Short Circuit Current Calculation
Short Circuit Current Calculation
ELECTRICAL SYSTEM ALL YOU WANTED TO KNOW ABOUT SHORT -CIRCUITS BUT WERE AFRAID T O ASK! DESIGN REVIEW
Issue 1 Revision 1 27-Nov-00
This document is the exclusive property of DC Maritime Technologies Inc. and is furnished on a confidential basis. No portion of this document may be copied, traced, photographed or in any way reproduced nor may items hereon depicted be manufactured as shown or as described without the written consent of DC Maritime Technologies Inc. The recepient of the information contained here on may not disclose or make available the same to any other person or business firm nor may information be used except for the specific purpose intended.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
AMENDMENT HISTORY
REV # 1 SECT. PAGE DESCRIPTION Editorial changes throughout document AUTHORITY D.Clark DATE Nov 27 00
COMPUTER DATA
FILE NAME Short-circuit current design report Rev 1 27 Nov 00 DISK IDENTITY General/Articles/ Short circuits APPLICATION Word 2000 COMPILED BY D.Clark
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
ii
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Foreword
The short- circuit current analysis is a fundamental requirement of all regulatory agencies, classification societies and governmental bodies. Although the short- circuit condition is an abnormal operating state, the analysis is essential to ensure that a marine and offshore unit electrical system is designed with due cognisance to system and personnel safety.
There are several calculation methods available, some easy, some complex. It is important to understand that a method involving complex calculations may not produce any better results than one using simple approximations; particularly if the basic information required for the calculation is preliminary. The calculation methods tend to be very sensitive to the input data and consequently the quality of the result depends entirely on the quality of information available.
The calculation methods described in this design review fall into three broad categories; based on broad approximations, on basic generator and system data and based on full generator characteristics enabling short- circuit current decrement to be estimated. The correct method to use may not always be easy to determine and like most engineering situations it is necessary to a p p l y p r o f e s s ional judgement to use the right tool at the right time. A general rule would be to apply the most simple method and approximations first; then make a judgement as to the need to complete a more extensive analysis. Generally once it is decided to complete an extensive analysis, the methods proposed by the International Electrotechnical Commission IEC 61363- 1 will give the best result for the calculation effort required.
This design review takes a light hearted view of short- circuit current calculation me thods describing the simplest up to the most complex suggested by IEC 61363- 1 . A n y r e v i e w o f calculation procedures cannot escape undertaking some calculations and in the case of electrical calculations, generally involves vector mathematics. This r e v i e w is no different however rather than deriving many of the formulae involved, the review only quotes the basic formula required to complete a short- circuit current calculation in an attempt to keep the mathematical proofs to a minimum.
A basic understanding of vector mathematics will help in understanding some of the processes described in Section 12 and on. A copy of IEC 61363- 1 is essential to understand the methods described in Section 16 and on.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
iii
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
TABLE OF CONTENTS: 1. 2. 3. INTRODUCTION WHY DO WE NEED TO CALCULATE THE SHORT-CIRCUIT CURRENT ANYWAY? THE SHORT-CIRCUIT CURRENT MUST THEREFORE BE RELATED TO THE SHORT-CIRCUIT PATH IMPEDANCE AND SYSTEM POWER? BUT THERE MUST BE AN EASY WAY TO DO THIS CALCULATION? DONT CONFUSE ME JUST GIVE ME A SIMPLE CALCULATION AND LETS GET ON WITH THE JOB! THE ABOVE CALCULATION HARDLY REQUIRES A ROCKET SCIENTIST, WHY SHOULD I EVER LOOK FOR MORE COMPLICATIONS? SO HOW CAN I CALCULATE THE SHORT-CIRCUIT CURRENT SPECIFIC TO MY GENERATORS BUT I DONT WANT TO DO ANYTHING COMPLICATED? BUT THIS LAST CALCULATION DOES NOT SEEM TO HAVE USED THE OHMS LAW FORMULA? WONT THE CIRCUIT EXTERNAL IMPEDANCE ALSO REDUCE THE SHORT-CIRCUIT CURRENT? SO SHOULD I WORRY ABOUT CABLES? HOW DO I CALCULATE THE SHORT-CIRCUIT CURRENT TAKING INTO ACCOUNT CABLES? Generator & cable impedances Motor load & its contribution to the short-circuit Main switchboard short-circuit current Main switchboard circuit breaker rating Engine Room Distribution Panel short-circuit current Asymmetrical short-circuit current values ERDP Circuit Breaker Ratings The effect of including cable impedance
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00
1 1
2 2 2
4. 5. 6.
7.
4 6 8 8 8 9 10 11 11 12 13 13 13
8. 9. 10. 11.
PAGE
iv
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
12. WHAT ABOUT FAULT POWER FACTOR, AND SURELY CABLE IMPEDANCE MUST AFFECT CURRENT ASYMMETRY Short-circuit power factor Circuit asymmetry 13. HOW CAN I EASILY ESTIMATE POWER FACTOR AND ENSURE MY CIRCUIT BREAKERS FUNCTION CORRECTLY Generator contribution Motor load contribution Generator & Motor Short-circuit current Power factor A Quickie Asymmetrical short-circuit current calculation by formula Asymmetrical short-circuit current calculation by table Engine Room Distribution Panel ERDP RMS symmetrical current calculation ERDP Power factor ERDP asymmetrical short-circuit current ERDP Short-circuit calculation summary Comparison between the Impedance Z Method and Resistance/inductance X/R method 14. 15. 16. SO WHAT IS THE TRUTH ABOUT SHORT-CIRCUIT CURRENT CALCULATIONS? ISNT IT GOOD THAT THE TRUE VALUES ARE LESS THAN THOSE CALCULATED? OK IS THERE A CALCULATION METHOD THAT OVERCOMES THESE PROBLEMS? IEC 61363-1 an example Data required Generator and cable characteristics Voltage driving the short-circuit current
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00
13 14 14
14 15 16 17 17 18 18 19 19 20 20 20 21 21 22 23 23 24 25 25 25
PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Sub-transient and transient initial values of short-circuit current Short-circuit current ac and dc components Motor load contribution Short-circuit power factor RMS Symmetrical short-circuit current Asymmetrical short-circuit current Main switchboard summary of short-circuit current calculations ERDP Short-circuit current calculation ERDP Summary of Short-circuit current calculations Comparison of the decrement method with the previous short-circuit current calculations 17. 25 26 26 27 27 27 27 28 29 29
OK SO WILL A DECREMENT CALCULATION GIVE ME THE LOWEST SHORT-CIRCUIT VALUE THAT I CAN APPLY WITH CONFIDENCE? 29 Motor load contribution including decay Main switchboard short-circuit current including motor decrement Main switchboard asymmetrical short-circuit current including motor decrement Main switchboard calculation summary including motor decrement ERDP short-circuit current including motor decrement ERDP summary of short-circuit current calculations including motor decrement Comparison of motor decrement calculation to previous methods 30 31 31 32 32 33 33 34 34 35 36 36 37
18. 19.
THERE IS STILL ANOTHER AVENUE TO EXPLORE! EVALUATION OF THE SHORT-CIRCUIT CURRENT USING THE IEC EQUIVALENT GENERATOR Principal characteristics of the Equivalent Generator Calculating the constants M and N EG sub-transient time constant EG Transient time constant
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
vi
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Evaluating T
dc
38 40 40
USING THE EQUIVALENT GENERATOR TO CALCULATE THE SHORT-CIRCUIT CURRENT AT A REMOTE PANEL BOARD. 41 Comparison of EG calculation with previous methods 43 43
21.
CONCLUSIONS
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
vii
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
1. Introduction
Sure I can calculate the short-circuit current. I really dont know what all the fuss is about and Im not even an electrical engineer the Chief shouted above the thud thud thud of his Sulzer super monster! The calculation of short-circuit currents is easy as is anything when you know how. But also one should not forget that a little knowledge is both dangerous and can be expensive; so perhaps we should look at this calculation a little closer!
It is important therefore to estimate or calculate the value of the prospective current likely to occur under shortcircuit conditions and ensure that the devices provided to interrupt that current are rated to withstand and interrupt it. Similarly it is important to ensure that devices connected in the short-circuit current path, for example motor starters, are adequately sized to withstand the short-circuit current for the time required for the protective devices to open.
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
3. The short-circuit current must therefore be related to the short-circuit path impedance and system power?
This is true, and is the fundamental logic applied to calculate the short-circuit current value. Unfortunately we never know when and where a short-circuit will occur. Accordingly estimating the short-circuit path impedance can be very complex. In addition, although the generator or system power may be known, other consumers on the system add to that power under short-circuit conditions. For example, as a motor decelerates, it acts like a generator and contributes to the power driving the short-circuit current. It is difficult to determine the likely number of motors or other consumers contributing power at the time the short-circuit occurs. Consequently to determine precisely the total power driving the short-circuit can be very difficult. Apart from these complications, when a generator experiences a short-circuit current, it responds in a non-linear fashion. In effect the generator impedance changes as the short-circuit current develops; this again affects the short-circuit current at any point in time.
