Grounding
Grounding
P
e
r
s
o
n
n
e
l
s
a
f
e
t
y
p
r
o
t
e
c
t
i
o
n
.
t (ats
rods should be driven, the depth of the rod away from the See the section Personnel safety protection.
foundation, in virgin soil for maximum effectiveness.
:ater,ipe#yste!s
Counterpoise
Acounterpoise is a system of conductors, usually arranged
Before the use of plastics, metallic water piping was installed. beneath the earth and under transmission lines. The
With the water piping in intimate contact with the earth, it poise is connected to the transmission towers to dissipate
was natural to make use of it as a grounding electrode. In lightning strike. A counterpoise conductor system can be
older houses, the soil piping was cast iron with lead joints cated above the ground and placed above buildings,
forming a path to earth. A person in a bathtub, lacking any buildings storing explosives, to intercept any lightning
dead, dry skin, could easily be electrocuted when any current- strikes.
carrying conductor was touched or fell into the tub. By con-
necting one of the two power conductors to the water pipe,
,o"e0uttGrounds
the chances of an accident occurring were reduced by 50%. In One of the methods the utilities use to ground their
addition, the metallic water pipe was an excellent conductor is a (pole) butt ground. Bare copper wire is wound in a
and could serve as a low-resistance (low-impedance) path to fashion and stapled around the bottom of a utility pole.
allow the ow of sufcient fault current to operate the protec- the weight of the pole pressing down on the bare copper
tive device. on the bottom of the pole, the copper wire is placed in inti-
Problems developed with the use of the water pipe as an mate contact with the earth. Tests conducted by the
earthing electrode. Where houses were in close proximity to Nevada Chapter, International Association of Electrical In-
each other, connected by underground metallic water piping, spectors, Las Vegas, indicated that this method of
stray current could ow from one house to another. With sin- to earth was the least effective (11).
gle-phase, three-wire service, the neutral conductor also
serves as the messenger and as the grounding conductor.
Should the messengerneutralgrounding conductor become
IN#*A++A*IONR'CO(('NDA*ION#AND,RAC*IC'#
corroded and develop a high resistance, the return current
would seek a lower resistance path. The current could ow
'"ectrica",o4er#yste!
over the water piping to the adjacent housing, with the neu-
tral return current owing back to the transformer over the The requirement that all continuous owing electrical
neighbors messengerneutralground conductor. Overload- must be contained in conductors is paramount. The
ing of conductors resulted. Electric water heaters sometimes used to earth electrical equipment should be a separate
burned out. Persons taking showers could experience electric ductor, either a bare copper or a green-insulated
shocks. In addition, water meter personnel removing the wa- earthing/grounding conductor. The earthing/grounding
ter meter for inspection and repairs could place themselves in ductor connecting electrical equipment enclosures to earth
the ground current circuit and experience electric shocks. must be contained within the raceway with the phase
conduc- The advent of plastic piping and the installation of GFCIs bond equipment.
has reduced the problems. However, all metallic water and
re piping within a building should still be connected to the
electrical grounding system. 0onding
0ui"ding#tee" Bonding is the connecting together of two electrical
conduct-
For the purposes of this discussion, building steel is a struc-
ture consisting of a steel skeleton, with the steel columns the potential difference drops to zero. For proper bonding the
4&6GROUNDING
conductor cross-section area, the magnitude of the ground usually loose and would be in relatively poor contact. Ideally,
fault current, the impedance of the bonding path, and the each down conductor should be connected to two or more ear-
spacing to the phase conductors must be taken into consider- thing electrodes.
ation. New information appears to validate the dissipation array
The connecting together, or bonding, of the motor frame to lightning protection system. A charged space cloud evidently
the supporting building steel is made so that both metal parts forms above the dissipation array and intercepts any light-
will be at the same potential. Bonding is critical when dealing ning stroke leader. A massive earthling system is installed to
with static. When the ow of materials crosses a glass section, earth the dissipations array system.
it is important to bond around the glass piping, as static For additional information consult Refs. 3 and 13. charges
can build up on the metallic piping where it changes
to glass.
