Duo Check
Duo Check
0227
TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: +1.574.295.3327 FAX: +1.574.295.3455
www.nibco.com
30
A H E A D O F T H E F L O W
www.nibco.com
Revision 4/20/2009
250 PSI WWP Iron Body Check Valves
Fire Protection Valve UL listed FM Approved
Double-Door Wafer Style Rubber Seat Spring Actuated
MATERIAL LIST
PART SPECIFICATION
1. Body
Ductile Iron ASTM A 536, Grade 65-45-12 - 2" thru 12"
14" thru 16" Cast Iron ASTM 126, Blass B
2. Disc Bronze ASTM B 584 Alloy C83600
3. Torsion Spring Stainless Steel
4. Hinge Pin Stainless Steel
5. Stop Pin Stainless Steel
6. Thrust Bearing Stainless Steel
7. Hinge Pin Retainer Steel
8. Stop Pin Retainer Steel
9. Stabilization Sphere Buna-N
10. Spacer High Density Polyethylene
250 PSI/13.8 Bar Non-Shock Cold Water General Service
UL/ULC LISTED FM APPROVED*
sizes
4" - 12" only
DIMENSIONSWEIGHTSQUANTITIES
Dimensions
Size A B C D E Weight
In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. C/V Lbs. Kg.
2 65 2.38 60 6.00 152 .125 3 3.50 89 1.313 33 108 4.3 1.95
3 80 2.63 67 5.63 143 .188 5 3.875 98 1.688 43 178 6.1 2.77
4 100 2.63 67 7.75 197 .625 16 4.75 121 3.063 78 440 8.8 3.99
5 125 3.25 83 7.56 192 .813 21 5.50 140 3.625 92 560 13.0 5.90
6 150 3.75 95 8.63 219 .813 21 6.25 159 4.250 108 840 18.0 8.16
8 200 5.00 127 12.25 311 1.000 25 8.00 203 5.500 140 1600 37.0 16.78
10 250 5.50 140 14.75 375 2.125 54 10.12 257 8.500 216 2700 65.0 29.48
12 300 7.13 181 17.38 441 1.938 49 12.00 305 9.250 235 4700 94.0 42.64
14 350 7.25 184 17.75 451 3.250 83 13.000 330 5200 200.0 90.75
16 400 7.50 191 20.25 514 4.500 114 15.000 381 7200 285.0 129.28
*Note: 14 and 16 sizes, 200 PSI WWP, FM approved only P.O.A.
Features
Spring loaded for fast closure, eliminating reverse flow slam and water hammer.
Easily installed, with gasket, between standard class 125 flanges.
Only one set of flange studs is needed.
May be installed in both horizontal and vertical lines with upward flow.
NOTE: 14" and 16" sizes, 150 PSI WWP, FM approved only P.O.A.
KW-900-W
Wafer Style
2
1
/2" - 12"
KW-900-W
Wafer
Drawing for sizes 2" thru 12"
NOTE: Twin Disc Check Valves can be installed horizontally or in the
vertical position with flow up.
CAUTION: For horizontal flow applications, the valve must be installed with
disc hinge pin in the vertical position to insure proper operation.
WARNING:
1. These are not to be used as steam valves
2. Valves are not to be used near a reciprocating air compressor
3. Install 5 pipe diameters minimum downstream from pump
discharge or elbows to avoid flow turbulence. Flow
straighteners may be required in extreme cases.
NOTE: On pump discharge, the preferred check valves are in-line spring loaded.
KW-900-W
Wafer Style
14" - 16"