Installation Manual MAS2600
Installation Manual MAS2600
DK49698119
Page 1 of 27
Handling ....................................................................................................................... 16 Installation .................................................................................................................... 17 Intrinsically Safe Installation ....................................................................................... 19 Testing and Recalibrating ............................................................................................ 22
Testing............................................................................................................................................. 22 Recalibrating Gauge Transmitter using Test Cup type G022S100................................................ 22 Recalibrating Gauge Transmitter using Vacuum (for gauge transmitters only) ............................ 23 Recalibrating the Absolute Transmitter using Test Cup type G022S100...................................... 24
Page 2 of 27
Differential version: For measuring of both pressure and vacuum measuring. The amplifier is housed in a sea water resistant polyester casing (IP56). Application The MAS 2600 has been developed for level measuring in ballast, oil, service and fresh water tanks as well as tanks containing media which are not hostile to titanium. Intrinsically Safe in Hazardous Areas The MAS 2600 is DEMKO approved for use with standard transmitter zener barriers or Ex isolation amplifiers and is EEx ia IIC T4 compliant in accordance with IEC 600790:2007 and IEC 60079-11:2006. Type Approvals DNV, GL, LRS, MRS, BV, RINA, NK, PRS, KRS, ABS, MSA.
As optional the transducer is available with a built-in Pt100 temperature sensor. Amplifier: The amplifier is available in the following options: Programmable version: Calibration is made by dip switches and potentiometers.
4-20 mA
x
EEX
ia
2600
-40 to +85 C IK < = 45 mA
CERTIFICATE REF.:
Lint = 20 uH
90-C.95948
Cint = 10 nF
Umax = 33 V
DMS
MAS 2600 PDCR-941-1 1.5 bar g S/N 46374
Transducer
Amplifier box
Page 3 of 27
Technical Specifications
Transducer Ranges: Gauge: 0-3.5 / 0-7 / 0-16 / 0-35 m H2O. Absolute: 0-20.394 / 0-35.690 m H2O. Programmable Measuring Ranges: Each transducer range is programmable in 8 steps. Accuracy: 0.25% F.S. at 20 C. Stability: Max. 0.1% / Year. TEB (Total Error Band): 2.0% F.S. at -20 to +80C. EMC immunity influence < 0.5%FS Overload Capability: Min. 4 x transducer range with no changes in calibration. 6 x transducer range burst pressure. Built-in Temperature Sensor Pt100: Optional. Power Supply: The Power Supply can vary from 17-33 VDC. Permissible load resistance is shown graphically below. Calculation formula: Rloop max. (Kohm) =
Output Current: 4-20 mA DC, loop powered 2-wire system. Current Limiting: Max: 25 mA Sensor Materials: Housing: Titanium Grade 2 Diaphragm: Titanium Grade 4 Operating Temperature Ranges: Transducer: -20 to +125C Standard cable: -20 to + 80C High temperature cable: -20 to +125C Amplifier: -20 to + 80C Protection Class: Transducer: Amplifier:
IP 68 IP 56
Intrinsic Safety: EEx ia IIC T4 compliant. Max. 75 m cable between transducer and transmitter amplifier. Transmitter dimensions Amplifier box:
110.0 55.0 98.0
2600 SERIES
EE X
ia
C T5
S/N:
2600
-40 to +85 C < 45 mA IK =
75.0
Use 4x20mm bolts and nuts for suspension on a 4mm thick surface
Transducer:
3.0 6-core vented cable, 8.0
30.0
25.0
120.0
Front view
Page 4 of 27
45.0
4 pcs. 4.5
X - XX -
/ X X
Type
A: Absolute Transducer. The absolute transducer has no breather pipe, because it refers to absolute vacuum. An atmospheric pressure sensor is used to compensate for the atmospheric pressure. The absolute transducer is especially suitable for open deck applications, where the amplifier box may be exposed to flooding. G: Gauge Transducer. The gauge transducer is fitted with a breather pipe at the back of the diaphragm to compensate for the atmospheric pressure. The breather pipe is connected to a vent plug in the amplifier box. The gauge transducer is suitable for most applications. H: High Temperature Transducer. The high temperature transducer is available in gauge version only. The transducer is mounted with a special high temperature cable and designed for heated tanks e.g. HFO tanks, and other applications with high tank media temperatures. The transducer can be flange mounted or internally mounted.
