Electrical Specification Division 16, Section 16116

This document provides specifications for cable trunking systems. It outlines requirements for materials, manufacturers, submittals, products, installation and field quality control. Cable trunking must be manufactured to standards like NEMA and constructed of steel with a corrosion resistant finish. Installation must comply with manufacturer instructions, standards and industry practices. Electrical bonding and grounding connections must be tested prior to cable installation.

Uploaded by

eng_asayed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
254 views4 pages

Electrical Specification Division 16, Section 16116

This document provides specifications for cable trunking systems. It outlines requirements for materials, manufacturers, submittals, products, installation and field quality control. Cable trunking must be manufactured to standards like NEMA and constructed of steel with a corrosion resistant finish. Installation must comply with manufacturer instructions, standards and industry practices. Electrical bonding and grounding connections must be tested prior to cable installation.

Uploaded by

eng_asayed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 4

SECTION 16116

CABLE TRUNKING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of Contract, including General and special Conditions and Division-1
(General requirements), apply to wor of t!is section.
". General #rovisions for $lectrical %or &ection 1'(1(.
C. &pecification &ection 1))*+, -ounting and .solation of -ec!anical and $lectrical &ystems and related
contract drawings, apply to t!is section of t!e wor.
1.2 DESCRIPTION OF WORK
A. %or includes providing all materials, equipment, accessories, services and tests necessary to
complete and mae ready for operation /y t!e 0wner, all ca/le truning in accordance wit! Drawings
and &pecifications.
1.3 QUALITY ASSURANCE
A. -anufacturers, 1irms regularly engaged in t!e manufacture of ca/le truning of t!e types and
capacities required, w!ose products !ave /een in satisfactory use in similar service for not less t!an )
years and s!all /e of one manufacturer, approved /y t!e a!ramaa, and conform to t!e requirements
set fort! in t!is specification .
". &tandards Compliance, Comply wit! requirements of applica/le local codes, a!ramaa regulations
latest edition, D.234D$, .$C, 2$C, 56, 2$-A, .$$$, and A2&. &tandards pertaining to ca/le truning
#rovide ca/le truning products and components w!ic! !ave /een listed and la/eled.
C. .n case of conflict among t!e referenced standards and codes, t!e more stringent provision will govern.
1.4 SUBMITTALS
A. #roduct Data, &u/mit manufacturer7s data for ca/le truning.
". &amples,- &u/mit )( cm lengt! of ca/le truning complete wit! its accessories and fittings.
C. &!op Drawings, &u/mit dimensioned layout drawings on arc!itectural /acgrounds of ca/le truning
including, /ut not limited to, offsets and connections. &!ow accurately scaled ca/le truning wit!
locations of supports and fittings, including fire stops and weat!er seals. .ndicate spatial relations!ip of
ca/le trunings to ot!er associated equipment.
#age 1 of *
Cab! T"#$%&$'

&ection 1'11'
PART 2 - PRODUCTS
2.1 CABLE TRUNKING
A. GENERAL
1. 8runing and connectors s!all /e manufactured generally in accordance wit! D.234D$ or 2$C
9. 8runing and connectors for internal use s!all /e finis!ed wit! protection in accordance wit!
D.234D$ or 2$C.
:. 6engt!s of truning s!all /e efficiently /onded to eac! ot!er using strip copper lins not less
t!an 19 mm wide ; 1.) mm t!ic and fi;ed wit! /rass nuts, /olts and ased serrated was!ers.
*. 6ids s!all /e lipped and fi;ed at intervals not e;ceeding 1 meter /y means of quic release can
fasteners. &teel screws and fasteners s!all /e protected against corrosion /y a finis! at least
equivalent to <inc coating to D.234D$ or 2$C.
). -etal partitions in truning s!all /e a minimum t!icness of 1.9 mm and t!e finis! s!all /e of
t!e same standard as t!e truning. 8!e met!od of fi;ing partitions to t!e truning s!all not
cause long term corrosion or electrolytic action and s!all /e suc! t!at t!e partitions cannot /e
inadvertently displaced.
'. Connectors s!all span t!e complete internal surface of t!e truning and s!all /e designed so
t!at t!e truning sections mate wit! /utting =oints.
+. 4ertical truning s!all /e supplied wit! a ca/le support unit wit! insulated pins at intervals not
e;ceeding : meters.
>. ?ori<ontal truning si<es e;ceeding 1(( mm ; )( mm s!all /e supplied wit! ca/le separators
wit! insulated pins at intervals not e;ceeding 9 meters.
@. 8runing s!all consist of /ase, snap-on covers, coupling end plates, wall flanges, panel to
truning ru//er grommet, el/ows, tees, adaptor plates and all necessary !angers supports and
accessories.
1(. 8runing s!all /e constructed of steel. All steel units s!all /e protected inside and outside wit!
a corrosion resistant finis! suc! as <inc or cadmium, wit! a top coat of enamel.
11. All trunings parts s!all /e mec!anically and electrically coupled w!ile protecting wires from
a/rasion.
". %!ere any cutting or damage is caused during erection, t!e finis! s!all /e made good. All /urrs and
roug! edges s!all /e removed. %!ere any corrosion !as occurred it s!all /e removed and t!e area
treated wit! a rust- proofing agent. After t!is it s!all /e treated /y t!e application of eit!er a <inc ric!
epo;y primer or equal alternative followed /y a coat of color matc!ing paint.
C. Any fi;ing used for securing or fitting s!all not cause any long term corrosion or electrolytic action -
/lac =apanned fi;ing screws s!all not /e used. %!ere /racets are used t!ey s!all /e constructed of
mild steel angle or c!annel iron finis!ed to t!e same standard as t!e truning.
#age 9 of *
Cab! T"#$%&$'

