MiCOM IEDs For Process Bus - Experts 2012
MiCOM IEDs For Process Bus - Experts 2012
April 2009
GRID
Scope
Page 3
Page 21
Page 31
Page 47
Testing, Conclusion
Page 60
Digital SS Components
Integrated Substation Automation System with 1. Substation Control System (SCS) 2. Condition Monitoring System (CMS) 3. Smart Grid Applications (SG APPS Cyber, Intrusion, Wide Area Management) 4. Substation Phasor Data Concentrator
WAN
SCS HMI
SG APPS
PDC
Proxy Switches Multiple Ethernet IEC61850.8-1 Station Bus C37.118 Phasor Data
sPDC
WACU
Prot. Px40
AMU
DMU
CMU
DRUs
Several IEDs 1. Protection / Measurement with 9-2 interface 2. Bay Controller Unit (BCU) 3. Condition Monitoring Unit (CMU) 4. Switches & Telecom 5. Proxy Server 6. Merging Units (AMU, DMU, NMU for NCIT) 7. Wide Area Control Unit (WACU) 8. Power Quality /Disturbance Record Unit (DRU) 9. Energy Meters
Time synchronisation
Microsec accuracy required
7 9
Technical Services
61850-8-1 1
Bay Level
Protection
Function A
Function B
6 3
Control
1 8
Bay Level
Protection
6 3
Control
4
HV Equipment
61850-9-2 61850-8-1
4
HV Equipment
Application Layer : IEC 61850-9-2 Light Edition guideline to aid implementation and interoperability
Sampling rate : 80 or 256 samples per cycle Neutral current and/or voltage may be measured, or derived Sampled values are multicast on the LAN Defines Logical Device MU Synchronising of sampling
Protection Bay 1
Protection Bay 2
Ia Quality 32 bits
Ic Quality 32 bits
Va x 1000 Va Quality Vb x 1000 Vb Quality Vc x 1000 Vc Quality Vn x 1000 Vn Quality 32 bit Int 32 bits 32 bit Int 32 bits 32 bit Int 32 bits 32 bit Int 32 bits
SV frames are multicast MAC Address range: 01-0C-CD-04-00-00 to 01-0C-CD-04-1F-FF input on Merging Units Note the frame overhead : 24 bytes of raw data (per 3-phase voltage and current) in about 125 byte Ethernet frame
CB
AMU #1
AMU #2
AMU #3
DMU#1
DMU#2
-8-1 PRP
-8-1 PRP
-9-2LE
-9-2LE
-9-2LE
V0 2.5 ms delay
V-18
I-36
I-81
SV frames from different MU may have uneven delays Relay measurements will be incorrect unless the SV frames are time-aligned
Presentation title - 01/01/2010 - P 13
Sample Count
0 3999 at 50 Hz 0 4799 at 60 Hz Counter resets every sec when a time sync signal is received
MiCOM P594
P594
Merging Unit
Merging Unit
Scope
Page 3
Page 21
Page 31
Page 47
Testing, Conclusion
Page 60
P446
MiCOM Alstom
Distance protection, with integral teleprotection and one / two breaker reclosing Line differential for 2 or 3 terminal lines, with distance and one / two breaker reclosing Transformer differential for up to 5 ends, with advanced loss-of-life thermal monitoring Numerical busbar protection
P546
MiCOM Alstom
P645
MiCOM Alstom
P746
MiCOM Alstom
P841
Transmission line terminal IED, for backup, reclose and breaker fail management
-9-2LE
HV+LV+TV
TV Current - 1
LV Current
HV Current 2
P645
-9-2LE
LAN A
LAN B
P446 Configuration
HV+LV+TV
P645
Scope
Page 3
Page 21
Page 31
Page 47
Testing, Conclusion
Page 60
Analog Inputs
CT / VT Input Module
Analog Inputs
80 samples / cycle
The Px4x -9-2LE interface conditions the SV to enable reuse of tried and tested protection algorithms
Presentation title - 01/01/2010 - P 31
AMU 2
AMU 1
AMU 2
In this case, there is a 1ms delay between SV frames from MU#1 and MU#2
Standard Px4x
LD1
B
LD2
IEC 61850-8-1 port / protocol options are the same for relays analogue inputs or -9-2LE inputs Important: P594 is mandatory for ALL P546 relays in a current diff scheme P594 version D
Scope
Page 3
Page 21
Page 31
Page 47
Testing, Conclusion
Page 60
CB
AMU #1
AMU #2
AMU #3
DMU#1
DMU#2
-8-1 PRP
-8-1 PRP
-9-2LE
-9-2LE
-9-2LE
P594
B C
H xxx H xxx
A B C D E
E
CB
C
I/O Card -9-2LE
-9-2LE
I/O Card
I/O Card
-9-2LE
P594
B C
AMU #1
AMU #2
AMU #3
-9-2LE
-9-2LE
-9-2LE
Physical Wiring
CB
* A Quantitative Evaluation of IEC61850 Process Bus Architectures Jean-Charles Tournier & Thomas Werner, ABB Corporate Research
Fibre links
Copper links
Main 1, Main 2, BCU AMU x 1, DMU x 1 Switch x 1
* A Quantitative Evaluation of IEC61850 Process Bus Architectures Jean-Charles Tournier & Thomas Werner, ABB Corporate Research
Fibre links
Copper links
Main 1, Main 2, BCU AMU x 2, DMU x 2 Ring with RSTP on all IEDs Alt. Ring with HSR on all IEDs
* A Quantitative Evaluation of IEC61850 Process Bus Architectures Jean-Charles Tournier & Thomas Werner, ABB Corporate Research
Main 1 with BCU, Main 2 with BCU AMU x 2, DMU x 2 Ring with RSTP on all IEDs Alt. Ring with HSR on all IEDs
Main 1 with BCU per bay Main 2 with BCU in common IED AMU x 1, DMU x 2 RB: HSR Red Box QB : HSR Quad Box
* A Quantitative Evaluation of IEC61850 Process Bus Architectures Jean-Charles Tournier & Thomas Werner, ABB Corporate Research
* A Quantitative Evaluation of IEC61850 Process Bus Architectures Jean-Charles Tournier & Thomas Werner, ABB Corporate Research
* A Quantitative Evaluation of IEC61850 Process Bus Architectures Jean-Charles Tournier & Thomas Werner, ABB Corporate Research
Notes: Only component costs considered; engineering, testing and commissioning may have significant impact. Project specifications (eg: number of MUs per bay, protection operating time) may become the deciding factor for architecture Primary plant technology may lead to alternative conclusions
Scope
Page 3
Page 21
Page 31
Page 47
Testing, Conclusion
Page 60
PC Ethernet Switch Ethernet GOOSE and SV IED (SV Interface) Trip Trip
Testing may also call for Ethernet switches, Time sync source