5. Dont confuse me just give me a simple calculation and lets get on with the job!
Thats fine. The easiest short-circuit current calculation is to multiply the total generator full load current by 10 and add to it the total running motor current multiplied by 4, i.e. 10 x Sum of Generator Full load Current PLUS 4 x Sum of running motor current. This will provide an approximate value of the Root mean square symmetrical short-circuit current or RMS Symmetrical short-circuit current , and may be used to specify the minimum short-circuit rating for all the electrical switchgear. This particular value defines the maximum breaking current of the switchgear. A reasonable design strategy would be to then specify electrical switchgear that has a standard rating above this calculated value. Using this approach however you must ensure that the standard rating used, is standard for the specific country where it is intended to purchase the switchgear. Standards do vary from country to country. In general, North American standards are different from the rest of the world, but countries within North America generally follow the same standards. The North American standard rms symmetrical current ratings for low voltage circuit breakers are 14, 18, 22, 25, 30, 35, 42, 50, 65, 85, 100, 125, 150 and 200 kA
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Electrical switchgear may be rated on a symmetrical current basis or an asymmetrical basis. It may be necessary therefore to determine other short-circuit values such as the average asymmetrical value, the maximum rms asymmetrical value or even the peak value of the short-circuit current. The asymmetrical values can be obtained by multiplying the RMS symmetrical current calculated above by specific factors as follows: Average asymmetrical rms current = 1.4 x rms symmetrical current
Maximum rms asymmetrical current = 1.8 x rms symmetrical current Peak asymmetrical current = 2.6 x rms symmetrical current.
An example illustrates the calculation: Calculate the short-circuit current for a tug and specify the switchgear ratings. The generators are 2 x 120 kW 0.8 power factor and may operate in parallel. The motor load is assumed to be 60 kW. The electrical system is 3 phase 440 volts. The rms symmetrical current is calculated as follows: Generator full load current = (120 x 1000) / (square root of 3 x 440 x 0.8) = 197 amps Motor running current = (60 x 1000) / (square root of 3 x 440 x 0.8 x 0.9) = 109 amps. (This assumes that the motors are approximately 90 % efficient and are designed for 0.8 power factor). Therefore the RMS symmetrical current = 2 x 10 x 197 + 4 x 109 = 4,376 amps. Therefore the average asymmetrical current is 1.4 x 4,376 = 6,126 amps Therefore the maximum rms asymmetrical current is 1.8 x 4,376 = 7,877 amps And the peak asymmetrical current is 2.6 x 4,376 = 11,378 amps.
Switchgear rated at 5,000 amps RMS symmetrical will be adequate for this installation. This easy calculation procedure gives the main system circuit breaker rating. If it is necessary to calculate the circuit breaker ratings for a low voltage system connected through transformers, we need the transformer rating and its low voltage rated current. The rms symmetrical current can be estimated by multiplying the low voltage current by 20. The asymmetrical current values may then be obtained by applying the same factors as above. For example the RMS symmetrical current for a 3 phase 120 volt switchboard connected through a 3 0 kVA transformer would be:
CLIENT DC Maritime Technologies Inc.
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
6. The above calculation hardly requires a rocket scientist, why should I ever look for more complications?
For most small installations, i.e. those with an installed generator capacity of less than 500 kVA the above calculation methodology is entirely satisfactory. Refining the calculation is unlikely to enable a lower rated switchgear to be used. However for larger installations, this simple calculation may result in over-rating the switchgear requirements. It is important to understand that the above calculation method has used rules of thumb. The calculations include several assumptions and these may not be correct for your particular system. The most significant assumption is that of the system or generator characteristics. As outlined above (in section 2) the major generator characteristic that determines the short-circuit current is its impedance. Unfortunately generators are not straightforward and the generator impedance changes under different generator operating conditions. Under short-circuit conditions, the generator impedance changes as the short-circuit develops with time. When rating switchgear, it is the impedance during the first few milliseconds of a fault that determines the short-circuit current values that are of interest. The easy calculation above has assumed a particular generator impedance value and that only the highest values of short-circuit current needs to be calculated. This impedance is termed the sub-transient impedance. In the simple calculation above, the worst case sub-transient impedance likely to be encountered on a marine generator, has been assumed. If on your installation the generator sub-transient impedance is more than the worst case, then the value of short-circuit current will be less. Similar assumptions have been made for the motor contribution, but this is not as significant as the generator contribution.
7. So how can I calculate the short-circuit current specific to my generators but I dont want to do anything complicated?
A simple calculation specific to your generators is possible but first it is necessary to understand a little more about sub-transient impedance values. As with most electrical calculations, the key to success is to use Ohms law. Simply put, this states that the current in an electrical circuit is equal to the voltage driving that current, divided by the impedance restricting the current. Or in symbols: I = V / Z
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
In the case of a short -c i r c uit, we can assume that the voltage is the generator voltage. The impedance will be the sub-transient impedance of the specific generator used on the installation. This is illustrated in figure 7.1. Again an example illustrates the method: Calculate the short-circuit current for a tug and specify the switchgear ratings. The generators are 2 x 120 kW 0.8 power factor and may operate in parallel. The motor load is assumed to be 60 kW. The electrical system is 3 phase 440 volts. The generator sub transient impedance is 12%. The generator short -circuit current can be calculated using the formula: Isc = (100 x Ig ) / % STI STI is the generator sub-transient impedance. To use this formula we need to calculate the generator full load current Ig This may be provided by the generator manufacturer; if not, use the formula: Ig = (1000 x kilowatts ) / (square root 3 x volts x power factor) For the example above, the generator full load current is therefore: Ig = (1000 x 120 ) / ( 1.732 x 440 x 0.8 ) = 196.8 amps The generator short-circuit current is therefore: Isc g = (100 x 196.8 ) / 12 = 1640 amps The full short-circuit current can be calculated using the same methodology as the previous example using the generator RMS symmetrical short-circuit current of 1640 amps and the motor running current of 109 amps. Therefore the RMS symmetrical current = 2 x 1640 + 4 x 109 = 3,716 amps. Therefore the average asymmetrical current is 1.4 x 3,716 = 5,202 amps Therefore the maximum rms asymmetrical current is 1.8 x 3,716 = 6,689 amps And the peak asymmetrical current is 2.6 x 3,716 = 9,662 amps.
Again, switchgear rated at 5,000 amps RMS symmetrical or above will be adequate for this installation. Although when determining the circuit breaker short-circuit ratings, the end result is the same as determined in Section 5, (i.e. switchgear rated at 5,000 amps RMS symmetrical is adequate), the calculated values of shortcircuit current are more appropriate to the actual system being investigated. For this simple example o ne may question use of the added complication; but it should be noted that the calculated values are now some 17 % less than that previously calculated. If the first calculation had revealed short-currents close to, or even just above the standard switchgear ratings, then the second calculation is
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
justified on the basis that it shows a 17% margin in the switchgear ratings and saves the use of a higher class of switchgear. Again for this simple illustration, the cost difference between say 5 kA or 10 kA switchgear is small but such differences would be much more significant on a large installation.
8. But this last calculation does not seem to have used the ohms law formula?
Not entirely true but a good observation! The calculation method used in section 7 includes many simplifications and approximations. If this method is used, switchgear should be chosen with at least a 10% margin above the calculated value. That is, for a calculated rms symmetrical current of 3,716 amps, select switchgear the next rating above 4,088 amps. The following ohms law calculation will indicate why. First convert the generator sub-transient impedance from a percentage value to an ohmic value. Again, rather than dwell on electrical theory, apply the following formulae blindly and leave the explanations to another time! The sub-transient impedance in ohms = (the sub-transient impedance in % x (generator voltage)2 x power factor) / (100,000 x generator kilowatts) that is: STI in ohms = (%STI x V2 x pf ) / (100,000 x kW) For the example above, Generator STI in ohms = (12 x 440 x 440 x 0.8 ) / (100,000 x 120 ) = 0.1549 ohms If we now apply ohms law, the short-circuit current for the generator will be: Iscg = 440 / 0.1549 amps, right? No, wrong! The generator STI in ohms is a phase value and accordingly we must use the phase voltage in the calculation. Therefore the generator short-circuit current Iscg = 440 / (square root 3 x 0.1549) = 1640 amps as previously calculated unfortunately this is still incorrect! In the previous section (Section 7), figure 7.1 indicated that the generator voltage V drives the short-circuit current through the circuit. This is true, but the generator sub-transient impedance is internal to the generator, whereas V, or in our case 440 volts is the generator terminal voltage. Therefore we must re-draw the circuit diagram and increase the internal generator driving voltage such that the terminal voltage is 440 volts. This means the generator internal voltage E will be V plus the voltage drop caused by the generator sub-transient impedance. Figure 8.1 illustrates this. Instead of calculating the internal voltage precisely we can assume that it is about 10% higher than the terminal voltage and use the following formula to calculate the generator short-circuit current: Iscg = 1.1 V / (square root 3 x STR ohms)
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
In our case, Is c g = (1.1 x 440)/ (1.73 x 0.1549) = 1804 amps. The asymmetrical short-circuit current values are calculated using the same factors as before. Knowing that the sub-transient impedance is 12%, a more precise RMS symmetrical current calculation is: Iscg = 1.12 V / (square root 3 x STR ohms) In this case this Iscg = (1.12 x 440)/ (1.73 x 0.1549) = 1837 amps.
