMESTIC HOT WATER TEMPERATURE RISE 7 8 56 49 9 44 10 39
Note: Each fitting used in the gas line from the meter is equivalent to a length of straight pipe which must be added to the straight pipe length to give total length. i.e: Bend=0.5 metre, Tee=0.5 metre, 90 Bend=0.3 metre. Table 8 CLEARANCES (mm) INSTALLATION ABOVE APPLIANCE AND/OR FLUE ELBOW 30 IN FRONT OF APPLIANCE 600 BENEATH APPLIANCE 200 RIGHT AND LEFT HAND SIDE 10 Refer to Section 6. Table 9 SYSTEM CAPACITY TOTAL SYSTEM VOLUME litres INITIAL CHARGE PRESSURE bar 0.5 1.0 1.5 57 75 N/A 31 42 52 SERVICE 30 600 200 10
450 10 10
200
All dimensions in mm
106
200
222
600 800
360
(D)
222
(E)
(F)
A B C D E F
All dimensions in mm
Safety Relief CH Flow DHW Out Gas Inlet Mains Cold Water In CH Return
= = = = = =
6. Air Supply
6.1 A separate vent for combustion air is not required. 6.2 The appliance can be fitted in a cupboard with no vents for cooling but the minimum clearances must be increased to those given below (note the clearances at the front are for a removable panel e.g. a door). Above the Turret In front Below Right-hand side Left-hand side 30mm 250mm 200mm 75mm 75mm
6.3 If the appliance is to be fitted in a cupboard or compartments with less clearance than those above (minimum clearances given in Section 4. Siting The Appliance) then permanent vents for cooling are required. One at high level and one at low level, either direct to outside air or to a room. Both vents must pass to the same room or be on the same wall to the outside air. 6.4 The minimum free areas required are given below. 6.5 Refer to BS 6798 and BS 5440:2 for additional information. POSITION OF AIR VENTS HIGH LEVEL LOW LEVEL AIR FROM THE ROOM 300cm
2 2
300cm
A L G D B,C L K F HI F
A F J E G M
TERMINAL POSITION
A directly below an openable window or other opening e.g. air brick. B Below gutters, soil pipes or drain pipes. C Below eaves. D Below balconies or car port roof. E From vertical drain pipes and soil pipes. F From internal or external corners. G Above ground, roof or balcony level. H From a surface facing a terminal.
MIN. DISTANCE
300mm 75mm 25mm 25mm 25mm 25mm 300mm 600mm
TERMINAL POSITION
I From a terminal facing a terminal J From an opening in a car port (e.g. door window) into dwelling. K Vertically from a terminal on the same wall. L Horizontally from a terminal on the same wall. M From door, window or air vent
MIN. DISTANCE
1200mm 1200mm 1500mm 300mm 300mm
7. Sealed System
7.1 The system must comply with the requirements of BS 6798 and BS 5449 and the appliance must not be operated without the system being full of water, properly vented and pressurised. 7.2 The pressure relief valve operates at 3 bar (45lb/in2). The discharge must be directed away from electrical components or where it might be a hazard to the user. 7.3 The pressure gauge indicates the system pressure which must be maintained. 7.4 The 8 litre expansion vessel is charged to 0.5 bar and is suitable for a static head of 5 metres (17.5ft). The pressure can be increased if the static head is greater than 5 metres (17.5ft). 7.5 With an initial system pressure of 0.5 bar, a system capacity of up to 100 litres can be accommodated. For system capacities greater than this an extra expansion vessel must be fitted. Refer to BS 7074 Pt. 1 for more information. The charge pressure can be increased but with a consequent decrease in system volume. 7.6 The filling point must be at low level. Refer to Fig. 8.
7.7 Water loss must be replaced. See Fig 4. The connection should be made in the central heating return as close to the appliance as possible. A filling loop kit is supplied. 7.8 Repeated venting loses water from the system. It is essential that this water is replaced and the system pressure maintained. 7.9 Connections to the mains water supply must not be made without the authority of the local Water Company. 7.10 The pump is set at maximum and should not be adjusted. 7.11 Connections in the system must sustain a pressure of up to 3 bar. 7.12 Radiator valves must conform to BS 2767:10. 7.13 Other valves used should conform to the requirements of BS 1010. 7.14 The appliance is fitted with a fixed internal by-pass. But it is advisable to keep one radiator permanently open.
Refer to Fig. 2.
Lockshield valve
Radiator valve
Heating flow
the lowest point of the heating circuit and beneath the appliance.
11. Electrical
11.1 MAINS SUPPLY. 230 V ~, 50 Hz, 180 watts. External Fuse: 3A. Internal Fuses: 2A SLOW (F1), and 1A FAST(F2). Spare fuses are supplied with the appliance and are fixed adjacent to the pressure gauge. 11.2 It must be possible to completely isolate the appliance. 11.3 The following connection alternatives must be used: A 3 amp fused three-pin plug and unswitched shuttered socket outlet (both complying with the requirements of BS 1363) or a double pole isolator with a contact separation of 3mm in all poles and supplying the appliance and controls only. 11.4 The appliance must be earthed. 11.5 Mains Cable. 0.75mm2 (24 x 0.20mm) to BS 6500 Table 16. The mains cable must be connected into the terminal X1 , marked L (Brown or Red lead), N (Blue or Black lead) and the earth stud and be held securely in the cable clamp. For access undo the three bottom screws and remove the facia access cover. See Fig. 11. The earth lead must be slack when the others are taut. 11.6 The wiring between the appliance and the electrical supply shall comply with current IEE Wiring Regulations and any local regulations which apply.
