CHINT Control Components 36p en 0708
CHINT Control Components 36p en 0708
US LISTED
www.klinkmann.com
CONTENTS
MCBs. ......................................................................................................3 RCDs.......................................................................................................5 RCBOs.....................................................................................................6 MCCBs....................................................................................................8 ACBs......................................................................................................12 Contactors............................................................................................15 Starters.................................................................................................22 Pushbuttons & Indicators....................................................................27 Modular Pushbuttons & Indicators & Disconnectors........................30 Accessories. ..........................................................................................32 Switch Disconnectors..........................................................................34
MCBs
C
R
MCBs MCB
US LISTED
2. Technical features
NB1
Standard
Rated current In Poles Rated voltage Ue Rated frequency Rated breaking capacity Energy limiting class Rated impulse withstand voltage(1.2/50) Uimp V Thermo-magnetic release characteristic Mounting Connection Auxiliary contact Shunt release Under voltage release Alarm contant Electrical life Mechanical life A
IEC/EN 60898-1
IEC/EN 60947-2
UL1077
UL1077
1P, 2P 110/125 DC 10k
1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 240/415 6k 6000 B, C, D 8-12In 8, 000 20, 000 On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom Yes Yes Yes Yes B, C, D 4-7In, 7-14In 277/480 5k
V 240/415 A 6000/10000 3
50/60Hz
3. Curve
IEC/EN 60898-1
B, C, D curve
MCBs NB1 Description NB1 6kA 1P B1 NB1 6kA 1P B2 NB1 6kA 1P B3 NB1 6kA 1P B4 NB1 6kA 1P B6 NB1 6kA 1P B10 NB1 6kA 1P B13 NB1 6kA 1P B16 NB1 6kA 1P B20 NB1 6kA 1P B25 NB1 6kA 1P B32 NB1 6kA 1P B40 NB1 6kA 1P B50 NB1 6kA 1P B63 NB1 6kA 1P C1 NB1 6kA 1P C2 NB1 6kA 1P C3 NB1 6kA 1P C4 NB1 6kA 1P C6 NB1 6kA 1P C10 NB1 6kA 1P C13 NB1 6kA 1P C16 NB1 6kA 1P C20 NB1 6kA 1P C25 NB1 6kA 1P C32 NB1 6kA 1P C40 NB1 6kA 1P C50 NB1 6kA 1P C63 NB1 6kA 1P D1 NB1 6kA 1P D2 NB1 6kA 1P D3 NB1 6kA 1P D4 NB1 6kA 1P D6 NB1 6kA 1P D10 NB1 6kA 1P D13 NB1 6kA 1P D16 NB1 6kA 1P D20 NB1 6kA 1P D25 NB1 6kA 1P D32 NB1 6kA 1P D40 NB1 6kA 1P D50 NB1 6kA 1P D63 NB1 6kA 2P C6 NB1 6kA 2P C10 NB1 6kA 2P C13 NB1 6kA 2P C16 NB1 6kA 2P C20 NB1 6kA 2P C25 NB1 6kA 2P C32 NB1 6kA 2P C40 NB1 6kA 2P C50 NB1 6kA 2P C63
MCBs
Pack 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 6 6 6 6 6 6 6 6 6 6 Description NB1 6kA 2P D4 NB1 6kA 2P D6 NB1 6kA 2P D10 NB1 6kA 2P D13 NB1 6kA 2P D16 NB1 6kA 2P D20 NB1 6kA 2P D25 NB1 6kA 2P D32 NB1 6kA 2P D40 NB1 6kA 2P D50 NB1 6kA 2P D63 NB1 6kA 3P B6 NB1 6kA 3P B10 NB1 6kA 3P B13 NB1 6kA 3P B16 NB1 6kA 3P B20 NB1 6kA 3P B25 NB1 6kA 3P B32 NB1 6kA 3P B40 NB1 6kA 3P B50 NB1 6kA 3P B63 NB1 6kA 3P C1 NB1 6kA 3P C2 NB1 6kA 3P C3 NB1 6kA 3P C4 NB1 6kA 3P C6 NB1 6kA 3P C10 NB1 6kA 3P C13 NB1 6kA 3P C16 NB1 6kA 3P C20 NB1 6kA 3P C25 NB1 6kA 3P C32 NB1 6kA 3P C40 NB1 6kA 3P C50 NB1 6kA 3P C63 NB1 6kA 3P D4 NB1 6kA 3P D6 NB1 6kA 3P D10 NB1 6kA 3P D13 NB1 6kA 3P D16 NB1 6kA 3P D20 NB1 6kA 3P D25 NB1 6kA 3P D32 NB1 6kA 3P D40 NB1 6kA 3P D50 NB1 6kA 3P D63 S9 Shunt Release for NB1 V9 Under Voltage Release for NB1 F9 Auxiliary contact for NB1 Pack 6 6 6 6 6 6 6 6 6 6 6 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
