Design Phase and Amplitude Comparators For Transmission Line Protection
This document describes the design of phase and amplitude comparators for polyphase relays used in transmission line protection. It proposes designs for phase-to-phase, three-phase, and phase-to-ground comparators that can be implemented on microprocessors. The designs are tested using simulated fault data from EMTDC simulations. Key results showing the performance of the comparators are included.
Design Phase and Amplitude Comparators For Transmission Line Protection
This document describes the design of phase and amplitude comparators for polyphase relays used in transmission line protection. It proposes designs for phase-to-phase, three-phase, and phase-to-ground comparators that can be implemented on microprocessors. The designs are tested using simulated fault data from EMTDC simulations. Key results showing the performance of the comparators are included.
Design of Phase and Amplitude Comparators for Transmission Line Protection
M.S. Sachdev' T.S. Sidhu' I. Uttamchandani' W.O. Kennedy Consultant Power Systems Research Group' University of Saskatchewan Saskatoon, Saskatchewan CANADA S7N 5A9 Abstract: This paper describes the design of polyphase relays by using the amplitude and phase comparison techniques. Both techniques are used for designing the phase-to-phase, three-phase and phase-to-ground relays. A new polyphase amplitude method, which uses inputs from the phase comparator, is proposed for protecting lines during phase-to-phase and three-phase faults. A unique amplitude and phase comparison approach is introduced for use in a polyphase phase-to-ground relaying unit. The proposed designs are suitable for implementation on microprocessors. Performance of the comparators was evaluated by using data simulated using EMTDC and some results are included i n the paper. Keywords: Polyphase relays, distance relay, polyphase amplitude comparator, polyphase phase comparator, digital re1ay s. I. INTRODUCTION Polyphase measuring units have been used extensively in electromechanical and electronic realizations of relays for protecting transmission lines. In 1958, Sonnemann & Lensner [l] outlined the theory of polyphase distance relays using the symmetrical components approach. Polyphase relays use either phase or amplitude comparison in a single measuring unit [2]. Inputs to these units are signals formed from voltages and currents of faulted and unfaulted phases. The characteristics of these relays can be analyzed by either mathematical analysis or graphical examination. Phasor diagrams were used to investigate the behavior of KD relays U]. Although, single phase mho units are capable of protecting transmission lines, they take considerable space and cost more than the polyphase units. Also, electric power utilities have been using electromagnetic and solid-state type distance relays to protect transmission lines. With the availability of modern microprocessors and Digital Signal Processing (DSP) chips, it has become possible to perform large amounts of calculations and implement logic in relatively short times. This has led to the availability of new and complex microprocessor based relays[4,5]. This paper describes the design of polyphase amplitude and phase comparators for detecting phase-to-phase, three- phase and single-phase-to-ground faults. Some results showing their performance, which was checked using data obtained from simulations performed on the EMTDC, are included. II. POLYPHASE COMPAFWTORS Polyphase distance relays differ from conventional mho relays which detect one type of fault only. For example, three mho elements are needed for phase to ground faults and another three are needed to detect phase-to-phase faults. A complete single zone protection system, therefore, requires six mho elements. Compared to this, only one polyphase element is needed to detect three types of phase-to-phase faults and another to detect the three single phase to ground faults. This section describes the design of phase and amplitude comparators for detecting phase-to-phase, three- phase and single-phase-to-ground faults. A. Phase-to-Phase Design Polyphase relays which detect phase-to-phase faults, such as A-B, B-C and C-A faults, use the phase comparison technique which is most commonly used by industry. For example the phase-to-phase fault element of KD4, marketed by the Westinghouse Electric Corporation (now ABB), is designed to perform phase comparison. The inputs to this comparator, Su b and s b c [3], are: In these equations, V,, v b , V , lu, Ib and IC are the voltages and currents and Z, is the replica impedance used in the relay. The comparator operates when Sbc leads Sab; this can be mathematically expressed as 0' 5 (AS,, - LS, b) 5 180' (3) It is possible to have a polyphase amplitude comparator which has the same characteristic as the phase comparator described by Equations 1 to 3. One possible design of such a comparator would use the following inputs. s O=s b c +j s u b (4) Sr =Sb c - j Su b ( 5) The operating condition of the polyphase amplitude comparator is ISBN 0-7803-4147-3AEEE CAT. NO. 97CH36117 Q 1997 IEEE 1991 Conference on Communications. Power and Computing WESCANEX'97 Proceedings; Winnipeg, MB; May 22-23, 1997; pp. 179-184 180 when plotted on R-X diagram and are independent of the source impedance but depend on the relay settling impedance. C. Phase-to-Ground Design The most frequent type of fault experienced on a power system is the phase-to-ground fault. It can occur between any of the three phases and the ground. Utilities have been using single phase units to protect their lines during phase- to-ground faults [3]. Three single phase units are needed for zone one protection, while one polyphase unit can provide protection during any single phase to ground fault, thereby saving considerable space and cost.. A more attractive technique, that uses positive-, negative- and zero-sequence components of voltages and currents for phase-to-ground polyphase design, is introduced in this section. The input signals to an amplitude comparator for correct measurement of a-ground, b-ground, and c-ground short-circuits are: so= vxo+ vx2 (12) Sr=V.l (13) The operating signal, So, is made up of negative and zero sequence components, VX2 and Vxo. The restraining signal, Sr, consists of a positive sequence component denoted by V,,. The sequence components can be expressed in terms of compensated voltages, V,, V,and V,, at the relay location as: