PLC Advanced Function Siemens PDF

This manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger. The device / system may only be set up and operated in conjunction with this manual. Only qualified personnel should be allowed to install and work on this equipment.

Uploaded by

Alaa Ramadan
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
546 views

PLC Advanced Function Siemens PDF

This manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger. The device / system may only be set up and operated in conjunction with this manual. Only qualified personnel should be allowed to install and work on this equipment.

Uploaded by

Alaa Ramadan
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 114

Preface, Contents

Bit Logic Functions


1
Table Functions
2
Shift Functions
3
Move Function and Function
Block
4
Timer Functions and Function
Blocks
5
Convert Functions and Function
Blocks
6
Floating Point Math Function
7
Compare Function Blocks
8
Glossary, Index
C79000-G7076-C113-02
Standard Software for S7-300
and S7-400
Standard Functions Part 2
User Manual
SIMATIC
ii
S7 Standard Functions Part 2
C79000 G7076 C113 02
This manual contains notices which you should observe to ensure your own personal safety, as well as to
protect the product and connected equipment. These notices are highlighted in the manual by a warning
triangle and are marked as follows according to the level of danger:
!
Danger
indicates that death, severe personal injury or substantial property damage will result if proper precautions are
not taken.
!
Warning
indicates that death, severe personal injury or substantial property damage can result if proper precautions are
not taken.
!
Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken.
Note
draws your attention to particularly important information on the product, handling the product, or to a particular
part of the documentation.
The device/system may only be set up and operated in conjunction with this manual.
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are
defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and sys-
tems in accordance with established safety practices and standards.
Note the following:
!
Warning
This device and its components may only be used for the applications described in the catalog or the technical
description, and only in connection with devices or components from other manufacturers which have been
approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and
operated and maintained as recommended.
SIMATICR and SINECR are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer to
trademarks might infringe upon the rights of the trademark owners.
We have checked the contents of this manual for agreement with the
hardware and software described. Since deviations cannot be precluded
entirely, we cannot guarantee full agreement. However, the data in this
manual are reviewed regularly and any necessary corrections included in
subsequent editions. Suggestions for improvement are welcomed.
E Siemens AG 1995
Technical data subject to change.
Disclaimer of Liability Copyright E Siemens AG 1995 All rights reserved
The reproduction, transmission or use of this document or its contents is
not permitted without express written authority. Offenders will be liable for
damages. All rights, including rights created by patent grant or registration
of a utility model or design, are reserved.
Siemens AG
Automation Group
Industrial Automation Systems
Postfach 4848, D-90327 Nrnberg
Siemens Aktiengesellschaft Order No. C79000-G7076-C113
Safety Guidelines
Qualified Personnel
Correct Usage
Trademarks
iii
S7 Standard Functions Part 2
C79000-G7076-C113-02
Preface
This manual provides descriptions and examples of S7 functions FCs and
function blocks FBs in ladder logic (LAD) representation. These FCs and
FBs are available to program your S7-300/S7-400 programmable logic
controller (PLC). This manual is intended as a reference to provide the
necessary information for each function.
The FCs and FBs described in this manual are located in the library named
Tilib, under the component FBLIB2. Using your STEP 7 file manager, you
can copy the FCs and FBs you need to your destination program directory.
First make certain that your program does not contain any FCs or FBs with
the same number as the ones you want to copy from FBLIB2. If you have
FCs or FBs with matching numbers, you must renumber either your program
FCs or FBs, or the one(s) you want to copy to your program.
This manual is intended for engineers, programmers, and maintenance
personnel who have a general knowledge of programmable logic controllers.
This manual groups the FCs and FBs into the following functional areas:
S Bit logic functions (Chapter 1)
S Table functions (Chapter 2)
S Shift functions (Chapter 3)
S Move functions and function blocks (Chapter 4)
S Timer functions and function blocks (Chapter 5)
S Convert functions and function blocks (Chapter 6)
S Floating Point Math functions (Chapter 7)
S Compare function blocks (Chapter 8)
S The glossary provides an alphabetical listing of definitions of key terms
and expressions that are applicable to ladder logic programming.
Purpose
Where to Find
the S7 Functions
Audience
How to Use This
Manual
iv
S7 Standard Functions Part 2
C79000-G7076-C113-02
Each chapter describes FCs and FBs that you can add to your standard set of
instructions to provide additional programming flexibility. Each FC or FB is
listed with the full name, the abbreviation, and the FC or FB number. Each
FC or FB is described according to the following topics:
S Description a basic functional description.
S Parameters a table giving the declaration, data type, valid memory
areas, and the description for each parameter.
S Error Information errors that would prevent the FC or FB from being
executed successfully.
S Example a figure consisting of a graphic representation of the FC or
FB with example parameters and the results of the execution.
This manual is a part of the STEP 7 documentation package that consists of
the manuals listed in the following table.
Title Content
S7-300 Programmable
Controller
Quick Start
Primer
The Primer offers a basic introduction to the methodology of the structure and
programming of an S7-300/S7-400. It is especially suited to first-time users of an S7
programmable control system.
S7-300 and S7-400
Program Design
Programming Manual
The S7-300/S7-400 Program Design Programming Manual provides basic information
on the structure of the operating system and of a user program of an S7 CPU. The
first-time user of an S7-300 or S7-400 should use this manual to acquire an overview of
the programming methodology and to use it to base their user program design on.
S7-300 and S7-400
System and Standard
Functions
Reference Manual
The S7 CPUs have integrated system functions and organization blocks included with
their operating system, which you can use when programming. The manual provides
you with an overview of the system functions, organization blocks, and loadable
standard functions available in S7, and in the form of reference information detailed
interface descriptions for their use in your user program.
STEP 7
User Manual
The STEP 7 User Manual explains the main usage and the functions of the STEP 7
automation software. As a first-time user of STEP 7 and as an experienced user of
STEP 5, this manual will provide you with an overview of the procedures used to
configure, program, and start up an S7-300/S7-400.
While you are working with the software you can access a range of on-line help topics
which offer detailed support on using the software.
Converting STEP 5
Programs
Manual
You will need the Converting STEP 5 Programs Manual if you want to convert existing
STEP 5 programs to run them on S7 CPUs. The manual provides an overview of the
procedures and usage of the Converter; you can find a detailed description of the
converter functions in the on-line help. You will also find the interface descriptions for
the converted S7 functions available in the on-line help.
Overview of the
STEP 7
Documentation Set
Preface
v
S7 Standard Functions Part 2
C79000-G7076-C113-02
Title Content
Statement List, Ladder
Logic, SCL
1
Manuals
The manuals for the programming language packages Statement List, Ladder Logic,
and SCL (Sequential Control Language) contain both the users guide and the reference
description of the programming language or representation type. You only require one
language type for programming an S7-300/S7-400, but you can mix the languages
within a project, if required. If you are using a language for the first time, it is
recommended that you use the manual to learn about the methodology of creating a
program in the chosen language first.
While you are working with the software you can access a range of on-line help topics
which offer detailed support on using the respective editors/compilers.
GRAPH
1
, HiGraph
1
,
CFC
1
Manuals
The languages GRAPH, HiGraph, and CFC (Continuous Function Chart) offer
additional methods of programming blocks in the form of sequential controls, state
graphs, or charts. The manuals contain both the users guide and the reference
description of the programming language. If you are using a language for the first time,
it is recommended that you use the manual to learn about the methodology of creating a
program in the chosen language first.
While you are working with the software you can access a range of on-line help topics
which offer detailed support on using the respective editors/compilers (with the
exception of HiGraph).
1 Optional package for system software for S7-300/S7-400
The various S7-300 and S7-400 CPUs, the S7-300 and S7-400 modules, and
the instructions of the CPU are described in the following manuals:
S For the S7-300 programmable logic controller, refer to the manuals:
Hardware and Installation (CPU Data, Module Data) and the Instruction
List.
S For the S7-400 programmable logic controller, refer to the manuals:
Hardware and Installation (CPU Data, Module Data) and the Instruction
List.
You can find additional information in the on-line help.
If you have any questions not answered in this or one of the other STEP 7
manuals, if you need information on ordering additional documentation or
equipment, or if you need information on training, please contact your
Siemens distributor or sales office.
Other Manuals
Additional
Assistance
Preface
vi
S7 Standard Functions Part 2
C79000-G7076-C113-02
The following functions and function blocks are described in this manual:
Function or Function Block Number Page
Software Timer On DelayRetentive (TONR) FC80 5-2
Indirect Block Move (IBLKMOV) FC81 4-2
Reset Range of Outputs (RSET) FC82 1-2
Set Range of Outputs (SET) FC83 1-6
Add to Table (ATT) FC84 2-2
First In/First Out Unload Table (FIFO) FC85 2-4
Table Find (TBL_FIND) FC86 2-6
Last In/First Out Unload Table (LIFO) FC87 2-9
Table (TBL) FC88 2-11
Move Table to Word (TBL_WRD) FC89 2-13
Word Shift Register (WSR) FC90 3-2
Word to Table (WRD_TBL) FC91 2-15
Bit Shift Register (SHRB) FC92 3-4
Seven Segment Decoder (SEG) FC93 6-2
ASCII to Hex (ATH) FC94 6-4
Hex to ASCII (HTA) FC95 6-6
Encode Binary Position (ENCO) FC96 6-8
Decode Binary Position (DECO) FC97 6-9
Tens Complement (BCDCPL) FC98 6-10
Sum Number of Bits (BITSUM) FC99 6-11
Reset Range of Immediate Outputs (RSETI) FC100 1-4
Set Range of Immediate Outputs (SETI) FC101 1-8
Standard Deviation (DEV) FC102 7-2
Correlated Data Table (CDT) FC103 2-18
Table to Table (TBL_TBL) FC104 2-21
Scaling Values (SCALE) FC105 6-12
Unscaling Values (UNSCALE) FC106 6-14
Lead/Lag Algorithm (LEAD_LAG) FB80 6-16
Discrete Control Alarm Timer (DCAT) FB81 5-4
Motor Control Alarm Timer (MCAT) FB82 5-7
Index Matrix Compare (IMC) FB83 8-2
Scan Matrix Compare (SMC) FB84 8-6
Event Maskable Drum (DRUM) FB85 5-10
Pack Data (PACK) FB86 4-4
List of Functions
and Function
Blocks
Preface
vii
S7 Standard Functions Part 2
C79000-G7076-C113-02
Contents
1 Bit Logic Functions
1.1 Reset Range of Outputs (RSET): FC82 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 1-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Reset Range of Immediate Outputs (RSETI): FC100 1-4 . . . . . . . . . . . . . . . . .
Description 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 1-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Set Range of Outputs (SET): FC83 1-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 1-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 1-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 1-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Set Range of Immediate Outputs (SETI): FC101 1-8 . . . . . . . . . . . . . . . . . . . .
Description 1-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 1-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 1-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Table Functions
2.1 Add to Table (ATT): FC84 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 First In/First Out Unload Table (FIFO): FC85 2-4 . . . . . . . . . . . . . . . . . . . . . . .
Description 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Table Find (TBL_FIND): FC86 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
viii
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.4 Last In/First Out Unload Table (LIFO): FC87 2-9 . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 Table (TBL): FC88 2-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 Move Table to Word (TBL_WRD): FC89 2-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.7 Word to Table (WRD_TBL): FC91 2-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8 Correlated Data Table (CDT): FC103 2-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.9 Table To Table (TBL_TBL): FC104 2-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 2-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 2-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Shift Functions
3.1 Word Shift Register (WSR): FC90 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Bit Shift Register (SHRB): FC92 3-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 3-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 3-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 3-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 3-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
ix
S7 Standard Functions Part 2
C79000-G7076-C113-02
4 Move Function and Function Block
4.1 Indirect Block Move (IBLKMOV): FC81 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 4-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 4-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Pack Data (PACK): FB86 4-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 4-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Timer Function and Function Blocks
5.1 Software Timer On DelayRetentive (TONR): FC80 5-2 . . . . . . . . . . . . . . . . .
Description 5-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 5-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 5-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 5-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Discrete Control Alarm Timer (DCAT): FB81 5-4 . . . . . . . . . . . . . . . . . . . . . . . .
Description 5-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 5-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 5-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 5-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Motor Control Alarm Timer (MCAT): FB82 5-7 . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 5-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 5-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 5-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 5-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Event Maskable Drum (DRUM): FB85 5-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 5-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 5-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 5-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 5-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Convert Functions and Function Block
6.1 Seven Segment Decoder (SEG): FC93 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 ASCII to Hex (ATH): FC94 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
x
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.3 Hex to ASCII (HTA): FC95 6-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Encode Binary Position (ENCO): FC96 6-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Decode Binary Position (DECO): FC97 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 Tens Complement (BCDCPL): FC98 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Sum Number of Bits (BITSUM): FC99 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.8 Scaling Values (SCALE): FC105 6-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.9 Unscaling Values (UNSCALE): FC106 6-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.10 Lead/Lag Algorithm (LEAD_LAG): FB80 6-16 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 6-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 6-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 6-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
xi
S7 Standard Functions Part 2
C79000-G7076-C113-02
7 Floating Point Math Function
7.1 Standard Deviation (DEV): FC102 7-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 7-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 7-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 7-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 7-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Compare Function Blocks
8.1 Index Matrix Compare (IMC): FB83 8-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 8-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 8-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 8-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 8-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 Scan Matrix Compare (SMC): FB84 8-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 8-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters 8-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Information 8-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 8-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary
Index
Contents
xii
S7 Standard Functions Part 2
C79000-G7076-C113-02
Figures
1-1 Reset Range of Outputs (RSET) 1-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Reset Range of Immediate Outputs (RSETI) 1-5 . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Set Range of Outputs (SET) 1-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Set Range of Immediate Outputs (SETI) 1-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1 Add to Table (ATT) 2-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 First In/First Out Unload Table (FIFO) 2-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Table Find (TBL_FIND) 2-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Last In/First Out Unload Table (LIFO) 2-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Table (TBL) 2-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Move Table to Word (TBL_WRD) 2-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7 Word To Table (WRD_TBL) 2-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8 Correlated Data Table (CDT) 2-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-9 Table To Table (TBL_TBL) 2-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Word Shift Register (WSR) 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Bit Shift Register (SHRB) 3-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Indirect Block Move (IBLKMOV) 4-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 PACK DATA (PACK) 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 Timer On DelayRetentive (TONR) 5-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Discrete Control Alarm Timer (DCAT) 5-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Motor Control Alarm Timer (MCAT) 5-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Event Maskable Drum (DRUM) 5-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Event Maskable Drum (DRUM) (continued) 5-14 . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Seven Segment Output Bit Patterns 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Seven Segment Decoder (SEG) 6-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 ASCII to Hex (ATH) 6-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 ASCII Characters and Equivalent Hexadecimal Values 6-5 . . . . . . . . . . . . . . .
6-5 Hex to ASCII (HTA) 6-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-6 Hexadecimal Digits and Equivalent ASCII Hex Values 6-7 . . . . . . . . . . . . . . . .
6-7 Encode Binary Position (ENCO) 6-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8 Decode Binary Position (DECO) 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-9 Tens Complement (BCDCPL) 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-10 Sum Number of Bits (BITSUM) 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-11 Scaling Values (SCALE) 6-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-12 Unscaling Values (UNSCALE) 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-13 LEAD/LAG Algorithm (LEAD_LAG) 6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1 Standard Deviation (DEV) 7-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1 Index Matrix Compare (IMC) 8-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Scan Matrix Compare (SMC) 8-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
xiii
S7 Standard Functions Part 2
C79000-G7076-C113-02
Tables
1-1 Reset Range of Outputs (FC82) Parameters 1-2 . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Reset Range of Outputs (FC82) Parameters 1-2 . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Reset Range of Immediate Outputs (FC100) Parameters 1-4 . . . . . . . . . . . . .
1-3 Set Range of Outputs (FC83) Parameters 1-6 . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Set Range of Immediate Outputs (FC101) Parameters 1-8 . . . . . . . . . . . . . . .
2-1 Add to Table (FC84) Parameters 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 First In/First Out Unload Table (FC85) Parameters 2-4 . . . . . . . . . . . . . . . . . . .
2-3 Table Find (FC86) Parameters 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Error Conditions for FC86 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Last In/First Out Unload Table (FC87) Parameters 2-9 . . . . . . . . . . . . . . . . . . .
2-6 Table (FC88) Parameters 2-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7 Move Table to Word (FC89) Parameters 2-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8 Error Conditions for FC89 2-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-9 Word to Table (FC91) Parameters 2-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-10 Error Conditions for FC91 2-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-11 Correlated Data Table (FC103) Parameters 2-17 . . . . . . . . . . . . . . . . . . . . . . . . .
2-12 Error Conditions for FC103 2-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-13 Table To Table (FC104) Parameters 2-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-14 Error Conditions for FC104 2-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Word Shift Register (FC90) Parameters 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Bit Shift Register (FC92) Parameters 3-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Indirect Block Move (FC81) Parameters 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Pack Data (FB86) Parameters 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Error Conditions for FB86 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 Software Timer On DelayRetentive (FC80) Parameters 5-2 . . . . . . . . . . . . .
5-2 Discrete Control Alarm Timer (FB81) Parameters 5-5 . . . . . . . . . . . . . . . . . . . .
5-3 MCAT Truth Table 5-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Motor Control Alarm Timer (FB82) Parameters 5-8 . . . . . . . . . . . . . . . . . . . . . .
5-5 Event Maskable Drum (FB85) Parameters 5-11 . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Error Conditions for FB85 5-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Seven Segment Decoder (FC93) Parameters 6-2 . . . . . . . . . . . . . . . . . . . . . . .
6-2 ASCII to Hex (FC94) Parameters 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Hex to ASCII (FC95) Parameters 6-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Encode Binary Position (FC96) Parameters 6-8 . . . . . . . . . . . . . . . . . . . . . . . . .
6-5 Decode Binary Position (FC97) Parameters 6-9 . . . . . . . . . . . . . . . . . . . . . . . . .