RCDs
NL1 Residual Current Operated Circuit Breaker without over-current protection (Magnetic) 1. General
RCDs
NL1
Protection against risk of fire Protection against risk of electric shock 3 protection class: AC, A, s Tripping class AC class Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase. A class Tripping is ensured for sinusoidal, alternating residual currents as well as for pulsed DC residual currents, whether they be quickly applied or slowly increase. s class can be used as upstream group switch for selective tripping contrary to a downstream standard RCCB 1.5 Rated residual operating current 30mA- to give a high degree of protection against electric shock in a situation where supplementary protection against shock from accidental direct contact is required when it must be able to trip within 40 milliseconds when a fault current of 150mA is detected. 100mA- to give a degree of protection against electric shock due to indirect contact situation.300mA- to gives overall protection against risk of fire form electrical faults in wiring etc, only where sufficient current (typically less than 500mA) may cause incandescence of metal parts in suitable circumstances and in consideration that installed over current devices would require far in excess of 300mA to operate. 1.6 Fault current indicator
2. Technical features
Standard
Type (wave form of the earth leakage sensed) Rated current In Poles Rated voltage Ue Rated sensitivity In Short-circuit current Icn=Ic Electrical life Mechanical life Terminal connection type Mounting Connection V A V A
IEC/EN 61008-1
AC, A, s 25, 40, 63, 80, 100 2P, 4P 230/400 0.03, 0.1, 0.3 6000/10000 2, 000 2, 000 Cable/U-type busbar/Pin-type busbar On DIN rail EN 60715 (35mm) by means of fast clip device From top and buttom
NL1 Description NL1 6KA 2P 25A 30mA A-TYPE NL1 6KA 2P 40A 30mA A-TYPE NL1 6KA 2P 63A 30mA A-TYPE NL1 6KA 4P 25A 30mA A-TYPE NL1 6KA 4P 40A 30mA A-TYPE NL1 6KA 4P 63A 30mA A-TYPE
Pack 1 1 1 1 1 1
Description NL1 10kA 2P 25A 30mA A-TYPE NL1 10kA 2P 40A 30mA A-TYPE NL1 10kA 2P 63A 30mA A-TYPE NL1 10kA 4P 25A 30mA A-TYPE NL1 10kA 4P 40A 30mA A-TYPE NL1 10kA 4P 63A 30mA A-TYPE
Pack 1 1 1 1 1 1
5
RCBOs
RCBOs
NB1L Residual Current Operated Circuit Breaker with over-current protection(Magnetic) 1. General
1.1 Protection against risk of fire 1.2 Protection against risk of electric shock 1.3 Protection against overload 1.4 Protection against short circuit 1.5 Contact position indicator
2. Technical features
Standard
Type (wave form of the NBL1 rarth leakage sensed) Thermo-magnetic release characteristic Rated current In MCB+add-on RCD block Combined Poles Rated voltage Ue Rated sensitivity In NBL1 Rated short-circuit capacity lcn Break time under In Electrical life Mechanical life Mounting Connection
V A A s
IEC/EN 61009-1
AC, A B, C
1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40 1P+N, 2P, 3P, 3P+N, 4P 1P+N, 2P 230/400 0.03, 0.1, 0.3 0.03 6,000/10,000 0.1 2,000 2,000
On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom (for combined type) From top (MCB+add-on RCD block)
3. urve
IEC/EN 61009-1
10000 5000 1h 2000 1000 500 200 100 50 20 10 5 t(s) 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001
B, C curve
0.5 1
RCBOs
4. Overall and Mounting Dimensions (mm)
MCB+add-on RCD block
RCBOs