Measuring Ranges
MAS 2600-XXX-XX-X/XX
Gauge Transmitter: The MAS 2600 Gauge Transmitter is supplied in 4 ranges. In the programmable amplifier the measuring range is divided into 8 sub-ranges and operated by means of the range select switch. The transmitter output signal can be adjusted to 20 mA within the following sub-ranges.
Transducer type
Range No. 1 2 3 4 5 6 7 8 Type 1: 0 3.5 mH2O 0.20 0.37 mH2O 0.37 0.54 mH2O 0.54 0.73 mH2O 0.73 1.10 mH2O 1.10 1.92 mH2O 1.92 3.10 mH2O 3.10 3.50 mH2O NOT APPLICABLE Type 2: 0 7.0 mH2O 0.20 0.30 mH2O 0.30 0.50 mH2O 0.50 0.70 mH2O 0.70 1.10 mH2O 1.10 1.80 mH2O 1.80 3.00 mH2O 3.00 4.80 mH2O 4.80 7.10 mH2O Type 3: 0 16.0 mH2O 0.50 0.75 mH2O 0.75 1.00 mH2O 1.00 1.50 mH2O 1.50 2.50 mH2O 2.50 4.00mH2O 4.00 6.00 mH2O 6.00 10.00 mH2O Type 4: 0 35.0 mH2O 1.00 1.90 mH2O 1.90 2.80 mH2O 2.80 3.90 mH2O 3.90 5.80 mH2O 5.80 9.90 mH2O 9.90 15.30 mH2O 15.30 25.10 mH2O
Page 6 of 27
Absolute Transmitter:
The MAS 2600 Absolute Transmitter is available in two ranges. The output signals are calibrated as follows: Transducer type 4 Transducer type 7 : 0.8 - 3.5 bar abs : 0.8 - 2.0 bar abs
4-20 mA
x
EE X
ia
Tankheight
To ensure measuring accuracy a transducer type within the range no. 4, 5, 6, 7 and 8 is recommended. Guidelines for selection of transducer measuring ranges are set out in the following.
Page 7 of 27
Absolute Transducers:
The Absolute Transmitter is typically used if the amplifier is exposed to water, e.g. on open deck. The Absolute Transmitter is available in 2 ranges: 0-20 and 0-35 mH2O. In practice this means 10 mH2O less than the nominal range because of the atmospheric pressure which must be taken into consideration when choosing the transducer. A transducer with an effective range larger than the tank height should be selected.
Basic Rules:
1. The selected measuring range must be larger than the tank height. 2. The selected measuring range must be larger than EXAMPLE: Tank height = 6m Vent pipe height = 14 m
tank height + vent pipe height 2
1. The selected measuring range must be larger than 6 m due to the height of the tank. 6 + 14 2. The selected measuring range must be lager than = 10 m due to the total height of the 2 tank and the vent pipe combined. Select a transducer with a measuring range of 16 mH2O as this is the next measuring range larger than 10 m. Turn the range select switch on the amplifier to range No. 7. Normally the selection of transducer, range select and calibration are done by DAMCOS. Special consideration applies to e.g. forepeak tanks and draft measuring when selecting the measuring range of the transducer.
Forepeak Tank:
Transducer measuring range > tank height: Select the next measuring range. EXAMPLE: Tank height 12 m. Based on the tank height a transducer with a measuring range of 16 mH2O should be selected. However, due to the dynamic conditions in the forepeak tank, a transducer with a measuring range of 35 mH2O, i.e. the next in line, should be selected. Turn amplifier range select switch to range No. 6.