It is interesting to note that, these more precise calculations lead to values very close to the quick method outlined in the 10 times rule and illustrated in section 4 above. The results of the various methods are tabulated below: CALCULATION METHOD GENERATOR RMS SYMMETRICAL SCC MOTOR CONTRIBUTION AMPS RMS SYM SCC AMPS RATIO TO 10X RULE 10TIMES RULE SECTION 5 1970 STI METHOD SECTION 7 1640 USING 1.1V S E CTION 8 1804 USING 1.12V SECTION 8 MODIFIED 1837
436
436
436
436
4376 1
3716 0.85
4044 0.92
4110 0.94
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
9. Wont the circuit external impedance also reduce the short-circuit current?
Yes that is true. The calculated short -circuit current at the generator switchboard, can be reduced by including the generator cable impedance. Similarly, the calculated short -circuit current at a distribution panel is reduc ed due to the feeder cable impedance between the switchboard to the distribution panel. The amount of the reduction is of course dependent upon cable size and length. A cable with a large cross sectional area has a small impedance and hence the reduction o n the calculated short -circuit current is less than for a small cross section cable that has a large impedance. Generally the generator cables are large and most times including generator cables has little effect on the final choice of circuit breakers. However for panel board feeder cables, this is not true and the cable impedance can often reduce the short-circuit level sufficiently to enable lower rated circuit breakers to be used. For the previous example, including the generator cable and distribution panel cables will not change the circuit breaker rating. This is because the calculated short-circuit level is already well below the minimum standard ratings for 440 volt circuit breakers. This is generally the case for most tugs and small vessels with generators of this size.
10.
For small vessels having installed generating capacities of up to about 500 kVA, 440 volts the complexity of the short-circuit current calculation is unlikely to change the choice of circuit breakers. In all probability standard 14 kA breakers or less will be applied throughout the installation and to include the effect of the cables would not be beneficial. An exception to this is if miniature circuit breakers can be used. In such cases, a calculation including distribution panel feeder cables will provide a better estimate of the feeder panel short-circuit current requirements. However for these small installations, generator cables are unlikely to cause a major change in circuit breaker requirements. For installations rated 500 kVA - 1000 kVA, it may be worthwhile to include the effects of the cables. For installed capacities in the range 1000 1500 kVA and above, cables should be included in order to minimize the required circuit breaker short-circuit ratings at the distribution panels.
11. How do I calculate the Short-circuit current taking into account cables?
The calculation is easiest explained through an example. Calculate the short-circuit current for a cargo ship and specify the main switchboard switchgear ratings and the Engine Room Power Panel board ratings. The generators are 3 x 400 kW 0.8 power factor and all three can operate in parallel. The motor load is assumed to be 300 kW. The electrical system is 3 phase 440 volts. The generator sub transient impedance is 12%. The generator is
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
connected to the switchboard using 2 three conductor 500 MCM cable 5 meters in length. The Engine Room Power Panel is connected to the switchboard using 20 meters of 3 conductor #2 cable. A diagram is useful! Figure 11.1 shows the 3 - 400 kW generators connected to a switchboard with two 5 meter lengths of 3 conductor 500 MCM cable. The 300 kW of motor load is shown connected to the switchboard and an engine room power panel is connected with 20 meter of 3c #2 cable. Although this example can be done using real ohmic values, it is easier to use a calculation method very familiar to electrical engineers; the per-unit or percentage method. The per-unit or percentage method changes all the values in the system to figures that are relative to a common base, such as 100, 500, or 1000.
The method simplifies the arithmetic. More importantly, the method is used in the electrical industry to define electrical equipment characteristics; for example the generator sub-transient impedance is generally expressed as a percentage value, say 12%. This is the value of the generator impedance based on the generator kilowatt or kVA rating. Rather than dwell on the mechanics of the method, its blind application is adequate to describe this short-circuit current calculation.
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The impedance of the cable is calculated as follows: Cable impedance Zc = Cable length L x [ R2 + X2 ] per cable For two cables in parallel this becomes Zc/2 i.e. Zc = (5/1000) x [0.069 x 0.069 + 0.092 x 0.092] = 0.00058 ohms i.e. Zc/2 = 0.00029 ohms This ohmic value must now be converted to a percentage value using the same base as the generator impedance. In this case the base is the generator rating of 400 kW or 500 kVA (400/0.8). Again, in order to circumvent a lengthy discussion on how to calculate percentage values, it is adequate to blindly apply a formula, which in this case is; Percentage impedance = [(100,000 x base kVA) / (Line Voltage)2] x ohmic value) Hence for the generator cable, the percentage impedance is; [(100,000 x 500) / (440 x 440)] x 0.00029 % = 0.0743% This value is now added to the generator impedance of 12 % to obtain the impedance of the generator and cable connected in series; i.e. Z(g+c) = 12.0743% The above addition of impedances is not 100% accurate because it has not considered the resistive and reactive components of the impedance as separate entities. This simplification does affect the accuracy of the final result as will be seen later. For three identical generators, the parallel impedance of the three generators is the impedance of one, divi ded by three. The combined impedance is therefore 12.0594/3 = 4.0248% Therefore applying the formulae used in 6 above the short-circuit current due to the generators is: Iscg = (100 x 656 ) / 4.0198 = 16,299 amps
10
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
different to that at a remote panel board. Furthermore, the amount of contribution to be included depends on the location of the short -circuit and the actual number of motors running just prior to the short -circuit. For faults at the main switchboard, the current contributed by a (series of) motor at a remote panel board will be affected by the impedance between the motor, panel board and the main switchboard where the motors are connected. Again we must remember the accuracy of this method and apply a little system knowledge in our decision making. For this particular example, the majority of the large motors on the system that could be running will be connected to the main switchboard; therefore we will make the bold assumption that ALL the 300 kW of motors are connected to the main switchboard and are all running at the time of the short-circuit. Now we must calculate the percentage impedance of the motor load. This is done by calculating the impedance of an equivalent generator on the system that would produce the same short-circuit current as the running motors. We noted previously that the short-circuit current produced by a motor is approximately 4 times its running current. Therefore as calculated in 4 above the motor short-circuit current contribution is: 4 x 547 = 2187 amps RMS symmetrical.
11
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
We also know there is an inaccuracy in the calculating method itself. For example the short-circuit current calculation has used a base system and selected one of the generators for the base quantities. Therefore the voltage assumed will be the generator voltage of 440 volts; but this is incorrect as shown in Section 8 above. The voltage should have been the voltage behind the generator reactance, which is higher than 440 volts. With all these uncertainties it is difficult to precisely quantify the accuracy of the above calculated value. It has been the authors practice to assume that the net sum of all inaccuracies will be at least 10 %, add this to the calculated value; then select the next highest value of switchgear. Therefore for a calculated value of 18.4 kA, the choice of 18 kA switchgear would be unwise and the next rating above 20.4 kA, i.e. 22 kA should be specified. This provides an approximate margin of 20 %, which is comfortable if somewhat conservative.
(ERDP)
= 0.105 ohms/km.
18506.9 = (100 x 656 ) / Z(g+c)(1,2,3,M) Z(g+c)(1,2,3,M) = 100x 656 / 18,486 = 3.5486 % Therefore adding the impedances in series gives: Z(g+c)(1,2,3,M)(ERDP) = Z(g+c)(1,2,3,M) + Z(ERDP) = 3.5486% + 2.7452% i.e. Z(g+c)(1,2,3,M)(ERDP) = 6.2938%
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
12
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Now the short -circuit current at the Engine Room Distribution Panel can be calculated as above using the formula: Isc = (100 x Ig ) / % Z i.e. Isc = (100 x 656) / 6.2938 = 10,422.9 amps = 10.4 kA
12.