The most common error made in the installation of bond- #*A*IC5,RO*'C*IONGROUNDING
ing and grounding conductors is placing them inside of fer-
rous conduit. The function of the bonding or grounding con- Static is considered a mystery by many. The key to protection
ductor can then be negated, especially if the conductor is against static is the completion of the circuit. Static charges
insulated. The insulated bonding or grounding conductor is a are developed when electrons are moved from one location to
single conductor that under fault conditions can carry largeanother without an adequate conductive return path back to
fault currents. It will have a magnetic eld around it when the source. Charges that are insulated from other conducting
carrying fault current. If it is placed inside the ferrous con- paths back to the source are the problem. Harm can develop
duit, the combination will act as a single-turn transformer, if the charges are allowed to concentrate, build up sufcient
introducing impedance into the circuit and restricting the potential, and break down the insulation properties of air, re-
ow of fault current. Both ends of the conductor must be sulting in a sparkover.
bonded (connected) to the end of the conduit so that the con- Bonding between the location losing charges and the loca-
duit carries the fault current in parallel with the conductor. tion gaining charges will permit the charges to recombine,
preventing any buildup of harmful voltages. The earth
#$ie"ding
See the subsections Grounding of power conductor shields
under Equipment grounding and Grounding of instrumen-
tation shields under Grounding of computer systems.
+IGH*NING,RO*'C*IONGROUNDING
(ground) may be a path allowing the charges to neutralize. Thus,
many times earthing is looked on as the remedy for static. There
are various methods to generating the neces- sary path.
Earthing and bonding are the rst line of defense. Natu- rally, if
the insulating medium is between the charge area and earth, the
connection to earth of the charged area will allow recombining of
the charges. Otherwise, installation of a
Adequate earthing is the key to lightning protection, as the bonding conductor between the charged area and the charge-
earthing electrodes must conduct (some would say dissi- decient area will allow recombining of the charges.
pate) currents as high as 300,000 A in 1 to 1,000 s. The An example is a rubber-lined pipe, connected to a metallic
lightning path begins with the air terminal. Several differ- pipe, connected to a glass section, connected to another metal-
ently designed air terminals are manufactured. One designlic pipe owing into a glass lined tank. Both metallic pipe
has multiple spikes closely spaced, mounted on an umbrella sections are insulated from earth. With sufcient ow of a
or shaped like barbed wire. material that was capable of carrying charges, charges can be
The air terminal is connected to down conductors. The high wiped from the rst metallic pipe section and deposited on
frequency of the lightning stroke forces the current to ow on the second.
the outside of the down conductor. Thus a braided, hollow There are two solutions. One would be just to connect
copper conductor should be considered. Because the lightning (bond) the two metallic sections together. This would allow
stroke will not make sharp turns, but tends to ow in a the charges to recombine. The other solution would be to con-
straight path, all bends must be made with a sweeping turn. nect both the rst and the second metallic section to earth.
If the structure has electrically continuous paths from the The return path would use the earth. This solution would also
top to the bottom and is effectively connected to the earth eliminate any touch-potential problems.
through the reinforcing bars, the steel columns can serve as Moisture is another solution to static problems. Moisture-
the down conductor. When the steel columns are less than laden air will conduct charges. If the air is in contact with
7.62 m (25 ft) apart they form a Faraday cage. A lightning both charged areas, the charges can return through it. Many
strike to the steel will travel down the perimeter of the build- times steam is injected into the air to provide moisture. Ex-
ing steel. The columns inside the structure will be devoid of plosive-powder-producing plants rely on this method. [In ad-
current. dition, since man-made clothing (nylon, rayon, etc.), when
In order to reduce any potential between the air terminals rubbed, can generate static charges, such plants require all
and the earth, a multiplicity of earthing electrodes must be employees to wear cotton clothing or other natural materials.]
installed over a large area. It has been shown that earthing Static charges can build up on computer personnel walking
terminals 1.0 m (40 in.) deep are effective when a multitude across a oor while wearing nylon clothing. The soles of the
are installed over a large area. An earthing electrode should shoes insulate their bodies from the conductive oor. Suf-
not be placed next to the foundation, as it will then be only cient charges sometimes built up to jump to a mainframe
half as effective as one that is placed the depth of the rod computer, damaging the sensitive computer chips. When
away from the foundation. The soil next to the foundation is working on computers, the human body should be bonded to
GROUNDING4&7
the computer frame through a wrist-bonding strap. Conduc- not only by leading computer manufacturers, but also by the
tive oors and conductive shoes are other methods that can new class of engineers known as (electronic) instrumentation
be used to solve the problem. This method is especially useful engineers.