11.7 If a room thermostat and/or external programmer is to be fitted refer to Figs 12 and 13. The devices must be suitable for use with mains voltage. 11.8 A facia mounted mechanical programmer is available as an optional extra. Instructions are supplied with the programmer kit. 11.9 A time switch or programmer can be fitted externally to the appliance. 11.10 The boiler provides automatic frost protection, the use of a frost thermostat is not recommended. However if an external frost thermostat is considered necessary then it must be used in conjunction with a programmer. Important: To provide external frost protection the appliance must have the Central Heating Temperature Control Knob set to supply heating (the appliance may then be left with the central heating turned off at the programmer). Connection must be made at X2 terminals RI and CL. refer to Fig. 28. For advice on external frost thermostats contact Worcester Heat Systems Technical Helpline 11.11 SAFETY CHECK. After installation or in the event of an electrical fault the electrical system shall be checked for short circuits, fuse failure, incorrect polarity of connections, earth continuity and resistance to earth.
Spark electrode
Spark transformer
Flow turbine
X5 X1 X2
X4
X3
X6
Brown
Yellow Brown
Blue Brown
Blue Brown
Blue
Link
Link
2 Red
2 Blue
Mains in
2 Orange
2 Yellow
DHW sensor
Gas valve
Pump Fan
10
Air pressure switch Pins 14,17 & 18 Flow signal Pins 19 & 20 CH temp. sensor Pins 3 & 4 DHW temp. sensor
X6 X6 X6
Overheat stat
X6
Pins 8 & 9
X6
X6
CH control POT
FAN
Outputs
Inputs N
X4 Pin 1 X4 Pin 3 PUMP
RL1
N
X3 Pin 1 RL3 X5 Pin 3 X3 Pin 2
Mains indicator
GAS VALVE
F2 1AT
X5 Pin 1
RL4
ROOM STAT 6 5 4 3 2
X2 1
FULL SEQUENCE CONTROLLER MAINS PROGRAMMER/CLOCK Flame sense Optional links Spark
F1 2A
X1
3 2 1 L N
11
L
X2
Brown
Blue
ue Bl
RI
RL
Switched live
Switched live
Neutral
Live
Motor
12
Technical Helpline.
Note: READ THIS SECTION FULLY BEFORE COMMENCING INSTALLATION. 12.1 General The appliance is only suitable for fitting to a sealed system. The flue must be installed as specified in BS5440:1. Check that the appliance is suitable for the local conditions. i.e. gas supply. 12.2 Unpacking Remove the appliance from its packaging and check the contents against the packing list. 12.3 Site Preparation Check the correct position for the appliance has been chosen. Refer to Section 4 and Table 8. Check that the wall is flat and and will support the weight of the appliance. Refer to Table 4. 12.4 Fixing Holes ad Flue Opening Hold the template against the wall. Check that the template is level. Mark the position of the fixing holes and the flue opening. Refer to Fig. 14 and 15.
Mark the centre-lines of the pipe connections to aid the preplumbing of the system pipework. Check the position of the fixing points and the flue opening before drilling the fixing holes 60mm deep for the No.12 size plugs and cutting the flue duct hole at 110mm diameter (150mm diameter for internally fitted flues. 12.5 Wall Mounting Plate and Manifold Fit the plugs and fix the top support to the wall. Refer to Fig. 14. Check the top support is properly aligned before tightening the screws. 12.6 Gas and Water Pipes Remove the gas cock and fix the appropriate fitting to connect the inlet pipe and re-fit. Pre-plumbing is not recommended if no movement in the pipes is available. If it is necessary for the pipes to run up the back of the appliance then they must be arranged to pass behind the expansion vessel. Pipework must not run horizontally within the limits of the casing. It is important that the pipes are not fixed near the appliance using clips that put a strain on the connections. Before the appliance is fitted to the wall thoroughly flush the system and mains water supply.
166mm 60mm Fixing holes Mounting (alternatives) plate Appliance casing 740mm Rear flue position Appliance casing Side flue position Mounting plate Mounting wall 222mm
Side wall
400mm 12.7 Install the Boiler Remove the cabinet by releasing the sides and lifting from the top location. Check that the gas and water valves are closed. Lift the appliance to the wall, engage in the top support. Fix and tighten the bottom screws. Refer to Fig. 14. Tighten the gas and water connections. Fit a discharge pipe to the relief valve leading it away from any electrics or where it might be a hazard. The pipe must not be less than 15mm in diameter and must run continuously downward outside the appliance. Refer to Fig. 6.
Mounting wall
222 mm
166mm
Sid ew all
13
The standard telescopic flue assembly is suitable for flues from 425mm (without cutting) up to 725mm measured from the centre-line of the boiler flue outlet to the outer face of the wall. Refer to Fig. 18. If L is greater than 725mm then flue extension kits will be required - each kit extends the flue by 750mm up to a maximum of 2-5m. See table below. EXTENSION 1 2 3 MAXIMUM FLUE LENGTH mm 1475 2225 2500
12.9 Measure and Cut the Ducts General: Cut the ducts as necessary, ensuring that the ducts are square and free from burrs. Always check the dimensions before cutting. Measure the distance L. Refer to Fig. 20 and 21 . The standard flue can be telescopically adjusted to any length between 425mm and 725mm. Fix the flue assembly together using the self-tapping screw provided. Refer to Fig. 18. It will only be necessary to cut the standard assembly if L is less than 425mm. Cut the flue turret assembly and the terminal assembly by the same amount i.e L=350 - remove 75mm from each assembly. Minimum side flue length = 335mm (accommodating a 10mm Service clearance and a 100mm wall) Minimum rear flue length = 322mm 100mm wall) If L is between 1175 - 1475mm 1925 - 2225mm (accommodating a (1 extension) (2 extension)
12.8 Air and Flue Duct Preparation The method of installation of the flue system may be varied to suit the actual site conditions. The instructions for connecting and fixing the ducts must, however, be strictly followed. Remove all packing material from the flue components. Horizontal Flues up to 725mm Length Fit the flue restrictor ring by unscrewing the flue spigot from the boiler. Refer to Fig. 17.