Pack 1 1 1 1 1 1 1 1 1 1 1 1
Description NB1L(3~) NB1L 4P 10A 30mA C A 10KA NB1L 4P 16A 30mA C A 10KA NB1L 4P 20A 30mA C A 10KA NB1L 4P 25A 30mA C A 10KA NB1L 4P 32A 30mA C A 10KA NB1L 4P 40A 30mA C A 10KA NB1L 3P+N 10A 30mA C AC 6KA NB1L 3P+N 16A 30mA C AC 6KA NB1L 3P+N 25A 30mA C AC 6KA
Pack 1 1 1 1 1 1 1 1 1
NB1L(2) NB1L 1P+N B6 30mA A 6KA (COMBINED) NB1L 1P+N B10 30mA A 6KA (COMBINED) NB1L 1P+N B13 30mA A 6KA (COMBINED) NB1L 1P+N B16 30mA A 6KA (COMBINED) NB1L 1P+N B20 30mA A 6KA (COMBINED) NB1L 1P+N B25 30mA A 6KA (COMBINED) NB1L 1P+N C6 30mA A 6KA (COMBINED) NB1L 1P+N C10 30mA A 6KA (COMBINED) NB1L 1P+N C13 30mA A 6KA (COMBINED) NB1L 1P+N C16 30mA A 6KA (COMBINED) NB1L 1P+N C20 30mA A 6KA (COMBINED) NB1L 1P+N C25 30mA A 6KA (COMBINED)
MCCBs
MCCBs
Adjustable type MCCB NM8
Rated current from 16 to 1250A Thermal-magnetic type/Electronic type/Magnetic-only type Adjustable thermal & adjustable magnetic trip 2P 3P 4P available AC/DC applicable 5-class breaking capacity from 25kA to 150kA Ics=100%Icu(In 630A),Ics=150%Icu(In>630A) Circuit breakers and auxiliaries comply with the following international standard: IEC/EN 60947-1: general rules IEC/EN 60947-2: circuit breakers IEC/EN 60947-3: switches, disconnectors, switch-disconnectors, etc. IEC/EN 60947-4: contactor and motor starters IEC/EN 60947-5.1 and following: control circuit devices and switching elements, Automatic control components. NM8 also comply with the specifications of the marine classification companies. Certified for operation in pollution-degree III environments as defined by IEC standard 60947 (industrial environments). Wide temperature range from -40C to +70C A complete system of add-on modules for NM8
NM8
1 2 3 4 5
Body Thermo magnetic release Electronic release Plug-in base Rotary manual operating handle
6 7 8 9 10
Motor driven operating mechanism Under-voltage release Shunt release Alarm contact Auxiliary contact
11 12 13 14 15
Front connection plate Rear connection plate Locking system(padlock) Short terminal cover Extended terminal cover
16 17 18 19
DIN rail adaptor Cage clamp terminal Mechanical interlock Communication module
MCCBs
Overall and Mounting Dimensions Overall and mounting dimensions of fixed type for front connection
MCCBs
(mm)
L1
NM8-125 NM8S-125/NM8-250/NM8S-250 NM8-400, 630/NM8S-400, 630 NM8-800, 1250/NM8S-800, 1250
140 157 255 370
L2
240 357 474 570
H0
72 82 95 132
H1
79 88 113 144
H2
103 126 168 206
K
15 17.5 22.5 35
K1
30 35 45 70
K2
60 70 90 140
G1
56 62.5 100 120
G2
112 125 200 240
W0
30 35 45 70
W1
90 105 140 210
W2 W3
120 140 185 280 62 70 -
d
6 6 6 7
NM8 Description 3 POL 16-125 A NM8-125S-16A/3P NM8-125S-20A/3P NM8-125S-25A/3P NM8-125S-32A/3P NM8-125S-40A/3P NM8-125S-50A/3P NM8-125S-63A/3P NM8-125S-80A/3P NM8-125S-100A/3P NM8-125S-125A/3P 3 POL 100-250A NM8-250S-100A/3P NM8-250S-125A/3P NM8-250S-160A/3P NM8-250S-200A/3P NM8-250S-250A/3P 3 POL NM8S-400S-400A/3P NM8S-630S-630A/3P NM8S-800S-800A/3P NM8S-1250S-1250A/3P
Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Description Accessories DIN-MOUNTINGSET NM8-125A-3P CAGE CLAMP TERMINAL NM8 125 1x502 CAGE CLAMP TERMINAL CU/AL NM8 125 1x35-952 DIRECT HANDLE NM8-125 DOOR OPERATING HANDLE NM8-125 ALARM AUXILIARY CONTACTSET NM8 125-630 TERMINAL CU/AL NM8 250/NM8 125 2x35-1502 DIRECT HANDLE NM8-250 DOOR OPERATING HANDLE NM8-250 TERMINAL CU/AL NM8S 630 1x2402 TERMINAL CU/AL NM8S 630 2x2402 DIRECT HANDLE NM8-400/630 DOOR OPERATING HANDLE NM8-400/630 TERMINAL CU/AL NM8S 1250 3x2402 TERMINAL CU/AL NM8S 1250 4x2402
Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
MCCBs
MCCBs
NM8-125 Frame 1
16, 20, 25, 32, 40, 50, 63, 80, 100, 125 750 8 690 500 2 3 4 2
Tehnical Data
Parametrs
NM8-250 Frame 2
100, 125, 160, 180, 200, 225, 250 750 8 690 500 3 4 3
25
Breaking capacity code AC 220V/230V/240V AC 380V/400V/415V Rated ultimate short-circuit breaking capacity (kA RMS) Icu AC 440V AC 500V AC 660V/690V DC 250V (1P) DC 500V (2P) Rated service breaking capacity Ics= (%Icu) Suitability for isolation Utilization category Safety of insulation Life(CO recycle) Protection Release units Over-load protection Short-circuit protection Residual current protection Mounting and connection Fixed DIN rail Plug-in Auxiliaries for control and indication Manual Motor-driven mechanism Manual, remote operated automatic source changeover systems Shunt and under-voltage release Auxiliary and alarm contact Pad locking system Mounting and connection accessories Connection terminal Front connection plate Rear connection plate DIN rail adaptor Plug-in type connection accessories Terminal covers Interphase barrier Dimension and weight Dimension(mm)W H L Weight(kg) Fixed type-front connection Fixed type-front connection Handle Direct or extended rotary handle Front connection Rear connection Front connection Front connection Rear connection Added on residual current protection module Mechanical Electrical
S 85 50 50 35 5 25 25
S 85 50 50 35 5 25 25
S 85 50 50 35 6 25 25
S 85 50 50 35 6 25 25
S 85 70 50 35 10 25 25
H 100 100 85 50 12 35 35
Thermo-magnetic
62 140 79 0.85
90 140 79 1.2
70 157 88 1.5
10
MCCBs
NM8-400
250, 315, 350, 400 750 8 690 500 4 3 4 3
MCCBs
Frame 3
NM8-630
250, 315, 350, 400, 500 750 8 690 500 4 3
NM8-800
630, 700, 800 750 8 690 500 4
Frame 4
NM8-1250
800, 1000, 1250 750 8 690 500 3 4
25, 250
S 85 50 50 35 6
S 85 70 50 35 10 25 25
H 100 100 85 50 12 35 35
S 85 70 50 35 10 25 25
H 100 100 85 50 12 35 35
S 85 70 50 35 10 25 25
H 100 100 85 50 12 35 35
S 85 70 50 35 10 25 25
H 100 100 85 50 12 35 35
S 65 50 35 30 10 35 35
H 100 70 65 50 20 50 50
R _ _ _ _ _ _ _ 50
S 65 50 35 30 10 35 35
H 100 70 65 50 20 50 50
S 65 50 35 30 10 35 35
H 100 70 65 50 20 50 50
R _ _ _ _ _ _ _ 50 A 10,000 4000
S 65 50 35 30 10 35 35
H 100 70 65 50 20 50 50
25 25
Thermo-magnetic
Thermo-magnetic
_ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _
_ _
_ _
_ _ _
_ _ _
11
ACBs
ACBs
ACB NA1
Rated current from 200 to 6300A Modulized mechanical part and accessories The terminal of the control circuit on the front enables easy handling Minimized arc space 3P 4P available Max. breaking capacity up to 120kA@400V Drawout type/fixed type Power supplied from either top bottom does no reduction in performance Circuit breakers comply with IEC/EN 60947-2 Certified for operation in pollution-degree III environments as defined by IEC standard 60947 (industrial environments). Temperature range from -5 to +65 A complete system of add-on modules for NA1
NA1
1 2 3 4
5 6 7 8
12
ACBs
Summary
5 basic frame sizes
For your various requirements, the Air Circuit Breaker NA1 includes 5 basic frame sizes as followed.
ACBs
NA1-1000
200A to 1000A
NA1-2000
400A to 2000A
NA1-3200, 4000
2000A to 4000A
NA1-6300
4000A to 6300A
C-01
13
ACBs