Page 8 of 27
Draft:
4-20 mA
x
EE X
ia
Weather deck
Min. draft
Ships hull
Transducer measuring range > max. draft minus sensor position. This rule applies provided the transducer is mounted in accordance with the installation drawing for draft transmitters (vent pipe min. 1"). The sensor may be mounted direct on the sea valve with an air release valve if the ship is sailing in calm waters. If the transducer is installed in tanks which may have excessive dynamic stresses such as e.g. high pump pressure, long bottomed tanks with a risk of slashing etc., contact Emerson Process Management Marine Solutions, Damcos.
Temperature Sensor MAS 2600-XXX-XX-X/XX The transducer can be supplied with a built-in Pt100 temperature sensor. The temperature sensor will only give a proper reading, if the transducer is an internally mounted type. 0: 1: Without temperature sensor. With temperature sensor
Cable MAS 2600-XXX-XX-X/XX Two types of transducer cable is available. The standard cable for applications with temperatures never exceeding 80 C, and high temperature cable for applications with temperatures up to 125 C. The transducer cable is delivered in whole meters. For further information require data sheet. To make the MAS 2600 transmitter easy to install, and for later service purposes, the transducer cable should be as short as possible, though considering the position of the transducer and amplifier box. Max. cable length: 300 m. When installing in hazardous areas max. cable length: 75 m. Page 9 of 27
2600 SERIES
4-20 mA
x
EE X
ia
Tank top
38.0
Bulkhead
125.0 160.0
Tank bottom
55.0
45.0
The brackets are U-shaped and manufactured of 2 mm SS 316L plated steel. Diameter of mounting holes: 11.5 mm. The transducer is secured by means of a spring fitted into two holes in the U shape, and can be mounted/dismounted without the use of tools. When installing in hazardous areas the cable must be protected by a steel pipe welded to the tank.
4-20 mA
x
EE X
ia
Tank top
24.0 40.0
Bulkhead
34.0
26.0
Tank bottom
1" Thread
The weldable collar and the nut are manufactured of SS 316L steel. The gaskets are made of nitrile rubber. Note: Max torque 20 Nm (slightly tighten by the hand + 1/8-1/4 turn). Remember the gasket.
Page 10 of 27
41.0
26.0
40.0
4-20 mA
x
EE X
ia
24.0
34.0
26,0
b
Bulkhead
Tank bottom
The thread collar and the nut are manufactured of SS 316L steel. The gaskets are made of nitrile rubber. Note: Max torque 20 Nm (slightly tighten by the hand + 1/8-1/4 turn). Remember the gasket.
4-20 mA
x
EE X
ia
26,0
Tank top
Bulkhead
Tank bottom
The standard transducer is supplied with DN25, DN40 or DN50 PN16 DIN2527 flange manufactured in AISI 316L steel. DN D Mm 115 150 165 Flange B mm 16 16 18 Bolts thread dia. M12 M16 M16
19,5
25 40 50
K Mm 85 110 125
No. of bolts 4 4 4
d mm 14 18 18
Note: Max torque 20 Nm (slightly tighten by the hand + 1/8-1/4 turn). Remember the gasket.
Page 11 of 27
41,0
4-20 mA
x
EE X
ia
Tank top
H
Bulkhead
Tank bottom
A top flange made of SS 316L connected to rubber tube by a tightening clip using a special tool. The opposite hose end covers the transducer body and is fixed by a tightening clip. NB: This mounting type can not be used in hazardous aria. When ordering this mounting type always specify length for the measurement of H cf. above drawing.