in computer rooms and in explosive-powder-producing factor- Because of the interconnection of neutral conductors and
ies. Ionizationthe generating of free-oating ionswill also other early wiring mistakes, uncontrolled current owed over
allow the recombining of charges. the computer circuits, resulting in damage to the computers.
Fast-moving belts will wipe charges from one rotating me- The popularity of isolated earth connections for computers
tallic roller to another. The charge can be collected by spirally grew. It became necessary, in order to meet the requirements
wound tinsel or wire set near the moving belt and connected of the computer companies and the instrumentation engi-
to earth. The earth conducts the charges back to the source neers, to run the computer grounding connection out to the
to be recombined. parking lots pink petunia bed and drive a rod for the com-
Any owing material, either dry or liquid, can generate puter earthing system. Common sense was lacking, though
static charges. The grain industries are particularly suscepti- all one had to do for a solution was look to the heavens, to
ble. For additional information see the NFPA standards.
GROUNDINGOCO(,U*'R#.#*'(#
Amajor problem is the earthing of sensitive electronic equip-
ment such as computers, process control equipment, program-
mable logic controllers (PLCs), instrumentation distributed
(process) control systems (DCSs), and similar sensitive elec-
tronic equipment. These items will be lumped together under
the term computers for ease of reference. The
proper installa-
tion of earthing is critical in order to achieve satisfactory op-
eration of such sensitive electronic equipment. The low volt-
the circling satellites with several computers on board. If it were
really necessary, for the operation of a computer, to be connected
to earth through a rod in the parking lot, the use of computers in
satellites would be difcult indeed.
The science of computer earthing has progressed to where the
majority of the misconceptions have been dispelled. Cor- rect
principles are now in place and are being used. First and
foremost is the principle that there must be only one connec- tion
to earth and that connection is by way of the electrical power
systems equipment ground conductor.
*ypeso/Co!puterGrounding#yste!s
ages that computers operate at makes them extremely Because of the various earthing functions thought necessary
sensitive to interference from other low voltages, voltages for computers, several types of computer earthing systems
that are not perceptible to humans. Such voltages do not af- came into being. Personnel safety required the frame of the
fect electrical power equipment. Thus, when computers came computer equipment to be connected to the electrical system
on the scene, new techniques had to be developed, new logic equipment grounding conductor. This grounding connection
applied, and new methods used to connect these sensitive became known as the safety ground bus. It was also called,
electronic pieces of equipment effectively to earth. naturally, the equipment ground bus. This was normally the green wire
emanating from the electrical power system
Historyo/Co!puterGrounding
It was unfortunate that the electronic technicians, who be- came
the leaders in this new eld of computers, were mostly not
schooled either in power distribution grounding or in ra- dio and
antenna construction techniques. One electronic computer
leader of a large project to automate the manufac- turing of
explosive blasting caps insisted on using 120 V to power a 50-hp
motor because 120 V was safer than higher voltages. (Even 120 V
can harm humans; see the section Per- sonnel safety protection.)
Exemplifying the maxim that a lit- tle learning is a dangerous
thing, there were many who knew the neutral was connected to
earth. Therefore, when a connec- tion to earth was needed in a
computer circuit, the neutral was employed and was usually
connected to the metal cabinet of the device under construction,
especially where no equip- ment ground conductor was present.
Isolation of the electrical conduit from the computer equipment
frame became preva- lent. Plastic couplings were required to be
installed in the power-supply conduit to the computer to isolate
the computer frame from the building electrical equipment
ground system. Yet, the computer water piping was connected to
the com- puter by persons who were not aware of the fact that the
me- tallic water piping was connected to the system neutral, the
equipment ground system, and earth also. To add to this, there
were those who viewed the earth as a collection of insu-
earthing connection.
