Calculation RED670 7SA R2

This document contains calculations for current transformers (CTs) used on 33kV cable line bays. It defines various resistances and ratings involved in CT specifications, including conductor resistance, CT burden, and knee point voltage. A table shows the calculated results for 6 CTs with different current ratios and ratings to ensure requirements for burden, knee point voltage, and power are met.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
577 views

Calculation RED670 7SA R2

This document contains calculations for current transformers (CTs) used on 33kV cable line bays. It defines various resistances and ratings involved in CT specifications, including conductor resistance, CT burden, and knee point voltage. A table shows the calculated results for 6 CTs with different current ratios and ratings to ensure requirements for burden, knee point voltage, and power are met.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

CT's calculation for cable line bay 33kV

RB RCond . RProt.

RCond .

2l

RN

PN
I N2

RB : connected burden
RCond . : conductor burden
l : conductor length
q : conductor cross - section
1
: specific resistence

RCT : internal CT burden

Vkmin Ktd

I scc _ max
1.3 I pn

RN : nominal burden

( RCt RB ) I sn

Vkp : kneepoint voltage

Ktd : trasient dimensioni ng factor

For ABB
I pn : CT rated primary current
Eal Ealreq I K m ax

I sn
0.25
RCt R L 2
I pn
I r

Eal Ealreq I t m ax 2

I sn : CT rated secundary current


I ssc _ max : symmetrica l short - circuit current

I sn
0.25
RCt R L 2
I pn
I r

ICC

CT

CORE

CLASS

Current
ratio
xxx/1A
1500

DEVICES

RED670

800
600

RED670

300

PX

600

7SA

300

Caculated: F. GMEZ
Reviewed: W. CASTAEDA
Approved: M. ROSETY

PX

600
300

7SA

R CT BURDEN
(Ohm)
(VA)

Conductor
length
(m)

#REF!

Conductor
section
(mm2)

R Cond.
(Ohm)

R Prot./
(Ohm)

RB
(Ohm)

Vkp

I''cc
(kA)

Ktd

Vk min

Request:

Ptot

>25%BURDEN

Vkp > Vk min

5.30

50

4.0

0.45

0.250

0.70

1300.00

40.00

319.81

0.70

-o-

OK

2.80

50

4.0

0.45

0.250

0.70

650.00

40.00

349.64

0.70

-o-

OK

6.50

50

4.0

0.45

0.250

0.70

1300.00

10.00

479.76

3.50

50

4.0

0.45

0.250

0.70

650.00

10.00

559.52

6.50

50

4.0

0.45

0.050

0.50

975.00

31.50

1.00

282.55

0.50

-o-

OK

3.50

50

4.0

0.45

0.050

0.50

650.00

31.50

1.00

322.79

0.50

-o-

OK

3.80

50

4.0

0.45

0.050

0.50

975.00

10.00

4.00

220.33

0.50

-o-

OK

3.50

50

4.0

0.45

0.050

0.50

650.00

10.00

4.00

409.89

0.50

-o-

OK

OK
OK

DOC: 233129495.xlsx.ms_office
Page: 1 of 1