The document provides information on 88 series plug-in timers. It describes the features of multi-voltage and multi-function timer models as well as mono-function timer models. The timers can be used for applications such as on-delay, interval, pulse delayed and symmetrical flasher functions. They have 8 or 11 pin plug-in versions, time scales ranging from 0.05 seconds to 100 hours, and AC/DC voltage supply options.
The document provides information on 88 series plug-in timers. It describes the features of multi-voltage and multi-function timer models as well as mono-function timer models. The timers can be used for applications such as on-delay, interval, pulse delayed and symmetrical flasher functions. They have 8 or 11 pin plug-in versions, time scales ranging from 0.05 seconds to 100 hours, and AC/DC voltage supply options.
Multi-voltage and multi-function timer range Front panel or socket mount 8 and 11 pin plug-in versions available Time scales from 0.05s to 100h 1 delayed contact +1 instantaneous contact version available (type 88.12) Front panel mounting fixing included 90 series sockets Multi-function 11 pin Plug-in for use with 90 series sockets AI: On-delay DI: Interval GI: Pulse delayed SW: Symmetrical flasher (starting pulse on) Al a: On-delay (2 timed contacts) Al b: On-delay (1 timed + 1 instantaneous contact) Dl a: Interval (2 timed contacts) Dl b: Interval (1 timed + 1 instantaneous contact) GI: Pulse delayed SW: Symmetrical flasher (starting pulse on) 2 CO (DPDT) 2 CO (DPDT) 8/15 8/15 250/400 250/400 2,000 2,000 400 400 0.3 0.3 8/0.3/0.12 8/0.3/0.12 300 (5/5) 300 (5/5) AgNi AgNi 24230 24230 24...230 24...230 2.5 (230 V)/1 (24 V) 2.5 (230 V)/1.5 (24 V) 20.4264.5 20.4264.5 20.4264.5 20.4264.5 (0.05 s5 h) - (0.05 s10 h) - (0.05 s50 h) - (0.05 s100 h) 1 1 300 200 50 3 3 10010 3 10010 3 10+55 10+55 IP 40 IP 40 Multi-function 8 pin, 2 timed contacts or 1 timed + 1 instantaneous contact Plug-in for use with 90 series sockets BE: Off-delay with control signal CE: On- and off-delay with control signal DE: Interval with control signal on without control signal with control signal without control signal Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA Single phase motor rating (230 V AC) kW Breaking capacity DC1: 30/110/220 V A Minimum switching load mW (V/mA) Standard contact material Supply specification Nominal voltage (U N ) V AC (50/60 Hz) V DC Rated power AC/DC VA (50 Hz)/W Operating range V AC V DC Technical data Specified time range Repeatability % Recovery time ms Minimum control impulse ms Setting accuracy-full range % Electrical life at rated load AC1 cycles Ambient temperature range C Protection category Approvals (according to type) 1 P = Pause S = Start R = Reset V - 2 0 1 4 ,
w w w . f i n d e r n e t . c o m 88 Series - Plug-in timers 8 A 88 SERIES 88.92 - 0000 88.92 - 0001 Features Multi-voltage and mono-function timer range Front panel or socket mount Asymmetrical flasher The ON and OFF time are independently adjustable 8 pin plug-in Time scales from 0.05s to 300h 2 contacts Front panel mounting fixing included 90 series sockets Mono-function 8 pin, 2 timed contacts Plug-in for use with 90 series sockets Mono-function 8 pin, 2 timed contacts Plug-in for use with 90 series sockets PI: Asymmetrical flasher (starting pulse OFF) LI: Asymmetrical flasher (starting pulse ON) 2 CO (DPDT) 2 CO (DPDT) 8/15 8/15 250/400 250/400 2,000 2,000 400 400 0.3 0.3 8/0.3/0.12 8/0.3/0.12 300 (5/5) 300 (5/5) AgNi AgNi 12240 12240 12...240 12...240 2.5 (230 V)/1.5 (24 V) 2.5 (230 V)/1.5 (24 V) 10.8264.5 10.8264.5 10.8264.5 10.8264.5 See Time Scale page 3 See Time Scale page 3 1 1 200 200
1 1 10010 3 10010 3 10+55 10+55 IP 40 IP 40 Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA Single phase motor rating (230 V AC) kW Breaking capacity DC1: 30/110/220 V A Minimum switching load mW (V/mA) Standard contact material Supply specification Nominal voltage (U N ) V AC (50/60 Hz) V DC Rated power AC/DC VA (50 Hz)/W Operating range V AC V DC Technical data Specified time range Repeatability % Recovery time ms Minimum control impulse ms Setting accuracy-full range % Electrical life at rated load AC1 cycles Ambient temperature range C Protection category Approvals (according to type) 2 V - 2 0 1 4 ,