What about fault power factor, and surely cable impedance must affect current asymmetry
This is very true and raises several issues: 1. 2. 3. Is short-circuit power factor an issue? What is asymmetry? Will such calculations affect the bottom line choice of circuit breakers?
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
13
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Each one of these topics could be the subject of several pages and rather than address them in detail, we will assume they are important, need to be addressed and worth at least a brief explanation!
Circuit asymmetry
Circuit asymmetry occurs when an electrical circuit contains elements other than resistance, such as the inductance of the generators and cables. It has a dynamic characteristic associated with it; the result being that whenever the current changes in a circuit due to switching, or short-circuits, a transient current occurs causing peak currents to be higher than those due to the resistive elements alone. The transient however does decay after a short period and the current settles into a symmetrical wave. The amount of asymmetry under fault conditions therefore depends on the amount of inductance caused by the generator and the distribution cables. Accordingly it is different at different points in the distribution system. The amount of asymmetry affects the instantaneous short-circuit current value; consequently it affects the multiplying factors that are applied to the symmetrical current to obtain the maximum asymmetrical and other circuit breaker ratings. Generally when taken into account, lower values of asymmetrical current will result.
13.
How can I easily estimate power factor and ensure my circuit breakers function correctly
There are simple and rigorous ways to make an engineering assessment of the situation. Unfortunately, the simple methods require fairly lengthy electrical calculations and are in themselves subject to inaccuracies. Choice of method requires an engineering judgment based on experience and the available circuit breakers. A short-circuit fault is analogous to a switch closing onto a resistive and inductive circuit. This causes an asymmetrical current to exist in the circuit. The asymmetrical current can be divided into two parts; a symmetrical part that is constant; and a part that decreases with time, down to zero. The symmetrical portion is often referred to as the a.c. component and its value depends primarily upon the generator and system
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
14
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
characteristics. The decaying portion is often referred to as the dc component, and its value depends upon the instant in time that the short-circuit is applied. The symmetrical component of the short-circuit current is calculated in a similar way to the previous example. Peak values and asymmetrical values are calculated using multiplying factors that are dependent upon the short-circuit power factor, rather than the fixed values quoted in 5 above. The method of calculation can be illustrated using the previous example, i.e. Calculate the short-circuit current for a cargo ship and specify the main switchboard switchgear ratings and the Engine Room Power Panel board ratings. The generators are 3 x 400 kW 0.8 power factor and all three can operate in parallel. The motor load is assumed to be 300 kW. The electrical system is 3 phase 440 volts. The generator sub transient impedance is 12%. The generator is connected to the switchboard using 2 three conductor 500 MCM cable 5 meters in length. The Engine Room Power Panel is connected to the switchboard using 20 meters of 3 conductor #2 cable.
Generator contribution
This time we need the generator resistance as well as its reactance. The resistance can be obtained from the manufacturer or from catalogue data. It is normally quoted as ra , the armature resistance. For generators of this size (400 kW), the armature resistance is of the order of 1.2%. Generator manufacturers can provide specific data for specific machines. Accordingly in order to assure the relevance of the short-circuit current analysis, such data should be considered as a contract requirement and provided to the designer before the system design is finalized. For this example the sub-transient impedance of one generator is 12% based on the 400 kW rating. We can therefore use resistance of 1.2% to calculate the generator sub-transient reactance using the formula: The impedance (Z) = square root of {the resistance(R)2 + the reactance(X)2} The generator sub-transient reactance (generally written as x) will be: X = {12 x 12 1.2 x 1.2} = 11.94% The generator cable is two 5 meter lengths of 3 conductor 500 MCM. As indicated in the previous example, for a 60 hz installation this cable has a resistance (R) of 0.069 ohms per kilometer and a reactance (X) of 0.092 ohms per kilometer. (These figures can be obtained from cable impedance tables). The ratio of the resistance and inductance is important. Instead of calculating the percentage impedance directly we need to calculate the percentage resistance and inductance separately. These values are calculated exactly as previously for impedance; i.e. use the formula: Percentage value = [(100,000 x base kVA) / (Line Voltage)2] x ohmic value) Hence for the generator cable, the percentage resistance is; [(100,000 x 500) / (440 x 440)] x 0.069 = 17.82% And the percentage reactance is;
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
15
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
[(100,000 x 500) / (440 x 440)] x 0.092 = 23.76% Therefore for 5 meters of 2 runs of cable connected in parallel: The resistance will be x 5/1000 x 17.82% = 0.04455% And the inductance will be x 5/1000 x 23.76% = 0.0594%. These values must now be added individually to the generator resistance and sub-transient reactance values to obtain the impedance of the generator and cable connected in series; i.e. R(g+c) = 1.2 + 0.04455 = 1.24455 % and X(g+c) = 11.94 + 0.0594 = 11.9994 % From these values we can calculate Z(g+c) i.e. Z(g+c) = {1.24455 2 + 11.9994 2 } = 12.0638% For three identical generators, the parallel impedance of the three generators is the impedance of one, divided by three. The combined impedance is therefore = 12.0638/3 = 4.02126% The differences between this value and the values calculated in Section 11 are minimal and due to calculation rounding errors. It should be remembered that the short-circuit current is a vector quantity and the resistive and reactive elements of the circuit will define the circuit power factor. The power factor can be calculated by dividing the resistance by the impedance, i.e. Power factor = 1.24455 / 12.0638 = 0.1032 Therefore the short-circuit current due to generators will be: Iscc (g+c)(1,2,3) = 100 x 656 / 4.02126 = 16,313.3 amps at 0.1032 power factor This value comparable to that calculated in Section 11 (16,299 amps). In addition, we now know the power factor associated with this part of the short-circuit current.
16
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Iscc(M) = 4 x FLC i.e. 4 x 547 = 2188 amps at 0.34 power factor
As these values are both vectors, they must be added together using vector mathematics. The easiest way to do this is to use a calculator capable of changing polar coordinates into rectangular coordinates and adding together the resolved components; i.e. Iscc (g+c)(1,2,3 = 16,313.3 amps at 0.1032 power factor =16,313.3 amps at 84.079 degrees i.e. 1,682.945 + j 16,226.258 If your calculator doesnt have these functions available, then it may be recalled that the two resolved components are actually equal to 16,313.3 cosine 84.079 and 16,313.3 sin 84.079. Similarly for the motor Iscc(M) = 2188 amps at 0.34 power factor = 2188 amps at 70.0123 degrees i.e. 743.92 + j 2057.65 Adding together the resolved components we have I scc(g+c)(1,2,3,M) = (1,682.945 + 743.92) + j (16,226.258 + 2057.65) = (2426.865 + j 18,283.908) If we now resolve this value back to polar coordinates we have; I scc(g+c)(1,2,3,M) = 18,444.27 at 82.439 degrees
Power factor
Recalling that the power factor is in fact the cosine of the angle, then; I scc(g+c)(1,2,3,M) = 18,444.27 at 0.1316 power factor This value is used for two purposes, one is to check the capabilities of the proposed circuit breakers by comparing this value to the circuit breaker test v alue, and secondly to calculate the asymmetrical short-circuit current values. For the anticipated circuit breaker short-circuit current rating (i.e. 22 kA breakers), molded case circuit breakers are generally tested at 0.15 0.2 power factor. The standards do allow testing at a lower power factor and accordingly if the circuit breaker you wish to use has not been tested at a lower power f actor, it would be prudent to check with the manufacturer that a prospective power factor of 0.13 is satisfactory.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
17
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK! A Quickie
When completing detailed short-circuit current calculations it is difficult to escape vector mathematics. However when calculating the main switchboard short-circuit current on the average marine installation, the above result is very typical. Consequently for the level of accuracy obtainable using these methods, arithmetically adding the generator and motor short-circuit currents as illustrated in the previous example and assuming a power factor of 0.12 0.15 is generally quite acceptable. More detailed calculations would be appropriate for installations when large bow thrusters or cargo pumps, with ratings comparable to one of the generators are powered from the main switchboard. Or alternatively if one or more of the generators are installed in say the forepeak, or other locations away from the main switchboard. In such instances the large motor load and generator cables will change increase power factor towards 0.15 or higher.
Noting that cos i.e. the circuit power factor is 0.1316 then tan will be 7.53396 Applying the above formula for this example we have: Peak value = 2 Irms { 1 + exp (-/ tan )} = 2 x 18,444.27 x { 1 + exp (-/ 7.53396)} = 2 x 1.65903 x 18,444 = 43,274 amps = 43.3 kA Asymmetrical RMS Iasy rms = Irms { 1 + 2 exp (-2/ tan )} = 18,444.27 { 1 + 2 exp (-2/ 7.53396)} = 18,444.27 x 1.36698 = 25,213 amps = 25.2 kA Average 3 phase RMS I3 ph avg rms = Irms [1/3 { 1 + 2 exp (-2/ tan )}+ 2/3 { 1 + exp (-2/ tan )} ] = Irms [0.45566+ 0.7355] = 18,444.27 x 1.19116 = 21,970 amps = 22.0kA Therefore we have calculated the following short-circuit current values for this example: Symmetrical RMS current Iscg
CLIENT DC Maritime Technologies Inc.