2
Turret assembly
Fixing screw
4 6 5 Appliance casing
Telescopic adjustment
Terminal assembly
14
L
Turret assembly Fixing screws Ducts of equal length Appliance casing
Shorten first extension fitted to the turret assembly if more than one extension is fitted
L L
Flue Turret assembly Terminal assembly Terminal assembly
External wall face Rear face of appliance and face of mounting wall
If L is between: 725 - 1175mm 1475 - 1925mm 2225 - 2500mm (1 extension) (2 extension) (3 extension)
Make good the internal wall face and the external brickwork or rendering. Replace the inner casing. 12.11 Fitting of the Flue Assembly without access to the Terminal A rubber gasket kit is available from Worcester Heat Systems. NOTE: A larger diameter opening in the wall is required. Refer to Table 2. Prepare the flue assembly as described in Section 12.9. Fit the rubber sealing gasket centrally onto the terminal assembly and tighten the clamp. Refer to Fig. 23. Apply the plastic tape to the air duct in contact with the external brickwork. From inside push the assembly through the wall so that the gasket flange is against the outer face. Refer to Fig. 23. It may be necessary to adjust the legs of the flue centering ring. Align the flue turret and push fully onto the socket on the appliance. Tighten the clamping ring and fix with the screw provided. Refer to Fig 22. Seal the gap around the duct at the inner wall face with the flexible seal provided and make good. Replace the inner casing. 15
it is necessary to shorten the assembly by cutting the first extension duct assembly i.e. L = 1000mm - remove 175mm from the air and flue ducts. NOTE: Extension duct measurements do not include the socketed end. Unless specifically instructed the socketed end must not be removed. Fix the flue ducts together before fixing the surrounding air duct, the cut ducts fit into the flue assembly. 12.10 Fitting the Flue Assembly with Access to the Terminal Prepare the flue duct assembly as described in Section 12.9. Apply the plastic tape to the air duct in contact with the external brickwork. From inside push the assembly through the wall. Align the flue turret and push fully onto the spigot on the appliance. Tighten the clamping ring and fix with the screw provided. Refer to Fig. 22.
3 3 4 1. 2. 3. 4. Flue turret Clamp Appliance Fixing Screw 2 1. Flue centering ring 2. Air duct 3. Flue duct 4. Rubber sealing gasket 5. Flue Terminal
12.12 Flue Bends 90 and 45 bends are available. A maximum of two bends may be used in addition to the first bend on the flue turret. A 90 bend is equivalent to 750mm of straight duct. A 45 bend is equivalent to 375mm of straight duct.
A maximum flue assembly of 2.5m is possible with 1 X 90 bend and 2m with 2 X 90 bends. Measure the lengths X,Y and Z. Refer to Fig. 24. The maximum value of X using the turret assembly only in 506mm. Reduce the ducts to the appropriate length i.e. X = 406mm, cut 100mm from the air duct and 120mm (to cover the entry into the 45 or 90 elbow) from the flue duct. Refer to Fig.24. NOTE: The flue system ducts between the elbows, dimension Y, requires the socketed ends (of the first extension if two or more are used) to be removed and the air and flue tubes to be cut to the same length. Cut the ducts to a length Y - 162mm. Refer to Fig. 24. The final section, dimension Z, of the flue system must include a section of plain duct assembly i.e . an extension assembly with the sockets removed. Reduce the final section, including the terminal assembly, by the appropriate amount i.e. Air duct Z 81mm and the flue duct Z - 51mm. Refer to Fig. 24. If Z<425mm it will be necessary to cut the air and flue ducts of the extension to a plain length of 100mm and reduce the length 16
of the terminal assembly i.e Z=350mm - remove 75mm from the terminal assembly. If Z in 425 - 725mm it is not necessary to cut the terminal assembly or use a second extension duct as the length can be set telescopically. If Z>725mm then two extension duct assemblies will be required, the first assembly being cut to length as plain tubes. If more than two extension ducts are needed in any section to achieve the required length then the final section of the assembly must not be less than 325mm without cutting the terminal assembly. NOTE: The flue duct of the final extension must be 30mm longer than the air duct. Each section must be connected to the previous section of the flue bend by fixing the flue ducts together and then similarly fixing the air ducts which engage the elbows. Fit the assembly as described in Section 12.10, 12.11 as appropriate. Make good the internal and external brickwork or rendering.
120mm
100mm
Flue Turret
Bend
5
1. Control Panel Fixing Screws 2. Facia 3. Control Panel Pivot Point 4. Connection Cover 5. Connection Cover Fixing Screws
Air Duct
Adapter
12.14 Completion of the Installation Check that all the connections on the appliance have been tightened. Remove the facia bottom panel. Refer to Fig. 27. Connect the mains electricity supply lead to the appliance and secure the cable clamp. Refer to Fig. 27. and 28. Check there is sufficient loose lead to allow the release of the facia panel assembly and that the earth lead of the mains supply cable is longer than the live and neutral leads. Fit the facia mounted clock. Full instructions are sent with the programmer. Refer to Fig. 28. and 29. Connect any external controls ensuring that the leads pass through the appropriate clamps. Refer to Fig.18. Test for gas soundness as described in BS6891. If the appliance is not to be commissioned immediately, replace the cabinet and facia bottom panel. Check that the gas and electricity services have been turned off.
