Elite 440 PDF
Elite 440 PDF
Elite 440 is a multi-line three-phase digital panel meter for accurate and reliable measurement of electrical quantities (voltage, current, power, frequency, etc.) in industrial and commercial applications. It has a large multi-line backlit LCD display which enables four parameters to be displayed at the same time. Modbus communications capability allows easy integration with energy monitoring systems. An expansion module can be fitted for enhanced functionality (pulse input/output)
Applications
Commercial and industrial sub-metering applications B u i l d i ng m a n age m e n t a n d m o n i to r i ng sys te m s
Features
Large four-line seven-digit display with quadrant
(SCADA/EMS/DAS)
High, medium and low-voltage switchgear panels Control and relay panels Power Control Centre (PCC) panels Motor Control Centre (MCC) panels Energy management for commerce and industry
Benefits
Easy interface with external devices through built-in Modbus
(RS-485) Detachable connectors for easy installation Onboard diagnostics make installation easy Suitable for star or delta connections and for low or highvoltage applications Cost-effective online monitoring Field-configurable CT/ PT primary and secondary values using push-buttons
identification section and bar graph for instantaneous power-level indication High accuracy: Class 1.0,0.5s,0.2s Average THD measurement for voltage, current and power, up to 31st harmonic Measurement selection (star or delta/ 3P4W or 3P3W) Modbus communication via RS-485 port True root-mean squared (RMS) metering Calibration LED for accuracy test on site Wide and configurable current range 1-2A and 5-10A Wide-range auxiliary power supply, suitable for high-voltage or low-voltage installations Maximum demand recording Midnight snapshot ( values) for selected energy registers Scroll-lock and 'Favourites Page' display support Expansion capability via add on modules for analogue outputs or pulse inputs/outputs Password protection for setup mode
Elite 440
Models 441 442 443 444 445 446 447* 448*
Features
P-N voltage Average P-N voltage P-P voltage Average P-P voltage Line current (L1, L2, L3 and Average) Active / Reactive Current Frequency Power factor Average Power factor Active Power Total Active Power Reactive Power Total Reactive Power Apparent Power Total Apparent Power Active Total Import / Export Energy Reactive Import (Q1+Q2) / Export (Q3+Q4) Energy Reactive (Q1,Q2,Q3,Q4) Energy Apparent Import / Export Energy Active / Apparent Forwarded Reactive Lag / Lead Forwarded Cumulative MD Phase Angle Power On / Off Hours Load On / Off Hours Feeder Interruptions Count (When Aux is also off) Min / Max Values THD Voltage ** THD Current ** THD Power ** RPM with Freq and VUnb and IUnb Modbus on RS 485
(*) Additional modules (Two pulse input & output) can be available with Elite 447 and Elite 448 (**) THD for Voltage, Current and Power are optional in 441 to 446. # Optional software config view is available for reading and configuration
Elite 440
Metering Parameter Accuracy
Parameters Voltage Current kW kVar kVA kWh kvarh Power Factor Frequency Accuracy Class 0.2* 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.1 Accuracy Class 0.5 0.1 0.2 0.5 0.5 0.5 0.5 0.5 0.5 0.1
Connection Diagram
LT 3P 4W
1
1
HT 3P 3W
1 2 3
HT 3P 4W
2
2
3
3 N
S1 S2 S1 S2 S1 S2 V1 V2 V3 VN I1 I2 I3
S1 S2 S1 S2 S1 S2 V1 V2 V3 VN I1 I2 I3
S1 S2 S1 S2 S1 S2 V1 V2 V3 VN I1 I2 I3
For CT/PT meter, ensure that it is connected on secondary side of instrument transformer.
Mechanical Dimensions
Available Option (2 Pulse input & output)
65 m
96 m
m 45 m
65 m
96 m
m 45 m
96 6 mm
55 mm
96 mm
module
Elite 440
Technical specifications
Electrical Connection type Wiring configuration Voltage range : Measurement voltage range Aux power supply range Current range Main frequency Accuracy Class Common product for HT3/ HT4/ LT application Common product for 3 P-3 W and 3 P-4 W application 57.7 V (100V) - 230 V (400V) AC 3 phase 4 wire (3 phase 3 wire) 80 VAC/DC - 300 VAC/DC or 24 VDC to 60 VDC (Variant) Available 1-2A and 5-10 A in single variant (field configurable) 50/60Hz with 5% 0.2s available for HT-4 (for 1A/5A Ibasic) 0.2s available for HT-3 (5A Ibasic) 0.5s & 1.0 available for LT-4 ( for 1A/5A Ibasic) Aux burden : 3.5 VA; 8VA when all modules connected. Current ckt burden : 1 A - 0.05VA per phase, 5 A - 0.25 VA per phase. Voltage ckt burden : 0.15 VA per phase.
Burden
Weight Enclosure Terminals Max conductor size Material Used Environmental Ingress protection Insulation Impulse withstand Temperature Humidity Feature Favourite page CT/VT primary Communication Baud rate Load survey
96 x 96 x 65 mm (w/o module); 96 x 96 x 110 mm (with module) Cut out size 92 x 92 mm 0.5 kg (approx) Poly Carbonate Combicon connector 2.5 mm2 Plastic material self-extinguishing
IP 52 (front fascia); IP20 (at terminals) 4 kV RMS 50 Hz 6 kV -20 C to +60 C (operating) -25 C to +80 C (storage) 95% non-condensing
Input supports voltage range of 8-40VDC with pre-define duration, Output are normally open type, voltage rating of 230 VAC @ 100mA with pre-defined pulse width.
On / Off Configurable in field through keypad RS485 Modbus half duplex (Default) and data will be available in floating point format from 1200-38400 bps (Default 9600 bps) 40 days for 6 parameters @ 30 min IP Options for 15 or 60-minute integration period.