The shield wires from the remote instrumentation signals needed
to be connected to earth. All the signal shields were gathered
together, and at one time they were connected to a separate,
isolated earth connection. The connection became known as the
signal ground.
The computer had its own power supplies. These ac and dc power
supplies needed to have one side connected to earth. Since the
object was to keep voltage excursions to a minimum, it would
have been sufcient to connect one side of the power supply to the
equipment metallic enclosure. Nevertheless, a separate isolated
earth connection was provided for the dc power supply reference
ground bus.
For each application where an earth connection was re- quired,
an isolated earth connection was listed as needed. There were
many different names for these connections to earth, such as
computer reference ground, earth common, dc master ground
point, ac safety ground, dc signal common, dc ground bus, and
power supply common ground point or bus. There were no
standards for computer grounding systems, and each computer
company had its own terminology. There were usually at least
three separate ground buses in each computer system.
Co!puterGrounding(et$ods
lated sponges that were capable of absorbing electrons. All In a properly designed system, there is only one connection to
of these misconceptions led to mass confusion and erroneous earth and that connection is by way of the electrical power
grounding methods that were applied to computer grounding, systems equipment ground conductor. How the various ear-
4&8GROUNDING
Centra"Radia"Grounding#yste!s% The computer parts that
%ignal "ro& need to be connected to earth can be connected in a radial or
re&ote location star type earthing connection. Again, this type of connection
-ain %ignal 1 -ode& 2nst9 achieves a single-point connection to earth. The main object is to
prevent the computer grounding conductor from carrying
co&(uter 1
%ignal conductors
%ignal conductors
continuous current. The exception to this is the equipment
ground conductor, as it is connected unintentionally at
many
places through the equipment sitting on earth.
%ignal conductors
%ignal 2-ain
co&(uter 2
-ode&
Building earth connection
%ingle!(oint connection to earth
Figure13. Single-point computer earthing.
r b
u
i
l
d
i
n
g
a
n
d
w
i
l
l
e
l
i
m
i
n
a
t
e
i
n
t
e
r
f
e
r
e
n
c
e
f
r
o
m
a
d
j
a
c
e
n
t
c
u
r
rent carrying conductors. Fiber optic cables are offered with a ground
conductor or shield and/or current-carrying conductors. Remember
that a shield can carry unwanted and interfering current from one
place to another.
Instrumentation cable should have a shield, consisting of ei- ther
solid metal foil or expanded braided wire, over the signal conductors to eliminate
interference from being inducted into the signal carrying conductors. To be effective
the shield must be grounded. The best method of connecting the shields to
#ing"e5,ointGrounding#yste!s% It is necessary to keep earth depends on the voltage difference at the ends, the fre-
stray uncontrolled current from entering the computer sys- quency of the interference signal, and the need to protect
tem, its signal conductors, its power supplies, etc. (See the against lightning and large current ows.
subsection Uncontrolled ow of current over the earth un- If one can be assured that the only interference will be
der Personnel safety protection.) The method used to accom- from either low frequency or high frequency, then a single
plish the control of stray currents is to connect the computer shield will be adequate. However, if frequencies below 1 MHz
ground buses to the equipment ground system at only one and also above 1 MHz are to be encountered, then a single
point. It is desirable to keep the grounding systems of differ- shield will be insufcient. For interference below 1 MHz the
ent computers isolated from each other except at one point shield needs to be grounded at one end only, to prevent circu-
where they are connected together. (See Fig. 13.) lating currents from inducing interference. Above 1 MHz, the
Remote computer locations pose a problem. When the com- shield needs to be grounded, not only at both ends, but per-
munication cables extend beyond the computer room and re- haps even at points in between, in order to attenuate the
mote inputs exist, voltage potentials can develop if the remote high-frequency interference.
locations are earthed locally. This is especially true when The earthing leads need to be short, as they develop im-
thunderclouds are in the vicinity. See Figure 14. pedance proportional to their length as well as to the fre-
777777 777 7 7
1 1
1 1;))) +
1 1 111
/e&ote
location
2nst9
Co&(uter 'uilding /e&ote
location
earthed
%ignal conductors
%ignal conductors
-ain %ignal 2
co&(uter 2
No &ode& installed1direct connection Building ground
1;))) + induced "ro& charged
Figure14. Dangerous and damaging potentials. cloud o$erhead
GROUNDING4&&
quency of the interference. A lead longer than of the wave- the amount of insulation that can be installed. Internal faults
length can produce a resonating circuit. As the wave travels to the generator ground can result in extremely high current
down the conductor, if the length is the same as the wave- ow that can damage the laminations. Generators are often
length and the peak is reected back, a new pulse will occur operated in parallel, producing additional problems.
