PowerSuite Generator

This document provides a recommended generator configuration for a boring machine project requiring 3 generators running in parallel. It specifies the project requirements including frequency, voltage, phase, fuel type and emissions standards. It then calculates the individual and total system load requirements and recommends a specific generator set configuration including alternator, engine, and other components to meet the running and peak load requirements within specified voltage and frequency dips. It confirms the recommended configuration meets the project needs while operating at 73.6% rated capacity.

Uploaded by

Kunik Swaroop
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
156 views

PowerSuite Generator

This document provides a recommended generator configuration for a boring machine project requiring 3 generators running in parallel. It specifies the project requirements including frequency, voltage, phase, fuel type and emissions standards. It then calculates the individual and total system load requirements and recommends a specific generator set configuration including alternator, engine, and other components to meet the running and peak load requirements within specified voltage and frequency dips. It confirms the recommended configuration meets the project needs while operating at 73.6% rated capacity.

Uploaded by

Kunik Swaroop
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Recommended Generator Report 09-Jun-2014 Page 1

Recommended Generator Report - 2250DQKAG


Project - BORING MACHINE
Comments - TBM
Project Requirements
Frequency, Hz : 50.0 Generators Running in Parallel : 3
Duty : Prime Site Altitude, ft(m) : 361(152)
Voltage : 230/400, Series Wye Site Temperature, C : 50
Phase : 3 Max. Altr Temp Rise, C : 125
Fuel : Diesel Project Voltage Distortion Limit, % : 10
Emissions : No Preference
Calculated Individual Generator Set Load Running and Peak Requirements
Running kW : 902.3 Max. Step kW : 75.2 In Step 1 Cumulative Step kW : 902.2
Running kVA : 1002.5 Max. Step kVA : 83.5 In Step 1 Cumulative Step kVA : 1002.5
Running PF : 0.9 Peak kW : None Cumulative Peak kW : None
Running NLL kVA : 1002.5 Peak kVA : None Cumulative Peak kVA : None
Alternator kW : 0.0 Pct Rated Capacity : 73.6
Total System Running Load and Step Load Requirements
Running kW : 2706.9 Max. Step kW : 225.6 Running NLL kVA : 3007.5
Running kVA : 3007.5 Max. Step kVA : 250.5
Generator Set Configuration
Alternator : LVSI804T Engine : QSK60-G11 NR2
BCode : BA27 Fuel : Diesel
Excitation : PMG Displacement, cu in. (Litre) : 3673(60)
Voltage Range : 380-440 Cylinders : 16
Number of Leads : 6 Altitude Knee, ft(m) : 1640(500)
Reconnectable : No Altitude Slope, % per 3281ft(1000.0m) : 12
Full Single Phase Output : No Temperature Knee, F(C) : 104(40)
Increased Motor Starting : No Temperature Slope, % per 10F(5.56C) : 13
Extended Stack : No Emissions : EPA Tier 2
Cooling Package :
Set Performance Load Requirements
Running At : 73.6% Rated Capacity
Max. Step Voltage Dip, % : 1 Max. Allowed Step Voltage Dip : 15 In Step 1
Max. Step Frequency Dip, % : 1 Max. Allowed Step Frequency Dip : 10 In Step 1
Peak Voltage Dip, % : Peak Voltage Dip Limit % : 15.0
Peak Frequency Dip, % : Peak Frequency Dip Limit % : 10
Site Rated Prime kW/kVA : 1226 / 1532 Running kW : 902.3
Running kW : 1002.5
Site Rated Max. SkW : 1405 Effective Step kW : 841.3
Max. SkVA : 7354 Effective Step kVA : 1002.5
Temp Rise at Full Load, C : 80 Percent Non-Linear Load : 100.0
Voltage Distortion : 9.2 Voltage Distortion Limit : 10
Site Rated Max Step kW Limit : Max Step kW :
*Note: Higher temperature rise at full rated load.
*Note: All generator set power derates are based on open generator sets.