6-6 Tens Complement (FC98) Parameters 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7 Sum Number of Bits (FC99) Parameters 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8 Scaling Values (FC105) Parameters 6-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-9 Unscaling Values (FC106) Parameters 6-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-10 Lead/Lag (FB80) Parameters 6-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1 Standard Deviation (FC102) Parameters 7-2 . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Error Conditions for FC102 7-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1 Index Matrix Compare (FB83) Parameters 8-3 . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Scan Matrix Compare (FB84) Parameters 8-6 . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
xiv
S7 Standard Functions Part 2
C79000-G7076-C113-02
Contents
1-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Bit Logic Functions
This chapter describes the bit logic functions (FCs) that you can add to your
standard set of instructions to provide additional programming flexibility.
Section Description Page
1.1 Reset Range of Outputs (RSET): FC82 1-2
1.2 Reset Range of Immediate Outputs (RSETI):
FC100
1-4
1.3 Set Range of Outputs (SET): FC83 1-6
1.4 Set Range of Immediate Outputs (SETI): FC101 1-8
1
1
1-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
1.1 Reset Range of Outputs (RSET): FC82
The Reset Range of Outputs (RSET) function resets the signal state of each
bit in a specified range to 0 if the MCR bit is 1. If the MCR bit is 0, the
signal state of each bit in the range remains unchanged. The number of bits
in the range to be reset is specified by N, and the starting point of the range is
pointed to by S_BIT.
Table 1-1 describes the Reset Range of Outputs (RSET) parameters.
Table 1-1 Reset Range of Outputs (FC82) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
S_BIT Input Pointer* I, Q, M, D Points to the first bit in the range
N Input INT I, Q, M, D, L, P
or constant
Number of bits in the range to be reset
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Bit Logic Functions
1
1-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the S_BIT pointer references the I/O external input and output memory
area (P memory), the signal state of each bit in the range remains unchanged
and the signal state of ENO is set to 0.
Figure 1-1 shows how the RSET instruction works. If the signal state of input
I 0.0 is 1 (activated) and the MCR bit is 1, the RSET function is executed. In
this example, S_BIT points to the first bit at location M0.0. The N parameter
specifies 10 bits to be reset. After the instruction is executed, the signal state
of each of the 10 bits in the range M0.0 through M1.1 is reset to 0.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
I 0.0 Q 4.0
RSET
FC82
EN ENO
S_BIT
N
P#M0.0
10
1
M0.0
Before execution:
1 1 1 1 1 1 1
1
M1.0
1 1 1 1 1 1 1
0
M0.0
After execution:
0 0 0 0 0 0 0
1
M1.0
1 1 1 1 1 0 0
M0.7
M1.7
M0.7
M1.7
Figure 1-1 Reset Range of Outputs (RSET)
Error Information
Example
Bit Logic Functions
1
1-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
1.2 Reset Range of Immediate Outputs (RSETI): FC100
The Reset Range of Immediate Outputs (RSETI) function resets the signal
state of a range of bytes to 0 if the MCR bit is 1. If the MCR bit is 0, the
signal state of each byte in the range remains unchanged. S_BYTE points to
the first byte in the range, and N specifies the size of the range. The size of
the range is expressed by specifying the number of bits in the range. For
example, to specify a range of 2 bytes, you would enter 16 (16 bits) for the
value of N.
Note
The value of N must be a multiple of eight (for example, 8, 16, 24, etc.).
The S_BYTE pointer must reference the external input and output memory
area (P memory). Since P memory is accessed as bytes, words, or double
words, the S_BYTE must reference an address that is byte-aligned, which
means that the bit number of the pointer must be 0.
Note
The signal state of the corresponding bits in the process-image output table
(Q memory) is also reset to 0.
Table 1-2 describes the Reset Range of Immediate Outputs (RSETI)
parameters.
Table 1-2 Reset Range of Immediate Outputs (FC100) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
S_BYTE Input Pointer* P Points to the first byte in the range
N Input INT I, Q, M, D, L, P
or constant
Size of the range of bytes to be reset to 0, specified
by the number of bits in multiples of 8, (for
example, 8, 16, etc.)
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Bit Logic Functions
1
1-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the following conditions occur, the signal state of each bit in the
range remains unchanged and the signal state of ENO is set to 0.
S The S_BYTE pointer references a memory area other than the I/O
external input and output memory area (P memory).
S The S_BYTE pointer references an address that is not byte-aligned.
S The value of N is not a multiple of eight.
Figure 1-2 shows how the RSETI instruction works. If the signal state of
input I 0.0 is 1 (activated) and the MCR bit is 1, the RSETI function is
executed. In this example, S_BYTE points to the first byte at location P2.0.
The N parameter specifies 16 bits (2 bytes) to be reset. After the instruction
is executed, the signal state of each bit in the range P2.0 through P3.7 is reset
to 0.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
I 0.0 Q 4.0
RSETI
FC100
EN ENO
S_BYTE
N
P#P2.0
16
1
P1.0
Before execution:
1 1 1 1 1 1 1
1
P2.0
1 1 1 1 1 1 1
1
P3.0
1 1 1 1 1 1 1
1
P4.0
1 1 1 1 1 1 1
After execution:
1
P1.0
1 1 1 1 1 1 1
0
P2.0
0 0 0 0 0 0 0
0
P3.0
0 0 0 0 0 0 0
1
P4.0
1 1 1 1 1 1 1
P1.7
P2.7
P3.7
P4.7
P1.7
P2.7
P3.7
P4.7
Figure 1-2 Reset Range of Immediate Outputs (RSETI)
Error Information
Example
Bit Logic Functions
1
1-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
1.3 Set Range of Outputs (SET): FC83
The Set Range of Outputs (SET) function sets the signal state of each bit in a
specified range to 1 if the MCR bit is 1. If the MCR bit is 0, the signal state
of each of the bits in the range remains unchanged. The number of bits in the
range to be set is specified by N, and the starting point of the range is pointed
to by S_BIT.
Table 1-3 describes the Set Range of Outputs (SET) parameters.
Table 1-3 Set Range of Outputs (FC83) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
S_BIT Input Pointer* I, Q, M, D Points to the first bit in the range
N Input INT I, Q, M, D, L, P
or constant
Number of bits in the range to be set
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Bit Logic Functions
1
1-7
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the S_BIT pointer references the I/O external input and output memory
area (P memory), the signal state of each bit in the range remains unchanged
and the signal state of ENO is set to 0.
Figure 1-3 shows how the SET instruction works. If the signal state of input
I 0.0 is 1 (activated) and the MCR bit is 1, the SET function is executed. In
this example, S_BIT points to the first bit at location M0.0. The N parameter
specifies 10 bits to be set. After the instruction is executed, the signal state of
each of the 10 bits in the range M0.0 through M1.1 is set to 1.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
I 0.0 Q 4.0
SET
FC83
EN ENO
S_BIT
N
P#M0.0
10
0
M0.0
Before execution:
0 0 0 0 0 0 0
0
M1.0
0 0 0 0 0 0 0
1
M0.0
After execution:
1
0 0 0 0 1 1 0
M1.0
0
1 1 1 1 1 1
M0.7
M1.7
M0.7
M1.7
Figure 1-3 Set Range of Outputs (SET)
Error Information
Example
Bit Logic Functions
1
1-8
S7 Standard Functions Part 2
C79000-G7076-C113-02
1.4 Set Range of Immediate Outputs (SETI): FC101
The Set Range of Immediate Outputs (SETI) function sets the signal state of
a range of bytes to 1 if the MCR bit is 1. If the MCR bit is 0, the signal state
of each byte in the range remains unchanged. S_BYTE points to the first byte
in the range, and N specifies the size of the range. The size of the range is
expressed by specifying the number of bits in the range. For example, to
specify a range of 2 bytes, you would enter 16 (16 bits) for the value of N.
Note
The value of N must be a multiple of eight (for example, 8, 16, 24, etc.).
The S_BYTE pointer must reference the external input and output memory
area (P memory). Since P memory is accessed as bytes, words, or double
words, the S_BYTE must reference an address that is byte-aligned, which
means that the bit number of the pointer must be 0.
Note
The signal state of the corresponding bits in the process-image output table
(Q memory) is also reset to 0.
Table 1-4 describes the Set Range of Immediate Outputs (SETI) parameters.
Table 1-4 Set Range of Immediate Outputs (FC101) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
S_BYTE Input Pointer* P Points to the first byte in the range
N Input INT I, Q, M, D, L, P
or constant
Size of the range of bytes to be set to 1, specified by
the number of bits in multiples of 8 (for example, 8,
16, etc.)
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Bit Logic Functions
1
1-9
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the following conditions occur, the signal state of each bit in the
range remains unchanged and the signal state of ENO is set to 0.
S The S_BYTE pointer references a memory area other than the I/O
external inputs and outputs (P) memory area.
S The S_BYTE pointer references an address that is not byte-aligned.
S The value of N is not a multiple of eight.
Figure 1-4 shows how the SETI instruction works. If the signal state of input
I 0.0 is 1 (activated) and the MCR bit is 1, the SETI function is executed. In
this example, S_BYTE points to the first byte at location P2.0. The N
parameter specifies 16 bits (2 bytes) to be set. After the instruction is
executed, the signal state of each bit in the range P2.0 through P3.7 is set
to 1.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
I 0.0 Q 4.0
SETI
FC101
EN ENO
S_BYTE
N
P#P2.0
16
P1.0
Before execution: After execution:
P2.0
P3.0
P4.0
1
P1.0
1 1 1 1 1 1 1
0
P2.0
0 0 0 0 0 0 0
0
P3.0
0 0 0 0 0 0 0
1
P4.0
1 1 1 1 1 1 1
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
P1.7
P2.7
P3.7
P4.7
P1.7
P2.7
P3.7
P4.7
Figure 1-4 Set Range of Immediate Outputs (SETI)
Error Information
Example
Bit Logic Functions
1
1-10
S7 Standard Functions Part 2
C79000-G7076-C113-02
Bit Logic Functions
2-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table Functions
This chapter describes the table functions (FCs) that you can add to your
standard set of instructions to provide additional programming flexibility.
Section Description Page
2.1 Add to Table (ATT): FC84 2-2
2.2 First In/First Out Unload Table (FIFO): FC85 2-4
2.3 Table Find (TBL_FIND): FC86 2-6
2.4 Last In/First Out Unload Table (LIFO): FC87 2-9
2.5 Table (TBL): FC88 2-11
2.6 Move Table to Word (TBL_WRD): FC89 2-13
2.7 Word to Table (WRD_TBL): FC91 2-15
2.8 Correlated Data Table (CDT): FC103 2-18
2.9 Table To Table (TBL_TBL): FC104 2-21
2
2
2-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.1 Add to Table (ATT): FC84
The Add to Table (ATT) function adds DATA into the next entry of a table
and increments the number of entries by one. The table consists of words.
This function allows you to add entries into tables for use by the FIFO and
LIFO functions.
S The first entry in the FIFO or LIFO table contains the maximum number
of entries of the table (table length).
S The second entry in the table contains the number of entries entered.
S The third entry in the table contains the first word of data.
Note
You must initialize the first two entries when you create the table.
Table 2-1 describes the Add to Table (ATT) parameters.
Table 2-1 Add to Table (FC84) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
DATA Input WORD I, Q, M, D, L, P
or constant
Data to add to table
TABLE Input Pointer* I, Q, M, D Points to the start of the FIFO or LIFO table
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the number of entries is equal to or greater than the table length, the data
will not be added to the table and the signal state of ENO is set to 0.
Figure 2-1 shows how the ATT instruction works. If the signal state of input
I 0.0 is 1 (activated), the ATT function is executed. In this example, DATA is
added as the fifth entry in the table and the number of entries increments
from 4 to 5.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1.
I 0.0 Q 4.0
ATT
FC84
EN ENO
DATA
TABLE
W#16#0024
P#DB1.DBX10.0
Before execution:
Table (table length) DBW10 = W#16#0006
number of entries DBW12 = W#16#0004
DBW14 = W#16#0012
DBW16 = W#16#0029
DBW18 = W#16#0090
DBW20 = W#16#0002
DBW22 = W#16#0000
DBW24 = W#16#0000
After execution:
Table (table length) DBW10 = W#16#0006
number of entries DBW12 = W#16#0005
DBW14 = W#16#0012
DBW16 = W#16#0029
DBW18 = W#16#0090
DBW20 = W#16#0002
DBW22 = W#16#0024
DBW24 = W#16#0000
Figure 2-1 Add to Table (ATT)
Error Information
Example
Table Functions
2
2-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.2 First In/First Out Unload Table (FIFO): FC85
The First In/First Out Unload Table (FIFO) function returns the oldest entry
from the FIFO table as the function value. The number of entries decrements
by one, and if more entries remain, they are shifted down in the table. The
FIFO table consists of words. You use the ATT function to add values into
the FIFO table.
S The first entry in the table contains the maximum number of entries of the
table (table length).
S The second entry in the table contains the number of entries entered.
S The third entry in the table contains the first word of data.
Table 2-2 describes the First In/First Out Unload Table (FIFO) parameters.
Table 2-2 First In/First Out Unload Table (FC85) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
TABLE Input Pointer* I, Q, M, D Points to the start of the FIFO table
RET_VAL Output WORD I, Q, M, D, L, P The oldest entry from the FIFO table
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the FIFO table is empty (number of entries = 0), the RET_VAL is not
changed and the signal state of ENO is set to 0.
Figure 2-2 shows how the FIFO instruction works. If the signal state of input
I 0.0 is 1 (activated), the FIFO function is executed. In this example, the
oldest entry in the table is returned as the function value (MW2). The number
of entries is decremented from 5 to 4, and the remaining entries are shifted
down in the table.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
RET_VAL MW2 = W#16#0012
RET_VAL MW2 = W#16#0000
I 0.0 Q 4.0
P#DB1.DBX10.0
FIFO
FC85
TABLE
RET_VAL
EN ENO
MW2
Before execution:
Table (table length) DBW10 = W#16#0006
number of entries DBW12 = W#16#0005
DBW14 = W#16#0012
DBW16 = W#16#0029
DBW18 = W#16#0090
DBW20 = W#16#0002
DBW22 = W#16#0024
DBW24 = W#16#0000
After execution:
Table (table length) DBW10 = W#16#0006
number of entries DBW12 = W#16#0004
DBW14 = W#16#0029
DBW16 = W#16#0090
DBW18 = W#16#0002
DBW20 = W#16#0024
DBW22 = W#16#0000
DBW24 = W#16#0000
Figure 2-2 First In/First Out Unload Table (FIFO)
Error Information
Example
Table Functions
2
2-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.3 Table Find (TBL_FIND): FC86
The Table Find (TBL_FIND) function is used to search for a distinct pattern
or to search for a non-consistent pattern in a block of memory. This function
performs the indicated compare command (CMD) between the source pattern
(PATRN) and the source table (SRC) entries. It locates the next entry (after
the entry indexed by INDX) in the table that satisfies the compare command
and places its entry number in INDX. If no match is found, INDX points past
the end of the table and the functions output is turned off.
S If CMD = 1, the function searches for the first value equal to the PATRN
value.
S If CMD = 2, the function searches for the first value that is not equal to
the PATRN value.
S The first entry in the table contains the maximum number of entries of the
table (table length).
S The second entry in the table contains the first table value.
Note
You must initialize the first entry (table length) of the table.
Description
Table Functions
2
2-7
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 2-3 describes the Table Find (TBL_FIND) parameters.
Table 2-3 Table Find (FC86) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
SRC Input Pointer* I, Q, M, D Points to the start of the table
PATRN Input Pointer* I, Q, M, D Points to the pattern to be searched for
CMD Input BYTE I, Q, M, D, L, P Indicates command type:
B#16#01 = equal
B#16#02 = not equal
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid data
types for the TBL_FIND function are as follows:
B#16#02 = BYTE
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
INDX Input_Output WORD I, Q, M, D, L Index into table that provides:
Input: starting entry number of the search
Output: entry number of the matching value
*Double word pointer format for area-crossing register indirect addressing
If any of the conditions shown in Table 2-4 occur, the table values are not
changed. The signal state of ENO is set to 0 and the return value is set
appropriately (see Table 2-4).
Table 2-4 Error Conditions for FC86
RET_VAL Explanation
W#16#0008 No match was found
W#16#0009 Invalid E_TYPE and/or CMD
Parameters
Error Information
Table Functions
2
2-8
S7 Standard Functions Part 2
C79000-G7076-C113-02
Figure 2-3 shows how the TBL_FIND instruction works. If the signal state of
input I 0.0 is 1 (activated), the TBL_FIND function is executed. In this
example, since E_TYPE is 4, data in the table is stored in words starting at
the entry pointed to by SRC. These words are compared against the pattern
value 5555, which is stored in the location pointed to by PATRN. Because the
CMD value is 1, the search locates the first table value in SRC that equals the
pattern value. The INDX value points to the entry where the search is to
begin. After the instruction is executed, the INDX value provides the entry
number in the table where the compare command was satisfied.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
I 0.0 Q 4.0
TBL_FIND
FC86
EN ENO
SRC
PATRN
CMD
E_TYPE
RET_VAL P#DB1.DBX0.0
P#DB2.DBX10.0
B#16#01
B#16#04
MW0
The first entry in the table provides the
length of the search operation. The
value of 0004 causes the next 4
entries in the table to be searched.
The INDX moves from DW0 (before
execution) to DW6 (after execution)
because the pattern at entry DW6
equals the pattern 5555 at the PATRN
pointer entry.
INDX
Before execution:
SRC (table length) DBW0 = W#16#0004
DBW2 = W#16#1111
DBW4 = W#16#3333
DBW6 = W#16#5555
DBW8 = W#16#7777
INDX MW2 = W#16#0000
PATRN DBW10 = W#16#5555
After execution:
INDX MW2 = W#16#0003
MW2
Figure 2-3 Table Find (TBL_FIND)
Example
Table Functions
2
2-9
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.4 Last In/First Out Unload Table (LIFO): FC87
The Last In/First Out Unload Table (LIFO) function returns the newest (most
recent) entry from the LIFO table as the function value and decrements the
number of entries by one. The LIFO table consists of words. You use the ATT
function to add entries into the LIFO table.
S The first entry in the table contains the maximum number of entries in the
table (table length).
S The second entry in the table contains the number of entries entered.
S The third entry in the table contains the first word of data.
Table 2-5 describes the Last In/First Out Unload Table (LIFO) parameters.