4-20 mA
x
EE X
ia
Tank top
H
Bulkhead
Tank bottom
A top flange made of SS 316L connected to a Stainless Steel braided PTFE tube by fittings fixed to the tube by using special tools. A fitting in the opposite tube end is fixed to the transducer by means of nut and ferrules. Min. hose bending radius 130 mm. NB: When ordering this mounting type always specify length for the measurement of H cf. above drawing. Note: This mounting type can only be assembled by Emerson Process Management Marine Solutions, Damcos because it requires special tools. The customer can exchange the MAS 2600 transmitter by ordering a G022B085 and a G022B082 together with the new MAS 2600 transducer. It must clearly be specified that it is a replacement for an MAS 2600 HXX-XX-P/XX. Page 12 of 27
4-20 mA
x
EE X
ia
Tank top
Bulkhead
Tank bottom
Flange, valve and nut are manufactured of SS 316L steel. The gaskets are made of nitrile rubber. Note: Max torque 20 Nm (slightly tighten by the hand + 1/8-1/4 turn). Remember the gasket.
Page 13 of 27
Amplifier Box
MAS 2600-XXX-XX-X/XX
The MAS 2600 amplifier box is manufactured in polyester, which has the strength and stability of aluminium, insulation and resistance properties of plastics. Colour code RAL 7000. The amplifier box is protected to the level of IP 56 and must be mounted outside the tank, e.g. in the engine room or other dry areas. The amplifier box is available with a PG9 hole for silicone gel filling to protect the amplifier from moisture. When the amplifier box is mounted on open deck with the risk of being drenched it is recommended to mount the amplifier box inside the deck box 165B9035. To further reduce the exposure of water place the amplifier box to the centre of the vessel. 0: Without amplifier box. 1: Standard box with PG 11/PG 11 cable glands. For cable diameter 5 -10 mm. 2: Standard box with PG 11/PG 13.5 cable glands. For cable diameter 6-12 mm. 3: Standard box with PG 11/PG 16 cable glands. For cable diameter 10-14 mm.
5: Standard box with PG 13.5/PG 13.5 cable glands. For cable diameter 6-12 mm. 6: Standard box with PG 11/PG 11 cable glands and filling hole. For cable diameter 5 -10 mm. 7: Standard box with PG 11/PG 13.5 cable glands and filling hole. For cable diameter 6-12 mm. 8: Standard box with PG 11/PG 16 cable glands and filling hole. For cable diameter 10-14 mm.
110.0 55.0 98.0
2600 SERIES
4 pcs. 4.5
EE X
ia
C T5
S/N:
2600
-40 to +85 C < 45 mA IK =
75.0
Use 4x20mm bolts and nuts for suspension on a 4mm thick surface
Page 14 of 27
45.0
Amplifier PCB
MAS 2600-XXX-XX-X/XX
The PCB is available in different types for the different transducers, with or without terminals for Pt100 temperature sensor. 0: Without amplifier PCB.
P or S: Programmable output range. The amplifier can be calibrated to 4-20 mA output in whatever range wanted within the transducer range. Calibration is made by means of dip switches and potentiometers. D or M: Differential output range. The output can be adjusted to 12 mA output with no pressure applied. With pressure or vacuum, the output goes against 20 mA and 4 mA respectively. Full-scale and zero point calibration by means of software, e.g. tank monitoring software. The types S and M are with terminals for temperature sensors. The types P and D are without terminals for temperature sensors.
Page 15 of 27
Handling
The MAS 2600 transducer is a highly sensitive electronic piece of equipment and proper handling is most important. To avoid damaging the transducers: NEVER lift by the cable if transducer is mounted with fittings. NEVER remove the protection cap in front of the diaphragm before installation. NEVER knock the transducer. NEVER apply pressure to the diaphragm in any way whatsoever, whether using fingers, tools or sharp objects. NEVER use sharp objects when cleaning the diaphragm. NEVER submerge the cable so that the breather tube is under water. NEVER bend the cable in a radius of less than 90 mm.