12.13 Vertical Adapter for Horizontal Flues An adapter is available for an initial short section of vertical flue. Refer to Fig. 26. Measure and cut the flue as described in Section 12.12. The first, vertical, section (equivalent to dimension X) is measured from the top of the boiler casing. Cut the vertical section of the extension duct to 167mm less than the measured distance. Do not remove the socketed ends. The minimum measured distance is 167mm. Seal the air duct to the turret using silicone sealant. Fix the adapter with the clamp and screw provided.
Fig. 28 -
N. L. Mains
Gas Valve
Fan
Pump
RN RI RL Room Thermostat
17
13. Commissioning
Benchmark Water Treatment: For optimum performance after installation, this boiler and its associated central heating system should be flushed in accordance with the guidelines given in BS7593:1992 - Treatment of water in domestic hot water systems. Full instructions are supplied with proprietary cleansers sold for this purpose. If an inhibitor is to be used after flushing, it should be used in accordance with the inhibitor manufacturers instructions. Suitable flushing agents and inhibitors are available from Betz Dearborn Tel: 0151 4209563 and Fernox Tel: 01799 550811. Instructions for use are supplied with these products. 13.1 Remove the appliance cabinet Check that the electrical supply and the gas supply to the appliance are turned off and that all the water connections throughout the system are tight. Open the system valves at the appliance. Refer to Fig.6 . Remove the automatic air vent cap. Refer to Fig. 30 . Fill the system through the external filling loop. Refer to Section 7, Sealed System. Vent each radiator in turn. The automatic air vent will vent the appliance. Remove the cap from the pump and turn the shaft about a half turn. Replace the cap. Refer to Fig. 31. Switch on the electricity supply (not the gas) and set the controls to give continuous operation in the CH mode. When the air is expelled turn off the electrical supply and the CH control to off. Check the pressure relief valve operates by turning the knob anticlockwise until it releases. Lower the facia to gain acces to the relief valve. Refer to Fig. 32. Water should be expelled from the discharge pipe. 13.2 Set the Expansion Vessel Pressure The charge pressure of the expansion vessel as despatched is 0.5bar, which is equivalent to a static head of 5m (17ft). The charge pressure must not be less than the static head at the point of connection. A Schraeder type valve is fitted to the expansion vessel to allow the discharge pressure to be increased if necessary. The expansion vessel must be charged to 0.35bar less than the initial system design pressure. 18
Flue hood
Overheat thermostat
Note: 1 bar = 10.2m = 33.5ft of water. 13.3 Set the System Pressure Fill the system until the pressure gauge is at 2.5 bar and check for leaks. Release water from the system using the relief valve test knob until the required system pressure is obtained, upto a maximum of 1.5 bar. Set the pointer on the pressure gauge to record the set system pressure. If the pressure indicated on the gauge is greater than 2.65 bar when operating at the maximum central heating temperature, an extra expansion vessel must be fitted to the system as close as possible to the appliance central heating return conection. The appliance (as despatched) can accomodate a system volume of 100 litres. Refer to BS7074 Part 1, BS5449 and table 8. If the system volume is greater then an extra vessel must be fitted as close as possible to the appliance central heating return connection and pressurised to the same figure as the integral vessel.
13.4 Clock/Programmer The controls fitted to the appliance should be set up at this stage. 13.5 Operation Check that the gas and electricity supplies are turned off. Connect a pressure gauge to the gas valve inlet and outlet pressure test points. Refer to Fig. 33. Set the temperature control to maximum and the clock/programmer to operate continuously. Turn on the gas and electricity supplies. Turn on a hot tap to give a maximum flow rate. A continuous spark will occur until the burner is alight and sensed by the control circuit. The burner will remain at its maximum domestic hot water pressure. Refer to Table 1. It should not be necessary for the gas valve to be adjusted. Refer to Section 16.4.11. Note: The burner pressure is factory set and if, after checking that the dynamic (working) supply pressure is sufficient i.e 1919.5 mb approx, at the gas valve inlet pressure test point, the correct pressure cannot be obtained then Worcester Heat Systems Service Department should be contacted. If the appliance does not light then check that it is not in the 'Lock-out' state by pressing the reset button. Refer to Fig. 34. Turn off the hot tap. The burner pressure will drop to the minimum CH setting and will ramp up to the maximum central heating pressure. 19
It should not be necessary for the gas valve to be adjusted. Refer to Section 16.4.11. Switch the appliance off and then on to reset the control. The burner pressure will remain at the minimum CH pressure for a period. Refer to Table 1. It should not be necessary for the gas valve to be adjusted. Refer to Section 16.4.11. Test for gas soundness at the joint between the burner and the gas valve with leak detection fluid. Turn the electricity supply off then back on to reset the controls. 13.6 Domestic Hot Water Turn the central heating temperature control knob fully anticlockwise. Open a hot tap near the appliance. The burner will light and go to the maximum burner pressure appropriate to the appliance and the gas. Refer to Table 1. Gradually close the tap and check that the burner pressure falls. Fully close the tap and check that the burner goes out. The fan will continue running until the appliance has cooled to a pre-set temperature. 13.7 Central Heating Check that all the radiator valves are open. Check that the system is pressurised and set to the required pressure as indicated on the gauge. Check that the clock/programmer is set to operate continuously. Set the room thermostat and the central heating control to maximum. The burner will light and the appliance will modulate its output from minimum to satisfy the required heating load. Check that all the radiators are heating up evenly. Shut down all but one of the radiators and observe the burner pressure fall. Open all the radiators and check that the burner pressure rises.