Table 2-5 Last In/First Out Unload Table (FC87) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
TABLE Input Pointer* I, Q, M, D Points to the start of the LIFO table
RET_VAL Output WORD I, Q, M, D, L, P The newest entry from the LIFO table
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-10
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the LIFO table is empty (number of entries = 0), the RET_VAL is not
changed and the signal state of ENO is set to 0.
Figure 2-4 shows how the LIFO instruction works. If the signal state of input
I 0.0 is 1 (activated), the LIFO function is executed. In this example, the
newest entry in the LIFO table is returned as the function value (MW2). The
number of entries is decremented from 5 to 4.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
I 0.0 Q 4.0
P#DB1.DBX10.0
LIFO
FC87
TABLE
RET_VAL
EN ENO
MW2
Before execution:
Table (table length) DBW10 =W#16#0006
number of entries DBW12 = W#16#0005
DBW14 = W#16#0012
DBW16 = W#16#0029
DBW18 = W#16#0090
DBW20 = W#16#0002
DBW22 = W#16#0024
DBW24 = W#16#0000
RET_VAL MW2 = W#16#0000
After execution:
Table (table length) DBW10 = W#16#0006
number of entries DBW12 = W#16#0004
DBW14 = W#16#0012
DBW16 = W#16#0029
DBW18 = W#16#0090
DBW20 = W#16#0002
DBW22 = W#16#0000
DBW24 = W#16#0000
RET_VAL MW2 = W#16#0024
Figure 2-4 Last In/First Out Unload Table (LIFO)
Error Information
Example
Table Functions
2
2-11
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.5 Table (TBL): FC88
The Table (TBL) function performs the indicated command (set by CMD) to
the source table and writes the result in the same table entry.
S The first entry in the table contains the maximum number of entries of the
table (table length).
S The second entry in the table contains the first table value.
S If the E_TYPE is set to REAL, then the CMD value for ones complement
is invalid.
Note
You must initialize the first entry when you create the table.
Table 2-6 describes the Table (TBL) parameters.
Table 2-6 Table (FC88) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
SRC Input Pointer* I, Q, M, D Points to the start of the table
CMD Input BYTE I, Q, M, D, L, P Indicates type of command to be performed. Valid
commands and their values are:
B#16#03 = ones complement
B#16#04 = clear
B#16#05 = negate
B#16#06 = square root
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid data
types for the TBL function are as follows:
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-12
S7 Standard Functions Part 2
C79000-G7076-C113-02
If CMD or E_TYPE are invalid or CMD and E_TYPE are inconsistent with
each other, the table values are not changed. The signal state of ENO is set to
0 and RET_VAL is set equal to W#16#0008.
Figure 2-5 shows how the TBL instruction works. If the signal state of input
I0.0 is 1 (activated), the TBL function is executed. In this example, SRC
points to the data block locations that will be manipulated by the instruction.
Since E_TYPE is 4, data in the table is stored in words starting at the entry
pointed to by SRC. Because the CMD value is 4 (Clear), all words in the
table are cleared (set to zero) when the TBL instruction is executed. The
table length value of 5 in the first table entry causes the next five table
entries to be cleared.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
TBL
FC88
EN ENO
SRC
CMD
E_TYPE
I 0.0 Q 4.0
RET_VAL P#DB1.DBX0.0
B#16#04
B#16#04
MW0
Before execution:
SRC (table length) DBW0 = W#16#0005
DBW2 = W#16#2000
DBW4 = W#16#3000
DBW6 = W#16#4000
DBW8 = W#16#5000
DBW10 = W#16#6000
After execution:
SRC (table length) DBW0 = W#16#0005
DBW2 = W#16#0000
DBW4 = W#16#0000
DBW6 = W#16#0000
DBW8 = W#16#0000
DBW10 = W#16#0000
Figure 2-5 Table (TBL)
Error Information
Example
Table Functions
2
2-13
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.6 Move Table to Word (TBL_WRD): FC89
The Move Table to Word (TBL_WRD) function copies the entry indicated by
INDX from the SRC table to the entry pointed to by DEST, and then
increments INDX as long as INDX is less than the table length that is given
in the first word of the table, SRC[0]. If the INDX is set to the last table entry
when this instruction is called, the Q output bit is set to 0 after execution.
S The first entry in the table contains the maximum number of entries of the
table (table length).
S The second entry in the table contains the first table value.
Note
You must initialize the first entry when you create the table.
Table 2-7 describes the Move Table to Word (TBL_WRD) parameters.
Table 2-7 Move Table to Word (FC89) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
SRC Input Pointer* I, Q, M, D Points to the start of the table
DEST Input Pointer* I, Q, M, D Points to the destination
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid
types for the TBL_WRD function are as follows:
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
Q Output BOOL Q, M, D, L Indicates 0 if the INDX variable contains the last
entry of the table when the function is called
INDX Input_Output WORD I, Q, M, L Entry number of the entry to move
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-14
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the conditions shown in Table 2-8 occur, the function is not
executed. The signal state of ENO is set to 0 and the return value is set
appropriately.
Table 2-8 Error Conditions for FC89
RET_VAL Explanation
W#16#0007 Index is 0
W#16#0008 Invalid E_TYPE
W#16#0009 Index is beyond the end of the table
Figure 2-6 shows how the TBL_WRD instruction works. If the signal state of
input I 0.0 is 1 (activated) the TBL_WRD function is executed. Since the
E_TYPE is 4, the word data that is stored in the table starting at the entry
pointed to by SRC is copied to the entry pointed to by DEST. The INDX
value points to the table entry to be moved. After the instruction is executed
successfully, the INDX is automatically incremented to one entry past the
entry that was moved. In this example, when the instruction is called, the
INDX is not set to the last table entry, so Q is set to 1 after execution.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
I 0.0 Q 4.0
TBL_WRD
FC89
EN ENO
SRC
DEST
E_TYPE
Q
INDX
RET_VAL
P#DB1.DBX0.0
P#DB2.DBX20.0
B#16#04
MW1
MW0
M2.0
Before execution:
SRC (table length) DBW0 = W#16#0004
DBW2 = W#16#2000
DBW4 = W#16#3000
DBW6 = W#16#4000
DBW8 = W#16#5000
INDX MW1 = W#16#0001
DEST DBW20 = W#16#0000
After execution:
INDX MW1 = W#16#0002
DEST DBW20 = W#16#2000
Figure 2-6 Move Table to Word (TBL_WRD)
Error Information
Example
Table Functions
2
2-15
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.7 Word to Table (WRD_TBL): FC91
The Word to Table (WRD_TBL) function performs the indicated command
(CMD) between the source data (pointed to by SRC) and the entry of the
table at the offset indicated by INDX, then increments INDX as long as
INDX is less than the length of the table.
S The first entry in the table contains the maximum number of entries of the
table (table length).
S The second entry in the table contains the first table value.
S If E_TYPE is REAL, then CMD can only be Move.
Note
You must initialize the first entry when you create the table.
Table 2-9 describes the Word to Table (WRD_TBL) parameters.
Table 2-9 Word to Table (FC91) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
SRC Input Pointer* I, Q, M, D Points to the source data
TABLE Input Pointer* I, Q, M, D Points to the start of the table
CMD Input BYTE I, Q, M, D, L, P Indicates the type of command to be performed.
Valid commands and their values are:
B#16#0E = move
B#16#07 = and
B#16#08 = or
B#16#09 = exclusive or
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid data
types for the WRD_TBL function are as follows:
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
Q Output BOOL Q, M, D, L Indicates 0 if the INDX contains the last entry
number of the table
INDX Input_Output WORD I, Q, M, D, L Entry number of the entry to be operated on
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-16
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the conditions shown in Table 2-10 occur, the function is not
executed. The signal state of ENO is set to 0 and the return value is set
appropriately.
Table 2-10 Error Conditions for FC91
RET_VAL Explanation
W#16#0007 Index is 0
W#16#0008 Invalid CMD or E_TYPE, or CMD and E_TYPE are inconsistent
with each other
W#16#0009 Index is beyond the end of the table
Figure 2-7 shows how the WRD_TBL instruction works. If the signal state of
input I 0.0 is 1 (activated), the WRD_TBL function is executed. Since the
E_TYPE is 6, double word data is stored in the table starting at the memory
location pointed to by TABLE. The table length in the first word indicates
that the table contains three double words. The INDX value points to the
table entry to be manipulated. Since the CMD value is 8, the instruction
performs an OR command on the value that INDX points to. Since the INDX
is 2, the second double word (66665544) is ORed with the value pointed to
by SRC (11111111). After the instruction is executed, the result of the OR
command (77775555) is written back into the table, and the INDX is
automatically incremented one entry. If the INDX is set to the last table entry
when this instruction is called, the Q output bit is set to 0 after execution. In
this example, when the instruction is called, the INDX is not set to the last
table entry, so Q is set to 1 after execution.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
Error Information
Example
Table Functions
2
2-17
S7 Standard Functions Part 2
C79000-G7076-C113-02
TABLE (table length) DBW0 = W#16#0003
DBD2 = DW#16#99998877
DBD6 = DW#16#66665544
DBD10 = DW#16#33332222
SRC DBD20 = DW#16#11111111
Before execution:
I 0.0 Q 4.0
WRD_TBL
FC91
EN ENO
SRC
TABLE
CMD
RET_VAL
E_TYPE
INDX
P#DB2.DBX20.0
P#DB1.DBX0.0
B#16#08
B#16#06
MW1
MW0
Q M2.0
INDX MW1 = W#16#0002
After execution:
TABLE (table length) DBW0 = W#16#0003
DBD2 = DW#16#99998877
DBD6 = DW#16#77775555
DBD10 = DW#16#33332222
INDX MW1 = W#16#0003
Figure 2-7 Word To Table (WRD_TBL)
Table Functions
2
2-18
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.8 Correlated Data Table (CDT): FC103
The Correlated Data Table (CDT) function compares an input value (IN) to a
pre-existing input table of values (IN_TBL) and locates the first value that is
greater than or equal to the input value. If located, the index of the located
value is used to copy the corresponding value in the output table (OUT_TBL)
to the output value (OUT).
S The input table values should be in ascending order. That is, the smallest
value is located in the first table entry and the largest value is located in
the last table entry.
S The size of the input value, the table values, and the output value is
determined from E_TYPE.
S The first entry in the table contains the number of entries of the table
(table length).
S The second entry in the table contains the first table value.
S The number of entries in both tables must be equal and be greater than
zero.
Note
You must initialize the first entry when you create each table.
Table 2-11 describes the Correlated Data Table (CDT) parameters.
Table 2-11 Correlated Data Table (FC103) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN_TBL Input Pointer* I, Q, M, D Points to the start of the input table
OUT_TBL Input Pointer* I, Q, M, D Points to the start of the output table
IN Input Pointer* I, Q, M, D Points to the input value
OUT Input Pointer* I, Q, M, D Points to the output value
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid data
types for the CDT function are as follows:
B#16#05 = INT
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-19
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the conditions shown in Table 2-12 occur, the function is not
executed. The signal state of ENO is set to 0 and the return value is set
appropriately.
Table 2-12 Error Conditions for FC103
RET_VAL Explanation
W#16#0001 Invalid memory type specified for a function parameter
W#16#0002 Invalid E_TYPE
W#16#0003 The input and output table lengths do not match
W#16#0004 Table length is zero
W#16#0007 No value in IN_TBL was greater than or equal to the input value
Figure 2-8 shows how the CDT instruction works. If the signal state of input
I0.0 is 1 (activated), the CDT function is executed. In this example, both
IN_TBL and OUT_TBL contain 5 table entries as indicated by the first word
of each table. The data type of the table values is INTEGER as indicated by
E_TYPE, and the value of IN is 22. The IN_TBL value that is greater than or
equal to 22 is 64, which has an index of 5. The correlated value in OUT_TBL
is 25. Therefore, the value 25 is written to OUT.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
Error Information
Example
Table Functions
2
2-20
S7 Standard Functions Part 2
C79000-G7076-C113-02
IN DBW200 = 22
OUT DBW210 = 0
OUT_TBL (table length) DBW100 = W#16#0005
DBW102 = 5
DBW104 = 10
DBW106 = 15
DBW108 = 20
DBW110 = 25
I 0.0 Q4.0
CDT
FC103
EN ENO
IN_TBL
OUT_TBL
IN
OUT
RET_VAL P#DB1.DBX0.0
P#DB1.DBX100.0
P#DB1.DBX200.0
P#DB1.DBX210.0
B#16#05
MW0
E_TYPE
Before execution:
IN_TBL (table length) DBW0 = W#16#0005
DBW2 = 2
DBW4 = 4
DBW6 = 8
DBW8 = 16
DBW10 = 64
After execution:
OUT DBW210 = 25
Figure 2-8 Correlated Data Table (CDT)
Table Functions
2
2-21
S7 Standard Functions Part 2
C79000-G7076-C113-02
2.9 Table To Table (TBL_TBL): FC104
The Table to Table (TBL_TBL) function performs the indicated command
(CMD) between the corresponding entries of the two source tables (TBL1
and TBL2) and writes the result in the corresponding entries of the
destination table (DEST_TBL).
S Data types of INT, DINT, or REAL are only valid for the math operations
S The first entry in the table contains the number of entries of the table
(table length)
S The number of entries in all of the tables must be equal and be greater
than zero
Note
You must initialize the first entry when you create each table.
Table 2-13 describes the Table to Table (TBL_TBL) parameters.
Table 2-13 Table To Table (FC104) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
TBL1 Input Pointer* I, Q, M, D Points to start of the first source table
TBL2 Input Pointer* I, Q, M, D Points to start of the second source table
DEST_TBL Input Pointer* I, Q, M, D Points to start of the destination table
CMD Input BYTE I, Q, M, D, L, P Indicates the type of command to be performed.
Valid commands and their values are:
B#16#07 = and
B#16#08 = or
B#16#09 = exclusive or
B#16#0a = add
B#16#0b = subtract
B#16#0c = multiply
B#16#0d = divide
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid data
types for the TBL_TBL function are as follows:
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#160000
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Table Functions
2
2-22
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the conditions shown in Table 2-14 occur, the function is not
executed. The signal state of ENO is set to 0 and the return value is set
appropriately.
Table 2-14 Error Conditions for FC104
RET_VAL Explanation
W#16#0001 Invalid memory type specified for a function parameter
W#16#0002 Invalid E_TYPE
W#16#0003 The input and output table lengths do not match
W#16#0004 Table length is zero
W#16#0005 E_TYPE and CMD are inconsistent with each other
W#16#0006 Invalid CMD
Figure 2-9 shows how the TBL_TBL instruction works. If the signal state of
input I0.0 is 1 (activated), the TBL_TBL function is executed. In this
example, all tables contain 3 table entries as indicated by the first word of
each table. The data type of the table values is WORD as indicated by
E_TYPE. The command to be performed on TBL1 and TBL2 is AND as
indicated by CMD.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
DEST_TBL (table length) DBW40 = W#16#0003
DBW42 = W#16#0000
DBW44 = W#16#0000
DBW46 = W#16#0000
TBL2 (table length) DBW20 = W#16#0003
DBW22 = W#16#1111
DBW24 = W#16#2222
DBW26 = W#16#3333
I 0.0 Q4.0
TBL_TBL
FC104
EN ENO
TBL1
TBL2
DEST_TBL
CMD
RET_VAL P#DB1.DBX0.0
P#DB1.DBX20.0
P#DB1.DBX40.0
B#16#07
B#16#04
MW0
E_TYPE
Before execution:
TBL1 (table length) DBW0 = W#16#0003
DBW2 = W#16#00FF
DBW4 = W#16#FF00
DBW6 = W#16#FFFF
After execution:
DEST_TBL (table length) DBW40 = W#16#0003
DBW42 = W#16#0011
DBW44 = W#16#2200
DBW46 = W#16#3333
Figure 2-9 Table To Table (TBL_TBL)
Error Information
Example
Table Functions
3-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Shift Functions
This section describes shift functions (FCs) that you can add to your standard
set of instructions to provide additional programming flexibility.
Section Description Page
3.1 Word Shift Register (WSR): FC90 3-2
3.2 Bit Shift Register (SHRB): FC92 3-4
3
3
3-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
3.1 Word Shift Register (WSR): FC90
The Word Shift Register (WSR) function shifts data into a shift register from
the indicated source. Each value is moved into the next location. LENGTH
specifies the number of locations to be shifted. The data contained in the last
location of the shift register is lost after the shift. New data is read from the
source (S_DATA) each time the instruction is executed; this data is shifted
into the shift register starting location (START) when the RESET input is set
to 0. If the RESET input is set to 1, the register location is set to zeros when
the instruction is executed. The output Q is turned on when the shift register
is empty or cleared (that is, after a reset or after all zeros are shifted in).
Table 3-1 describes the Word Shift Register (WSR) parameters.
Table 3-1 Word Shift Register (FC90) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
RESET Input BOOL I, Q, M, D, L Resets the shift register when set to 1
S_DATA Input Pointer* I, Q, M, D Points to the source data to be inserted into the table
START Input Pointer* I, Q, M, D Points to the start of the table
LENGTH Input WORD I, Q, M, D, L, P Number of items to be shifted
E_TYPE Input BYTE I, Q, M, D, L, P Indicates the data type of the table entries. Valid data
types for the WSR function are as follows:
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
Q Output BOOL Q, M, D, L Indicates 0 if the RESET is active (1) or all items to
be shifted are a value of 0
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Shift Functions
3
3-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
If an invalid E_TYPE is used, the function is not executed and the signal
state of ENO is set to 0.
Figure 3-1 shows how the WSR instruction works. If the signal state of input
I 0.0 is 1 (activated) the WSR function is executed. Since the E_TYPE is 4,
word data is stored in the table starting at the memory location pointed to by
START. The LENGTH parameter is set to 4, indicating that 4 word locations
will be shifted, starting with the first word at the START pointer. After the
first value in a table is shifted to the next location, the first location is filled
with the data pointed to by the S_DATA pointer. The last table value is lost.
Whenever the RESET input is set to 1, the locations in the table are set to
zero rather than being shifted.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1.