Page 16 of 27
Installation
Prior to installation please check that: the serial numbers on the transducer, amplifier and lid of amplifier box agree. The serial numbers are to be found on the inside of the lid of the amplifier box on the bottom line amplifier S/N and transducer S/N on the range label. the transducer is fitted in the correct tank. the transducer is correctly connected to the amplifier. NOTE: The white and brown wires in the transducer cable are only used when a Pt100 sensor is built into the transducer. all cable glands are properly secured to the amplifier box. Use torque of 6 Nm. the amplifier box is mounted in such a way that the breather tube cannot be flooded. the cable is fastened with cable clips with a distance of max. 50 cm. the cable isolation is not damaged (cracks, weld spatter, burns etc.). shut-off valves can be either ball valves or other valves not generating over pressure exceeding 4 x the transducer range between valve seat and transducer when the valve is closed. As for flange mounted applications it is recommended that a ball valve is fitted in the front of the transducer to facilitate testing and calibrating of the transmitter. Using a shielded cable to the 4-20 mA signal, the shield should not be connected in the amplifier box but the earth terminal of the instrument. Using a shielded cable ensures maximum protection against electric noise.
Page 17 of 27
If the amplifier box is installed in an area with over pressure or negative pressure in relation to the atmospheric pressure in the tank, the breather tube must be directed to an area with atmospheric pressure equalling the pressure inside the tank. This applies to gauge transmitters only. For absolute transmitters this has no affect, due to the reference to absolute vacuum and not atmospheric pressure. This is also the reason why no breather tube is necessary. Be sure that the cable glands are tight. Use a torque of 6 Nm.
Breather hose
Page 18 of 27
S/N: XXXXXX-YYYY
DEMKO 11 ATEX 146506X IECEx ULD 10.0013X Ui: 29V Ii: 93 mA Li: 20H Ci: 60 nF Pi: 0.68 W II 2(1) G Ex ia IIC T4 Tamb.: -20 to +80 C Damcos A/S, Aaderupvej 41,DK-4700, Naestved
Where S/N : : II 2(1) : : serial number production year. Ex identification according to guideline 94/9/EC (ATEX). other aria than mines. sensor mounted in zone 0 and amplifier in zone 1 denotes the type of protection intrinsic safety , i.e. the system is incapable of causing ignition in normal operation or with any combination of up to two faults applied. This category will be adequate for use in zone 0, 1 and 2. denotes the group of gases. denotes the maximum surface temperature classification specified (T4: 135 C).
Ex ia :
IIC T4
: :
Tamb : denotes the minimum and maximum ambient temperature for the amplifier box permitted by the certificate. DEMKO 11 ATEX 146506X: The ATEX Certificate No 146506 is issued by DEMKO 201 with remarks. Relevant intrinsic safety certificates to be supplied with the system units. The certification of electric apparatus as intrinsically safe requires the apparatus to be designed and tested in accordance with approved drawings and the apparatus to be installed in accordance with approved block schematic diagrams.