13.8 Balance the system to give a temperature differential of 11C or 13C. A non-adjustable by-pass is fitted to the appliance. Refer to Table 3. 13.10 Set the room thermostat to minimum and check that the burner goes out. Reset the room thermostat to maximum and the burner will relight and follow the normal operating procedure. Turn off the gas service cock. The burner will go out but sparking from the electrode will continue for 10 seconds when the appliance will 'Lock-out'. After 60 seconds carefully open the gas service cock. Switch mains electricity off and on and observe the burner relight and follow the normal sequence of operation. Turn off the gas service cock and electricity supply to the appliance. Drain the system while the appliance is hot. Refill, vent and re-pressurise the system as described in Section 13.1 preceding, adding, if necessary, a suitable proprietary inhibitor. Further information is available from Betz Dearborn, 0151 4209563 or Fernox 01799 550811. 13.11 Domestic Hot Water and Central heating Set all controls to maximum. Turn on the electricity supply to the appliance and open the gas service cock at the appliance. The burner will light and heat will pass into the system. Turn on a hot tap and check that hot water is soon discharged from the tap. Close the tap and the burner will go off. The appliance will then return to the central heating mode and automatically balance with the system requirements. 13.12 Completion of Commissioning Disconnect the pressure gauge and tighten the test point screw. Refit the cabinet. If the appliance is to be passed over to the user immediately then set the controls to the users requirements. If the appliance is to be left inoperative in frosty conditions then set the programmer, if fitted, to off. Do not turn electricity or gas supplies off. The appliance will operate under the control of the integral frost protection facility. If there is any possibility of the appliance being left totaly unused in freezing conditions then switch off the gas and electricity supplies and drain the appliance and system.
14. Handover
14.1 Tell the user how to operate the appliance and hand over the Users Instructions leaflet. 14.2 Tell the user what to do if the heating system is not to be used in frosty weather. 14.3 Tell the user the sealed system set pressure. 14.4 Tell the user of the importance of regular servicing. Worcester Heat Systems Ltd. offer a comprehensive maintenance contract. 14.5 Set the system controls to the users requirements. 14.6 Complete and hand over to the user the Benchmark Log-Book.
3 1 2 3 4 Reset Button Mains Indicator C.H. Temperature Control System Pressure Gauge
20
After taking the measurement replace the sealing cap. IMPORTANT Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock on the appliance before servicing. After completing the service always test for gas soundness as indicated in BS 6891. 15.3 DISMANTLE THE APPLIANCE To carry out a full and comprehensive service of the appliance remove the following parts to gain access to the components which need to be checked or serviced. (a) Cabinet Front Panel. Remove by lifting off the supports. (b) Inner Casing Cover. Check that the electricity supply to the appliance is turned off. Remove the cabinet front panel. Unscrew the four screws securing the cover to the casing and lift off. See Fig. 35. (c) Facia Panel. Check that the electricity supply to the appliance is turned off. Remove the cabinet front panel. Unscrew the two upper screws as shown in Fig. 35. and hinge down the facia taking care not to damage the pressure gauge capillary tube or electrical connections. (d) Bottom panel. Unclip and remove the appliance bottom panel. (e) Fan. Remove the inner casing cover as detailed in Section 15.3(b) above. Carefully unplug the electrical connections and pull off the sensing tubes. Unscrew the four fixing screws and remove the fan assembly. See Fig. 36. (f) Combustion Chamber Front. Remove the inner casing cover. Undo the spring clips fixing the combustion chamber front taking care not to damage the insulation on removal. See Fig. 36. (g) Flue Hood Assembly. Remove the fan assembly as described in Section 15.3(e). Remove the combustion chamber front taking care not to damage the insulation. Lift and slide the flue hood assembly from the appliance. See Fig. 36. When refitting the hood ensure that the rear return edge passes under the lip at the rear of the combustion chamber. 21
5 1 2 3 4 5 6 7 Flue hood Flue Gas Test Point Fan assembly fixing screws (4) Auto air vent Burner fixing screw Combustion chamber cover fixing clips (2) Overheat thermostat
Spark electrode
(h) Burner Assembly. Remove the combustion chamber front as described in Section 15.3(f). Pull off the two spark electrode leads, disconnect the flame sense lead at the connector and remove the grommet. Undo the burner fixing screw. Lift up and remove the burner assembly from the appliance. See Fig. 37 15.4 SERVICE OF COMPONENTS Clean the Fan. Any dust or fluff should be removed with a soft brush or by blowing. Take care not to distort the pressure sensing device. Clean the Main Burner. Brush the blade tops and mixing tube with a soft brush and check that all the flame ports are clear. Remove any blockages with a non-metallic brush. Inspect the injector and clean with a soft brush. Replace the injector if it appears damaged. Do not use a wire brush or anything likely to cause damage. Replace the spark and sense electrodes if they appear damaged. Clean the Gas to Water Heat Exchanger. Clean the heat exchanger using a soft brush. Remove the deposits from the bottom of the combustion chamber. Do not distort any of the blades. Combustion Chamber Insulation. Examine and replace any pads that are damaged. Remove any dust or deposits using a soft brush. Re-assemble the appliance in the reverse order. Check that all components are in place and correctly fixed. Leave the cabinet front panel to be fitted after checking the operation of the appliance. 15.5 TEST THE APPLIANCE On completion of the service and reassembly of the appliance, check for gas soundness and the correct operation of the appliance as described in Section 13 - Commissioning. Refit the cabinet front panel and reset the controls to the users requirements.