I 0.0 Q 4.0
WSR
FC90
EN ENO
RESET
S_DATA
START
Q
LENGTH
E_TYPE
M1.0
P#DB2.DBX6.0
P#DB1.DBX0.0
B#16#04
B#16#04
M2.0
RESET M1.0 = FALSE
S_DATA DW6 = W#16#1234
Before execution:
START DW0 = W#16#1111
DW2 = W#16#2222
DW4 = W#16#3333
DW6 = W#16#4444
After execution:
START DW0 = W#16#1234
DW2 = W#16#1111
DW4 = W#16#2222
DW6 = W#16#3333
Figure 3-1 Word Shift Register (WSR)
Error Information
Example
Shift Functions
3
3-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
3.2 Bit Shift Register (SHRB): FC92
The Bit Shift Register (SHRB) function shifts a bit into a shift register from
the indicated source in DATA. New data is read from the source each time
the instruction is executed, and this data is shifted into the shift register
starting location (S_BIT) while the RESET input has a signal state of 0. All
successive bits are shifted by one. The bit contained in the last location
(S_BIT+N) is lost after the shift. Whenever the RESET input is set to 1, the
locations in the table are set to 0 rather than being shifted.
Table 3-2 describes the Bit Shift Register (SHRB) parameters.
Table 3-2 Bit Shift Register (FC92) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
DATA Input BOOL I, Q, M, D, L Source data bit
RESET Input BOOL I, Q, M, D, L Resets the shift register when set to 1
S_BIT Input Pointer* I, Q, M, D Points to the starting bit in the shift register
N Input WORD I, Q, M, D, L, P Length of the shift register (number of bits to be
shifted)
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Shift Functions
3
3-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
This function does not detect any error conditions.
Figure 3-2 shows how the SHRB instruction works. If the signal state of input
I 0.0 is 1 (activated) the SHRB function is executed. The N parameter in this
example is set to 14 (E in hexadecimal notation), indicating that 14 bit
locations will be shifted, starting with the first bit at the S_BIT pointer
location. After the bits are shifted, the first location is filled with the data
indicated by the input DATA. The very last bit value is lost.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1.
I 0.0 Q 4.0
SHRB
FC92
EN ENO
DATA
RESET
S_BIT
N
P#DB1.DBX1.4
B#16#0E
0
0
0
1.7
Before shifting:
0 1 1 1 0 1 0
0
2.7
0 1 1 1 0 1 0
0
1.7
After shifting:
1
1 1 0 1 0 0 0
2.7
1
1 0 1 0 1 0
0
3.7
0 1 1 1 0 1 0 1 1 1 0 0 0 0
3.7
0
1.0
2.0
1.0
2.0
3.0 3.0
S_BIT S_BIT
Figure 3-2 Bit Shift Register (SHRB)
Error Information
Example
Shift Functions
3
3-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
Shift Functions
4-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Move Function and Function Block
This section describes move function (FC) and function block (FB) that you
can add to your standard set of instructions to provide additional
programming flexibility.
Section Description Page
4.1 Indirect Block Move (IBLKMOV): FC81 4-2
4.2 Pack Data (PACK): FB86 4-4
4
4
4-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
4.1 Indirect Block Move (IBLKMOV): FC81
You can use the Indirect Block Move (IBLKMOV) instruction to move a
block of data consisting of either bytes, words, integers, double words, or
double integers from a source block to a destination block. The number of
elements to be moved is determined by LENGTH and the element size is
identified by E_TYPE. The S_DATA and D_DATA pointers identify the
location of pointers that identify the starting locations of the source and
destination data. Because of this indirect method of identifying the data to be
moved, this function is called an indirect block move.
Table 4-1 describes the Indirect Block Move (IBLKMOV) parameters.
Table 4-1 Indirect Block Move (FC81) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
S_DATA Input Pointer* I, Q, M, D Points to a pointer which identifies the starting
location of the source data
LENGTH Input Pointer* I, Q, M, D Points to the length of the block to be moved
D_DATA Input Pointer* I, Q, M, D Points to a pointer which identifies the starting
location of the destination data
E_TYPE Input BYTE I, Q, M, D, L Indicates the data type. Valid data types for the
IBLKMOV function are as follows:
B#16#02 = BYTE
B#16#04 = WORD
B#16#05 = INT
B#16#06 = DWORD
B#16#07 = DINT
B#16#08 = REAL
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Move Function and Function Block
4
4-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
If an invalid E_TYPE is entered, the function is not executed and the signal
state of ENO is set to 0.
Figure 4-1 shows how the Indirect Block Move instruction works. If the
signal state of input I 0.0 is 1 (activated), the function is executed. S_DATA
points to DB1.DBX0.0 which contains the pointer DB1.DBX50.0 (the
starting location of the source data). D_DATA points to DB1.DBX20.0,
which contains the pointer DB2.DBX10.0 (the starting location of the
destination data). After the function is executed, a block of two words is
moved.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1.
I 0.0 Q 4.0
IBLKMOV
FC81
EN ENO
S_DATA
LENGTH
D_DATA
E_TYPE
P#DB1.DBX0.0
P#DB1.DBX10.0
P#DB1.DBX20.0
B#16#04
Before execution:
S_DATA DBX0.0 = P#DB1.DBX50.0
DBW50 = W#16#2424
DBW52 = W#16#2525
LENGTH DBW10 = W#16#0002
D_DATA DBX20.0= P#DB2.DBX10.0
DBW10 = W#16#0000
DBW12 = W#16#0000
After execution:
D_DATA DBW10 = W#16#2424
DBW12 = W#16#2525
Figure 4-1 Indirect Block Move (IBLKMOV)
Error Information
Example
Move Function and Function Block
4
4-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
4.2 Pack Data (PACK): FB86
The Pack Data (PACK) function block moves data interleaved between
random locations and a table. The direction of transfer is specified by DIR.
Each PACK instruction processes up to five blocks of data (P_DATA1 to
P_DATA5). If DIR indicates to, the PACK moves data from these
locations to the indicated table. Similarly, if the DIR indicates from, data
is distributed from the table to the locations.
The rules for packing to a table are as follows:
S Single bits (BOOL) are packed into the next available bit in the table.
S 8-bit data types are packed into the next available byte in the table. When
a byte is written to the table, unused bits in the previous byte are filled
with zeros.
S 16- and 32-bit data types are packed into the next available word in the
table. When a word is written to the table, unused bits in the previous
word are filled with zeros.
The rules for packing data from a table are as follows:
S Sections of a table cannot be skipped.
S All BOOL points specified are packed from the table.
S 8-bit data types are packed from the first available byte in the table. That
is, unused bits in the previous byte of the table are not included as part of
a byte that is packed from the table.
S 16- and 32-bit data types are packed from the first available word in the
table. That is, unused bits in the previous word of the table are not
included as part of a word that is packed from the table.
Valid data types of the ANY pointer which are supported by the PACK
function block are:
S BOOL
S WORD
S INT
S BYTE
S DINT
S REAL
S CHAR
S DWORD
Description
Move Function and Function Block
4
4-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 4-2 describes the Pack Data (PACK) parameters.
Table 4-2 Pack Data (FB86) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
block is executed without error
TABLE Input Pointer* I, Q, M, D Points to the start of the table
P_DATA1 Input Any I, Q, M, D Points to the start of a block of data to pack
P_DATA2 Input Any I, Q, M, D Points to the start of a block of data to pack
P_DATA3 Input Any I, Q, M, D Points to the start of a block of data to pack
P_DATA4 Input Any I, Q, M,D Points to the start of a block of data to pack
P_DATA5 Input Any I, Q, M, D Points to the start of a block of data to pack
ERR_CODE Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
DIR Static BOOL I, Q, M, D, L Direction of pack. A signal state of
0 = to, and 1 = from
*Double word pointer format for area-crossing register indirect addressing
If any of the conditions shown in Table 4-3 occur, the function block is not
executed. The signal state of ENO is set to 0 and ERR_CODE is set
appropriately.
Table 4-3 Error Conditions for FB86
ERR_CODE Explanation
W#16#0001 Invalid memory type specified for a function parameter
W#16#0002 Invalid E_TYPE
Parameters
Error Information
Move Function and Function Block
4
4-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
Figure 4-2 shows how the Pack Data instruction works. If the signal state of
input I0.0 is 1 (activated), the PACK function block is executed. In this
example, there are four blocks of data being packed to the table.
If the function block is executed without error, the signal states of ENO and
Q4.0 are set to 1 and ERR_CODE is set equal to W#16#0000.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
I 0.0 Q 4.0
PACK
FB86
EN ENO
TABLE
P_DATA1
P_DATA2
ERR_CODE
P_DATA3
P_DATA4
P#DB1.DBX0.0
P#M200.0 BOOL 2
P#M210.0 BYTE 1
P#M300.0 BOOL 2
P#M330.0 WORD 1
MW0
DB86
P_DATA5
Before execution:
TABLE DBB0 = B#16#00
DBB1 = B#16#00
DBB2 = B#16#00
DBB3 = B#16#00
DBB4 = B#16#00
DBB5 = B#16#00
P_DATA1 M200.0 = TRUE
M200.1 = TRUE
P_DATA2 MB210 = B#16#FF
P_DATA3 M300.0 = TRUE
M300.1 = TRUE
P_DATA4 MW330 = W#16#FFFF
Instance DB86
DIR DBX58.0 = FALSE
After execution:
TABLE DBB0 = B#16#03
DBB1 = B#16#FF
DBB2 = B#16#03
DBB3 = B#16#00
DBB4 = B#16#FF
DBB5 = B#16#FF
Figure 4-2 PACK DATA (PACK)
Example
Move Function and Function Block
5-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Timer Function and Function Blocks
This section describes the timer function (FC) and function blocks (FBs) that
you can add to your standard set of instructions to provide additional
programming flexibility.
Section Description Page
5.1 Software Timer On DelayRetentive (TONR):
FC80
5-2
5.2 Discrete Control Alarm Timer (DCAT): FB81 5-4
5.3 Motor Control Alarm Timer (MCAT): FB82 5-7
5.4 Event Maskable Drum (DRUM): FB85 5-10
5
5
5-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
5.1 Software Timer On DelayRetentive (TONR): FC80
The Software Timer On DelayRetentive (TONR) function accumulates
time until the current value of elapsed time (ET) equals or exceeds the preset
value (PV). Since TONR uses the execution time of the last cycle of the OB
(Organization Block) in which it runs to accumulate time, this function is
intended to be used only in the OBs that have a repetitive nature, such as
OB1 and the cyclic OBs.
Note
You must move the OB scan time from the start-up local variables in the
variable declaration table of the OB to the global variable DELTA_T.
As long as the signal state of RESET is 0, the signal state of TMR_EN is 1,
and the signal state of Q is 0, the TONR function adds DELTA_T to ET. If
the signal state of TMR_EN is not 1, then no time is added to ET. When ET
reaches or exceeds PV, the signal state of output Q is set to 1. Once Q turns
on, it remains on and ET is held at the last value until reset. The function
resets ET to 0 and turns off output Q when the signal state of RESET is 1.
Table 5-1 describes the Software Timer On DelayRetentive (TONR)
parameters.
Table 5-1 Software Timer On DelayRetentive (FC80) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
TMR_EN Input BOOL I, Q, M, D, L Enables timer to accumulate time
RESET Input BOOL I, Q, M, D, L If RESET = 1, the timer is reset to 0
PV Input DINT I, Q, M, D, L, P
or constant
Preset value
DELTA_T Input INT I, Q, M, D, L or
constant
OB scan time for previous cycle
Q Output BOOL Q, M, D, L If ET equals or exceeds PV, the signal state of Q is
set to 1
ET Input_Output DINT I, Q, M, D, L or
constant
Current value of elapsed time
Description
Parameters
Timer Functions and Function Blocks
5
5-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
This function does not detect any error conditions.
Figure 5-1 shows how the TONR instruction works. If the signal state of
input I 0.0 is 1 (activated), the TONR function is executed. If the signal state
of I 0.1 is 1 and the signal states of I 0.2 and Q 1.1 are both 0, then
DELTA_T is added to ET (100 + 50 = 150). Since ET is less than PV, the
signal state of Q 1.1 remains 0.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1.
I 0.0 Q 4.0
TONR
FC80
EN
TMR_EN
RESET
PV
DELTA_T
ENO
Q
ET
I 0.1
I 0.2
1000
50
100
Q 1.1
Figure 5-1 Timer On DelayRetentive (TONR)
Error Information
Example
Timer Functions and Function Blocks
5
5-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
5.2 Discrete Control Alarm Timer (DCAT): FB81
The Discrete Control Alarm Timer (DCAT) function block accumulates time
from the command (CMD) input transition to open (or close) until the preset
time (PT) is exceeded or the feedback input (O_FB or C_FB) indicates the
device opened (or closed) within the prescribed time. If the preset time is
exceeded before the feedback is received, the corresponding alarm is turned
on. If the input command switches states before the preset time, the time is
restarted.
S When the signal state of CMD input transitions from 0 to 1, the signal
state of Q is set to 1, ET is set to zero, the signal states of both alarm
outputs (OA, CA) are set to 0, and the signal state of CMD_HIS is set
to 1.
S When the signal state of CMD input transitions from 1 to 0, the signal
state of Q is set to 0, ET is set to zero, the signal states of both alarm
outputs (OA, CA) are set to 0, and the signal state of CMD_HIS is set
to 0.
S When the signal states of both CMD and CMD_HIS are 1, and the signal
state of O_FB is 0, then the time (msec) delta since the last function block
execution is added to ET. If ET exceeds PT, then the signal state of OA is
set to 1, otherwise it is set to 0. The signal state of CMD_HIS is set equal
to CMD.
S When the signal states of both CMD and CMD_HIS are 1, the signal state
of O_FB is 1, and the signal state of C_FB is 0, then the signal state of the
OA is set to 0. ET is set equal to PT so that if the signal state of O_FB is
later set to 0, the alarm will be set on the next function block execution.
The signal state of CMD_HIS is set equal to CMD.
S When the signal states of both CMD and CMD_HIS are 0, and the signal
state of C_FB is 0, then the time (msec) delta since the last function block
execution is added to ET. If ET exceeds PT, then the signal state of the
CA is set to 1, otherwise it is set to 0. The signal state of CMD_HIS is set
equal to CMD.
S When the signal states of both CMD and CMD_HIS are 0, the signal state
of O_FB is 0, and the C_FB is 1, then the signal state of the CA is set to
0. ET is set equal to PT so that if the signal state of C_FB is later set to 0,
the alarm will be set on the next function block execution. The signal
state of CMD_HIS is set equal to CMD.
S If the signal states of both O_FB and C_FB are 1 simultaneously, then this
is considered an error condition and the signal states of both alarm
outputs are set to 1.
Description
Timer Functions and Function Blocks
5
5-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 5-2 describes the Discrete Control Alarm Timer (DCAT) parameters.
Table 5-2 Discrete Control Alarm Timer (FB81) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
block is executed without error
CMD Input BOOL I, Q, M, D, L A signal state of 0 indicates a close command and a
signal state of 1 indicates an open command
O_FB Input BOOL I, Q, M, D, L Open feedback input
C_FB Input BOOL I, Q, M, D, L Closed feedback input
Q Output BOOL I, Q, M, D, L Follows CMD input
OA Output BOOL I, Q, M, D, L Open alarm output
CA Output BOOL I, Q, M, D, L Closed alarm output
ET Static DINT I, Q, M, D, L Current count of elapsed time,
where 1 count = 1 msec
PT Static DINT I, Q, M, D, L Timer preset count, where 1 count = 1 msec
PREV_TIME Static DWORD I, Q, M, D, L Previous system time
CMD_HIS Static BOOL I, Q, M, D, L CMD history bit
Parameters
Timer Functions and Function Blocks
5
5-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
This function block does not detect any error conditions.
Figure 5-2 shows how the DCAT instruction works. If the signal state of input
I0.0 is 1 (activated), the DCAT function block is executed. In this example,
the CMD input is transitioning from a signal state of 0 to 1 as indicated by
CMD_HIS and CMD. Based upon these conditions, Q and CMD_HIS are
given a signal state of 1, ET is set to 0, and both alarm outputs OA and CA
are given a signal state of 0.
If the function block is executed without error, the signal state of ENO and
Q4.0 are set to 1.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
I 0.0 Q4.0
DCAT
FB81
EN
CMD
O_FB
ENO
Q
M0.0
M1.0
Q2.0
OA Q3.0
C_FB
M1.1
CA Q3.1
DB81
Before execution:
CMD M0.0 = TRUE
O_FB M1.0 = FALSE
C_FB M1.1 = FALSE
Q M2.0 = FALSE
OA M3.0 = FALSE
CA M3.1 = FALSE
Instance DB81
ET DBD4 = L#12
PT DBD8 = L#222
CMD_HIS DBX16.0 = FALSE
After execution:
Q M2.0 = TRUE
OA M3.0 = FALSE
CA M3.1 = FALSE
Instance DB81
ET DBD4 = L#0
CMD_HIS DBX16.0 = TRUE
Figure 5-2 Discrete Control Alarm Timer (DCAT)
Error Information
Example
Timer Functions and Function Blocks
5
5-7
S7 Standard Functions Part 2
C79000-G7076-C113-02
5.3 Motor Control Alarm Timer (MCAT): FB82
The Motor Control Alarm Timer (MCAT) function block accumulates time
from the on transition of one of the command inputs (open or close) until the
preset time is exceeded or the corresponding feedback input indicates the
device completed the commanded operation within the prescribed time. If the
preset time is exceeded before the feedback is received, the corresponding
alarm is turned on. Descriptions of the MCAT reaction to the various input
conditions are summarized in the MCAT Truth Table (see Table 5-3 ).