Pack Description Pack Manual & Fixed 3P NA1-2000-630M 3P Manual/Fixed NA1-2000-800M 3P Manual/Fixed NA1-2000-1000M 3P Manual/Fixed NA1-2000-1250M 3P Manual/Fixed NA1-2000-16000M 3P Manual/Fixed NA1-2000-2000M 3P Manual/Fixed NA1-3200-2000M 3P Manual/Fixed NA1-3200-2500M 3P Manual/Fixed NA1-3200-3200M 3P Manual/Fixed NA1-4000-4000M 3P Manual/Fixed NA1-6300-5000M 3P Manual/Fixed 4P NA1-2000-630M 4P Manual/Fixed NA1-2000-800M 4P Manual/Fixed NA1-2000-1000M 4P Manual/Fixed NA1-2000-1250M 4P Manual/Fixed NA1-2000-16000M 4P Manual/Fixed NA1-2000-2000M 4P Manual/Fixed NA1-3200-2000M 3P Manual/Fixed NA1-3200-2500M 3P Manual/Fixed NA1-3200-3200M 3P Manual/Fixed NA1-4000-4000M 3P Manual/Fixed NA1-6300-5000M 3P Manual/Fixed NA1-6300-6300M 3P Manual/Drawable
Motor & Fixed 3P NA1-2000-630M 3P Motor/Fixed 1 NA1-2000-800M 3P Motor/Fixed 1 NA1-2000-1000M 3P Motor/Fixed 1 NA1-2000-1250M 3P Motor/Fixed 1 NA1-2000-1600M 3P Motor/Fixed 1 NA1-2000-2000M 3P Motor/Fixed 1 NA1-3200-2000M 3P Motor/Fixed 1 NA1-3200-2500M 3P Motor/Fixed 1 NA1-3200-3200M 3P Motor/Fixed 1 NA1-4000-4000M 3P Motor/Fixed 1 NA1-6300-5000M 3P Motor/Drawable 1 NA1-6300-6300M 3P Motor/Drawable 1 4P NA1-2000-630M 4P Motor/Fixed 1 NA1-2000-800M 4P Motor/Fixed 1 NA1-2000-1000M 4P Motor/Fixed 1 NA1-2000-1250M 4P Motor/Fixed 1 NA1-2000-1600M 4P Motor/Fixed 1 NA1-2000-2000M 4P Motor/Fixed 1 NA1-3200-2000M 4P Motor/Fixed 1 NA1-3200-2500M 4P Motor/Fixed 1 NA1-3200-3200M 4P Motor/Fixed 1 NA1-4000-4000M 3P Motor/Fixed 1 NA1-6300-5000M 3P Motor/Drawable 1 NA1-6300-5000M 4P Motor/Drawable 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
14
Contactors
NC6 Mini Contactor
Contactors
C
R
US LISTED
The NC6 Series Mini Contactor is used in remote motor (4kW) control application. Rating up to 690V, 9A (AC3). ----- (06A, 09A) Standard: IEC/EN 60947-4-1 Two kinds of mounting available: Normal type (without pins); Pin type (with pins) Ambient Temp: -5 ~ 40 Coil Voltage (AC): 24V, 36V, 48V, 110V, 127V, 220V, 230V, 380V, 400V; Auxiliary contacts: NCF6-02 & NCF6-20 (2NO or 2NC) NCF6-13 & NCF6-31 (1NO & 3NC or 3NO & 1NC) NCF6-13 & NCF6-31 (4NO or 4NC) Assemble with Thermal overload Relay NR2-11.5 to be a DOL Starter. NC6
C
R
US LISTED
NC1 Contactor
The NC1 Series Contactor is used in remote motor (45kW) control application. Rating up to 690V, 95A (AC3). ----- (09A, 12A, 18A, 25A, 32A, 40A, 50A, 65A, 80A, 95A) Standard: IEC/EN 60947-4-1 Ambient Temp: -5 ~ 40 Coil Voltage (AC): 24V, 36V, 48V, 110V, 127V, 220V, 230V, 380V, 415V, 440V, 480V, 500V, 600V, 660V Coil Voltage (DC): 24V, 36V, 48V, 110V, 220; Side mounting Auxiliary contacts: NCF1-11C (1NO & 1NC) Top mounting Auxiliary contacts: F4-20 & F4-02 (2NO & 2NC) F4-13 &F4-31 (1NO & 3NC or 3NO & 1NC) F4-40 & F4-04 (4NO or 4NC) Top mounting time delay block: F5-T (making time delay); F5-D (breaking time delay) Assemble with Thermal overload Relay NR2 (or NRE8) to be a DOL Starter. Assemble with another one & F4 & F5 & NR2 (or NRE8) to be a Star-Delta Starter called QJX2; Assemble with a current limiting block to be a Capacitor Contactor. Assemble with another one to be a reversing contactor;
NC1
US LISTED
NC2 Contactor
The NC2 Series Contactor is used in remote motor (450kW) control application. Rating up to 690V, 630A (AC3). ----- (115A, 150A, 185A, 225A, 265A, 330A, 400A, 500A, 630A) Standard: IEC/EN 60947-4-1 Ambient Temp: -5 ~ 40 Coil Voltage (AC): 110V, 127V, 220V, 230V, 380V, 400V; Top mounting Auxiliary contacts: F4-20 & F4-02 (2NO & 2NC) F4-13 &F4-31 (1NO & 3NC or 3NO & 1NC) F4-40 & F4-04 (4NO or 4NC) Top mounting time delay block: F5-T (making time delay); F5-D (breaking time delay) Assemble with Thermal overload Relay NR2 to be a DOL Starter. Assemble with another one to be a reversing contactor;
NC2
15
Contactors