Page 19 of 27
Before installing intrinsically safe units within an approved installation, it is essential to ensure that there are no deviations from the conditions of the order or the requirements of the approved block schematic diagram and the following related instructions: 1. No circuits other than those shown on the drawing are permitted. There must be no interconnection to any other circuits. 2. The intrinsically safe cabling must not be connected to non-intrinsically safe circuits, through any plug, socket or other form of electric connector containing the cable. 3. Adequate precautions must be taken to prevent danger arising from the charging of the intrinsically safe circuit by the contact leakage or inductance from any other circuit. To prevent static electricity do not rub cables or amplifier housing with a dry piece of cloth. 4. The intrinsically safe circuit must be adequately insulated from earth in the hazardous area and the insulation of all cabling must be at least 500 V r.m.s. 5. The safety barrier (zener barrier) must be placed in a safe area and be mounted within a protective enclosure with a protection degree, at least equal to IP 20. 6. The cable between the safety barrier and the amplifier should be provided with a cable shield which is connected to earth at the zener barrier. The impedance between the safety barrier earth rail and a secure bond to the hull must not exceed 1 ohm. 7. Safe area apparatus must not be supplied from, nor contain, a source of potential with respect to earth under normal or abnormal conditions exceeding 250V r.m.s. or 250 V DC. 8. The inductance/resistance ratio, total inductance and total capacitance, of the cable and the amplifier must not exceed the values stated by the manufacturer of the approved safety barriers. 9. Prevent impacts on the sensor housing to avoid sparks. Do not mount or dismount the sensor when there is a hazardous condition in the tank. Be sure the tank is vented and gas free. 10. Be sure that the amplifier box is dry and clean before the lid is mounted. The four screws in the lid should be tightened fully. 11. Be sure to order and use sensor cable with the right temperature specification. Check that the ambient temperature for the entire cable run do not exceed the max limit for the cable. 12. MAS 2600 contain no repairable parts. Repairing or fixing the circuit or replacing components may impact the intrinsic safety. 13. The sensor cable shall remain in one piece from sensor to amplifier box.
Reference is made to manufacturer instructions of zener barriers and to the rules in force at the time in question concerning intrinsically safe area installation.
Page 20 of 27
Safe area
Hazardous area
m3 Amplifier box
2600 SERIES
+ 24 VDC
Any Shunt zener Any 28V /diode 300R barrier or Ex repeater with safty Uo Shunt zener diode <= 28V barrier DC and Io <= 93 mA or Ex repeater certified to Ex Ia IIC.
4-20 mA +
EE X
ia
C T5
S/N:
2600
-40 to +85 C < 45 mA IK =
4-20 mA
Transducer
Page 21 of 27
5.
6. 7. 8.
Page 22 of 27
Recalibrating Gauge Transmitter using Vacuum (for gauge transmitters only) An internally mounted transducer can also be recalibrated by using vacuum. 1. 2. 3. 4. 5. Check that the tank is empty. Check that the range select switch on the amplifier is correctly set. Set the calibrator to vacuum mode. Connect the hose from the calibrator to the breather tube from the transducer cable. In conditions of no pressure the output signal should be adjusted to 4.00 mA on the zero potentiometer. Increase the vacuum equal to the maximum height of the fluid (water gauge) and adjust the output signal to 20.00 mA on the span potentiometer. Remove the vacuum and check the zero point. Check the linearity at 0-25-50-75 and 100% of the measuring range. If necessary, repeat the steps 5 to 8. If the calibrated maximum water gauge is greater than the maximum water gauge that can be generated by the vacuum calibrator, the proportional mA output signal equal to the maximum vacuum signal should be calculated.
6.
7. 8. 9.
NOTE:
EXAMPLE: If the full-scale of the transmitter is 15 mH2O, and the maximum capacity of the vacuum calibrator is 7.5 mH2O, the mA output signal at 7.5 mH2O is calculated as: 15 mH2O = 20 mA and 0 mH2O = 4 mA 7.5 mH2O = 4 +
(20 4) * 7.5 15
12 mA
The span potentiometer is adjusted so that the output signal shows 12 mA at 7.5 mH2O.
Page 23 of 27
Recalibrating the Absolute Transmitter using Test Cup type G022S100 When recalibrating the MAS 2600 Absolute Transmitter a pressure calibrator with a range of -1 to 3.5 bar should be used. It should have an accuracy of 0.05% FS or better, as well as a 4 digit milliampmeter. If a calibrator without reference transmitter is used, the atmospheric pressure must be known to calculate the correction. Atmospheric pressure and Transducer range to be entered into the formulas as mbar. 1. The calibrator with the output selector switch set to pressure mode is connected to the MAS 2600 transmitter via a Test Cup, type G022S100. Check the transducer range. The transducer range is indicated on the lid inside the amplifier box. Calculate output signal in conditions of no pressure (atmospheric pressure), using below formula. The output signal should be adjusted to the calculated value on the zero potentiometer. 16 *( Atm. press 800) mA @ Atmospheric pressure = 4 Trd . range 800 Calculate the pressure for maximum output signal, using the following formula. mbarg @ 20 mA = Trd . range Atm. press Increase the pressure to calculated pressure and adjust the output signal to 20.00 mA on the span potentiometer. 5. 6. Remove the pressure and check the zero point. Check the linearity at 0-25-50-75 and 100% of the measuring range. Output signal at different pressures P can be calculated, using the following formula. mA @ P mbarg = 4
2.