Table 5-3 MCAT Truth Table
INPUTS OUTPUTS
ET O_HIS C_HIS O_CMD C_CMD S_CMD O_FB C_FB OO CO OA CA ET O_HIS C_HIS Q STATE
X 1 1 X X X X X 0 0 1 1 PT 0 0 0 Alarm
X X X X X X 1 1 0 0 1 1 PT 0 0 0 Alarm
X X X X X 1 X X 0 0 0 0 X 0 0 1 Stop
X X X 1 1 X X X 0 0 0 0 X 0 0 1 Stop
X 0 X 1 0 0 X X 1 0 0 0 0 1 0 1 Begin Open
<PT 1 0 X 0 0 0 X 1 0 0 0 INC 1 0 1 Opening
X 1 0 X 0 0 1 0 0 0 0 0 PT 1 0 1 Opened
>=PT 1 0 X 0 0 0 X 0 0 1 0 PT 1 0 0 Open Alarm
X X 0 0 1 0 X X 0 1 0 0 0 0 1 1 Begin Close
<PT 0 1 0 X 0 X 0 0 1 0 0 INC 0 1 1 Closing
X 0 1 0 X 0 0 1 0 0 0 0 PT 0 1 1 Closed
>=PT 0 1 0 X 0 X 0 0 0 0 1 PT 0 1 0 Close Alarm
X 0 0 0 0 0 X X 0 0 0 0 X 0 0 1 Stopped
Where:
INC = Add the time (msec) delta since the last function block execution to ET
PT = PT is set equal to ET
X = Not applicable
<PT = ET < PT
>= PT = ET >= PT
Description
Timer Functions and Function Blocks
5
5-8
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 5-4 describes the Motor Control Alarm Timer (MCAT) parameters.
Table 5-4 Motor Control Alarm Timer (FB82) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
O_CMD Input BOOL I, Q, M, D, L Open command input
C_CMD Input BOOL I, Q, M, D, L Close command input
S_CMD Input BOOL I, Q, M, D, L Stop command input
O_FB Input BOOL I, Q, M, D, L Open feedback input
C_FB Input BOOL I, Q, M, D, L Closed feedback input
OO Output BOOL I, Q, M, D, L Open output
CO Output BOOL I, Q, M, D, L Close output
OA Output BOOL I, Q, M, D, L Open alarm output
CA Output BOOL I, Q, M, D, L Closed alarm output
Q Output BOOL I, Q, M, D, L A signal state of 1 indicates an alarm condition
ET Static DINT I, Q, M, D, L Current count of elapsed time,
where 1 count = 1 msec
PT Static DINT I, Q, M, D, L Timer preset count, where 1 count = 1 msec
PREV_TIME Static DWORD I, Q, M, D, L Previous system time
O_HIS Static BOOL I, Q, M, D, L Open history bit
C_HIS Static BOOL I, Q, M, D, L Close history bit
This function block does not detect any error conditions.
Figure 5-3 shows how the MCAT instruction works. If the signal state of
input I0.0 is 1 (activated), the MCAT function block is executed. In this
example, based upon the status of the inputs, the MCAT is in the OPENING
state and the outputs are set appropriately.
If the function block is executed without error, the signal states of ENO and
Q4.0 are set to 1.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
Parameters
Error Information
Example
Timer Functions and Function Blocks
5
5-9
S7 Standard Functions Part 2
C79000-G7076-C113-02
O_CMD M0.0 = TRUE
C_CMD M0.1 = FALSE
S_CMD M0.2 = FALSE
O_FB M1.0 = FALSE
C_FB M1.1 = FALSE
OO M2.0 = FALSE
CO M2.1 = FALSE
OA M3.0 = FALSE
CA M3.1 = FALSE
Q M4.0 = FALSE
Instance DB82
ET DBD4 = L#2
PT DBD8 = L#22
O_HIS DBX16.0 = TRUE
C_HIS DBX16.1 = FALSE
I 0.0 Q4.0
MCAT
FB82
EN
O_CMD
C_CMD
ENO
OO
M0.0
M0.1
M2.0
CO M2.1
S_CMD
M0.2
OA M3.0
DB82
Before execution:
After execution:
OO M2.0 = TRUE
CO M2.1 = FALSE
OA M3.0 = FALSE
CA M3.1 = FALSE
Q M4.0 = TRUE
Instance DB82
ET DBD4 = L#4
O_HIS DBX16.0 = TRUE
CMD_HIS DBX16.1 = FALSE
O_FB
M1.0
CA M3.1
C_FB
M1.1
Q M4.0
Figure 5-3 Motor Control Alarm Timer (MCAT)
Timer Functions and Function Blocks
5
5-10
S7 Standard Functions Part 2
C79000-G7076-C113-02
5.4 Event Maskable Drum (DRUM): FB85
The Event Maskable Drum (DRUM) function block drives the programmed
output bits (OUT1 to OUT16) and the word output (OUT_WORD) with the
programmed values (OUT_VAL) of the appropriate step conditioned by the
enabling masks (S_MASK) for that step while the DRUM remains on that
step. The DRUM will advance to the next step when either the event for the
step is true and the programmed time for the current step has expired, or the
jog input transitions from 0 to 1. When the signal state of RESET is 1, the
DRUM is reset, which sets the current step equal to the preset step (DSP).
The amount of time spent on a step is determined by the product of the
DRUM time base preset (DTBP) and the count preset/step values
(S_PRESET) corresponding to each step. At the start of a new step, this
calculated value is loaded into DCC which contains the time remaining for
the current step. For example, if DTBP is equal to 2, and the preset value for
step 1 is equal to 100 (100 msec), then DCC equals 200 (200 msec).
A step may be programmed with a time value, or an event, or both. Steps
with an event bit and a time value of zero, advance to the next step as soon as
the signal state of the event bit is 1. Steps with only a time start timing
immediately. Steps with an event bit and a time value greater than 0 begin
timing when the signal state of the event bit is 1. The event bits are
initialized with a signal state of 1.
When the step pointer is on the last programmed step (LST_STEP) and the
time for that step has expired, the signal state of output (Q) is set to 1,
otherwise it is set to 0. Once Q is set, the DRUM remains on that step until
reset.
The configurable mask (S_MASK) allows selection of the individual bits in
the output word (OUT_WORD) and the output bits (OUT1 to OUT16) to be
set/reset by the output values (OUT_VAL). When a bit of the configurable
mask has a signal state of 1, the OUT_VAL value sets/resets the
corresponding bit. When a bit of the configurable mask has a signal state of
0, the corresponding bit is left unchanged. Each of the bits of the
configurable mask for all 16 steps is initialized with a signal state of 1.
The output bit OUT1 corresponds with the least-significant bit of the word
output OUT_WORD. The output bit OUT16 corresponds with the
most-significant bit of the word output OUT_WORD.
Description
Timer Functions and Function Blocks
5
5-11
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 5-5 describes the Event Maskable Drum (DRUM) parameters.
Table 5-5 Event Maskable Drum (FB85) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
RESET Input BOOL I, Q, M, D, L A signal state of 1 indicates a reset condition
JOG Input BOOL I, Q, M, D, L A transition of a signal state of 0 to 1 advances
DRUM to the next step
DRUM_EN Input BOOL I, Q, M, D, L A signal state of 1 enables the timing operation
LST_STEP Input BYTE I, Q, M, D, L,
or constant
Step number of the last step programmed
EVENT1 Input BOOL I, Q, M, D, L Event bit 1; initial signal state is 1
EVENT2 Input BOOL I, Q, M, D, L Event bit 2; initial signal state is 1
EVENT3 Input BOOL I, Q, M, D, L Event bit 3; initial signal state is 1
EVENT4 Input BOOL I, Q, M, D, L Event bit 4; initial signal state is 1
EVENT5 Input BOOL I, Q, M, D, L Event bit 5; initial signal state is 1
EVENT6 Input BOOL I, Q, M, D, L Event bit 6; initial signal state is 1
EVENT7 Input BOOL I, Q, M, D, L Event bit 7; initial signal state is 1
EVENT8 Input BOOL I, Q, M, D, L Event bit 8; initial signal state is 1
EVENT9 Input BOOL I, Q, M, D, L Event bit 9; initial signal state is 1
EVENT10 Input BOOL I, Q, M, D, L Event bit 10; initial signal state is 1
EVENT11 Input BOOL I, Q, M, D, L Event bit 11; initial signal state is 1
EVENT12 Input BOOL I, Q, M, D, L Event bit 12; initial signal state is 1
EVENT13 Input BOOL I, Q, M, D, L Event bit 13; initial signal state is 1
EVENT14 Input BOOL I, Q, M, D, L Event bit 14; initial signal state is 1
EVENT15 Input BOOL I, Q, M, D, L Event bit 15; initial signal state is 1
EVENT16 Input BOOL I, Q, M, D, L Event bit 16; initial signal state is 1
OUT1 Output BOOL I, Q, M, D, L Output bit 1
OUT2 Output BOOL I, Q, M, D, L Output bit 2
OUT3 Output BOOL I, Q, M, D, L Output bit 3
OUT4 Output BOOL I, Q, M, D, L Output bit 4
OUT5 Output BOOL I, Q, M, D, L Output bit 5
OUT6 Output BOOL I, Q, M, D, L Output bit 6
OUT7 Output BOOL I, Q, M, D, L Output bit 7
OUT8 Output BOOL I, Q, M, D, L Output bit 8
OUT9 Output BOOL I, Q, M, D, L Output bit 9
OUT10 Output BOOL I, Q, M, D, L Output bit 10
OUT11 Output BOOL I, Q, M, D, L Output bit 11
Parameters
Timer Functions and Function Blocks
5
5-12
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 5-5 Event Maskable Drum (FB85) Parameters
Parameter Description Memory Area Data Type Declaration
OUT12 Output BOOL I, Q, M, D, L Output bit 12
OUT13 Output BOOL I, Q, M, D, L Output bit 13
OUT14 Output BOOL I, Q, M, D, L Output bit 14
OUT15 Output BOOL I, Q, M, D, L Output bit 15
OUT16 Output BOOL I, Q, M, D, L Output bit 16
Q Output BOOL I, Q, M, D, L A signal state of 1 indicates the last step timed out
OUT_WORD Output WORD I, Q, M, D, L, P Word location to which the drum writes the output
values
ERR_CODE Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
JOG_HIS Static BOOL I, Q, M, D, L Jog history bit
EOD Static BOOL I, Q, M, D, L A signal state of 1 indicates the last step timed out
DSP Static BYTE I, Q, M, D, L, P Drum step preset
DSC Static BYTE I, Q, M, D, L, P Drum step current
DCC Static DWORD I, Q, M, D, L, P Drum count current
DTBP Static WORD I, Q, M, D, L, P Drum time base preset
PREV_TIME Static DWORD I, Q, M, D, L Previous system time
S_PRESET Static ARRAY of
WORD
I, Q, M, D, L Count preset for each step [1 to 16],
where 1 count = 1 msec
OUT_VAL Static ARRAY of
BOOL
I, Q, M, D, L Output values for each step [1 to 16, 0 to 15]
S_MASK Static ARRAY of
BOOL
I, Q, M, D, L Configurable mask for each step [1 to 16, 0 to 15]
Initial signal states are 1
If any of the conditions shown in Table 5-6 occur, the DRUM will remain on
the current step. The signal state of ENO is set to 0 and ERR_CODE is set
appropriately.
Table 5-6 Error Conditions for FB85
ERR_CODE Explanation
W#16#000B LST_STEP value is less than 1 or greater than 16
W#16#000C DSC value is less than 1 or greater than LST_STEP
W#16#000D DSP value is less than 1 or greater than LST_STEP
Error Information
Timer Functions and Function Blocks
5
5-13
S7 Standard Functions Part 2
C79000-G7076-C113-02
Figure 5-4 shows how the DRUM instruction works. If the signal state of
input I0.0 is 1 (activated), the DRUM function block is executed. In this
example, the DRUM advances from step 1 to step 2. The output bits (OUT1,
etc.) and OUT_WORD are set based upon the configured mask for step 2 and
the OUT_VAL bits for step 2.
If the function block is executed without error, the signal states of ENO and
Q4.0 are set to 1 and ERR_CODE is set equal to W#16#0000.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
I 0.0 Q4.0
DRUM
FB85
EN
RESET
JOG
ENO
OUT1
M0.0
M0.1
M4.0
DRUM_EN
M0.2
DB85
LST_STEP
EVENT1
EVENT2
M20.0
EVENT4
M20.1
EVENT6
M20.2
M20.3
EVENT8
EVENT10
M20.4
EVENT12
M20.5
EVENT14
EVENT16
M20.6
M20.7
MB1
EVENT3
EVENT5
EVENT7
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT15
Q
ERR_CODE
M4.1
M4.2
M4.3
M4.4
M4.5
M4.6
M4.7
M5.0
M5.1
M5.2
M5.3
M5.4
EVENT9
EVENT11
EVENT13
EVENT15
OUT14
OUT16
OUT_WORD
M5.5
M5.7
MW8
M5.6
M6.0
MW10
Figure 5-4 Event Maskable Drum (DRUM)
Example
Timer Functions and Function Blocks
5
5-14
S7 Standard Functions Part 2
C79000-G7076-C113-02
Instance DB85
OUT_VAL[2,0] DBX62.0 = FALSE
OUT_VAL [2,1] DBX62.1 = FALSE
OUT_VAL [2,2] DBX62.2 = FALSE
OUT_VAL [2,3] DBX62.3 = FALSE
OUT_VAL [2,4] DBX62.4 = FALSE
OUT_VAL [2,5] DBX62.5 = FALSE
OUT_VAL [2,6] DBX62.6 = FALSE
OUT_VAL [2,7] DBX62.7 = FALSE
OUT_VAL [2,8] DBX63.0 = FALSE
OUT_VAL [2,9] DBX63.1 = FALSE
OUT_VAL [2,10] DBX63.2 = FALSE
OUT_VAL [2,11] DBX63.3 = FALSE
OUT_VAL [2,12] DBX63.4 = FALSE
OUT_VAL [2,13] DBX63.5 = FALSE
OUT_VAL [2,14] DBX63.6 = FALSE
OUT_VAL [2,15] DBX63.7 = FALSE

After execution:
OUT1 M4.0 = TRUE
OUT2 M4.1 = FALSE
OUT3 M4.2 = FALSE
OUT4 M4.3 = FALSE
OUT5 M4.4 = FALSE
OUT6 M4.5 = TRUE
OUT7 M4.6 = FALSE
OUT8 M4.7 = FALSE
OUT9 M5.0 = TRUE
OUT10 M5.1 = TRUE
OUT11 M5.2 = FALSE
OUT12 M5.3 = FALSE
OUT13 M5.4 = FALSE
OUT14 M5.5 = FALSE
OUT15 M5.6 = TRUE
OUT16 M5.7 = FALSE
Q M6.0 = FALSE
OUTWORD MW8 = W#16#4321
ERR_CODE MW10 = W#16#0000
Instance DB85
JOG_HIS DBX12.0 = FALSE
EOD DBX12.1 = FALSE
DSC DBW16 = W#16#0002
DCC DBD18 = DW#16#000000C8
Instance DB85
JOG_HIS DBX12.0 = FALSE
EOD DBX12.1 = FALSE
DSP DBW14 = W#16#0001
DSC DBW16 = W#16#0001
DCC DBD18 = DW#16#0000000A
DTBP DBW22 = W#16#0001
S_PRESET[1] DBW28 = W#16#0064
S_PRESET[2] DBW30 = W#16#00C8
S_MASK [2,0] DBX94.0 = FALSE
S_MASK [2,1] DBX94.1 = TRUE
S_MASK [2,2] DBX94.2 = TRUE
S_MASK [2,3] DBX94.3 = TRUE
S_MASK [2,4] DBX94.4 = TRUE
S_MASK [2,5] DBX94.5 = FALSE
S_MASK [2,6] DBX94.6 = TRUE
S_MASK [2,7] DBX94.7 = TRUE
S_MASK [2,8] DBX95.0 = FALSE
S_MASK [2,9] DBX95.1 = FALSE
S_MASK [2,10] DBX95.2 = TRUE
S_MASK [2,11] DBX95.3 = TRUE
S_MASK [2,12] DBX95.4 = TRUE
S_MASK [2,13] DBX95.5 = TRUE
S_MASK [2,14] DBX95.6 = FALSE
S_MASK [2,15] DBX95.7 = TRUE
RESET M0.0 = FALSE
JOG M0.1 = FALSE
DRUM_EN M0.2 = TRUE
LST_STEP MB1 = B#16#08
EVENT2 M20.0 = TRUE
EVENT4 M20.1 = FALSE
EVENT6 M20.2 = FALSE
EVENT8 M20.3 = FALSE
EVENT10 M20.4 = FALSE
EVENT12 M20.5 = FALSE
EVENT14 M20.6 = FALSE
EVENT16 M20.7 = FALSE
Q M6.0 = FALSE
OUTWORD MW8 = W#16#FFFF
OUT1 M4.0 = TRUE
OUT2 M4.1 = TRUE
OUT3 M4.2 = TRUE
OUT4 M4.3 = TRUE
OUT5 M4.4 = TRUE
OUT6 M4.5 = TRUE
OUT7 M4.6 = TRUE
OUT8 M4.7 = TRUE
OUT9 M5.0 = TRUE
OUT10 M5.1 = TRUE
OUT11 M5.2 = TRUE
OUT12 M5.3 = TRUE
OUT13 M5.4 = TRUE
OUT14 M5.5 = TRUE
OUT15 M5.6 = TRUE
OUT16 M5.7 = TRUE
Before execution: Before execution (continued):
Figure 5-4 Event Maskable Drum (DRUM) (continued)
Timer Functions and Function Blocks
6-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Convert Functions and Function Block
This section describes conversion functions (FCs) and function block (FB)
that you can add to your standard set of instructions to provide additional
programming flexibility.
Section Description Page
6.1 Seven Segment Decoder (SEG): FC93 6-2
6.2 ASCII to Hex (ATH): FC94 6-4
6.3 Hex to ASCII (HTA): FC95 6-6
6.4 Encode Binary Position (ENCO): FC96 6-8
6.5 Decode Binary Position (DECO): FC97 6-9
6.6 Tens Complement (BCDCPL): FC98 6-10
6.7 Sum Number of Bits (BITSUM): FC99 6-11
6.8 Scaling Values (SCALE): FC105 6-12
6.9 Unscaling Values (UNSCALE): FC106 6-14
6.10 Lead/Lag (LEAD_LAG): FB80 6-16
6
6
6-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.1 Seven Segment Decoder (SEG): FC93
The Seven Segment Decoder (SEG) function converts each of the four
hexadecimal digits in the designated source data word (IN) into four
equivalent 7-segment display codes and writes it to the output destination
double word (OUT).