Contactors
Tehnical Data
AC operation
AC coil operation
Items
Frame
Model
NC1-09
NC1-12
NC1-18
Frame 2 (3P)
NC1-25
Frame 3 (3P, 4P)
NC1
Frame
Rated conventional heating current (A) AC-1 Rated operational current (A)
380/400V 660/690V
hp
Electrical
RT
16
Contactors
Contactors
NC1-32
Frame 4 (3P)
NC1-40
NC1-50
Frame 5 (3P, 4P)
NC1-65
NC1-80
NC1-95
Frame 6 (3P, 4P)
P, 4P)
80 50 24 39 12 690 15 22 37 15 20 30 30
80 65 28 42 14 690 18.5 30 37 20 25 40 40
600 300 3,600 600 150 8 RT16-80
95 80 37 49 17.3 690 22 37 45 25 30 40 40
95 95 44 49 21.3 690 25 45 45 30 30 50 50
600 300 3,600 600 100 6 RT16-125
0 0
40
17
Contactors
Contactors
Tehnical Data
3P contactors AC coil operation
Model
Frame Rated Conventional heating current (A) AC-1 Rated operational current (A) AC-3 AC-4 380/400V AC 660/690V AC 1000V AC 380/400V AC kW Power of controlled 3-phase cage motor (AC-3) hp 660/690V AC 1000V AC 240V AC 415V AC 480V AC 600V AC Operating cycles (operations /h) AC-3 Electrical life ( ( 10 operations) AC-3 10 operations) Model Rated current A
6 6
NC2-115
Frame 1 200 115 86 46 55 80 65 40 60 75 75 1,200 1.2 10 RT16-1 200
NC2-150
200 150 108 50 75 100 65 50 75 100 100 1,200 1.2 10 RT16-1 225
NC2-185
Frame 2 275 185 118 71 90 110 100 60 100 100 100 600 1 6 RT16-2 315
Model
Frame Conventional heating current A Rated operational current (A) AC-3 AC-4 380/400V AC 660/690V AC 1000V AC 380/400V AC kW Power of controlled 3-phase cage motor (AC-3) hp 660/690V AC 1000V AC 240V AC 415V AC 480V AC 600V AC Operating cycles (operations /h) AC-3 Electrical life ( ( 10 operations) AC-3 10 operations) Model Rated current (A)
6 6
NC2-115
Frame 1 200 115 86 46 55 80 65 40 60 75 75 1,200 1.2 10 RT16-1 200
NC2-150
200 150 108 50 75 100 65 50 75 100 100 1,200 1.2 10 RT16-1 225
NC2-185
Frame 2 275 185 118 71 90 110 100 60 100 100 100 600 1 6 RT16-2 315
18
Contactors
Contactors
NC2-225
Frame 2 275 225 137 90 110 129 100 75 125 125 125 600 1 6 RT16-2 315
NC2-265
Frame 3 315 265 170 112 132 160 147 100 150 150 150 600 0.8 6 RT16-2 355
NC2-330
Frame 4
380 330 235 155 160 220 160
NC2-400
Frame 5
450 400 303 200 200 280 185
NC2-500
Frame 6
630 500 353 232 250 335 335
NC2-630
800 630 462 331 335 450 450
NC2-225
Frame 2 275 225 137 90 110 129 100 75 125 125 125 600 1 6 RT16-2 315
NC2-265
Frame 3 315 265 170 112 132 160 147 100 150 150 150 600 0.8 6 RT16-2 355
NC2-330
Frame 4
380 330 235 155 160 220 160
NC2-400
Frame 5
450 400 303 200 200 280 185
NC2-630
Frame 6
800 630 462 331 335 450 450
19
Contactors
Assembly with terminal over-load replay relay 4.3 Assembly with thermal over-load
Contactors
Assembled thermal over-load relay Model Rated current (A)
0.1~0.16 0.16~0.25 0.25~0.4 0.4~0.63 NR2-11.5 0.63~1 1~1.6 1.25~2 1.6~2.5 2.5~4 4~6 5.5~8 7~10 NR2-11.5 9~13 0.1~0.16 0.16~0.25 0.25~0.4 0.4~0.63 0.63~1 1~1.6 1.25~2 1.6~2.5 2.5~4 4~6 5.5~8 7~10 9~13 12~18 17~25
Model of contactor
NR2-25
23~32 NC1-32 28~36 23~32 NC1-40 NC1-50 NC1-65 NC1-80 NC1-95 NR2-93 30~40 37~50 48~65 55~70 63~80 80~93
40
63
NR2-36
40 40 40 63 63 80 80 100
20
Contactors
Accessories to NC1
Contactors
Model
F4-20 F4-11 F4-02 F4-40 F4-31 F4-22 F4-13 F4-04
Picture
Model
F5-T0 F5-T2 F5-T4 F5-D0 F5-D2 F5-D4
Time-delay range
0.1s~3s 0.1s~30s 10s~180s 0.1s~3s 0.1s~30s 10s~180s
Picture
F4 -
F4 auxiliary contact
Number of N/C auxiliary contact Number of N/O auxiliary contact Auxiliary contact assembly
F5 -
F5 auxiliary contact
0: time-delay range, 0.1s~3s 2: time-delay range, 0.1s~30s 2: time-delay range, 10s~180s T: making time-delay; D: breaking time-delay Time-delay module