&ection 1'11'
D. Connections to conduit, multiple /o;, switc!gear and distri/ution /oards s!all /e made wit! flanged
units.
$. %!ere truning crosses settlement and e;pansion =oints a truning =oints s!all /e made. 8!e connector
at t!is point s!all /e made wit! slotted fi;ing !oles to permit a movement of 1( mm in /ot! t!e
!ori<ontal and vertical planes. 8!e eart! continuity lins across suc! =oints s!all /e of /raided copper
tape not less t!an 1) mm wide ; 9 mm t!ic !aving a resistance from fi;ing to fi;ing equal to or less
t!an t!e lins used for t!e standard truning =oints.
8!e /raid s!all /e long enoug! to allow for t!e ma;imum movement of t!e truning. 8!e /raid ends
s!all /e folded, and sweated soiled.
2.2 ACCEPTABLE MANUFACTURERS
R!(!" T) *+! ,S-+!.#! )( P"!(!""!. E!-*"&-a Ma$#(a-*#"!"/ 0 S#11&!"/,.
PART 3 - E2ECUTION
3.1 INSPECTION
A. $;amine conditions under w!ic! ca/le trunings are to /e installed. 2otify $ngineer in writing of
conditions detrimental to proper completion of t!e wor. Do not proceed wit! t!e wor until
unsatisfactory conditions !ave /een corrected.
3.2 INSTALLATION
A. .nstall ca/le truning and accessories as indicated in accordance wit! manufacturer7s written
instructions, requirements of applica/le standards and in accordance wit! recogni<ed industry
practices to ensure t!at installation complies wit! requirements and serves intended function.
". Coordinate as necessary to interface installation of ca/le truning wor wit! ot!er wors.
C. .nstall integral fire stops w!ere ca/le truning penetrates fire-rated walls and floors. &eal /etween
ca/le truning and opening and around opening wit! fire-rated sealant not less t!an wall, or floor, fire
ratings.
D. At floor openings provide concrete cur/, 1( cm wide and 1( cm !ig!, around ca/le truning and seal
wit! non-com/usti/le material.
$. #rovide electrical /onding and equipment eart!ing connections for ca/le truning 8ig!ten connections
to comply wit! tig!tening torques specified /y manufacturers to assure permanent and effective
connections and grounds.
1. Anc!or mounting !ardware firmly to walls, floors, or ceilings, to ensure enclosures are permanently
and mec!anically secured. #rovide all !ardware and accessories for proper mounting.
G. Aoute ca/le truning as required and mae final field measurements /efore ordering ca/le truning.
?. %!ere t!ere is insufficient elevation or lateral c!ange in direction to accommodate fittings directly
connected, ad=usta/le vertical connectors or ad=usta/le !ori<ontal connectors wit! straig!t section in
/etween may /e used. Avoid slopes t!at would cause ca/le to /end on smaller radiiB t!an t!at allowed
/y ca/le manufacturer.
#age : of *
Cab! T"#$%&$'

&ection 1'11'
.. #rovide !angers, rods, straps, special /racets, and ot!er means of supporting ca/le truning as
required.
3.3 FIELD QUALITY CONTROL
A. #rior to installing ca/les in ca/le truning, test for electrical continuity of /onding, and eart!ing
connections, and to demonstrate compliance wit! grounding requirements.
". $lectrically energi<e ca/le truning systems and demonstrate functioning in accordance wit!
requirements. %!ere necessary, correct malfunctioning units, and t!en retest to demonstrate
compliance. Aeplace equipment w!ic! cannot /e satisfactorily corrected.
END OF SECTION 16116