Figure 6-1 shows the relationship between the input hex digits and the output
bit patterns.
Digit Display
0 0 1 1 1 1 1 1 0 0 0 0 0
0 0 0 0 0 1 1 0 0 0 0 1 1
0 1 0 1 1 0 1 1 0 0 1 0 2
0 1 0 0 1 1 1 1 0 0 1 1 3
0 1 1 0 0 1 1 0 0 1 0 0 4
0 1 1 0 1 1 0 1 0 1 0 1 5
0 1 1 1 1 1 0 1 0 1 1 0 6
0 0 0 0 0 1 1 1 0 1 1 1 7
0 1 1 1 1 1 1 1 1 0 0 0 8
0 1 1 0 0 1 1 1 1 0 0 1 9
0 1 1 1 0 1 1 1 1 0 1 0 A
0 1 1 1 1 1 0 0 1 0 1 1 b
0 0 1 1 1 0 0 1 1 1 0 0 C
0 1 0 1 1 1 1 0 1 1 0 1 d
0 1 1 1 1 0 0 1 1 1 1 0 E
0 1 1 1 0 0 0 1 1 1 1 1 F
7-segment
Display
b
c
f
e
a
g
d
g f e d c b a
Figure 6-1 Seven Segment Output Bit Patterns
Table 6-1 describes the Seven Segment Decoder (SEG) parameters.
Table 6-1 Seven Segment Decoder (FC93) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input WORD I, M, D, P, or
constant
Source data word in four hexadecimal digits
OUT Output DWORD Q, M, D, L, P Destination bit pattern in four bytes
Description
Parameters
Convert Functions and Function Block
6
6-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
This function does not detect any error conditions.
Figure 6-2 shows how the SEG instruction works. If the signal state of input
I 0.0 is 1 (activated), the SEG function is executed.
If the function is executed without error, the signal states of ENO and Q 4.0
are set to 1.
I 0.0 Q 4.0
SEG
FC93
EN ENO
IN W#16#1234 OUT MD0
OUT MD0 = DW#16#065B4F66
Figure 6-2 Seven Segment Decoder (SEG)
Error Information
Example
Convert Functions and Function Block
6
6-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.2 ASCII to Hex (ATH): FC94
The ASCII to Hex (ATH) function converts the ASCII character string
pointed to by IN into packed hexadecimal digits and stores these in the
destination table pointed to by OUT. Since 8 bits are required for the ASCII
character and only 4 bits for the hexadecimal digit, the output word length is
only half of the input word length. The ASCII characters are converted and
placed into the hexadecimal output in the same order as they are read in. If
there is an odd number of ASCII characters, the hexadecimal digit is padded
with zeros in the right-most nibble of the last converted hexadecimal digit.
Table 6-2 describes the ASCII to Hex (ATH) parameters.
Table 6-2 ASCII to Hex (FC94) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input Pointer* I, Q, M, D, L Points to the starting location of an ASCII string
N Input INT I, Q, M, L, P Number of ASCII input characters to be converted
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
OUT Output Pointer* Q, M, D, L Points to the starting location of the table
*Double word pointer format for area-crossing register indirect addressing
If any ASCII character is found to be invalid, it is converted as 0. The signal
state of ENO is set to 0 and RET_VAL is set equal to W#16#0007.
Figure 6-3 shows how the ATH instruction works. If the signal state of input
I 0.0 is 1 (activated), the ATH function is executed. The N input parameter of
5 indicates that five ASCII characters are to be converted. The ASCII
characters are stored in data block 1 beginning at the IN pointer location,
DB1.DBX10.0. The output string will be located at the OUT pointer location
beginning at DB2.DBX0.0 (data block 2). Since there is an odd number of
ASCII input characters, the last hexadecimal digit contains all zeros in the
right-most nibble, producing the hexadecimal value 0xC0. (Refer to
Figure 6-4 for the equivalent hexadecimal value for each ASCII character.)
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
Description
Parameters
Error Information
Example
Convert Functions and Function Block
6
6-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
I 0.0 Q 4.0
ATH
FC94
EN ENO
IN
N
RET_VAL P#DB1.DBX10.0
W#16#05
MW0
OUT P#DB2.DBX0.0
Before execution:
ASCII string representation: B90AC
IN DBB10 = B#16#42
DBB11 = B#16#39
DBB12 = B#16#30
DBB13 = B#16#41
DBB14 = B#16#43
After execution:
HEX byte representation: B90AC0
OUT DBB0 = B#16#B9
DBB1 = B#16#0A
DBB2 = B#16#C0
Figure 6-3 ASCII to Hex (ATH)
ASCII Character ASCII Hex Value Converted Hex Digit
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
30
31
32
33
34
35
36
37
38
39
41
42
43
44
45
46
Figure 6-4 ASCII Characters and Equivalent Hexadecimal Values
Convert Functions and Function Block
6
6-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.3 Hex to ASCII (HTA): FC95
The Hex to ASCII (HTA) function converts packed hexadecimal digits,
pointed to by IN, and stores them in the destination string pointed to by OUT.
Since 8 bits are required for the character and only 4 bits for the hex digit,
the output word length is two times that of the input word length. Each nibble
of the hexadecimal digit is converted into a character in the same order as
they are read in (left-most nibble of a hexadecimal digit is converted first,
followed by the right-most nibble of that same digit).
Table 6-3 describes the Hex to ASCII (HTA) parameters.
Table 6-3 Hex to ASCII (FC95) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input Pointer* I, Q, M, D Points to the starting location of the hexadecimal
digit string
N Input WORD I, Q, M, L, P Number of hex input bytes to be converted
OUT Output Pointer* Q, M, D, L Points to the starting location of the destination table
*Double word pointer format for area-crossing register indirect addressing
This function does not detect any error conditions.
Description
Parameters
Error Information
Convert Functions and Function Block
6
6-7
S7 Standard Functions Part 2
C79000-G7076-C113-02
Figure 6-5 shows how the HTA instruction works. If the signal state of input
I 0.0 is 1 (activated), the HTA function is executed. The N input parameter of
3 indicates that three hexadecimal characters are to be converted. The hex
bytes are stored in data block 1 beginning at the IN pointer location,
DB1.DBX10.0. The output string will be located at the OUT pointer location
beginning at DB2.DBX0.0 (data block 2). (Refer to Figure 6-6 for the ASCII
equivalent for each hex value.)
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1.
I 0.0 Q 4.0
HTA
FC95
EN ENO
IN
N
OUT P#DB1.DBX10.0
W#16#03
P#DB2.DBX0.0
Before execution:
HEX byte representation: F97AC1
IN DBB10 = B#16#F9
DBB11 = B#16#7A
DBB12 = B#16#C1
After execution:
ASCII byte representation: F97AC1
OUT DBB0 = B#16#46
DBB1 = B#16#39
DBB2 = B#16#37
DBB3 = B#16#41
DBB4 = B#16#43
DBB5 = B#16#31
Figure 6-5 Hex to ASCII (HTA)
Hex Digit ASCII Hex Value Converted ASCII
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
30
31
32
33
34
35
36
37
38
39
41
42
43
44
45
46
Figure 6-6 Hexadecimal Digits and Equivalent ASCII Hex Values
Example
Convert Functions and Function Block
6
6-8
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.4 Encode Binary Position (ENCO): FC96
The Encode Binary Position (ENCO) function converts the contents of IN to
the 5-bit binary number corresponding to the bit position of the right-most set
bit in IN and returns the result as the functions value. If IN is either 0000
0001 or 0000 0000, a value of 0 is returned.
Table 6-4 describes the Encode Binary Position (ENCO) parameters.
Table 6-4 Encode Binary Position (FC96) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input DWORD I, M, D, L, P, or
constant
Value to be encoded
RET_VAL Output INT Q, M, D, L, P Value returned (contains 5-bit binary number)
This function does not detect any error conditions.
Figure 6-7 shows how the ENCO instruction works. If the signal state of
input I 0.0 is 1 (activated), the ENCO function is executed.
If the function executes without error, the signal states of ENO and Q 4.0 are
set to 1.
I 0.0 Q 4.0
ENCO
FC96
EN ENO
IN
RET_VAL
RET_VAL MW0 = 3
MW0
DW#16#12345678
Figure 6-7 Encode Binary Position (ENCO)
Description
Parameters
Error Information
Example
Convert Functions and Function Block
6
6-9
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.5 Decode Binary Position (DECO): FC97
The Decode Binary Position (DECO) function converts a 5-bit binary number
(0 31) from input IN to a value by setting the corresponding bit position in
the functions return value. If IN is greater than 31, a modulo 32 operation is
performed to get a 5-bit binary number.
Table 6-5 describes the Decode Binary Position (DECO) parameters.
Table 6-5 Decode Binary Position (FC97) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input WORD I, M, D, L, P, or
constant
Variable to decode
RET_VAL Output DWORD Q, M, D, L, P Value returned
This function does not detect any error conditions.
Figure 6-8 shows how the DECO instruction works. If the signal state of
input I 0.0 is 1 (activated), the DECO function is executed.
If the function executes without error, the signal states of ENO and Q 4.0 are
set to 1.
RET_VAL MD0 = DW#16#00000008
I 0.0 Q 4.0
DECO
FC97
EN ENO
IN
RET_VAL
W#16#0003
MD0
Figure 6-8 Decode Binary Position (DECO)
Description
Parameters
Error Information
Example
Convert Functions and Function Block
6
6-10
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.6 Tens Complement (BCDCPL): FC98
The Tens Complement (BCDCPL) function returns the Tens complement of a
7-digit BCD number IN. The mathematical formula for this operation is the
following:
10000000 (in BCD)
7-digit BCD value
= Tens complement value (in BCD)
Table 6-6 describes the Tens Complement (BCDCPL) parameters.
Table 6-6 Tens Complement (FC98) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input DWORD I, M, D, L, P, or
constant
7-digit BCD number
RET_VAL Output DWORD Q, M, D, L, P Value returned
This function does not detect any error conditions.
Figure 6-9 shows how the BCDCPL instruction works. If the signal state of
input I 0.0 is 1 (activated), the BCDCPL function is executed.
If the function executes without error, the signal states of ENO and Q 4.0 are
set to 1.
I 0.0 Q 4.0
BCDCPL
FC98
EN ENO
IN
RET_VAL
DW#16#01234567
MD0
RET_VAL MD0 = DW#16#08765433
Figure 6-9 Tens Complement (BCDCPL)
Description
Parameters
Error Information
Example
Convert Functions and Function Block
6
6-11
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.7 Sum Number of Bits (BITSUM): FC99
The Sum Number of Bits (BITSUM) function counts the number of bits that
are set to a value of 1 in the input IN and returns this as the functions value.
Table 6-7 describes the Sum Number of Bits (BITSUM) parameters.
Table 6-7 Sum Number of Bits (FC99) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input DWORD I, M, D, L, P, or
constant
Variable to count bits in
RET_VAL Output INT Q, M, D, L, P Value returned
This function does not detect any error conditions.
Figure 6-10 shows how the BITSUM instruction works. If the signal state of
input I 0.0 is 1 (activated), the BITSUM function is executed. In this
example, the value returned in MW0 is 13 (D in hexadecimal notation),
which is the sum of bits set to 1 in the double word input hex value
DW#16#12345678.
If the function executes without error, the signal states of ENO and Q4.0 are
set to 1.
I 0.0 Q 4.0
BITSUM
FC99
EN ENO
IN
RET_VAL
DW#16#12345678
MW0
RET_VAL MW0 = W#16#000D
Figure 6-10 Sum Number of Bits (BITSUM)
Description
Parameters
Error Information
Example
Convert Functions and Function Block
6
6-12
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.8 Scaling Values (SCALE): FC105
The Scaling Values (SCALE) function takes an integer value (IN) and
converts it to a real value in engineering units scaled between a low and a
high limit (LO_LIM and HI_LIM). The result is written to OUT. The SCALE
function uses the equation:
OUT = [ FLOAT (IN) K1/(K2K1) * (HI_LIM LO_LIM)] + LO_LIM
The constants K1 and K2 are set based upon whether the input value is
BIPOLAR or UNIPOLAR.
S BIPOLAR: The input integer value is assumed to be between
27648 and 27648, therefore,
K1 = 27648.0 and K2 = +27648.0
S UNIPOLAR: The input integer value is assumed to be between
0 and 27648, therefore,
K1 = 0.0 and K2 = +27648.0
If the input integer value is outside the specified range for its type
(BIPOLAR or UNIPOLAR), the output (OUT) is clamped to the nearer of
either LO_LIM or HI_LIM, and an error is returned.
Reverse scaling can be obtained by programming LO_LIM > HI_LIM. With
reverse scaling, the value of the output decreases as the value of the input
increases.
Table 6-8 describes the Scaling Values (SCALE) parameters.
Table 6-8 Scaling Values (FC105) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
executed without error
IN Input INT I, Q, M, D, L,
P, or constant
The input value to be scaled to a REAL value in
engineering units
HI_LIM Input REAL I, Q, M, D, L,
P, or constant
Upper limit in engineering units
LO_LIM Input REAL I, Q, M, D, L,
P, or constant
Lower limit in engineering units
BIPOLAR Input BOOL I, Q, M, D, L A signal state of 1 indicates the input value is
bipolar and a signal state of 0 indicates unipolar
OUT Output REAL I, Q, M, D, L,
P, or constant
The result of the scale conversion
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
Description
Parameters
Convert Functions and Function Block
6
6-13
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the input integer value is outside the specified range for its type
(BIPOLAR or UNIPOLAR), the output (OUT) is clamped to the nearer of
either LO_LIM or HI_LIM and an error is returned. The signal state of ENO
is set to 0 and RET_VAL is set equal to W#16#0008.
Figure 6-11 shows how the SCALE instruction works. If the signal state of
input I0.0 is 1 (activated), the SCALE function is executed. In this example,
the integer value 22 will be converted to a REAL value scaled between 0.0
and 100.0 and written to OUT. The input value is BIPOLAR as indicated by
the signal state of I2.0.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
I 0.0 Q4.0
SCALE
FC105
EN ENO
IN
HI_LIM
LO_LIM
RET_VAL MW10
MD20
MD30
MW0
BIPOLAR
Before execution:
IN MW10 = 22
HI_LIM MD20 = 100.0
LO_LIM MD30 = 0.0
OUT MD40 = 0.0
BIPOLAR I2.0 = TRUE
After execution:
OUT MD40 = 50.03978588
I2.0
OUT MD40
Figure 6-11 Scaling Values (SCALE)
Error Information
Example
Convert Functions and Function Block
6
6-14
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.9 Unscaling Values (UNSCALE): FC106
The Unscaling Values (UNSCALE) function takes a real input value (IN) in
engineering units scaled between a low and a high limit (LO_LIM and
HI_LIM) and converts it to an integer value. The result is written to OUT.
The UNSCALE function uses the equation:
OUT = [ (INLO_LIM/HI_LIMLO_LIM) * (K2K1) ] + K1
and sets the constants K1 and K2 based upon whether the input value is
BIPOLAR or UNIPOLAR.
S BIPOLAR: The input real value is assumed to be between
27648 and 27648, therefore,
K1 = 27648.0 and K2 = +27648.0
S UNIPOLAR: The input real value is assumed to be between
0 and 27648, therefore
K1 = 0.0 and K2 = +27648.0
If the input value is outside the LO_LIM and HI_LIM range, the output
(OUT) is clamped to the nearer of either the low limit or the high limit of the
specified range for its type (BIPOLAR or UNIPOLAR), and an error is
returned.
Table 6-9 describes the Unscaling Values (UNSCALE) parameters.
Table 6-9 Unscaling Values (FC106) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN Input REAL I, Q, M, D, L,
P, or constant
The input value to be unscaled to an integer value
HI_LIM Input REAL I, Q, M, D, L,
P, or constant
Upper limit in engineering units
LO_LIM Input REAL I, Q, M, D, L,
P, or constant
Lower limit in engineering units
BIPOLAR Input BOOL I, Q, M, D, L A signal state of 1 indicates the input value is
bipolar and a signal state of 0 indicates unipolar
OUT Output INT I, Q, M, D, L,
P, or constant
The result of the unscale conversion
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
Description
Parameters
Convert Functions and Function Block
6
6-15
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the input real value is outside the LO_LIM and HI_LIM range the output
(OUT) is clamped to the nearer of either the low limit or the high limit of the
specified range for its type (BIPOLAR or UNIPOLAR), and an error is
returned. The signal state of ENO is set to 0 and RET_VAL is set equal to
W#16#0008.
Figure 6-12 shows how the UNSCALE instruction works. If the signal state
of input I0.0 is 1 (activated), the UNSCALE function is executed. In this
example, the REAL value 50.03978588, scaled between 0.0 and 100.0 will
be converted to an INTEGER value and written to OUT. The input value is
BIPOLAR as indicated by the signal state of I2.0.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1 and RET_VAL is set equal to W#16#0000.
I 0.0 Q4.0
UNSCALE
FC106
EN ENO
IN
HI_LIM
LO_LIM
RET_VAL MD10
MD20
MD30
MW0
BIPOLAR
Before execution:
IN MD10 = 50.03978588
HI_LIM MD20 = 100.0
LO_LIM MD30 = 0.0
OUT MD40 = 0.0
BIPOLAR I2.0 = TRUE
After execution:
OUT MD40 = 22
I2.0
OUT MD40
Figure 6-12 Unscaling Values (UNSCALE)
Error Information
Example
Convert Functions and Function Block
6
6-16
S7 Standard Functions Part 2
C79000-G7076-C113-02
6.10 Lead/Lag Algorithm (LEAD_LAG): FB80
The Lead/Lag Algorithm (LEAD_LAG) function block allows signal
processing to be done on an analog variable. An output (OUT) is calculated
based on an input (IN) and the specified gain (GAIN), lead (LD_TIME), and
lag (LG_TIME) values. The gain value must be greater than zero. The
LEAD_LAG algorithm uses the following equation:
LG_TIME + SAMPLE_T
where OUT =
LG_TIME
PREV_OUT + GAIN
LG_TIME + SAMPLE_T
LD_TIME + SAMPLE_T
IN GAIN
LG_TIME + SAMPLE_T
LD_TIME
PREV_IN
Typically, LEAD_LAG is used in conjunction with loops as a compensator in
dynamic feed-forward control. LEAD_LAG consists of two parts. Phase lead
shifts the phase of the function blocks output so that it leads the input
whereas phase lag shifts the output so that it lags the input. Because the lag
operation is equivalent to an integration, it can be used as a noise suppressor
or a low-pass filter. A lead operation is equivalent to a differentiation and is
thus a high-pass filter. LEAD_LAG combined can cause the output phase to
lag input at low frequency, and to lead input at high frequency, and can thus
be used as a band-pass filter.