w w w . f i n d e r n e t . c o m 88 SERIE S 88 Series - Plug-in timers 8 A without control signal without control signal H A Yellow LED: power ON (U) B Red LED: timing in progress (C) C Unit of time selected D Time scale selector E Function selector F Function selected G Time scale selected H Unit of time selector s min h 10h 0.5 0.5 second 0.5 minute 0.5 hour 5 hour 1 1 second 1 minute 1 hour 10 hour 5 5 second 5 minute 5 hour 50 hour 10 10 second 10 minute 10 hour 100 hour Time scales Full scale value for types 88.02, 88.12 Full scale value for type 88.92 Types 88.02, 88.12 Type 88.92 3 EMC specifications Type of test Reference standard 88.02/88.12 88.92 Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV air discharge EN 61000-4-2 8 kV 6 kV Radio-frequency electromagnetic field (80 1,000 MHz) EN 61000-4-3 10 V/m 10 V/m Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 2 kV Surges (1.2/50 s) on Supply terminals common mode EN 61000-4-5 2 kV differential mode EN 61000-4-5 1 kV Radio-frequency common mode (0.15 80 MHz) on Supply terminals EN 61000-4-6 3 V Technical data Example: 88 series multi-function timer, 2 CO (DPDT) 8 A contacts, (24230)V AC (50/60 Hz) and (24230)V DC supply. Ordering information Special versions 0 = Functions PI (starting pulse OFF) for 88.92 1 = Functions LI (starting pulse ON) for 88.92 2 = Standard Supply voltage 230 = (24230)V AC/DC for 88.02, 88.12 240 = (12...240)V AC/DC for 88.92 Codes 88.02.0.230.0002 88.12.0.230.0002 88.92.0.240.0000 88.92.0.240.0001 Series Type 0 = Functions AI, DI, GI, SW, BE, CE, DE, 11 pin 1 = Functions Al a, Al b, Dl a, Dl b, GI, SW, 8 pin 9 = Functions LI, PI, 8 pin No. of poles 2 = 2 pole Supply version 0 = AC (50/60 Hz)/DC 0 2 0 0 0 2 . . . . 2 3 0 8 8 0 Selection of: function, time scale and units NOTE: time scales and functions must be set before energising the timer. 88.02 88.12 88.92 - 0000 88.92 - 0001 Function AI, DI, GI, SW, BE, CE, DE Al a, Al b, Dl a, Dl b, GI, SW PI LI Time scale 0.5, 1, 5, 10 1.2, 3, 12, 30 Unit of time s (second), min (minute), h (hour), 10h (10 hours) s (second), 10s (second x 10), min (minute), 10 min (minute x 10), h (hour), 10h (hour x 10) D H LED/visual indication Types 88.02, 88.12 A Red LED: pulse ON (T1) B Green LED: pulse OFF (T2) C Red timing regulator: T1 time setting D Unit of time selector: T1 (ON) E Unit of time selector: T2 (OFF) F Green timing regulator: T2 time setting G Time scale selected H Time scale selector Type 88.92 V - 2 0 1 4 ,
w w w . f i n d e r n e t . c o m 88 Series - Plug-in timers 8 A 88 SERIES 1.2 3 12 30 s min 1.2 second 3 second 12 second 30 second 12 second 30 second 120 second 300 second 1.2 minute 3 minute 12 minute 30 minute 12 minute 30 minute 120 minute 300 minute 1.2 hour 3 hour 12 hour 30 hour 12 hour 30 hour 120 hour 300 hour 10s 10min h 10h A B C D G E F H H H D-E 4 V - 2 0 1 4 ,
w w w . f i n d e r n e t . c o m U =Supply Voltage S =Signal switch P =Pause R = Reset = Output Contact LED (red) LED (yellow) Supply voltage NO output contact OFF ON ON ON Open Open Open (timing in progress) Closed Functions for types 88.02, 88.12 Contact (AI) On-delay. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs when power is removed. (BE) Off-delay with control signal. Power is permenently applied to the timer. The output contacts transfer immediately on closure of the Signal Switch (S). Opening the Signal Switch initiates the preset delay, after which time the output contacts reset. (DE) Interval with control signal on. Power is permenently applied to the timer. On momentary or maintained closure of Signal Switch (S), the output contacts transfer, and remain so for the duration of the preset delay, after which they reset. (SW) Symmetrical flasher (starting pulse on). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ratio is 1:1 (time on = time off). without control signal with control signal Wiring diagram Type 88.02 x1 - x4 x1 - x4 x1 - x2 x1 - x4 x1 - x2 x1 - x2 x1 - x2 x1 - x4 x1 - x2 x1 - x4 Open Closed (DI) Interval. Apply power to timer. Output contacts transfer immediately. After the preset time has elapsed, contacts reset. (GI) Pulse delayed. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs after a fixed time of 0.5s. (CE) On- and off-delay with control signal. Power is permenently applied to the timer. Closing the Signal Switch (S) initiates the preset delay, after which time the output contacts transfer. Opening the Signal switch initiates the same preset delay, after which time the output contacts reset. PAUSE (P) Closure of the pause switch (2-5) will immediately halt the timing process, but the elapsed time will be retained, and the current state of the output contacts will be maintained. On opening of the pause switch, timing resumes from the retained value. This is applicable for all functions. RESET (R) A momentary closure of the reset switch (2-7) will reset the timer. Longer term closure of the reset switch will hold the timer in the reset state. This is applicable for all functions. 88 SERIE S 88 Series - Plug-in timers 8 A H (Al a) On-delay (2 timed contacts). Apply power to timer. Contacts (C 1 and C 2 ) transfer after preset time has elasped. Reset occurs when power is removed. (Al b) On-delay (1 timed contact + 1 instantaneous contact). Apply power to timer. Output contact (C 1 ) transfers immediately. Contact (C 2 ) transfers after the preset time has elasped. Reset occurs when power is removed. (Dl a) Interval (2 timed contacts). Apply power to timer. Output contacts (C 1 and C 2 ) transfer immediately. After preset time has elasped, the contacts reset. (Dl b) Interval (1 timed contact + 1 instantaneous contact). Apply powert to timer. Output contacts (C 1 and C 2 ) transfer immediately. After preset time has elasped, the contact (C 2 ) resets. Contact (C 1 ) resets when power is removed. Functions for type 88.12 without control signal Wiring diagram Type 88.12 (GI) Pulse delayed. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs after a fixed time of 0.5s. (SW) Symmetrical flasher (starting pulse on). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ratio is 1:1 (time on = time off). 5 (LI) Asymmetrical flasher (starting pulse ON). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ON and OFF times are independently adjustable. without control signal Wiring diagram Type 88.92 V - 2 0 1 4 ,
w w w . f i n d e r n e t . c o m (PI) Asymmetrical flasher (starting pulse OFF). Apply power to timer. Output contacts transfer after time T2 has elapsed and cycle between OFF and ON for as long as power is applied. The ON and OFF times are independently adjustable. 88 Series - Plug-in timers 8 A 88 SERIES H U = Supply Voltage LED OFF (green) LED ON (red) Supply voltage OFF ON ON Functions for type 88.92 Contact 11 - 14 21 - 24 11 - 12 21 - 22 11 - 14 21 - 24 11 - 12 21 - 22 11 - 14 21 - 24 11 - 12 21 - 22 Open Closed 6 V - 2 0 1 4 ,
w w w . f i n d e r n e t . c o m 90.26 90.21 Approvals (according to type): Screw terminal (Box clamp) socket 90.20 90.20.0 90.21 90.21.0 panel or 35 mm rail (EN 60715) mount Blue Black Blue Black For timer type 88.12, 88.92 88.02 Technical data Rated values 10 A - 250 V Dielectric strength 2 kV AC Protection category IP 20 Ambient temperature C 40+70 Screw torque Nm 0.5 Wire strip length mm 10 Max. wire size for 90.20 and 90.21 sockets solid wire stranded wire mm 2 1x6 / 2x2.5 1x6 / 2x2.5 AWG 1x10 / 2x14 1x10 / 2x14 Approvals (according to type): Screw terminal (Plate clamp) socket 90.26 90.26.0 90.27 90.27.0 panel or 35 mm rail (EN 60715) mount Blue Black Blue Black For timer type 88.12, 88.92 88.02 Technical data Rated values 10 A - 250 V Dielectric strength 2 kV AC Protection category IP 20 Ambient temperature C 40+70 Screw torque Nm 0.8 Wire strip length mm 10 Max. wire size for 90.26 and 90.27 sockets solid wire stranded wire mm 2 1x4 / 2x2.5 1x4 / 2x2.5 AWG 1x12 / 2x14 1x12 / 2x14 Approvals (according to type): Sockets 8-11 pin backwired with solder terminals 90.12.4 (black) 90.13.4 (black) For timer type 88.12, 88.92 88.02 Technical data Rated values 10 A - 250 V Dielectric strength 2 kV AC Ambient temperature C 40+70 90.13.4 90.20 90.21 90.27 90.26 88 SERIE S 90 Series - Sockets and Accessories for 88 series Timers H