= 18.4 kA
DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
18
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph avg rms Short-circuit power factor = 43.3 kA = 2.35 x Iscg = 25.2 kA = 1.37 x Iscg = 22.0 kA = 1.19 x Iscg = 0.132
It can be seen that using Figure 11-1 of IEEE 45 1998 provides very comparable results.
Recall that the ERDP is connected to the Main Switchboard with 20m of 3c #2 cable for which the characteristics are: Cable resistance is 0.521 ohms/km Cable reactance is 0.105 ohms/km Therefore for 20 meters of cable we have:
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
19
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Cable resistance is 0.521 x 20/1000 = 0.0104 ohms Cable reactance is 0.105 x 20/1000 = 0.0021 ohms Cable impedance = 0.0106 ohms Converting these values to percentage figures gives; Cable resistance = [(100,000 x 500)/(440 x 440)] x 0.0104 = 2.6911% Cable reactance = [(100,000 x 500)/(440 x 440)] x 0.0021 = 0.5424% By combining these values with the generator and motor impedance we can calculate the resistance and reactance at the ERDP, i.e.; R(g+c)(1,2,3,M,ERDP) = 0.4681 + 2.6911 = 3.1592% X(g+c)(1,2,3,M,ERDP) = 3.5258 + 0.5424= 4.0682% Therefore Z(g+c)(1,2,3,M,ERDP) = 5.1508 %
20
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
TP 127 also provide K1 and K2 values but again not for the x/r calculated on this installation. The closest values available are for an x/r of 1.3333, i.e. K1 = 1.004 and K2 = 1.009 Therefore based on a Symmetrical RMS Current Iscg of 12.74 kA ; Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph avg rms = K2 x 12.74 = 1.009 x 12.74 = 12.9 kA = K1 x 12.74 = 1.004 x 12.74 = 12.8 kA
Using the TP 127 Table 3 multipliers again provides very comparable results.
MAIN SWITCHBOARD
Symmetrical RMS current Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph avg rms Short-circuit power factor ENGINE ROOM DP Symmetrical RMS current Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph avg rms Short-circuit power factor
Z METHOD SECTION 11 18.5 47.5 32.9 25.6 UNKNOWN Z METHOD SECTION 11 10.4 27.0 18.7 14.6 UNKNOWN
X/R METHOD SECTION 13 18.4 43.3 25.2 22.0 0.13 X/R METHOD SECTION 13 12.7 19.6 12.8 12.8 0.613
It can be seen that whereas the calculations at the Main Switchboard provide comparable results o f r the Symmetrical RMS current, at other locations, e.g. at the Engine Room Distribution Panel, the differences can be substantial. It can only be recommended that whenever it is necessary to calculate asymmetrical values, particularly at locations away from the main switchboard, a full calculation dividing the cable characteristics into their resistive and reactive components is preferred. Again though we must remember the inaccuracies associated with these calculating methods. Of significance is that the symmetrical rms short-circuit current values have been calculated based on 440 volts the system nominal voltage and not the generator internal voltage behind its sub-transient reactance.
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
21
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Of equal significance is that the asymmetrical values are all calculated based on the rms symmetrical value calculated at time t = zero. But the asymmetrical calculations are all assume a value at the first 0.5 cycles of the short-circuit current. The most significant issue is that the rms symmetrical value has been calculated without consideration of time; i.e. at fault initiation. The quick response to the above is that the increase in short-circuit current due to the increased internal voltage of the generators, will probably be balanced by the reduction that would occur if the symmetrical rms current was also calculated at 0.5 cycles. An interesting response but not one we can really guarantee.
14.
To understand the previous criticism, it is first necessary to understand what the symmetrical and asymmetrical values really are. This is easiest done through a picture! Figure 14.1 shows the way a short-circuit current decays over a period of time. It is a time dependent, alternating, decaying asymmetrical current! The asymmetrical current has a peak value I p and an RMS value I asyrms
The asymmetrical current can also be considered as a symmetrical alternating current, I ac (t) that is displaced by a time dependent direct current, I dc (t). The asymmetrical current I
asy
If the dc component is removed from asymmetrical current, the resulting current is symmetrical as shown in Fig 14.2.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
22
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The symmetrical RMS current calculated in the previous examples, i.e. using the sub-transient impedance, corresponds to that shown in Fig 12.2 and marked as I IRM SYM It can be seen that the RMS value corresponding to the maximum value during the first 0.5 cycle of fault current, is somewhat less. Accordingly, since the calculated asymmetrical current values are multiples of the symmetrical value, they too will be somewhat less than those calculated above.
15.
Isnt it good that the true values are less than those calculated?
The answer is it depends! So far the short-circuit current calculations have assumed a single value for the generator sub-transient impedance. Unfortunately this is not true and can be seen by reviewing Fig 1 4.1. The short-circuit current decays over the first few cycles and then settles down to a steady value. Therefore the impedance must be increasing, or the internal voltage decreasing, or a combination of the two. When calculating the short-circuit current at distribution panels installed several hundred meters from the main switchboard, e.g. a Fcstle panel, the actual decay may not too important as the reduction in short-circuit current is mainly dependent upon the feeder cable impedance. However for the main switchboard and panels located close to it, that use circuit breakers that open in 0.5 cycle or less, the decay can affect the rating of circuit breakers installed. For medium voltage installations, the circuit breakers generally do not operate until 3 cycles of short-circuit current have occurred. Accordingly the short-circuit current to be interrupted can be appreciably less than that calculated by any of the previous methods. The short-circuit current decay during the first few cycles of short-circuit current occurs because the magnetic effects and saturation caused by the high initial values of short-circuit current affect the machine parameters. Electrical engineers have quantified these effects by considering the machine parameters over three distinct time periods; the initial values, referred to as the sub-transient values, the values following the sub-transient period, called the transient values, and the final values or those that occur in steady conditions, the steady-state values. The sub-transient and transient values are time dependent and have time constants associated with them, the sub transient and transient time constants.
16.
For marine installations, the calculation methods of the International Electrotechnical Commission, IEC 61363-1 are perhaps the best available at this point in time; best meaning that the IEC formulae and methods use the minimum amount of calculation procedures and produce the lowest calculated values of short-circuit current that can be used with confidence to select circuit breakers and fuses. The IEC method also makes certain
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
23
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
assumptions that introduce inaccuracies, however such inaccuracies are estimated to affect the result by less than 10%. The IEC method is based on evaluating the upper envelope of the short-circuit current at discrete time intervals in order to obtain the maximum values. Having obtained the short-circuit current at the main switchboard, the values at other distribution panels are calculated similarly to that shown in 13 above, using cable resistance and reactance values to obtain the appropriate impedance value. In addition however, the change in circuit time constants that result from the additional feeder cable, is also included. Motor loads may be considered either lumped at the main switchboard or divided through out the installation. Large motors are considered individually, treating the motor as a decaying exponential short-circuit current. The basic formulae used to calculate the generator short-circuit current are: Iac (t) = (Ikd Ikd ) exp (-t/Td )+ (Ikd Ikd ) exp (-t/Td )+ I kd Idc (t) = 2 (Ikd - Io sin o ) exp (-t/Tdc ) The above formula describe the ac and dc components. Consequently the current defined by the upper envelope, will be I k (t) = 2 Iac (t) + Idc (t) The values of Ikd and Ikd are dependent upon the sub-transient and transient impedances of the generator and the active internal machine voltage. The impedances may be obtained from the generator manufacturer. The voltages must be calculated from the nominal voltage of the machine increased to overcome the internal impedance. The voltages are therefore divided into sub-transient and transient values, and the proportion required to overcome the internal impedance depends upon the current operating in the system just prior to the shortcircuit. To ease the calculations, it is generally assumed that the machine was operating at full load prior to the shortcircuit; this therefore ensures that the highest values of short-circuit current are calculated.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
24
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
To simplify the calculation, and for comparison purposes, it will be assumed that the entire motor load is concentrated at the main switchboard. This is generally in compliance with IEC clause 6.3.4 on the assumption that no motors are rated more than 100 kW.