Description
Convert Functions and Function Block
6
6-17
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 6-10 describes the Lead/Lag (LEAD_LAG) parameters.
Table 6-10 Lead/Lag (FB80) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
block is executed without error
IN Input REAL I, Q, M, D, L,
P, or constant
The input value of the current sample period to be
processed
SAMPLE_T Input INT I, Q, M, D, L,
P, or constant
Sample time
OUT Output REAL I, Q, M, D, L,
P, or constant
The result of the LEAD_LAG operation
ERR_CODE Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
LD_TIME Static REAL I, Q, M, D, L,
P, or constant
Lead time in minutes
LG_TIME Static REAL I, Q, M, D, L,
P, or constant
Lag time in minutes
GAIN Static REAL I, Q, M, D, L,
P, or constant
Gain as % / % (the ratio of the change in output to
the change in input as a steady state).
PREV_IN Static REAL I, Q, M, D, L,
P, or constant
Previous input
PREV_OUT Static REAL I, Q, M, D, L,
P, or constant
Previous output
If GAIN is less than or equal to 0, the function block is not executed. The
signal state of ENO is set to 0 and ERR_CODE is set equal to W#16#0009.
Parameters
Error Information
Convert Functions and Function Block
6
6-18
S7 Standard Functions Part 2
C79000-G7076-C113-02
Figure 6-13 shows how the LEAD_LAG instruction works. If the signal state
of input I0.0 is 1 (activated), the LEAD_LAG function block is executed. In
this example, the input value (IN) 2.0 is processed using the LEAD_LAG
algorithm to produce the output (OUT).
If the function block is executed without error, the signal states of ENO and
Q4.0 are set to 1 and ERR_CODE is set equal to W#16#0000.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
Instance DB80
LD_TIME DBD12 = 2.0
LG_TIME DBD16 = 2.0
GAIN DBD20 = 1.0
PREV_IN DBD24 = 6.0
PREV_OUT DBD28 = 6.0
I 0.0 Q 4.0
LEAD_LAG
FB80
EN ENO
IN
SAMPLE_T
OUT MD10
10
MD20
ERR_CODE
DB80
Before execution:
IN MD10 = 2.0
OUT MD20 = 0.0
After execution:
Instance DB80
PREV_IN DBD24 = 2.0
PREV_OUT DBD28 = 2.0
OUT MD20 = 2.0
MW0
Figure 6-13 LEAD/LAG Algorithm (LEAD_LAG)
Example
Convert Functions and Function Block
7-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Floating Point Math Function
This section describes the floating point math function (FC) that you can add
to your standard set of instructions to provide additional programming
flexibility.
Section Description Page
7.1 Standard Deviation (DEV): FC102 7-2
7
7
7-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
7.1 Standard Deviation (DEV): FC102
The Standard Deviation (DEV) function computes the standard deviation of a
set of values stored in a table (TBL) and stores the result in OUT. The
standard deviation is computed according to the following formula:
(N * SqSum) Sum
2
N * (N 1)
Standard
Deviation
=
where: Sum = The sum of values in TBL
N = The number of values in TBL
SqSum = Sum of all the values in TBL squared
All calculations use IEEE floating point values with any necessary type
conversions being done automatically by the function call.
S The first entry in the table contains the number of entries of the table
(table length).
S The second entry in the table contains the first table value.
S The size of the table entries and the computed value (OUT) are
determined by E_TYPE.
Table 7-1 describes the Standard Deviation (DEV) parameters.
Table 7-1 Standard Deviation (FC102) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
TBL Input Pointer* I, Q, M, D Points to the starting location of a table of values
OUT Input Pointer* I, Q, M, D Points to location of the computed standard
deviation value
E_TYPE Input BYTE I, Q, M, D, L,P Indicates the data type of the table entries. Valid data
types for the DEV function are as follows:
B#16#05 = INT
B#16#07 = DINT
B#16#08 = REAL
RET_VAL Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
*Double word pointer format for area-crossing register indirect addressing
Description
Parameters
Floating Point Math Function
7
7-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
If any of the conditions shown in Table 7-2 occur, the function is not
executed. The signal state of ENO is set to 0 and the return value is set
appropriately.
Table 7-2 Error Conditions for FC102
RET_VAL Explanation
W#16#0001 Invalid memory type specified for a function parameter
W#16#0002 Invalid E_TYPE
W#16#0004 The table length is zero
Figure 7-1 shows how the Standard Deviation instruction works. If the signal
state of input I0.0 is 1 (activated), the DEV function is executed. In this
example, there are five table values as indicated by the first word in the table.
The data type of the table values is REAL as indicated by E_TYPE.
If the function is executed without error, the signal states of ENO and Q4.0
are set to 1, and RET_VAL is set equal to W#16#0000.
OUT DBD130 = 12.19836055
DEV
FC102
EN ENO
TBL
OUT
E_TYPE
I 0.0 Q4.0
RET_VAL P#DB1.DBX100.0
P#DB1.DBX130.0
B#16#08
MW0
Before execution:
TBL (table length) DBW100=W#16#0005
DBD102 = 2.0
DBD106 = 4.0
DBD110 = 8.0
DBD114 = 16.0
DBD118 = 32.0
OUT DBD130 = 0.0
After execution:
Figure 7-1 Standard Deviation (DEV)
Error Information
Example
Floating Point Math Function
7
7-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
Floating Point Math Function
8-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Compare Function Blocks
This section describes compare function blocks (FBs) that you can add to
your standard set of instructions to provide additional programming
flexibility.
Section Description Page
8.1 Index Matrix Compare (IMC): FB83 8-2
8.2 Scan Matrix Compare (SMC): FB84 8-6
8
8
8-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
8.1 Index Matrix Compare (IMC): FB83
The Index Matrix Compare (IMC) function block compares the signal state
of up to 16 programmed input bits (IN_BIT0 to IN_BIT15) with the
corresponding bits of a compare mask. Up to 16 steps with masks can be
programmed. IN_BIT0 is compared to CMP_VAL [x, 0], where x is the step
number, IN_BIT1 is compared to CMP_VAL [x,1], etc. The step number of
the mask to compare against is indicated by the value of CMP_STEP.
Unprogrammed input bits or unprogrammed bits of the masks have a default
signal state of FALSE. If a match is found, the signal state of output (OUT) is
set to 1, otherwise, it is set to 0.
Description
Compare Function Blocks
8
8-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 8-1 describes the Index Matrix Compare (IMC) parameters.
Table 8-1 Index Matrix Compare (FB83) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN_BIT0 Input BOOL I, Q, M, D, L Input bit 0 to be compared to bit 0 of the mask
IN_BIT1 Input BOOL I, Q, M, D, L Input bit 1 to be compared to bit 1 of the mask
IN_BIT2 Input BOOL I, Q, M, D, L Input bit 2 to be compared to bit 2 of the mask
IN_BIT3 Input BOOL I, Q, M, D, L Input bit 3 to be compared to bit 3 of the mask
IN_BIT4 Input BOOL I, Q, M, D, L Input bit 4 to be compared to bit 4 of the mask
IN_BIT5 Input BOOL I, Q, M, D, L Input bit 5 to be compared to bit 5 of the mask
IN_BIT6 Input BOOL I, Q, M, D, L Input bit 6 to be compared to bit 6 of the mask
IN_BIT7 Input BOOL I, Q, M, D, L Input bit 7 to be compared to bit 7 of the mask
IN_BIT8 Input BOOL I, Q, M, D, L Input bit 8 to be compared to bit 8 of the mask
IN_BIT9 Input BOOL I, Q, M, D, L Input bit 9 to be compared to bit 9 of the mask
IN_BIT10 Input BOOL I, Q, M, D, L Input bit 10 to be compared to bit 10 of the mask
IN_BIT11 Input BOOL I, Q, M, D, L Input bit 11 to be compared to bit 11 of the mask
IN_BIT12 Input BOOL I, Q, M, D, L Input bit 12 to be compared to bit 12 of the mask
IN_BIT13 Input BOOL I, Q, M, D, L Input bit 13 to be compared to bit 13 of the mask
IN_BIT14 Input BOOL I, Q, M, D, L Input bit 14 to be compared to bit 14 of the mask
IN_BIT15 Input BOOL I, Q, M, D, L Input bit 15 to be compared to bit 15 of the mask
CMP_STEP Input BYTE I, Q, M, D, L, P The step number of the mask to compare against
OUT Output BOOL I, Q, M, D, L A signal state of 1 indicates a match was found and
a signal state of 0 indicates no match was found
ERR_CODE Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
CMP_VAL Static ARRAY
OF BOOL
I, Q, M, D, L The compare masks [0 to 15, 0 to 15], where the
first number of the index is the step number and the
second number is the bit number of the mask
Parameters
Compare Function Blocks
8
8-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
If the value of CMP_STEP is greater than 15, the function block is not
executed. The signal state of ENO is set to 0 and ERR_CODE is set equal to
W#16#000A.
Figure 8-1 shows how the IMC instruction works. If the signal state of input
I0.0 is 1 (activated), the IMC function block is executed. In this example, all
16 input bits are compared against the mask for step 2 (as indicated by
CMP_STEP). The signal state of OUT is set TRUE since the input bits match
the mask for step 2.
If the function block is executed without error, the signal states of ENO and
Q4.0 are set to 1 and ERR_CODE is set equal to W#16#0000.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
Error Information
Example
Compare Function Blocks
8
8-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
IN_BIT0 M0.0 = TRUE <compare to> CMP_VAL [2, 0] DBX12.0 = TRUE
IN_BIT1 M0.1 = TRUE <compare to> CMP_VAL [2, 1] DBX12.1 = TRUE
IN_BIT2 M0.2 = FALSE <compare to> CMP_VAL [2, 2] DBX12.2 = FALSE
IN_BIT3 M0.3 = TRUE <compare to> CMP_VAL [2, 3] DBX12.3 = TRUE
IN_BIT4 M0.4 = TRUE <compare to> CMP_VAL [2, 4] DBX12.4 = TRUE
IN_BIT5 M0.5 = FALSE <compare to> CMP_VAL [2, 5] DBX12.5 = FALSE
IN_BIT6 M0.6 = TRUE <compare to> CMP_VAL [2, 6] DBX12.6 = TRUE
IN_BIT7 M0.7 = TRUE <compare to> CMP_VAL [2, 7] DBX12.7 = TRUE
IN_BIT8 M1.0 = FALSE <compare to> CMP_VAL [2, 8] DBX13.0 = FALSE
IN_BIT9 M1.1 = TRUE <compare to> CMP_VAL [2, 9] DBX13.1 = TRUE
IN_BIT10 M1.2 = TRUE <compare to> CMP_VAL [2, 10] DBX13.2 = TRUE
IN_BIT11 M1.3 = FALSE <compare to> CMP_VAL [2, 11] DBX13.3 = FALSE
IN_BIT12 M1.4 = TRUE <compare to> CMP_VAL [2, 12] DBX13.4 = TRUE
IN_BIT13 M1.5 = TRUE <compare to> CMP_VAL [2, 13] DBX13.5 = TRUE
IN_BIT14 M1.6 = FALSE <compare to> CMP_VAL [2, 14] DBX13.6 = FALSE
IN_BIT15 M1.7 = TRUE <compare to> CMP_VAL [2, 15] DBX13.7 = TRUE
OUT Q2.0 = FALSE
Before execution: Instance DB83
OUT Q2.0 = TRUE
After execution:
I 0.0 Q4.0
IMC
FB83
EN
IN_BIT0
IN_BIT1
ENO
OUT
CMP_STEP
M0.0
M0.1
B#16#02
Q2.0
ERR_CODE MW0
IN_BIT2
M0.2
DB83
IN_BIT3
M0.3
IN_BIT4
M0.4
IN_BIT5
IN_BIT6
M0.5
M0.6
IN_BIT7
M0.7
IN_BIT8
M1.0
M1.1
IN_BIT9
IN_BIT10
M1.2
IN_BIT11
M1.3
IN_BIT12
IN_BIT13
M1.4
M1.5
IN_BIT14
M1.6
IN_BIT15
M1.7
Note: Only the values that form the mask for step 2 are shown. Other steps are programmed similarly.
Figure 8-1 Index Matrix Compare (IMC)
Compare Function Blocks
8
8-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
8.2 Scan Matrix Compare (SMC): FB84
The Scan Matrix Compare (SMC) function block compares the signal state of
up to 16 programmed input bits (IN_BIT0 to IN_BIT15) with the
corresponding bits of the compare mask of each step, beginning with step 1
and progressing through the last step programmed (LAST) or until a match is
found. IN_BIT0 is compared to CMP_VAL [x,0], where x is the step number,
IN_BIT1 is compared to CMP_VAL [x,1], etc. When a match is found, the
signal state of output (OUT) is set to 1 and the step number with the
matching mask is written to OUT_STEP. Unprogrammed input bits or
unprogrammed bits of the masks have a default signal state of FALSE. If
more than one step has a matching mask, only the first one encountered is
indicated in OUT_STEP. If no match is found, the signal state of output
(OUT) is set to 0 and OUT_STEP is one greater than LAST.
Table 8-2 describes the Scan Matrix Compare (SMC) parameters.
Table 8-2 Scan Matrix Compare (FB84) Parameters
Parameter Declaration Data Type Memory Area Description
EN Input BOOL I, Q, M, D, L Enable input with signal state of 1 activates the box
ENO Output BOOL I, Q, M, D, L Enable output has a signal state of 1 if the function
is executed without error
IN_BIT0 Input BOOL I, Q, M, D, L Input bit 0 to be compared to bit 0 of the mask
IN_BIT1 Input BOOL I, Q, M, D, L Input bit 1 to be compared to bit 1 of the mask
IN_BIT2 Input BOOL I, Q, M, D, L Input bit 2 to be compared to bit 2 of the mask
IN_BIT3 Input BOOL I, Q, M, D, L Input bit 3 to be compared to bit 3 of the mask
IN_BIT4 Input BOOL I, Q, M, D, L Input bit 4 to be compared to bit 4 of the mask
IN_BIT5 Input BOOL I, Q, M, D, L Input bit 5 to be compared to bit 5 of the mask
IN_BIT6 Input BOOL I, Q, M, D, L Input bit 6 to be compared to bit 6 of the mask
IN_BIT7 Input BOOL I, Q, M, D, L Input bit 7 to be compared to bit 7 of the mask
IN_BIT8 Input BOOL I, Q, M, D, L Input bit 8 to be compared to bit 8 of the mask
IN_BIT9 Input BOOL I, Q, M, D, L Input bit 9 to be compared to bit 9 of the mask
IN_BIT10 Input BOOL I, Q, M, D, L Input bit 10 to be compared to bit 10 of the mask
IN_BIT11 Input BOOL I, Q, M, D, L Input bit 11 to be compared to bit 11 of the mask
IN_BIT12 Input BOOL I, Q, M, D, L Input bit 12 to be compared to bit 12 of the mask
IN_BIT13 Input BOOL I, Q, M, D, L Input bit 13 to be compared to bit 13 of the mask
IN_BIT14 Input BOOL I, Q, M, D, L Input bit 14 to be compared to bit 14 of the mask
IN_BIT15 Input BOOL I, Q, M, D, L Input bit 15 to be compared to bit 15 of the mask
OUT Output BOOL I, Q, M, D, L A signal state of 1 indicates a match was found and
a signal state of 0 indicates no match was found
ERR_CODE Output WORD I, Q, M, D, L, P Returns a value of W#16#0000 if the instruction
executes without error; see Error Information for
values other than W#16#0000
Description
Parameters
Compare Function Blocks
8
8-7
S7 Standard Functions Part 2
C79000-G7076-C113-02
Table 8-2 Scan Matrix Compare (FB84) Parameters
Parameter Description Memory Area Data Type Declaration
OUT_STEP Output BOOL I, Q, M, D, L, P Contains the step number with the matching mask,
or contains the step number one greater than LAST
if no match is found
LAST Static BYTE I, Q, M, D, L, P Specifies the step number of the last step to be
scanned for a matching mask
CMP_VAL Static ARRAY
OF BOOL
I, Q, M, D, L The compare masks [0 to 15, 0 to 15], where the
first number of the index is the step number and the
second number is the bit number of the mask
If the value of LAST is greater than 15, the function block is not executed.
The signal state of EN0 is set to 0 and ERR_CODE is set equal to
W#16#000E.
Figure 8-2 shows how the SMC instruction works. If the signal state of input
I0.0 is 1 (activated), the SMC function block is executed. In this example, all
16 input bits are compared against the masks for steps 0 through 5 (as
indicated by LAST) or until a match is found. Only the masks for steps 0
through 2 are scanned since the mask for step 2 matches the input bits.
If the function block is executed without error, the signal states of ENO and
Q4.0 are set to 1 and ERR_CODE is set equal to W#16#0000.
Note
Initialization of static parameters may be accomplished by using the Data
Block Editor.
