ATS22 Quickstart
ATS22 Quickstart
Preliminary information
Information below is designed to use for simple applications with 2-wire control mode and freewheel stop. If you need more information, or for other applications, see the User manual on www.schneider-electric.com. For a hard copy, contact your local sales Office or Schneider Electric representative. Note: DO NOT USE this guide for Altistart 22 connected inside the delta of the motor (it means Altistart 22 connected to the motor with delta connections in series with each motor windings). In this case, see User manual on www.schneider-electric.com. Read and understand these instructions before performing any procedure with this soft starter.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION AND ARC FLASH
Read and understand this manual before installing or operating the Altistart 22 starter. Installation, adjustment, repair, and maintenance must be performed by qualified personnel. The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment. Many parts of this soft starter, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools. DO NOT touch unshielded components or terminal strip screw connections with voltage present. Before servicing the starter: - Disconnect all power, including external control power that will be present. - Place a DO NOT TURN ON label on all power disconnects. - Lock all power disconnects in the open position. Before applying power section close the enclosure.
WARNING
DAMAGED SOFT STARTER EQUIPMENT
Do not operate or install any soft starter or soft starter accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Check that the soft starter reference on the nameplate is similar to the purchase order delivery note.
Write the soft starter model Reference: ATS22 ______ and Serial Number:___________________
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION AND ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
www.schneider-electric.com
1/4
S1A10388 - 08/2009
a) Connect Power:
- Wire the soft starter to the ground. - Wire the soft starter to the line supply: 1/L1 3/L2 5/L3. - Check that the motor voltage is compatible with the soft starter voltage. - Wire the soft starter to the motor.
(1) Check the operating limits of the contact. (2) Select a voltage transformer in accordance with the mains voltage.
b) Connect Control:
Remove the red sticker which covers the CL1-CL2 terminals. Wire control supply: CL1 and CL2. Wire logical inputs: LI1 and LI2. Wire the relay: R2A and R2C.
Note: For additional information in order to size the protective and control devices, refer to the catalog or the user manual available on www.schneider-electric.com
www.schneider-electric.com 2/4 S1A10388 - 08/2009
For ATS22pppS6U
2-wire control, freewheel stop
a) Connect Power:
- Wire the soft starter to the ground. - Wire the soft starter to the line supply: 1/L1 3/L2 5/L3. - Check that the motor voltage is compatible with the soft starter voltage. - Wire the soft starter to the motor.
(1) Check the operating limits of the contact. (2) Select a voltage transformer in accordance with the mains voltage.
b) Connect Control:
Remove the red sticker which covers the CL1-CL2 terminals. Wire control supply: CL1 and CL2. Wire logical inputs: LI1 and LI2. Wire the relay: R2A and R2C.
Note: For additional information in order to size the protective and control devices, refer to the catalog or the user manual available on www.schneider-electric.com
www.schneider-electric.com 3/4 S1A10388 - 08/2009
Factory settings
The Altistart 22 is factory configured for most standard applications. If the factory configuration is not suitable for your application, refer to User manual on www.schneider-electric.com. Here is the list of writable parameters in an easy start up mode. Menu Code ICL dLtA conF Configuration UIn In Cod LAC t90 ILt tLS SEt Adjustments ACC dEC EdC tHP Description Soft starter rated current Connection type (Line or delta) Line voltage Motor rated current Setting lock Advanced mode Initial voltage Current limit Max start time Acceleration time Deceleration time Final torque Motor thermal protection LInE ATS22pppQ range:400 Vac ATS22pppS6-S6U ranges:480 Vac According to the soft starter rating nLoC (Not locked) oFF 30 % of input voltage 350 % of In IS s ID s FrEE (Freewheel) O IO (IEC class 10) Factory setting According to the soft starter rating Customer setting
rdY: soft starter ready, when power and control voltage are present and the motor is not operating. nrdY: when power is not supplied and control voltage is supplied or when power and control voltage are present with LI1 not connected and LI2 present (run command).
Short-circuit rating and branch circuit protection (use in place of Q1 shown on page 2 and 3)
Recommended fuse ratings for UL and CSA requirements. Components for use together in accordance with standard UL508
ATS22 Stand-alone product ATS22D17ppp ATS22D32ppp ATS22D47ppp ATS22D62ppp ATS22D75ppp ATS22D88ppp ATS22C11ppp ATS22C14ppp ATS22C17ppp ATS22C21ppp ATS22C25ppp ATS22C32ppp ATS22C41ppp ATS22C48ppp ATS22C59ppp 30 kA 18 kA 10 kA 5 kA Max. short circuit current rating (SCCR) X Branch circuit protection Z1 (1) AJT40 AJT70 AJT100 AJT125 AJT175 AJT200 AJT250 AJT300 AJT400 AJT500 AJT600 2 x AJT350 2 x AJT400 2 x AJT500 2 x AJT600 Rating Z2 40 A 70 A 100 A 125 A 175 A 200 A 250 A 300 A 400 A 500 A 600 A 2 x 350 A 2 x 400 A 2 x 500 A 2 x 600 A
Suitable for use on a circuit capable of delivering not more than ___X____ rms symmetrical Amperes, 575 Volts maximum, when protected by ___Z 1____ with a maximum rating of___Z 2___. (1) Ferraz Shawmut manufacturer.
www.schneider-electric.com
4/4
S1A10388 - 08/2009