Data required
Additional generator data is required. This includes the generator sub-transient and transient reactance, resistance and time constants under saturated conditions. This information is generally available from the manufacturer. For a 400 kW 0.8 pf 440 volt generator for the above example, typical values are: Sub transient reactance Transient reactance Resistance DC time constant xd = 11.94% sub-transient time constant td = 12 ms xd = 15.00% transient time constant td = 80 ms ra = 0.0046 ohms per phase; i.e. 1.2% on 500 kVA base Tdc = 17 ms
25
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The impedance and voltage data can now be used in IEC (3) and (4) to calculate the sub-transient and transient initial values of short-circuit current, i.e. Initial value of the sub-transient short-circuit current Initial value of the transient short-circuit current Ikd = 5903.79 amps Ikd = 4802.48 amps
26
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Thus for an impedance of 4.31%, the reactance must be: {(4.31)2 (0.41)2 } = 4.29% The motor contribution was calculated in the previous example as; Motor resistance = 10.2%; motor reactance = 28.20 % The three generator and motor impedances must now be combined to obtain the equivalent impedance of the parallel combination, i.e. R(g+c)(1,2,3,M) = 0.48% and X(g+c)(1,2,3,M) = 3.75% Giving an impedance of 3.78%
27
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Asymmetrical RMS current Iasy rms = 23.89 kA = 1.008 x Iscg Average 3 phase RMS I3 ph avg rms = 20.76 kA = 1.004 x Iscg Short-circuit power factor = 0.127
The power factor of the short-circuit current is given by; R(g+c)(1,2,3,M,ERDP) / Z(g+c)(1,2,3,M,ERDP) = 3.17 / 5.33 = 0.5948 The X/R value is 4.29 / 3.17 = 1.353. Consequently the asymmetrical current values will be: Peak value = 2 Irms { 1 + exp (-/ tan )} = 2 x 12,825 { 1 + exp (-/ 1.353)} = 2 x 1.098 x 12,298 = 19,098 amps = 19.1 kA Asymmetrical RMS Iasy rms = Irms { 1 + 2 exp (-2/ tan )} = 12,298 { 1 + 2 exp (-2/ 1.353)} = 12,298 x 1.0096 = 12,416 amps = 12.4 kA Average 3 phase RMS I3 ph avg rms = Irms [1/3 { 1 + 2 exp (-2/ tan )}+ 2/3 { 1 + exp (-2/ tan )} ] = Irms [0.3365+ 0.6683] = 12,298 x 1.00479 = 12,357 amps
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
28
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
= 12.4kA
Comparison of the decrement method with the previous short-circuit current calculations
The above values can now be compared with the previous calculations:
SHORT-CIRCUIT CURRENT
Symmetrical RMS current Iscg 18.5 18.4 Peak value Ipk at 0.5 cycles 47.5 43.3 Asymmetrical RMS current Iasy rms 32.9 25.2 Average 3 phase RMS I3 ph avg rms 25.6 22.0 Short-circuit power factor UNKNOWN 0.13 ENGINE ROOM DISTRIBUTION PANEL Z METHOD X/R METHOD SHORT-CIRCUIT (SECT 9)
INCLUDING GENERATOR DECREMENT 17.4 40.94 23.9 20.8 0.127 INCLUDING GENERATOR DECREMENT 12.3 19.1 12.4 12.4 0.595
CURRENT
Symmetrical RMS current Iscg Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph avg rms Short-circuit power factor
It can be seen that by including generator decrement the calculated short-circuit current is reduced. The symmetrical RMS current is reduced by approximately 6.5 % and the asymmetrical current by 9.1%. If we were prepared to apply a 10% margin to the symmetrical current prior to choosing circuit breakers, then when calculating using decrement, this margin can be reduced. For this particular example, the bottom line may still be to use 22 kA circuit breakers at the main switchboard, but in some cases, using a decrement calculation may permit dropping one short-circuit level with confidence.
17. OK so will a decrement calculation give me the lowest short-circuit value that I can apply with confidence?
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
29
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The answer is Yes but, we can perhaps do even better. That is we can calculate a lower value with confidence and perhaps use lower rated, less expensive equipment on the system without compromising safety or reliability. The above decrement calculation (Section 16) introduced a concept of an equivalent generator that produces the same short-circuit current as the three generators and motors on the system. The short-circuit current for each generator was calculated based on an exponential decay to obtain the current at the cycle point. The motor short-circuit current contribution was considered as a fixed value for the duration of the generator shortcircuit current. Unfortunately this methodology is only partly accurate! There are two aspects that affect the short-circuit current, particularly at the Engine Room Distribution Panel that we have not considered: Firstly the motor contribution is not a steady fixed value, but also decays with time. Furthermore at the instant of short -circuit, the voltage driving the motor short -circuit current, the internal voltage of the motor, is considerably less than the terminal voltage. Consequently the actual motor short -circuit current contribution during the first few milliseconds, may be some 15 20% lower at the cycle point, than that if it were assumed constant. Secondly the feeder cable resistance and reactance affect both the impedance to the short -circuit, and the ac and dc time constants. Therefore the generator short -circuit current decrement due to a fault at the ER DP will be lower in value and slower to decay as a result of the additional resistance and reactance.
30
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The sub-transient active voltage EM is 203.91 volts per phase
The impedance and voltage data can now be used in IEC (17) to calculate the sub-transient value of short-circuit current, i.e. Initial value of the sub-transient short-circuit current IM = 1756 amps The initial value of short-circuit current, together with the ac and dc time constants is used to calculate the ac and dc components. These values are substituted into IEC ((16) and (20) to calculate the ac and dc components at a particular point in time; i.e. to align with the previous examples, at the first cycle (8.33 ms for 60 Hz) of the shortcircuit condition, i.e.. This gives: I acM (t) evaluated at 8.33 ms = 1124 amps I dcM (t) evaluated at 8.33 ms = 1435 amps The peak value can be calculated from IEC equation (21), i.e. I pM = 3025 amps In the previous calculation we determined that the ac and dc components at cycle are 3xI 3xI
ac(g1,2,3) dc(g1,2,3)
(t) evaluated at 8.33 ms = 15,224.04 amps (t) evaluated at 8.33 ms = 14,115.57 amps
(t) = 15,224 + 1124 amps = 16,348 amps dcM (t) = 14,116 + 1435 amps = 15,551 amps
acM
(t) + I
pM
31
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
32
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
This impedance value can now be used to calculate the rms symmetrical short-circuit current at the engine room panel board i.e: I sc ERDP = (100 x 656) / 5.53 = 11,858 amps = 11.9 kA The X/R value is 4.52 / 3.19 = 1.42. Therefore tan = 1.42 and cos = power factor = 0.5758. Consequently the asymmetrical current values will be: Peak value = 2 Irms { 1 + exp (-/ tan )} = 2 x 11,858 { 1 + exp (-/ 1.42)} = 2 x 1.109 x 11,858 = 18,605 amps = 18.6 kA Asymmetrical RMS Iasy rms = Irms { 1 + 2 exp (-2/ tan )} = 11,858 { 1 + 2 exp (-2/ 1.42)} = 11,858 x 1.0119 = 11,999 amps = 12.0 kA Average 3 phase RMS I3 ph avg rms = Irms [1/3 { 1 + 2 exp (-2/ tan )}+ 2/3 { 1 + exp (-2/ tan )} ] = Irms [0.3373+ 0.6687] = 11,999 x 1.00596 = 12,071 amps = 12.1kA
SHORT-CIRCUIT CURRENT
INCLUDING GEN & MOTOR DECREMENT SECTION 17 16.4 38.7 22.6 19.6 0.125 INCLUDING GEN & MOTOR DECREMENT SECTION 17 11.9 18.6 12.0
ISSUEREV 1-1 DATE 27-Nov-00 PAGE
33
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Average 3 phase RMS I3 ph avg rms Short-circuit power factor 14.6 UNKNOWN 12.8 0.613 12.4 0.595 12.1 0.576
It can be seen that with the latest values, we can confidently use 18 kA switchgear at the main switchboard and 14kA at the ERDP, and still know that we have a 10 % margin over the calculated short-circuit current value.
18.
One of the main problems with the previous calculation methods is the evaluation of the asymmetrical shortcircuit current based on a calculation of circuit impedance at cycle. This methodology is correct in principal, but it contains a major flaw. The calculation uses the formulae, 100 x FLC / I ac(g1,2,3)M (t) at cycle to determine the impedance of the motor/generator combination. By using this formula, the calculation assumes that the voltage behind the short-circuit current is constant and equal to rated voltage. We know that this is not the case, the voltage is higher. IEC clause 7 considers the evaluation of an equivalent generator. The short-circuit current for the equivalent generator is evaluated from the individual generator and motor characteristics, which themselves consider the change in voltage from the sub-transient to the transient stage. The characteristics of the equivalent generator are then considered at one point in time and are based on the system rated voltage. Accordingly evaluation of the asymmetrical current using the equivalent generator impedance, will provide a more accurate assessment.