Burner
Open the valves and fill and re-pressurise the system as described in Section 13.2. 6. Combustion Chamber Insulation. Check that the electricity supply to the appliance is turned off. If replacing the rear insulation the appliance must be drained as described in Section 16.3(a) and 16.3(b) and the gas to water heat exchanger removed (see 16.4.5). If changing the front or side pieces it is not necessary to drain the appliance. Remove the inner casing cover, combustion chamber front, fan and flue hood assembly as described in Sections 15.3 (b,e,f & g). Remove the fibre insulation pads to be changed and fit the replacements taking care not to damage them. If the system has been drained, open the valves and fill and repressurise the system as described in Section 13.2. 7. Burner. See Fig. 37. Check that the electricity and gas supplies to the appliance are turned off. Remove the burner assembly as described in Section 15.3 (h). Fit the replacement burner in the reverse order taking care not to damage the electrode leads. 8. Burner Injector. See Fig. 37. Remove the burner as described in Section 15.3 (h). Unscrew the brass injector from the manifold. Fit the replacement injector in the reverse order. 9. Spark Electrode Assembly. See Fig. 39. Remove the combustion chamber front as described in 14.3 (g) Carefully pull off the two electrode leads, Undo the M4 extended nut and remove the spark electrode assembly from the burner. Fit the replacement electrode in the reverse order, checking that the spark gap is 3.5 to 4.5mm.
10. Flame Sensor. See Fig. 39. Remove the burner as described in section 15.3(h). Undo the M3 screw and remove the sense electrode from the burner. Fit the replacement electrode in the reverse order, checking that the sense gap is 5 to 6mm. 11. Gas Valve. See Figs. 33. and 40. Check that the electricity and gas supplies to the appliance are turned off. Hinge down the control box assembly in the servicing position as described in Section 15.3(c). Note: The adjuster sealing cap should be fitted after setting the burner pressure and coated with a small amount of paint to make any subsequent adjustment obvious. Whilst supporting the valve unscrew the plug retaining screw and carefully pull off the electrical solenoid plug connection and the two modureg leads. Undo the 8 manifold screws and remove the gas valve. See Fig. 40. Fit the replacement gas valve in the reverse order ensuring the O rings are correctly fitted. Turn on the gas supply and check for soundness.
2 1
1 2 3 4
Burner pressure test point Electrical connections modulator (Blue : Blue) Modulating solenoid Minimum / Maximum pressure adjuster - Allen key Note: Clockwise to increase and anti-clockwise to decrease the pressure 5 Inlet pressure test point 6 Main gas valve connections
23
To set the burner pressure. See Fig. 40. The minimum and maximum burner pressures must be set after a new gas control has been fitted. The maximum burner pressure must be set first, as any adjustment of the maximum pressure influences the minimum pressure setting. Start the appliance in the domestic hot water mode as described in section 13.6. - Appliance Operation. Adjust the maximum pressure adjustment (2mm Allen screw on the gas valve) to give a burner pressure of 13.5 mbar on natural gas. End the demand and reset the appliance by interrupting the mains electricity supply. (Otherwise there is a four minute anticycle delay at the end of a demand). Open a hot tap. Remove one of the blue leads from the modulating solenoid on the gas valve to ensure that the burner pressure remains at the minimum setting. See Fig. 40. Adjust the minimum pressure to 1 mbar using a 3mm Allen key. Replace the blue lead and re-check the pressures. After completing the adjustments, check the minimum and maximum pressures and re-adjust as necessary. Re-fit the adjuster sealing cap and coat with a small amount of paint to seal the cap to make any subsequent adjustment obvious. 12. Central Heating Sensor. See Fig. 41. Check that the electricity supply to the appliance is turned off. Hinge the facia assembly in the servicing position as described in Section 15.3(c and d). Carefully pull off the two leads from the sensor. Pull off the sensor and spring retaining clip from the pipe. Fit the replacement sensor in reverse order with a layer of heat sink compound between the faces. Refit the leads.
1 2 3 4 5 6 7 8 9 10 11 12
9 10 12 8 Pressure relief valve Domestic hot water sensor Water flow turbine Gas valve Pump Air pressure switch Air pressure switch connecting tubes Pressure gauge connection Gas valve electrical connections By-pass pipe Fixing disc and screw Central heating sensor
11 7
13. Domestic Hot Water Sensor. See Fig. 41. Check that the electricity supply to the appliance is turned off. Hinge the facia assembly in the servicing position as described in Section 15.3(c and d). Carefully pull off the two leads from the sensor. 24
Undo and remove the clamping screw. Pull off the sensor and spring retaining clip from the pipe. Fit the replacement sensor in the reverse order ensuring a layer of heat sink compound is between the faces. Refit the leads. 14. Circulating Pump. See Fig. 41. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 16.3(a). Hinge the facia assembly in the servicing position as described in Section 15.3(c). Remove the burner assembly as described in Section 15.3(h). Undo the two union nuts and the pipe to the expansion vessel, remove the pump from the pipe-work. Support the pump and remove the electrical cover. Disconnect the electrical wires taking note of their positions. Fit the replacement pump in the reverse order using new sealing washers. (Alternatively replace the pump head only by removing the four Allen screws on the pump, remove the head and support whilst removing the electrical connections. Refit the new head). Open the valves and fill and re-pressurise the system as described in Section 13.2 Note: The direction of flow should be upwards. The speed should always be set to maximum. 15. Expansion Vessel. Drain the central heating circuit as described in Section 16.3(a). Isolate the gas supply at the mains. Then either fit a separate expansion vessel on the central heating return to the appliance or replace the existing vessel as described below. Drain the domestic circuit as described in Section 16.3(b). Disconnect the flue system at the boiler. Disconnect the appliance pipework at the appliance entry points ensuring precautions are taken to cope with any water remaining in the appliance. Remove the appliance from the wall. Disconnect the expansion vessel from the appliance by undoing the fitting nut at its base. Fit the replacement vessel in the reverse order. Open the valves and fill and re-pressurise the system as described in Section 13.3 16. Pressure Relief Valve. See Fig. 41 and 42. Drain the central heating circuit as described in Section 16.3(a). Hinge down the facia assembly as described in Section 15.3(c). Remove the Bottom panel as described in Section 15..3(d). Undo the discharge pipe connection and remove the valve retaining clip. Remove the valve taking care not to distort the pipework. Fit the replacement valve in reverse order. Reconnect the discharge pipe. Open the valves and fill and re-pressurise the system as described in Section 13.3. 17. Water Flow Turbine. See Fig. 41 and 43. Check that the electricity supply to the appliance is turned off. Drain the domestic hot water circuit as described in Section 16.3(b). Remove the two upper screws and hinge down the facia panel as described in Section 15.3(c). Disconnect the electrical connection. Unscrew the securing nuts and remove the turbine housing from the pipework. Fit the replacement water flow turbine in the reverse order ensuring new fibre washers are fitted to the new turbine body. Check that the correct, blue, flow restrictor is fitted. NOTE: Washers are different Inlet = Outlet =
Remove the four corner screws on the rear of the facia and separate the metal back panel from the plastic facia. Remove the flame sense and ignitor leads from the control board. Remove and retain the brass nut and washer. Release the six pillars on the control board and pull the control board forward off the back panel. Fit the replacement board in the reverse order ensuring it is pushed firmly onto the six pillars and clicks into place. Special care should be taken with the brass post and nut to ensure a good earth contact. (Check earth continuity between the incoming earth and the appliance chassis). Refit the facia panel and hinge the control box assembly in the servicing position as described in Section 15.3 (c).