at the same time, effectively doubling the pulse. Peaks will Depending on the voltage, generators should be grounded
occur at -wavelength intervals. Since the speed of an electro- by one of the methods already discussed. For additional infor-
magnetic wave in a vacuum is about 300,000 km (186,000 mation on industrial generation grounding see Ref. 3, and for
miles) per second, the wavelength in meters is 300 divided by utility generators see the IEEE Power Engineering Society
the frequency in megahertz. Standards.
Example. A10 MHz pulse in a conductor will travel ap-
proximately 30 m (98 ft) in free space during one cycle (0.1
s). In a conductor, the speed is lower. The pulse might travel *'#*ING*H'GROUNDINGAND0ONDING#.#*'(#
26.82 m (88 ft) in 0.1 s. The peak will occur wavelength, or
6.7 m (22 ft). Thus, the connection cannot be longer than 6.7 mif
the voltage is to be equalized between the ends.
If current were to ow over the inner shield, the current
Finding neutral-to-ground faults is difcult and can be time-
consuming. Determining that they exist is very easy. A pre-
liminary test involves placing a clamp-on ammeter on the
could induce unwanted voltages into the signal conductors. In conductor between the transformers neutral
X
0
connection
order to eliminate this possibility, the shield is connected to earth
at only one end, usually at the control end. (The excep- tion is
thermocouples, where the shield is connected at the
thermocouple.) If the shield were connected at both ends, ca-
pacitive current could ow over the shield.
Before the advent of cable-tray installations, instrumenta- tion
cables were installed within rigid ferrous-metal conduit. This
overall shield was connected to ground at support points,
approximately every 3 m. It acted as an outer shield and, be- ing
grounded at multiple points, attenuated high-frequency
interference and the large magnetic elds from nearby light- ning
strikes.
The advent of cable tray eliminated the rigid conduit and the
protection it afforded against high-frequency interference and
lightning strikes. Computer-controlled instrumentation has
inputs of 3 V to 5 V today. At this low voltage, interfer- ence is
easily injected into the instrumentation control cables. Anearby
lightning strike can induce sufcient voltage to de- stroy the
sensitive control circuits and equipment. Instrumentation cables
are manufactured with an inner shield over the signal
conductors, and sometimes also with an overall outer shield.
However, this overall shield lacks suf- cient ferrous cross section
to overcome the effects of large cur- rent ows through the earth
or air or of strong magnetic elds; also, it usually has insufcient
current-carrying capac- ity. Therefore, for maximum protection
against interference from large current ow through the earth,
the magnetic elds associated with lightning, and other strong
electric and mag- netic elds from adjacent current-carrying
conductors, all sensitive electronic circuits extending outside the
control room should be installed within ferrous conduit or ber
optic
and the earth connection (see Fig. 2, terminals T and TG). Any
current ow will indicate neutral-to-ground faults exist. To verify
that there are such faults, the power to the panel is disconnected
or the circuit breakers are all opened (turned off). The incoming
neutral conductor is lifted from the panel terminals. One lead of
an ohmmeter is placed on the neutral bus bar, and the other lead
is placed on earth or ground. The reading should be innity. If
the reading of the resistance is zero, there are solid connections
from neutral to ground.
The neutral-to-ground faults can be isolated by lifting all the
neutral connections from the neutral bus bar and replac- ing
them one at a time, checking the resistance each time a conductor
is replaced.
Bonding and grounding connections can be tested using
the direct method; see the subsection Measuring ground
re-
sistance under Electrical properties of the earth.
For a description of Ground-fault detectors see the White Book
(7).
0I0+IOGRA,H.
1. IEEE standard dictionary of electrical and electronic terms,6th
ed., ANSI/IEEE Std. 100, New York: IEEE, 1997.