19.
The IEC Equivalent Generator method is based on the premise that the short-circuit current at any point on the electrical system can be evaluated by determining the characteristics of a single generator (or motor but generally a generator) that produces the same short-circuit current as the individual machines it replaces. The method requires a lot of reasonably complex calculations but it is useful when the system incorporates generators of different sizes, or generators and a large bow thruster, and the effects of the short-circuit current decrement must be considered. As can be seen from the previous calculations, inclusion of the generator and motor short-circuit current decrement has enabled the required main switchboard rating to be reduced with confidence from 22 kA to 18 kA. In these examples the generators are all rated equally, and the equivalent generator approach was taken to evaluate the short-circuit current at the main switchboard. Use of the IEC Equivalent Generator methodology with these examples, will not reduce the short-circuit current at the main switchboard any further than that already determined. However if we can determine the characteristics of the equivalent generator, and then modify those characteristics to include the ERDP feeder cable impedance, it is likely that the calculated short-circuit current at the ERDP will be reduced. Unfortunately in order to determine if this can be advantageous, it is necessary to go through the complete Equivalent Generator calculation procedures. Although for the example we are using, 14 kA equipment (North American standard for this voltage) is likely to be used, we will complete the work both to illustrate the method and to determine the effects it has on the end result. Again as previously, only the major steps using the IEC 61363-1 Clause 7 formulae will be noted here leaving the reader to confirm the results.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
34
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK! Principal characteristics of the Equivalent Generator
The first step is to determine the principal characteristics of the generators and motors that will form the equivalent generator (EG). For our example this comprises three 400 kW generators and 300 kW of motor load having a power of 333.3 kW from the system. Therefore the EG rating is; 3 x 400 + 1 x 333.33 = 1533 kW All machines are assumed to have an 0.8 power factor; therefore the EG has a kVA rating of; 1917 kVA 0.8 pf
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
35
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK! Calculating the constants M and N
M and N are used to calculate the EG ac sub-transient and transient time constants. They are evaluated using the EG initial values of short-circuit current. The EG short-circuit current at the main switchboard, both ac and dc components, comprises the sum of the individual generator and motor short-circuit current, at the main switchboard. This is defined by IEC equations (61) and (62). The ac component of the EG short-circuit current is also defined by equation (63), which is the same format as that used for a normal generator in section 14 above, i.e. Iac (t) = (I I ) exp (-t/Td )+ (I I
k
) exp (-t/Td )+ I k
The subscript is added to indicate that the values apply to the EG. I I and I k are the initial values of the EG sub-transient, transient and steady state short-circuit current and can b e evaluated by summing the initial values of each machines sub-transient, transient and steady state short-circuit current. Therefore in this case we have; For the generators as described in section 16; Initial value of the sub-transient short-circuit current Initial value of the transient short-circuit current Steady state short-circuit current For the motors as described in section 17 Initial value of the sub-transient short-circuit current Therefore for the EG Initial value of the sub-transient short-circuit current Initial value of the transient short-circuit current Steady state short-circuit current I = 3 x 5903.79 + 1756 = 19,468 amps I = 3 x 4802.48 amps = 14,407 amps Ik =3x 1968.24 amps = 5,905 amps IM = 1756 amps Ikd = 5903.79 amps Ikd = 4802.48 amps Ikd =1968.24 amps
The above values can be used to calculate the two constants M and N using equations (68) and (69). Therefore: M = I - I = 19,468 14,407 = 5061 amps N = I - I k = 14,407 5,905 = 8503 amps
36
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
K(t) for each generator. It should be noted that there is an error in equation (70); Td is incorrect this should be Td .
Therefore we must first evaluate K(t) for each generator: K(t) = (Ikd Ikd )exp (-t/ Td) + Ikd This formulae is evaluated at the cycle point, i.e. at t = / 2 From section 17 we know that; Initial value of the sub-transient short-circuit current Initial value of the transient short-circuit current Sub-transient time constant Te = 12.04 ms Transient time constant T e = 80.43 ms DC time constant T dce = 16.52 ms Therefore for each generator: K(t) = (5904 4802) exp (-8.33 / 12.04) + 4802 = 5354 Therefore for three generators; K(t) = 3 x 5354 = 16,061 We can now evaluate Im exp (-t/TM) to include the motor contribution. From section 17 we calculated the initial value of the sub-transient short-circuit current for the motor contribution, Im = 1756 amps. Section 1 7 also lists the motor time constants using values from IEC clause 6.3.4 b) for 60 hz, i.e. T M = 18.67 ms and T dcM = 11.73 ms. Therefore: Im exp (-t/TM) = 1756 exp (-8.33 / 18.67) = 1124 And hence: K(t) = 16,061 + 1124 = 17,185 We can place these values in equation (73) to calculate the EG sub-transient time constant, i.e. Td = -tx / ln [(K(t) - I ) / M ] = -8.33 / ln [(17,185 14,407) / 5061 ] = 13.89 ms Ikd = 5903.79 amps Ikd = 4802.48 amps
37
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Equation (75) tells us that Iac(t x) is the sum of Iac(t x) (ac component of short-circuit current) for each generator and for each motor. To obtain the time constant applicable to the cycle point, Iac(tx) must be evaluated for each generator and motor, at the cycle point. From section 17 we know that the ac component of short-circuit current at cycle is; I ac (t) evaluated at 8.33 ms = 5074.68 amps Therefore for the three generators the ac components at this point in time will be three times the above, i.e. 3xI
ac
For the motors, the value calculated in Section 17 is: I acM (t) evaluated at 8.33 ms = 1124 amps Therefore for the EG; Iac(t x) = 15,224 + 1124 = 16,348 amps Equation (76) also requires calculation of I k which according to equation (67) is the sum of I kd the individual machine steady state currents. For the motors this is zero but for the three generators, we calculated I kd as 3 x FLC for each generator, i.e. 1968.24 amps. Therefore for three generators, the value is 3 x 1968 = 5905 amps, i.e. for the EG I
k
= 5905 amps
We have calculated values for M and T d above. Therefore placing these values in equation (76) to calculate the EG transient time constant give: Td = -tx / ln {[ Iac(t x) - ( M exp (-tx / Td )+ I
k
) ] / N } i.e.
(t x) is
Therefore for three generators and motor contribution, I dc (t x) = 3 x 4705 + 1435 = 15,550 amps
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
38
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
I has been calculated previously in order to evaluate M and is given above as I = 3 x 5903.79 + 1756 = 19,468 amps
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
39
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
Therefore substituting these values into equation (79) to evaluate Tdc gives: (t x) / (2 I )] = -8.33 / ln [15,550 / (2 x 19,469)] = 14.58ms
Tdc = -tx / ln [I
dc
In order to obtain the corresponding resistance and reactance values, a constant c3 must be evaluated using the equivalent generator dc time constant Tdc Equation (81) gives the formulae: c 3 = 1/ (2 x x f x Tdc ) = 1/ (2 x x 60 x 14.58/1000) = 0.1819 The constant c3 can now be applied in equation (86) to obtain the EG sub-transient reactance and equation (80) to obtain the EG resistance R These values may then be applied in equations (87) and (88) to obtain the transient and steady state impedance values noting again that these values apply at the short-circuit current cycle point only. Therefore we have: X = Z /(1 + c32 ) R = c 3 x X X = [Z 2 - R2 ] X = [Z2 - R2 ] = 0.0130 / (1 + 0.18192 ) = 0.1819 x 0.0128 = [0.01762 - 0.00232 ] = [0.04302 - 0.00232 ] = 0.0128 ohms = 0.0023 ohms = 0.0175 ohms = 0.0429 ohms
40
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
EG Sub-transient impedance Z = 0.0130 ohms EG transient reactance X = 0.0175 ohms EG transient impedance Z = = 0.0176 ohms Steady state reactance X = 0.0429 ohms Steady state impedance Z = = 0.0430 ohms These values may be used as described in IEC clause 5.1.1.5 to calculate the short-circuit current using equations (1) through (10) however this would only serve as a check to the calculations. As the information used to obtain these characteristics depends upon the calculated short-circuit current for the generators and motors that comprise the equivalent generator, such a calculation now is purely repetitive. Recall that the purpose of doing this work was to calculate the short-circuit at the ERDP.
20.
Using the Equivalent Generator to calculate the short-circuit current at a remote panel board.
