0% found this document useful (0 votes)
75 views4 pages

1C.3.1-Voltage Balance: 1 Scope 2 General

This document defines PacifiCorp's guidelines for voltage balance. Voltage imbalance can cause problems for three-phase motors and variable speed drives. It defines voltage imbalance as the maximum deviation from average voltage over the average voltage. It recommends limiting maximum voltage imbalance to 3% and describes how to measure and evaluate voltage imbalance.

Uploaded by

Mouna Nj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views4 pages

1C.3.1-Voltage Balance: 1 Scope 2 General

This document defines PacifiCorp's guidelines for voltage balance. Voltage imbalance can cause problems for three-phase motors and variable speed drives. It defines voltage imbalance as the maximum deviation from average voltage over the average voltage. It recommends limiting maximum voltage imbalance to 3% and describes how to measure and evaluate voltage imbalance.

Uploaded by

Mouna Nj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Engineering Handbook

Volume 1General
Part CPower Quality
1C.3.1Voltage Balance
21 Jan 14 1C.3.1 Page 1 of 4
1C.3.1Voltage Balance
1 Scope
This document defines PacifiCorps guidelines for voltage balance.
2 General
Voltage imbalance can cause various problems. Three-phase motors may run hotter and un-
less the motors are operated below their rated capacity (de-rated) may wear prematurely. Un-
balanced voltages have caused malfunctions in variable speed drives.
A major cause of unbalanced voltage is unbalanced load current. This imbalance can be due
to customer load imbalance, utility system imbalance, external influence or self induced.
3 Definition of Voltage Unbalance
The definition of voltage imbalance is found in Appendix D of ANSI Std. C84.1, Voltage
Ratings for Electrical Power Systems and Equipment. That standard was concerned with the
effect on motors; therefore, phase-to-phase voltages were used in the example. Voltage unbal-
ance of a polyphase system is defined as follows:
% voltage unbalance + 100 x
(maximum deviation from average voltage)
(average voltage)
Example:
With phase-to-phase voltages of 230, 232, and 225, the average is 229; the maximum devi-
ation from average is 4; and the percent unbalance is (100 x 4) / 229 = 1.75 percent.
4 Voltage Unbalance Limits
Relatively small voltage imbalances are often achievable close to substations on circuits with
well-balanced loads. Farther out on circuits it can be extremely difficult and very expensive
to achieve a high level of voltage balance.
An excessive level of voltage imbalance can have serious impacts on induction motors. In-
duction motors are designed to tolerate a small level of imbalance, but they have to be
de-rated if the imbalance is excessive, which is an added cost for the installation. Applying
the recommendations of ANSI Std. C84.1. is a reasonable middle ground in an attempt to
optimize voltage balance and minimize total cost to the customer and the utility.
Those recommendations are:
1. Electric supply systems should be designed and operated to limit the maximum voltage
imbalance to three percent when measured at the electric utility revenue meter under
no-load conditions. This corresponds to a motor de-rating to 90% of its full load rating
according to ANSI C84.1.
Engineering Handbook
Volume 1General
1C.3.1Voltage Balance
Part CPower Quality
21 Jan 14 1C.3.1 Page 2 of 4
2. If an electric supply system is operating near the upper or lower limits of the ANSI
Std. C84.1 voltage ranges, each individual phase voltage should be within the listed
limits. (These voltage ranges are listed in 1C.2.1, Voltage Level and Range, in this
Handbook.)
It is important to recognize that operation under strict limits for voltage balance would re-
quire major system changes, which cannot be economically justified from the standpoint of
the customer or PacifiCorp. In other instances, unique or changing system conditions may
make it impractical to remain within specific limits for all operating situations. However,
PacifiCorp makes every reasonable effort to maintain voltage balance to meet the needs of
typical customer equipment and the most efficient utilization of the distribution system.
5 Voltage Balance Measurements
Voltage imbalance in a three-phase system exists when the magnitudes of phase or line
voltages are different, the phase angles differ from the balanced conditions, or both. This can
occur due to unequal system impedances or unequal distribution of single-phase loads.
Many three-phase loads are served from transformers with four-wire wye connected
low-voltage windings, such as 208Y/120 volts, or 480Y/277 volts. Voltage should be meas-
ured line-to-line and line-to-neutral. Balance may be evaluated for both cases. Appropriate
actions should be considered to resolve conditions at places where unacceptable imbalance
exists.
Example: Three line-to-neutral voltage readings of 122.0, 118.0 and 118.0 volts are recorded.
The average is 119.3 volts with maximum deviation of 2.7 volts and an apparent imbalance
of 2.23%.
The same case using voltage measured line-to-line yields a different result. The line-to-line
voltages would be 207.8, 204.4 and 207.8 volts. This would give an average of 206.7 volts, a
maximum deviation of 2.3 volts and a voltage imbalance of 1.12%.
This shows the difference in voltage imbalance on the line-to-line calculations and the need
to measure voltages from phase-to-phase as well as phase-to-neutral.
Motor windings are often delta connected and are sensitive to the phase-to-phase voltages.
Line-to-line and line-to-neutral measurements provide the data needed to evaluate either case.
Failure to collect all the data may yield incomplete conclusions. In some complete cases,
time recordings are required to see actual change of values through a loading cycle and the
apparatus results. Some recording volt/amp meters may give vector values but the six simple
voltages measured at the time of impact provide the required information to determine the
magnitude of the imbalance and possibly determine alternatives for a solution.
Engineering Handbook
Volume 1General
Part CPower Quality
1C.3.1Voltage Balance
21 Jan 14 1C.3.1 Page 3 of 4
6 Issuing Department
The T&D Engineering Publications department of PacifiCorp issued this document.
Questions regarding editing, revision history and document output may be directed to the
lead editor at (503) 8135293. Technical questions and comments may be directed to:
Dennis Hansen, principal engineer, (801) 2204816, or
Rohit Nair, engineer, (801) 2204352
This material specification shall be used and duplicated only in support of PacifiCorp
projects. This document was last revised by a team that included the following authors and
reviewers:
Dennis Hansen, principal engineer
Rohit Nair, engineer
Greg Lyons, Smart Grid manager
Craig Quist, area / transmission director
Ken Shortt, engineering & environmental director
Brandon Prescott, risk & strategy director
Mark Adams, area / transmission supervisor
Larry Frick, area / transmission planning director
Aleksey Shkuratkov, engineer
Chuck Wright, senior engineer
Dave Hagen, area / transmission planning manager
Joshua Jones, engineering & environmental manager
Engineering Handbook
Volume 1General
1C.3.1Voltage Balance
Part CPower Quality
21 Jan 14 1C.3.1 Page 4 of 4
This page is left blank intentionally.

You might also like