NCF1-11C
Lateral side 1 N/C contact 1 N/O contact Design sequence No. Auxiliary contact assembly Contactor Company code
21
Starters
Starters
C
R
US LISTED
NS2
22
Starters
Technical Parametrs
Starters
23
Starters
Starters
Technical Parametrs
24
Starters
Starters
25
Starters
Pack Description NR2 Series Thermal Overload Relay NR2-25G 0.1-0.16A NR2-25G 0.16-0.25A NR2-25G 0.25-0.4A NR2-25G 0.4-0.63A NR2-25G 0.63-1A NR2-25G 1-1.6A NR2-25G 1.25-2A NR2-25G 1.6-2.5A NR2-25G 2.5-4A NR2-25G 4-6A NR2-25G 5.5-8A NR2-25G 7-10A NR2-25G 9-13A NR2-25G 12-18A NR2-25G 17-25A NR2-36G 23-32A NR2-36G 28-36A NR2-93G 23-32A NR2-93G 30-40A NR2-93G 37-50A NR2-93G 48-65A NR2-93G 55-70A NR2-93G 63-80A NR2-93G 80-93A NR2-200G 80-125A NR2-200G 100-160A NR2-200G 125-200A NS2 Series Manual Motor Starter NS2-25 0.1-0.16A NS2-25 0.16-0.25A NS2-25 0.25-0.4A NS2-25 0.4-0.63A NS2-25 0.63-1A NS2-25 1-1.6A NS2-25 1.6-2.5A NS2-25 2.5-4A NS2-25 4-6.3A NS2-25 6-10A NS2-25 9-14A NS2-25 13-18A NS2-25 17-23A NS2-25 20-25A NS2-80B NS2-80B NS2-80B NS2-80B 16A-25A 25A-40A 40A-63A 56A-80A Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NC1 Series Contactor 3P NC1-0901(0910) 1 3P NC1-1201(1210) 1 3P NC1-1801(1810) 1 3P NC1-2501(2510) 1 3P NC1-3201(3210) 1 3P NC1-4011 1 3P NC1-5011 1 3P NC1-6511 1 3P NC1-8011 1 3P NC1-9511 1 NC2 Series Contactor 3P NC2-115 1 3P NC2-150 1 3P NC2-185 1 3P NC2-225 1 3P NC2-265 1 3P NC2-330 1 3P NC2-400 1 3P NC2-500 1 3P NC2-630 1 NC6 Series Contactor NC6-0601 (0610) 1 NC6-0901 (0910) 1 NC6-0901 (0910) 1 NC6-0604 (0608) 1 NC6-0904 (0908) 1 NCH8 Series Contactor NCH8-20/2P 1 NCH8-63/4P 1 Auxiliary contacts F5 1 F4-2 1 F4-4 1 NCF6-4 1 NCF6-2 1 NCF1 (Side Contact) 1 NC1 Accessory AC Coil for NC1 1 CJX2(NC1)-09/12/18 1 CJX2(NC1)-25/32 1 CJX2(NC1)-40/50/65/80/95 1 Mechanical Interlock CJX2(NC1)-09/12/18/25/32 1 CJX2(NC1)-40/50/65 1 CJX2(NC1)-80/95 1
NS2 Accessory NS2-MC Pushbutton Box Shunt Release NS2-SH220 Shunt Release NS2-SH380 Fault Signal Contact/ Auxilary contact NS2-FA1001 NS2-AU11 Under Voltage Release NS2-UV220 Under Voltage Release NS2-UV380
26
Pilot Devices
US LISTED
Pilot Devices
NP2
US LISTED
ND16 Indicator
The ND16 Series Indicator is used in remote indication. Rating up to 400V (AC/DC) Standard: IEC/EN 60947-5-1 IP65; Drill Plan: 22mm Electrical Endurance: 30103 Hours Ambient Temp: -5~40 Head colors available: Red, Black, Green, Blue, Yellow; ND16-22A(S)/2: For AC/DC application, Flat-platform lampshade; ND16-22A(S)/4: For AC application, Flat-platform lampshade; ND16-22B(S)/2: For AC/DC application, Flat-round platform lampshade; ND16-22B(S)/4: For AC application, Flat-round platform lampshade; ND16-22C(S)/2: For AC/DC application, Arc-surface ripple lampshade; ND16-22C(S)/4: For AC application, Arc-surface ripple lampshade; ND16-22D(S)/2: For AC/DC application, Arc-surface round lampshade; ND16-22D(S)/4: For AC application, Arc-surface round lampshade; Note: (S) for compact type;
ND16
NP2 Description NP2-BA11 NP2-BA21 NP2-BA31 NP2-BA42 NP2-BA41 NP2-EA11 NP2-EA21 NP2-EA31 NP2-EA41 NP2-EA42 Metal head
Pack 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
ND16 Description ND1622D2230VG ND1622D2230VR ND1622D2230VW ND1622D224VR ND1622D224VW ND1622D4230VW ND1622DS224VB ND1622DS224VG ND1622DS224VR ND1622DS224VW ND1622DS224VY ND1622DS4110VG ND1622DS4110VR ND1622DS4130VG ND1622DS4130VR ND1622DS4130VW ND1622DS4130VY ND1622DS4230VB ND1622DS4230VG ND1622DS4230VR ND1622DS4230VW ND1622DS4230VY