The Engine Room Distribution Panel is fed by 20 m of 3c # 2 cable. Recall for 20 meters of cable we have: Cable resistance is 0.521 x 20/1000 = 0.0104 ohms Cable reactance is 0.105 x 20/1000 = 0.0021 ohms Cable impedance = 0.0106 ohms These values can now be used to modify the EG characteristics. IEC clause 8.2 describes how to include the feeder cable resistance and reactance values with the equivalent generator values. Therefore when the feeder cable is included, the Equivalent Generator plus ERDP feeder characteristics become:
EG+ERDP Resistance RERDP = 0.0023+ 0.0104 = 0.0127 ohms EG+ERDP Sub-transient reactance X ERDP = 0.0128 + 0.0021 = 0.0149 ohms EG+ERDP Sub-transient impedance Z ERDP = 0.0196 ohms EG+ERDP transient reactance X ERDP = 0.0175 + 0.0021 = 0.0196 ohms EG+ERDP transient impedance Z ERDP = 0.0233 ohms EG+ERDP Steady state reactance XERDP = 0.0429 + 0.0021 = 0.045 ohms EG+ERDP Steady state impedance Z ERDP = 0.0468 ohms Using equations (93), (94) and (95) we can calculate the new time constants, i.e. Sub-transient time constant T dERDP = 16.03 ms Transient time constant T dERDP = 103.15ms DC Time constant TdcERDP = 3.08ms In evaluating the equivalent generator, we assumed the voltage behind the short-circuit current was the system voltage 440 volts. As we have learnt previously if the generator is on load, the voltage will be higher than this. Therefore we must make the same assumptions here when calculating the decrement at the ERDP, i.e. that the EG is at no load in order that the internal voltage can be the same as the external voltage of 440 volts. Therefore using the above values substituted into equations (5) and (6) and assuming for the EG that the generator is at no load the active voltages are;
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
41
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The sub-transient active voltage EqoERDP is The transient active voltage EqoERDP becomes 254.03 volts per phase 254.03 volts per phase
The impedance and voltage data can now be used in IEC (3) and (4) to calculate the sub-transient and transient initial values of short-circuit current, i.e. Initial value of the sub-transient short-circuit current Initial value of the transient short-circuit current Steady state short-circuit current IkdERDP = 12,952.73 amps IkdERDP = 10,882.56 amps I kdERDP = 5904.72 amps
The above values can now be substituted into IEC (2) and (9) to calculate the ac and dc components at the first cycle of the short-circuit condition, i.e. 8.33 ms for a 60 Hz application. This gives: I ac (t) evaluated at 8.33 ms = 11,727 amps I dc (t) evaluated at 8.33 ms = 1,220.50 amps The peak value = 2 x I
ac
(t) + I
dc
Furthermore the peak value is given by: Peak value = 2 Irms { 1 + exp (-/ tan )} Therefore tan = - / ln {[Peak value / 2 Irms ] 1} = 1.2041 ; and = 50.3 deg. Hence the power factor cos = 0.6389 The asymmetrical values are calculated as before: Asymmetrical RMS Iasy rms = Irms { 1 + 2 exp (-2/ tan )} = 11,727 { 1 + 2 exp (-2/ 1.2041)} = 11,727 x 1.0054 = 11,790 amps = 11.79 kA Average 3 phase RMS I3 ph avg rms = Irms [1/3 { 1 + 2 exp (-2/ tan )}+ 2/3 { 1 + exp (-2/ tan )} ] = Irms [1/3 { 1 + 2 exp (-2/ 1.2041)}+ 2/3 { 1 + exp (-2/ 1.2041)} ] = Irms [0.33513+ 0.66757] = 11,727 x 1.0027 = 11,758 amps = 11.75kA Therefore the calculated short-circuit current values at the ERDP are; Symmetrical RMS current Iscg Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph avg rms Short-circuit power factor = 11.7 kA = 17.81 kA = 1.52 x Iscg = 11.79 kA = 1.005 x Iscg = 11.75 kA = 1.003 x Iscg = 0.639
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
42
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK! Comparison of EG calculation with previous methods
We can now compare these with the previous calculations: MAIN SWITCHBOARD X/R INCLUDING METHOD GENERATOR SECTION DECREMENT 13 SECTION 16 18.4 17.4 43.3 25.2 22.0 40.9 23.9 20.8
SHORTCIRCUIT CURRENT
Symmetrical RMS current Iscg Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph
avg rms
Z METHOD SECTION 11
INCLUDING GEN & MOTOR DECREMENT SECTION 17 16.4 38.7 22.6 19.6
EQUIVALENT GENERATOR METHOD SECTION 20 16.4 38.7 22.6 19.6 0.125 EQUIVALENT GENERATOR METHOD SECTION 20 11.7 17.8 11.8 11.8 0.639
SHORTCIRCUIT CURRENT
Symmetrical RMS current Iscg Peak value Ipk at 0.5 cycles Asymmetrical RMS current Iasy rms Average 3 phase RMS I3 ph
avg rms
UNKNOWN 0.13 0.127 0.125 ENGINE ROOM DISTRIBUTION PANEL Z METHOD X/R INCLUDING INCLUDING SECTION 11 METHOD GENERATOR GEN & SECTION DECREMENT MOTOR 13 SECTION 16 DECREMENT SECTION 17 10.4 12.7 12.3 11.9 27.0 18.7 14.6 UNKNOWN 19.6 12.8 12.8 0.613 19.1 12.4 12.4 0.595 18.6 12.0 12.1 0.576
21.
Conclusions
There are many ways to calculate the short-circuit current for a marine electrical system, some very simple, others quite complex. The complexity of the calculation is not always a good guide as to the worth of the result that is produced. Some calculation methods involve extensive calculations, but the result obtained cannot be relied upon. Other methods that also involve extensive calculations, do not necessarily provide final results that are as equally reliable to those attained by less complex methods. This design guide has outlined three broad calculation methods: 1. 2. 3. Based on the 10 times rule or the generator sub-transient reactance Based on Ohms Law and neglecting short-circuit current decrement as a function of time Based on IEC 61363-1 using an approximate estimate of the generator and motor short-circuit current decrements.
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
43
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
The best calculation method to use is difficult to determine and depends on the size of installation, the point of interest on the system and the purpose of the calculation. For any installation having an installed generating capacity of 500 kVA or less at 440 V, or 300 kVA or less at 230 volts the 10 times calculation method is generally adequate. The advice would be to try it and provided the result justifies the use of the minimum rated circuit breakers (10 or 14 kA at the main switchboard), then additional calculations would seem unnecessary. The ten times rule calculation can be refined if the generator sub-transient reactance is known, however care should be taken to use the generator internal voltage and not the system voltage or the results will be inaccurately low. For larger installations, it is strongly advised that a more complex method of calculation be used; if the 10 times rule is used, the short-circuit current calculated values will result in vastly over rated switchgear being installed, with consequent increase in equipment costs. The reduction in short-circuit requirements due to feeder cables can be significant, particularly for the lower rated feeders (e.g. 100 amps or less). Accordingly when calculating the short-circuit level at panel boards, distribution panels and other switchboards supplied from the main switchboard, the impedance of the feeder cables should be included. Account should be taken of both the feeder cable resistance and reactance otherwise the calculation results may be unacceptably low. Calculation methods that include generator and motor short-circuit decrement will produce the lowest acceptable values of short-circuit current. Such methods are based on IEC Standard 61363-1. The amount of calculation required for these methods is much the same as for the Z and X/R methods described; but the results are significantly less. Furthermore the sensitivity of the calculations can produce widely differeing results for small changes in impedance values. Consequently the IEC methods are therefore preferred as they offer a more accurate calculation method and give more value for calculation time (money) than other methods. For systems involving different sizes of generator, or generators at different voltages located on different switchboards,
the short-circuit current calculations at distribution and power panels that take into account current decrement are not straightforward. Essentially there are two approaches, ignore the time constant changes resulting from the feeder cable impedance, or to take the time constant changes into account
The later calculation can be completed using the Equivalent Generator approach outlined in IEC 61363-1 Section 7. For most conventional marine electrical systems, the Equivalent Generator method will involve extensive calculations and produce results marginally different from more simple methods. For the majority of marine electrical systems used in the commercial marine industry, a calculation method based on IEC 61363-1 taking into account both generator and motor short-circuit current decrement will produce
CLIENT DC Maritime Technologies Inc. CLIENTS PROJ. NO. DCMT PROJ. NO. DESIGN REVIEW DCMT DOC. NO. 906-00 ISSUEREV 1-1 DATE 27-Nov-00 PAGE
44
ALL YOU WANTED TO KNOW ABOUT SHORT-CIRCUITS BUT WERE AFRAID TO ASK!
the lowest reliable calculated value for the short-circuit current. Even with this method, cognisance should be given to the accuracy of the data used in the calculation (sub-transient reactance tolerances etc.), in order to apply a calculation error margin to the result, particularly when choosing protection gear with rating close to the calculated values. The author generally applies a 5 10% margin to all calculated values.
ISSUEREV 1-1
DATE 27-Nov-00
PAGE
45