Error Information
Example
Compare Function Blocks
8
8-8
S7 Standard Functions Part 2
C79000-G7076-C113-02
OUT Q2.0 = FALSE
OUT_STEP MB10 = B#16#00
Instance DB84
LAST DB84 = B#16#05
IN_BIT0 M0.0 = TRUE <compare to> CMP_VAL [2, 0] DBX12.0 = TRUE
IN_BIT1 M0.1 = TRUE <compare to> CMP_VAL [2, 1] DBX12.1 = TRUE
IN_BIT2 M0.2 = FALSE <compare to> CMP_VAL [2, 2] DBX12.2 = FALSE
IN_BIT3 M0.3 = TRUE <compare to> CMP_VAL [2, 3] DBX12.3 = TRUE
IN_BIT4 M0.4 = TRUE <compare to> CMP_VAL [2, 4] DBX12.4 = TRUE
IN_BIT5 M0.5 = FALSE <compare to> CMP_VAL [2, 5] DBX12.5 = FALSE
IN_BIT6 M0.6 = TRUE <compare to> CMP_VAL [2, 6] DBX12.6 = TRUE
IN_BIT7 M0.7 = TRUE <compare to> CMP_VAL [2, 7] DBX12.7 = TRUE
IN_BIT8 M1.0 = FALSE <compare to> CMP_VAL [2, 8] DBX13.0 = FALSE
IN_BIT9 M1.1 = TRUE <compare to> CMP_VAL [2, 9] DBX13.1 = TRUE
IN_BIT10 M1.2 = TRUE <compare to> CMP_VAL [2, 10] DBX13.2 = TRUE
IN_BIT11 M1.3 = FALSE <compare to> CMP_VAL [2, 11] DBX13.3 = FALSE
IN_BIT12 M1.4 = TRUE <compare to> CMP_VAL [2, 12] DBX13.4 = TRUE
IN_BIT13 M1.5 = TRUE <compare to> CMP_VAL [2, 13] DBX13.5 = TRUE
IN_BIT14 M1.6 = FALSE <compare to> CMP_VAL [2, 14] DBX13.6 = FALSE
IN_BIT15 M1.7 = TRUE <compare to> CMP_VAL [2, 15] DBX13.7 = TRUE
Before execution: Instance DB84
OUT Q2.0 = TRUE
OUT_STEP MB10 = B#16#02
After execution:
I 0.0 Q4.0
SMC
FB84
EN
IN_BIT0
IN_BIT1
ENO
OUT
M0.0
M0.1
Q2.0
OUT_STEP MB10
IN_BIT2
M0.2
DB84
IN_BIT3
M0.3
IN_BIT4
M0.4
IN_BIT5
IN_BIT6
M0.5
M0.6
IN_BIT7
M0.7
IN_BIT8
M1.0
M1.1
IN_BIT9
IN_BIT10
M1.2
IN_BIT11
M1.3
IN_BIT12
IN_BIT13
M1.4
M1.5
IN_BIT14
M1.6
IN_BIT15
M1.7
Note: Only the values that form the mask for step 2 are shown. Other steps are programmed similarly.
Figure 8-2 Scan Matrix Compare (SMC)
Compare Function Blocks
Glossary-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
.Glossary
A
A type of addressing which indicates the actual location of a particular unit
of data in storage in a CPU. Absolute addressing enables you to reference an
I/O point, for example, using an address that includes the type of point (I =
input, Q = output), the number of the I/O module, and the individual point.
For example, output Q 4.0. The programmable logic controller interprets
absolute addresses without the aid of a symbol table. See Symbolic
Addressing.
An actual parameter is an address or value which is provided as an input or
output during the call of a function block (FB) or function (FC). Actual
parameters correspond to the formal parameters that are declared in the
variable declaration table of the FB or FC.
The address of a ladder logic instruction indicates a constant or the location
where the instruction finds a value on which to perform an operation. The
address can have a symbolic name, an absolute designation, or a combination
of the two. The address can point to any of the following items:
S A constant, the value of a timer or counter, or an ASCII character string
S A location in the status word of the programmable logic controller
S A data block and a location within the data block area
S A function (FC), function block (FB), integrated system function (SFC),
or integrated system function block (SFB) and the number of the function
or block
S A label for a jump instruction
S An address identifier and a location within the memory area that is
indicated by the address identifier (for example, I 1.0)
S The number of a timer or counter
The address of an instruction is sometimes referred to as the operand of the
instruction.
Absolute
Addressing
Actual Parameter
Address
Glossary-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
An address identifier is that part of the address of an instruction which
provides such information as the memory area in which an instruction finds a
value (data object) on which to perform an operation size of the value (data
object) on which the instruction is to perform its operation. For example, in
the address IB10, IB is the address identifier (where I indicates the
input area of memory and B indicates a byte in that area).
B
Bit 8 of the status word is called the binary result bit (BR bit). The BR bit
forms a link between the processing of bits and words. This bit enables your
program to interpret the result of a word operation as a binary result and to
integrate this result in a binary logic chain.
For example, the BR bit makes it possible for you to write a function block
(FB) or a function (FC) in statement list (STL, see the STEP 7 Statement List
Reference Manual) and then call the FB or FC from ladder logic (LAD).
When writing a function block or function that you want to call from LAD,
no matter whether you write the FB or FC in STL or LAD, you are
responsible for managing the BR bit. The BR bit corresponds to the enable
output (ENO) of a LAD box. You should use the SAVE instruction (in STL)
or the (SAVE) coil (in LAD) to store an RLO in the BR bit according to
the following criteria:
S Store an RLO of 1 in the BR bit for a case where the FB or FC is
executed without error.
S Store an RLO of 0 in the BR bit for a case where the FB or FC is
executed with error.
You should program these instructions at the end of the FB or FC so that
these are the last instructions that are executed in the block.
!
Warning
Possible unintentional resetting of the BR bit to 0.
When writing FBs and FCs in LAD, if you fail to manage the BR bit as
described above, one FB or FC may overwrite the BR bit of another FB
or FC.
To avoid this problem, store the RLO at the end of each FB or FC as
described above.
Address Identifier
Binary Result Bit
Glossary
Glossary-3
S7 Standard Functions Part 2
C79000-G7076-C113-02
C
The Central Processing Unit (CPU) module contains the user program and
processes the data for the programmable logic controller.
D
A data block (DB) stores data for the user program. You define the structure
for the information that is stored in the DB. This information can be shared
with (accessed by) all of the logic blocks in a program, or can be used as a
specific instance of a particular FB (where the structure of the DB is
associated with the variable declaration table of the FB).
Data to be used in a program can be assigned a data type. When you define
symbolic names in the Symbol Editor or when you define block-local
variables in the variable declaration table, you must specify a data type. The
data type defines the length and organization for the bits of memory that is
being reserved by the CPU.
S Elementary data types: BOOL (boolean), BYTE, WORD, DWORD
(double-word), CHAR (character), INT (integer), DINT (double-integer),
REAL (floating point), TIME, DATE, TOD (time of day), and S5TIME.
The operating system allocates a fixed length of memory for each of the
elementary data types. For example, a boolean data type (BOOL) is one
bit, a byte (BYTE) is 8 bits, a word (WORD) is 2 bytes (or 16 bits), and a
double word (DWORD) is 4 bytes (or 32 bits).
S Complex data types: DT (data and time), STRING (up to 255 characters),
STRUCT, UDT and ARRAY. Complex data types are typically larger than
32 bits (4 bytes). You can create combinations of data types either by
defining a group of data types into a structure (STRUCT), or by defining
a number of a specific data types into an array.
S Parameter types: TIMER (timer number), COUNTER (counter number),
BLOCK_[DB, FB, FC, SDB, SFC, SFB] (number of the type of block
identified), POINTER (pointer reference to an address), or ANY (allows
an undefined, or any, data type).
A type of addressing in which the address of an instruction points directly to
the location of the value with which the instruction is to work. Compare
Immediate Addressing.
CPU
Data Block (DB)
Data Types
Direct Addressing
Glossary
Glossary-4
S7 Standard Functions Part 2
C79000-G7076-C113-02
F
Formal parameters are declared in the variable declaration table of an FB or
FC. When you call the FB or FC, you must supply an actual parameter
(either an address or a value) to each formal parameter.
A function (FC) is a logic block which contains a program segment but has
no associated memory area. It functions like a sub-routine in a computer
program. You create FCs and call them from your program. Since your
program can call an FC many times (and pass different values for each call),
an FC is defined as a reusable block. When the FC finishes processing, the
local temporary data that was used by the FC is reallocated.
A function block (FB) is a logic block which contains a program segment and
has an associated memory area. Each time an FB is called, a data block
(instance DB) must be provided. A single FB can be called several times,
each time with a different instance DB. Parameters and static variables for
the FB are stored in the instance DB.
I
A type of addressing in which the actual value with which the instruction is
to work is provided as an input parameter. This value is the address of the
instruction. Compare Direct Addressing.
An instance DB provides memory for a specific call (or instance) of an FB.
By creating multiple instances (instance DBs) of an FB, you can use one FB
to control several devices.
The structure of an instance DB reflects the variable declaration table of an
FB. The instance DB stores the actual parameters for the in, out, in_out, and
var variables.
A ladder logic instruction tells the CPU of your programmable controller
what function the controller should perform. Ladder logic instructions can be
in the form of elements or boxes.
Formal Parameter
Function (FC)
Function Block
(FB)
Immediate
Addressing
Instance Data
Block (DB)
Instruction
Glossary
Glossary-5
S7 Standard Functions Part 2
C79000-G7076-C113-02
L
Ladder logic (LAD) is one of two languages of the STEP7 programming
software that you can use to program your STEP 7-300 programmable logic
controller (PLC). LAD is a graphic language whose components resemble
elements of a hard-wired control relay panel.
Logic blocks are the blocks within STEP 7 that contain the program for the
control logic. These are the organization blocks (OBs), functions and
function blocks (FCs and FBs), and system functions and system function
blocks (SFCs and SFBs). A data block (DB) is not considered a logic block.
M
The Master Control Relay (MCR) is an American relay ladder logic master
switch for energizing and de-energizing power flow (current path). A
de-energized current path corresponds to an instruction sequence that writes a
zero value instead of the calculated value, or, to an instruction sequence that
leaves the existing memory value unchanged.
A memory area represents the location in the CPU where an instruction finds
a value (data object) on which to perform an operation. Your programmable
logic controller has the following memory areas that you can designate as
part of the address of an instruction:
S Process-image input
S Process-image output
S Bit memory
S I/O (peripheral I/O)
S Timer
S Counter
S Data block
S Temporary data (dynamic local data)
Mnemonic representation is an abbreviated form for displaying the names of
addresses and programming instructions in the program (for example, I
stands for input and A stands for the And instruction). STEP 7 supports
the international representation (based on the English language), and the
SIMATIC representation (based on the German representations of the
instruction set and the SIMATIC addressing conventions).
Ladder Logic
(LAD)
Logic Block
Master Control
Relay
Memory Area
Mnemonic
Representation
Glossary
Glossary-6
S7 Standard Functions Part 2
C79000-G7076-C113-02
N
In STEP 7 ladder logic, a network is a rung of ladder logic instructions.
Compare Rung.
O
See Address
P
A pointer is a device that identifies the location of a variable. A pointer
contains an address instead of a value. When assigning an actual parameter
for the parameter type pointer, you provide the memory address. STEP 7
allows you to enter the pointer in either a pointer format or simply as an
address (such as M 50.0). The following is an example of the pointer format
for accessing data starting at M 50.0:
P#M50.0
R
Bit 1 of the status word is called the result of logic operation bit (RLO bit).
This bit stores the result of a bit logic instruction or math comparison. The
signal state of the RLO bit can provide information related to power flow. A
signal state of 1 can indicate power flow (on); a signal state of 0 can indicate
no power flow (off).
For example, the first instruction in a rung of ladder logic checks the signal
state of a contact and produces a result of 1 or 0. The instruction stores the
result of this signal state check in the RLO bit. The second instruction in a
rung of bit logic instructions also checks the signal state of a contact and
produces a result. Then the instruction combines this result with the value
stored in the RLO bit of the status word according to the principles of
Boolean logic (see First Check above). The result of this logic operation is
stored in the RLO bit of the status word, replacing the former value in the
RLO bit. Each subsequent instruction in the rung performs a logic operation
on two values: the result produced when the instruction checks the contact,
and the current RLO.
You can use a Boolean bit logic instruction on a first check to assign the state
of the contents of a Boolean bit memory location to the RLO. You can also
use the RLO to trigger jump instructions.
Network
Operand
Pointer
Result of Logic
Operation
Glossary
Glossary-7
S7 Standard Functions Part 2
C79000-G7076-C113-02
A rung is a row of ladder logic instructions, generally input contacts and box
instructions, terminated by an output instruction at the end of the row. In
STEP 7 ladder logic, a rung constitutes a network.
S
Statement list (STL) is one of the languages of the STEP 7 programming
software that you can use to communicate with your S7 300 programmable
logic controller. Each statement in your program includes an instruction that
uses a mnemonic abbreviation to represent a function of the programmable
logic controller.
While every element in the CPU has an absolute address (such as I 0.0),
you can also create a symbolic name which can be used for addressing. For
example, you can associate input I 1.3 with Pump_2_feedback. The
symbolic names are defined in a symbol table that you create with the
Symbol Editor.
A system function (SFC) is a pre-programmed, tested function that is
integrated in the S7 operating system. You can call an SFC from your
program. Because SFCs are a part of the operating system, they do not take
up any space in the main memory. As with an FC, an SFC does not use an
instance DB.
A system function block (SFB) is a function block that is integrated in the S7
operating system. You can call an SFB from your program. Similar to the FB,
the SFB has its own working memory in which data can be stored until the
next time the SFB is called. This memory is implemented as an instance data
block (instance DB). You must create this DB (which is opened as part of the
Call instruction). Because SFBs are a part of the operating system, you do
not have to load them.
U
The user program contains the control logic for an automation project. This
control logic is stored in the form of instructions to the PLC which is
controlling plant or a process.
Rung
Statement List
Symbolic
Addressing
System Function
(SFC)
System Function
Block (SFB)
User Program
Glossary
Glossary-8
S7 Standard Functions Part 2
C79000-G7076-C113-02
V
All logic blocks have a variable declaration table. When you enter
information in the variable declaration table, you declare (define) the
parameters and variables that are used by the block.
Variable
Declaration Table
Glossary
Index-1
S7 Standard Functions Part 2
C79000-G7076-C113-02
Index
A
Add to table (ATT), 2-22-3
ASCII to Hex (ATH), 6-46-5
B
Bit logic functions
reset range of immediate outputs (RSETI),
1-41-5
reset range of outputs (RSET), 1-21-3
set range of immediate outputs (SETI),
1-81-10
set range of outputs (SET), 1-61-7
Bit shift register (SHRB), 3-43-6
C
Compare function blocks, index matrix compare
(IMC), 8-2
Conversion functions
ASCII to hex (ATH), 6-46-5
decode binary position (DECO), 6-9
encode binary position (ENCO), 6-8
hex to ASCII (HTA), 6-66-7
seven segment decoder (SEG), 6-26-3
sum number of bits (BITSUM), 6-11
Tens complement (BCDCPL), 6-10
Convert functions and function block
lead/lag algorithm (LEAD_LAG), 6-16
scaling values (SCALE), 6-12
unscaling values (UNSCALE), 6-14
Correlated Data Table (CDT), 2-16
D
Decode binary position (DECO), 6-9
Discrete Control Alarm Timer (DCAT), 5-4
E
Encode binary position (ENCO), 6-8
Event maskable drum (DRUM), 5-10
F
First in/first out unload table (FIFO), 2-42-5
Floating Point Math Functions, standard
deviation (DEV), 7-2
H
Hex to ASCII (HTA), 6-66-7
I
Index matrix compare (IMC), 8-2
Indirect block move (IBLKMOV), 4-24-3
L
Last in/first out unload table (LIFO), 2-82-9
Lead/Lag algorithm (LEAD_LAG), 6-16
M
Motor control alarm timer (MCAT), 5-7
Move function and function block, pack data
(PACK), 4-4
Move functions, indirect block move
(IBLKMOV), 4-24-3
Move table to word (TBL_WRD), 2-122-13
Index-2
S7 Standard Functions Part 2
C79000-G7076-C113-02
P
Pack Data (PACK), 4-4
R
Reset range of immediate outputs (RSETI),
1-41-5
Reset range of outputs (RSET), 1-21-3
S
Scaling values (SCALE), 6-12
Scan matrix compare (SMC), 8-6
Set range of immediate outputs (SETI),
1-81-10
Set range of outputs (SET), 1-61-7
Seven segment decoder (SEG), 6-26-3
Shift functions
bit shift register (SHRB), 3-43-6
word shift register (WSR), 3-23-3
Software timer on delay-retentive (TONR),
5-25-3
Standard Deviation (DEV), 7-2
Sum number of bits (BITSUM), 6-11
T
Table (TBL), 2-102-11
Table find (TBL_FIND), 2-62-7
Table functions
add to table (ATT), 2-22-3
correlated data table (CDT), 2-16
first in/first out unload table (FIFO), 2-42-5
last in/first out unload table (LIFO), 2-82-9
move table to word (TBL_WRD), 2-122-13
table (TBL), 2-102-11
table find (TBL_FIND), 2-62-7
table to table (TBL_TBL), 2-18
word to table (WRD_TBL), 2-142-15
Table To Table (TBL_TBL), 2-18
Tens complement (BCDCPL), 6-10
Timer functions, software timer on delay-
retentive (TONR), 5-25-3
Timer functions and function blocks
discrete control alarm timer (DCAT), 5-4
event maskable drum (DRUM), 5-10
motor control alarm timer (MCAT), 5-7
U
Unscaling values (UNSCALE), 6-14
W
Word shift register (WSR), 3-23-3
Word to table (WRD_TBL), 2-142-15
Index
S7 Standard Functions Part 2
C79000-G7076-C113-02
1 $
Siemens AG
A&D AS E 46
Oestliche Rheinbrueckenstr. 50
D76181 Karlsruhe
Federal Republic of Germany
Please check any industry that applies to you:
r Automotive
r Chemical
r Electrical Machinery
r Food
r Instrument and Control
r Nonelectrical Machinery
r Petrochemical
r Pharmaceutical
r Plastic
r Pulp and Paper
r Textiles
r Transportation
r Other _ _ _ _ _ _ _ _ _ _ _
From:
Your Name: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Your Title: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Company Name: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Street: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
City, Zip Code_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Country: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Phone: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2
S7 Standard Functions Part 2
C79000-G7076-C113-02
Additional comments:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Remarks Form
Your comments and recommendations will help us to improve the quality and usefulness
of our publications. Please take the first available opportunity to fill out this questionnaire
and return it to Siemens.
Please give each of the following questions your own personal mark within the range
from 1 (very good) to 5 (poor).
1. Do the contents meet your requirements?
2. Is the information you need easy to find?
3. Is the text easy to understand?
4. Does the level of technical detail meet your requirements?
5. Please rate the quality of the graphics/tables:

You might also like