G=green, R=red, Y=yellow, W=white, B=blue
Pack 1 1 1 1 1 1 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
27
Plastic head
Metal head twist release NP2-BS442 30mm NP2-BS541 40mm NP2-BS642 60mm NP2 Selector Switches Metal head NP2-BD21 NP2-BD33 Plastic head NP2-ED21 NP2-ED33
Pushbuttons
Pushbuttons
Type Designation
Specification code (Refer to table below) Derivative type (Refer to table below) Structure classes: B: Metal head; E: Plastic head Design sequence number Buttons Company code
US LISTED
Pushbutton, NP2
Metal-headed
Flushbutton NP2-BA
Plastic-headed
Flushbutton NP2-EA
US LISTED
ND16-22A
ND16-22AS
ND16-22B
ND16-22BS
ND16-22C
ND16-22CS
ND16-22D
ND16-22DS
28
3. Technical Data
3.1 Life (operations): a. Electric life: 100103 b. Mechanical life: 250103 3.3 Assembly of contact: 1NC+2NO, 2NC+1NO, 3NO, 2NC+2NO (Not available for illuminated type) 3.4 Technical data of signal lamp a. Rated operational voltage: AC/DC6.3V, AC/DC12V, AC/DC24V, AC/DC110V, AC/DC230V b. Rated operational current: 20mA 3.5 Life: incandescence lamp1000h, neon lamp2000h, LED30000h
ND9
29
Pushbuttons & Indicators ND9 Description ND91G230V ND91R230V ND91W230V ND91Y230V ND923031 ND923032 ND923033 ND92GR230V ND92WW230V ND9PR NP9 Description
2. Technical features
30
Main Switch
Ordering Information
Main Switch
31
Length L (m)
1
Order code
131501
Fork Type
1P
Fork Type
2P
16
131502
Fork Type
L
3P
16
131503
Fork Type
L
4P
16
131504
Pin Type
L
1P
16
131505
Pin Type
L
1P
20
131506
Pin Type
L
2P
16
131507
Pin Type
L
2P
20
131508
16
L
Pin Type
3P 20
131509
Pin Type
3P
131510
32
Pin Type
4P
16
Pin Type
4P
20
131512
Length L (m)
Order code
Pin Type
2P
131514
Pin Type
3P
10
131515
1-phase
Feed-in from end cross section (mm2 ) max. current (A) 10 12 16 20 25 35 10
2, 3 and 4 phase
16 25 36
IE=Is
63
65
80
90
100 130
63
80
100
130
100
130
180
220
3. DIN rail
Model
DIN rail
L(m)
1
Order code
131550
33
Switch Disconnectors
Switch Disconnectors
HH15-QA/QP Switch Disconnector
Mainly used in the distributing and motor circuit which has high short-circuit current, and acted as main switch or master switch infrequently operated by hand, it is particularly suitable in the relative high class with drawable low voltage complete equipment. They provide safety isolation and protection against overcurrent for any low voltage electrical circuit. Standard: IEC/EN 60947-3 Rated current: 125-3150A
HH15-QA/QP
NHR17
34
Switch Disconnectors
NHR40 Fuse-switch disconnector
Switch Disconnector
NHR40
NHR40 series switch-disconnector with fuse is applicable in the circuit of AC50Hz, rated voltage AC690V and below, DC440V and below, rated current up to 630A. NHR40 series are infrequently manually operated multipolar fuse combination switches, They break or switch off on load and provide safely isolation and protection against overcurrent for any voltage electrical circuit. Standard: IEC/EN 60947-3. Rated current: 160-630A
NH40S
NH40SZ
35
Panel and motor control components from the Asian market leader
Chint is the largest manufacturer in Asia and one of the TOP3 global manufacturers of electrical panel and motor control components. Many well known international component suppliers supply Chint products under their own name and brand - you secure the most cost effective component sourcing by buying the Chint products directly from Klinkmann. Reliable Chint components offer good technical performance and they have wide international approvals - select Chint for the most optimal component sourcing.