GS33K50F20 50e
GS33K50F20 50e
General Specications
GS 33K50F20-50E
GENERAL
The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a eld with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules. This node units are connected to FCU via an ESB bus.
HARDWARE SPECIFICATIONS
For the installation specications and environmental conditions that are common to the systems, refer to FIO System Overview (for Vnet/IP) (GS 33K50F1050E).
Total Number of ESB Bus Node Units (ANB10) and Optical ESB Bus Node Units (ANB11) Connected per FCU Max. 3 Max. 9 Max. 13
Control Function for Field Control Station (LFS1700) AFV30 Control Function for Field Control Station (LFS1700) AFV40 plus Node Expansion Package (LFS1750-V1) (*1) Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V2) *1: Up to 11 node units per 1 cabinet can be installed in AFV40.
Database
ESB Bus Node Units (ANB10) Connected per FCU Max. 3 Max. 9
Control Function for Field Control Station (LFS1500) AFV10 Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)
Total Number of ESB Bus Node Units (ANB10) and ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 14
Vnet
Field Control Unit AFF50 ESB Bus Node Units (ANB10) Connected per FCU Max. 3 Max. 10 Max. 10 (*1) ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 14 Max. 9 (*1) Total Number of ESB Bus Node Units (ANB10) and ER Bus Node Units (ANR10) Connected per FCU Max. 3 Max. 15 Max. 10 (*1)
Database
Control Function for Compact Field Control Station (LFS1350) AFG30 Control Function for Enhanced Field Control Station AFG40 (LFS1330) with Node expanded databases Others *1:
In Case of AFG81 and AFG82, there are total number with SIO Nest (for CENTUM V or CENTUM-XL). Total number of SIO: Max 5/FCU
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802
GS 33K50F20-50E Copyright Aug. 2011 (YK) 6th Edition June 12, 2013 (YK)
<<Contents>> <<Index>>
Power Supply
Specify with Sufx Codes Voltage: 100-120 V AC, Frequency: 50/60 Hz Voltage: 220-240 V AC, Frequency: 50/60 Hz Voltage: 24 V DC
Weight
10 kg (incl. 8 I/O Modules)
Mounting
19-inch Rack Mounting Rack mount (M5 x 4 screws) Insulation bash (accessory)
Regulatory Compliance
For the detailed information of following standards, see System Overview (GS 33K01A10-50E). Safety Standards [CSA] (for 100-120 V AC and 24 V DC power supply) [CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) EMC Conformity Standards [CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [C-Tick Marking] (for 220-240 V AC and 24 V DC power supply) [KC Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) Standards for Hazardous Location Equipment [CSA Non-Incendive] (for 100-120 V AC and 24 V DC power supply) [FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [Type n] (for 24 V DC power supply)
CONFIGURATION
Module conguration
Power Supply Module (PW481 or PW482 or PW484): Two modules in case of a dual-redundant conguration. Power supply to the I/O Modules, and supply power to the transmitters. The power supply terminals use M4 screws. ESB Bus Interface Slave Module (SB401): Two modules in case of a dual-redundant conguration. I/O Modules (*1): Max. 8
*1: Non-standard components.
For installing I/O modules in node unit, the quantity and allocation are limited. Also, when installing a node unit to the dedicated cabinet, there are limitations of installation under the ambient operating temperature conditions. When modules with built-in barriers are installed in any node unit, an insulating partition (Part No. T9083NA) must be installed. For details, please refer to FIO System Overview (for Vnet/IP) (GS 33K50F10-50E) and Installation Guidance (TI 33K01J10-50E).
<<Contents>> <<Index>>
EXTERNAL DIMENSIONS
ANB10D, ANB10S ESB Bus Node Unit (Figure of ANB10D)
Unit: mm
8.75 21.3
146 221.5
37.75
<<Contents>> <<Index>>
*2: *3:
Dummy Cover
ADCV01 ADCV02
Model
Insulating Partition
Part No. T9083NA Description Insulating Partition
Note: When mounting an FIO module with built-in barrier to a node unit, place this part to the 8th slot.
ORDERING INFORMATION
Specify the model and sufx codes. For selecting the right products for explosion protection, please refer to TI 33Q01J30-01E without fail.
TRADEMARKS
CENTUM and Vnet/IP are registered trademarks of Yokogawa Electric Corporation. Other product and company names appearing in this document are trademarks or registered trademarks of their respective holders.
All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation Subject to change without notice.