1 4 5 1 2 3 1 2 3 4 5 6 Flow turbine Flow restrictor (10l Blue) Fibre washer (inlet) Electrical connection Direction of flow Fibre washer (outlet) 1 2 3 4 Facia Control board Rear cover Fixing screws
Type
19. Pressure Gauge. See Fig. 34. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 16.3(a). Remove the two upper screws and hinge down the facia panel as described in Section 15.3(c). Prise back the retaining clips securing the gauge to the facia panel. Unscrew the fixing disk and unplug the gauge from the pump inlet pipe. Fit the replacement gauge in the reverse order ensuring the O ring is in place. Open the valves and fill and re-pressurise the system as described in Section 13.3. 20. Control Board. See Fig. 44. Check that the electricity supply to the appliance is turned off. Undo the 3 screws and remove the facia bottom panel. Remove the two upper screws and hinge down the facia assembly. Carefully pull off all the connectors. Disconnect the mains supply lead at terminal X1 and unscrew the earth lead from the left and side panel. 25
21. Gauze Filter. See Fig. 45. Remove the water flow turbine as described in section 16.4-17. Undo the lower union nut on flow switch housing. Undo the nut on the isolating valve and remove the mains water inlet pipe. Carefully extract the filter from the valve end of the pipe. Replace the filter and refit the pipe in reverse order using a new fibre washer.
22. Flue flow sensor. See Fig. 46. Check that the electricity supply to the appliance is turned off. Remove the fan assembly as described in Section 15.3(e). Unscrew the single central retaining screw and withdraw the sensor from the fan. Fit the new sensor ensuring the correct orientation and carefully tighten the retaining screw. Refit the fan assembly in reverse order.
Positive
26
End of a domestic hot water overrun Anti-cycle delay Main gas valve OFF
Central heating temperature 6C above set point Operating Switch (or programmer) OFF
EITHER 6
Gas valve OFF AUTOMATIC START-UP SEQUENCE Burner pressure CH min (1.5 mbar ) Burner pressure automatically adjusted for range rating and then modulated to maintain set flow temperature CENTRAL HEATING DEMAND SATISFIED
Continue pump and fan for 4 mins plus extra 4 mins pump.
Pump on
27
Initiate sparking Stop sparking
YES PASS
Fan ON Sense air pressure
NO ABSENT
Wait (fan or fan and pump on)
PRESENT
Sense flame
PRESENT ABSENT
Ignition Time out (after 9secs) Ignition Lock-out
FAIL
HOT WATER DEMAND (Overrides all other overrun modes and functions)
Inhibit operations for approximately 1 second. 6 second delay before reignition from any other demand. Modulate heat input to maintain hot water temperature at the factory pre-set level HOT WATER DEMAND SATISFIED Pump OFF
Domestic hot water temperature monitored by hot water sensor Is the central heating mode interrupted? AUTOMATIC START-UP SEQUENCE
3. "Autofrostat" Function
Commence normal central heating mode until heating temperature reaches 20C
If burner on more than 3 min; 10 sec over-run 80 sec fan over run 10 sec pump over run 80 sec fan over run
28
Above 8C Return to normal OFF state Burner never to be extinguished irrespective of the rate of temperature rise At the set point change to a wide band proportional control
No demand and primary temperature below 6C monitored by the central heating sensor
Below 4C
Run pump
No demand and central heating temperature above 50C monitored by the central heating sensor
4C to 8C
Burner pressure adjusted based on the temperature rise over the previous minute. Aiming at 4C rise/minute.
End of demand or central heating temperature above 70C monitored by the central heating sensor
CH temp. sensor
Overheat stat
Modulating valve
X6 Pins 15 & 16
X6 Pins 8 & 9
X6 Pins 19 & 20
CH control POT
Flow signal
FAN
Outputs Inputs
N
X4 Pin 1 LOW VOLTAGE ELECTRONICS (Microcontroller)
RL1
X4 Pin 3 PUMP
X3 Pin 1
RL3
X3 Pin 2
X5 Pin 3
Mains indicator
GAS VALVE
F2 1AT
X5 Pin 1
RL4
ROOM STAT
6 5 4 3 2
X2 1 MAINS PROGRAMMER/CLOCK
Flame sense Spark
Optional links F1 2A
X1
321 L N
29
YES
GO TO CHECK D
YES
NO
Is mains LED illuminated?