3.
4.
7.
Page 24 of 27
EXAMPLE: If the range of the transducer is 3.5 bar abs and the atmospheric pressure is 1005 mbar. Calculated output at atmospheric pressure: mA @ Atm.press = 4
Calculated applied pressure for maximum output: mbarg @ 20 mA = 3500 1005 = 2495 mbarg Calculated pressure at 50% of the transducer range: mA @ P mbarg = 4
Page 25 of 27
Trouble Shooting If the MAS 2600 transmitter is not functioning in accordance with Emerson Process Management Marine Solutions, Damcos instructions, check that: 1. 2. 3. the 24 VDC power supply has been correctly connected, and is between 14-33 VDC. the 4 - 20 mA output signal is functioning (compared with e.g. hand sounding). the transducer cable has been correctly fitted and the shield connected to the shield terminal in the amplifier box. the diaphragm has not been damaged.
4.
If this does not succeed, fill in the test sheet on page 27 and submit this to our Service department fax no.: +45 5578 7272. When contacting our Service department please specify the serial numbers of both transducer and amplifier. The test sheet will be examined to see whether it can be established that the transmitter is broken or not. When returning a defective MAS 2600 transmitter for repairs, please ensure that: The transducer diaphragm is protected against blows of any kind. Both the transducer and the amplifier are returned. A detailed description of the fault is enclosed.
Page 26 of 27
FAX.: Name:
Ship name: MAS2600: Transducer serial no.: Tank name: Liquid in tank HFO: The tank is Full: Measurements:
1 2 3 4 5
Yard:
NB No:
Ballast: Other:
Other:
Measure voltage between terminal 5 and 6 Measure ripple voltage between terminal 5 and 6 Measure sensor excitation voltage between terminal 7 and 10 Measure sensor excitation voltage between terminal 8 and 9 Measure current in supply lead to terminal 5 Measure current in supply lead to terminal 6 Measure sensor resistance with sensor cable unconnected Terminal 7 to cable shield Terminal 8 to cable shield Terminal 9 to cable shield Terminal 10 to cable shield Measure sensor bridge resistance with sensor cable unconnected Terminal 7 to Terminal 8 Terminal 7 to Terminal 9 Terminal 7 to Terminal 10 Terminal 8 to Terminal 9 Terminal 8 to Terminal 10 Terminal 9 to Terminal 10
Voltage should be in the range 14 to 33 V DC. Check power supply. Voltage must not exceed 2 V AC. Check power supply. Voltage should be in the range 3.0 to 6.2 V DC Voltage should be in the range -15 to 100 mV DC Current should be in the range 4 to 20 mA and the same value as measured in point 6. If not the amplifier may be defect. Current should be in the range 4 to 20 mA and the same value as measured in point 5. If not the amplifier may be defect. If the resistance measured is less that 1 M Ohm the sensor is defect.
mA DC
M Ohm M Ohm M Ohm M Ohm If the resistance measured is less than 1 K Ohm or greater that 50 K Ohm the sensor is defect. K Ohm K Ohm K Ohm K Ohm K Ohm K Ohm
Visual inspection of the transmitter: Is the cable damaged? Are there sharp bends on the cable? Are there moisture/liquids in the breather tube? Is the diaphragm damaged? Comments:
10
Page 27 of 27