". IEEE guide for safety in substation grounding, ANSI/IEEE Std.
80.
#. IEEE recommended practice for groundingof industrial and
com- mercial power systems, ANSI/IEEE Std. 142.
%. F. J. Shields, System grounding for low-voltage power systems,
12345GET-3548B, 12-76. General Electric Company, Industrial Power Systems
Engineering Operations, Schenectady, NY.
cable. In particular, ferrous conduit should be used under- 5. R. H. Lee, The other electrical hazard: Electric arc blast burns,
ground, as PVC conduit offers no protection against mag- netic
interference.
G'N'RA*ORGROUNDING
Generators have characteristics considerably different from other
electrical devices, such as transformers and other sources of
power. The construction of a generator lacks the ability to
withstand the mechanical effects of short-circuit currents, as well
as heating effects. The reactances of the gen- erator are not equal,
as a transformers are. A generator can develop third-harmonic
voltages. Space limitations restrict
IEEE Trans. Ind. Appl., IA-18:246251, 1982.
'. M. Capelli-Schellpfeffer and R. C. Lee, Advances in the evalua-
tion and treatment of electrical and thermal injury emergencies,
IEEE Trans. Ind. Appl., 31:11471152, 1995.
*. IEEE recommended practice for electric systems in health care
facilities, ANSI/IEEE Std. 602.
+. B. Bridger, Jr., High resistance grounding, IEEE Trans.
Ind.
Appl.19:1521, 1983.
9. AIEE Committee Report, Application of ground fault neutraliz-
ers, Electrical Eng., 72:606, July 1953.
1,. E. J. Fagan and R. H. Lee, The use of concrete enclosed
reinforc-
ing rods as grounding electrodes, IEEE Trans. Ind. Appl., IGA-6:
337348, 1970.
;--GROU,CO((UNICA*ION
11. T. Lindsey, Grounding/Earthing electrode studies, 1 of 2,
IAEI/ SNC Grounding Committee, Clark County Building Department,
Las Vegas, NV 89101, May 1997.
1". R. B. West, Impedance testing equipment grounding conductors,
IEEE Trans. Ind. Appl., IA-25:124136, 1981.
1#. Lightning protection code, ANSINFPA Std. 780.
ReadingList
American National Standard for electrical power systems and equip-
mentvoltage ratings (60 Hz), ANSI C84.1, 1984.
National Fire Protection Associations National Electrical Code,
ANSI/NFPA 70, 1996.
National Fire Protection Associations Lightning Protection Code,
ANSI/NFPA 780, 1998.
Canadian Electrical Code Part I, Canadian Standards Association,
Rexdale, Ontario, Canada M9W 1R3, 1997.
Grounding for process control computers and distributed control sys-
tems: The National Electrical Code and present grounding prac-
tices, IEEE Trans. Ind. Appl., IA-23 (3): 417423, 1987.
Guideline on electrical power for ADP (Automatic Data Processing)
installations, Federal Information Processing Standards Publica-
tion 94 (FIPS 94), National Technical Information Service, 1983.
Recommended practice for powering and grounding sensitive elec-
tronic equipment (Emerald Books), IEEE Std 1100, 1992.
). R. Kaufmann, Some fundamentals of equipment grounding circuit
design, IEEE Trans. Ind. Gen. Appl., IGA73:part 2, November
1954.
-. H. Lee, Grounding of computers and other sensitive equipment,
IEEE Trans. Ind. Appl., IA-23:408411, 1987.
-. B. West, Grounding for emergency and standby power systems,
IEEE Trans. Ind. Appl., IA-15:124136, 1979.
-. B. West, Equipment grounding for reliable ground-fault protection
in electrical systems below 600 V, IEEE Trans. Ind. Appl., IA-10:
175189, 1974.
.. W. Zipse, Multiple neutral to ground connections, in IEEE 1972
I&CPS Technical Conference, 72CH0600-7-1A, pp. 6064.
D.W. Zipse,Lightning protectionsystems: Advantagesand disadvan-
tages, IEEE Trans. Ind. Appl., IA-30:13511361, 1994.
DONALD W. ZIPSE
Zipse Electrical Engineering, Inc.