NO NO
GO TO CHECK C
NO
YES
Is control knob set for demand?
YES NO
Turn control knob fully clockwise
YES
Is a room thermostat fitted?
NO
YES
Is room thermostat calling for heating?
NO
YES
Is programmer fitted?
NO
GO TO CHECK O
YES
Is programmer calling for heat?
YES NO
Set clock to call for heat
YES
Is pump running?
NO
GO TO CHECK F
YES
Has overheat thermostat tripped?
YES
GO TO CHECK E
YES
NO
NO
GO TO CHECK K
GO TO CHECK K
30
No mains LED
NO
YES
Is Fuse F1 OK?
NO
Replace fuse
YES
Is F2 (1.25AT) OK?
NO
Replace fuse
YES
Faulty PCB Replace
Remove X6
NO
Open circuit?
NO
Short circuit
YES
Is resistance between pins 19 & 20 between 690ohms & 33k?
YES NO
GO TO CHECK H
Faulty
Replace thermistor
Faulty
GO TO CHECK H
YES
OK
GO TO CHECK I
OK Faulty
Replace harness
Faulty
GO TO CHECK J
OK
OK
31
NO
Is capillary broken?
NO
YES
Is capillary firmly ATTACHED to exchanger?
YES NO
ATTACH to heat exchanger Replace overheat thermostat
YES
GO TO CHECK I
Pump Check
Is pump connector secure on the PCB (X3)?
NO
Secure Connector
YES
Is mains present at the pump connector (X3 pins 1 & 2)?
NO
GO TO CHECK O
YES
Faulty pump
Fan Check
Is fan connector secure on the PCB (X4)?
NO
Secure Connector
YES
Is mains present at the fan connector (X4 pins 1 & 2)?
NO
GO TO CHECK L
YES
Mains at fan
NO
Faulty Harness
YES
Faulty fan
32
Thermistor Check
YES
Is resistance between terminals of thermistor between 690ohms & 33k?
NO
Faulty thermistor
YES
Thermistor OK
YES
Is continuity observed between each end of wire in question?
NO
YES
Harness OK
YES
Is short circuit observed between pair of wires in question?
NO
Faulty harness
YES
Harness OK
33
Ignition Check
Is fan running?
NO
GO TO CHECK G
YES
Does sparking occur?
NO
GO TO CHECK E
GO TO CHECK L
YES
Does ignition occur?
NO
NO
NO
YES
YES
GO TO CHECK M
YES
Are leads breaking down?
NO
YES
Replace leads
NO
NO
YES
YES
Is lead secure both ends?
NO
Secure lead
YES
GO TO CHECK I
HARNESS OK
Faulty PCB Replace
NO
GO TO CHECK N
YES
Ignition OK
34
NO
YES
Reconnect the WHITE & BROWN wire and remove the GREEN wire. Initiate a demand. Does the fan run?
NO
NO
PCB faulty
YES
Fan or fan cable faulty
YES NO
With fan running disconnect BROWN wire. (DO NOT touch chassis with it). Is a short circuit observed across exposed APS terminals?
YES
APS OK
NO
YES
Is live output present at X5 pins 1 & 2 relative to neutral at pin 3? Note: Readings to be taken within 9 seconds of a demand.
NO
YES
Is gas pressure present at input to burner?
NO
YES
Gas valve OK
It is not possible to seperately test the gas valve and the supply lead. Relpace the gas valve or the lead.
35
YES
NO
GO TO CHECK I
NO
YES
Is pressure at burner always the same?
YES
NO
Gas valve OK
With pressure above minimum, remove Modureg Lead. Does pressure drop to minimum?
NO
YES YES
Does voltage go above 6.25V?
NO
Faulty PCB. Replace
With boiler cold, slowly open HW tap. When flow reaches 3l/min does boiler ignite? (Flow can be checked using a measuring jug and stop watch)
NO
YES
NO
Disconnect the 3 way in-line connector. Check that there is 5V DC output from the PCB at the connector. Red +5V Black 0V
YES
NO
GO TO CHECK I
HARNESS OK
YES
Re-connect the 3 way connector and open a tap to run the turbine. Check that there is between 1.5 and 4.5 V DC across the green and black wires/terminals.
YES
NO
Turbine OK Faulty turbine. Replace
36
E01-892 375-697 E01-612 E01-930 E01-598 E01-599 E01-600 E01-601 299-506 375-699 E01-602 E01-603 E58-079 E04-582 E01-900 299-495 E01-605 324-822
18 19 20 21 22 23 24
LM7
FLUE OPTIONS E01-943 E01-944 E01-945 E01-946 E01-058 E01-059 Telescopic Horizontal Flue Kit Extension Flue Kit Vertical Flue Kit Vertical Flue Adaptor Internal Fixing Kit Flue Elbow Kit Flue Elbow Kit 425 - 725mm 750mm 7 716 191 068 7 716 191 006 7 716 191 069 7 716 191 016 7 716 191 019 7 716 191 013 7 716 191 014
37
14
3 21
3
15 22 13 4 11 7
12
10 23
20
20 6
24 25
23 24
19
18
16
38
39
This manual is to be used in conjunction with the variant part number of the bar code below:
Worcester Heat Systems Limited (Bosch Group), Cotswold Way, Warndon, Worcester WR4 9SW. Telephone: (01905) 754624. Fax: (01905) 754619. Technical Helpline (08705) 266241. www.worcester-bosch.co.uk
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued improvement. All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.