V,=( u3)( vx+ vy+ V,) (14) The characteristic equation describing the behavior of the phase and amplitude comparators can be derived and they are identical. The characteristic plotted on R-X plane is shown in Figure 1. The characteristic is in the shape of a circle which expands and shrinks depending on the source impedance. If source impedance is zero, the characteristic circle passes through the origin of the R-X diagram. For faults behind the relay, current reversal occurs and the relay restrains. Memory action is not needed because sufficient torque exists for close-in faults. Fig. 1. Characteristic of the phase-to-phase relay on the R-X diagram. B. Three-phase Design Westinghouse Electric Corporation [3] are: The inputs to the phase comparator introduced by the The comparator operates when V,leads VZy i.e. 0 S( LV, . . -LVz, , ) S 180 (9) Three-phase faults can also be detected by using an amplitude comparator which has the same characteristics as the phase comparator described by Equations 7 to 9. The operating and restraining signals of such a comparator would be as follows: The operating condition of this three-phase amplitude comparator is given in Equation 6. It can be shown that the characteristic equations of both comparators are identical. The characteristics are circular V,~=(I/~)(V,+ a2 Vy+a vz) (16) The voltages V,, V, and V, are defined as V,= Vc-(Ic+ KIo)Zn where: K=(ZO-Z&ZI is the complex constant made of the positive and zero sequence impedance of the transmission line. is the zero sequence current measured at the relay location. IO It is possible to have a polyphase phase comparator which has the same characteristic as the amplitude comparator defined by Equations 12 and 13. One possible design of such a comparator is given as: The signals SI and Sz can be calculated from Equations 2.0 and 21. The comparator will operate when S, leads Sz i.e. 181 0' 5 ( LS, - LS,) 5180' (22) The characteristic equations derived for the amplitude and phase comparators are identical. The characteristic of the comparators is circular whose center and radius can be computed. Also, the operating characteristics of the phase- to-ground relays are the same as that of the phase-to-phase relays. HI. DETERMINATION OF FUNDAMENTAL FREQUENCY COMPONENTS Signals formed from the voltage and current phasors of the fundamental frequency are used for making decisions. It is, therefore, essential that the fundamental frequency components of voltages and currents be determined. Microprocessor based relays sample voltages and currents and compute phasors representing their fundamental frequency components [4,5]. Voltage and current signals contain transient components such as, exponentially decaying dc, harmonics and other high frequencies. This is especially true for currents and voltages experienced during a fault. Since phasors of the fundamental frequency components are to be used in the designed comparator, decaying dc and harmonics must be eliminated from the inputs. In the work reported i n this paper the real and imaginary parts of the fundamental frequency phasors were estimated using Least Error Square (LES) digital filters [6]. During the design of the filters, it was assumed that each input signal is composed of an exponentially decaying dc and fundamental, second, third, fourth and the fifth harmonics. A data window of 13 samples taken at 720 Hz was used. IV. TEST RESULTS Four software modules were written to test the performance of the phase and amplitude comparators. Module A was written to simulate, on the EMTDC, a sample power shown in Figure 2. The voltages and currents provided by the simulation performed by Module A were processed in Module B which included 4th order anti-aliasing low pass filters. Outputs from Module B were then provided to Module C which estimated the real and imaginary parts of the fundamental frequency phasors. The estimates of the phasors were presented to Module D which made the 'trip'/'do not trip' decisions. Polyphase relays were set to protect 80% of the 200-km long line. Several phase-to-phase, three-phase and phase-to- ground faults at different locations on the line were simulated. The data were processed by Module D which used phase and amplitude comparison for making decisions. Some results are presented in this section. Module D TRIP S1& s2 P away from the relay. Figure 3 shows the difference between the phase angles of sbc and Sab, the signals used for phase comparison. Originally, the difference between the phase angles is out of the operating range. After the fault, the difference changes and moves into the operating range and the relay operates. The comparator took about 9.7 ms (7 samples) to produce the trip command. Figure 4 shows the operating and the restraining signals of the amplitude comparator. Immediately after the inception of the fault, the operating signal starts to increase and the restraining signal starts to decrease. A trip command is issued 9.7 ms (7 samples) after the inception of the fault. A phase-to-phase fault (c-a) was also applied on the line at 190 km away from the relay. Both comparators remained stable and did not produce any trip signals as shown in Figures 5 and 6. Figures 7 and 8 show the decision-making signals for phase and amplitude comparators when b-c fault is applied at the relay. Both comparators produce trip signals in 8.3 ms (6 samples). transmission line SAMPLES Module A va, vb, vc ia, ib, ic 4t h ORDER DIGITAL Low PASS FILTER Module B is, ib, ic va, vb, vc 13 SAMPLE LEAST ERROR SQU- DIGITAL FILTER Module c Fig. 2. Flow Chart for testing the comparators. A. Results of Phase-to-Phase Design Figures 3 and 4 show the performance of the comparators for a line side phase-to-phase (a-b) fault at a location 50 km 182 B. Results of Three-phase Design A three-phase fault (a-b-c) was simulated at 100 km away from the relay. The phase comparator issued a trip command in 13.9 ms (10 samples) as shown in Figure 9. The amplitude comparator also issued a trip signal in 13.9 ms; the operating and restraining signals are shown in Figure 10. The phase and amplitude comparators did not issue any trip commands for a three-phase fault at 190 km away from the relay, as is shown in Figures 11 and 12. C. Results of Phase-to-Ground Design Figures 13 and 14 show the performance of the comparatalrs for a line-side b-g fault 100 km from the relay. Both comparators produced trip commands 15.3 ms (1 1 samples) after the inception of the fault. Faults behind the relay location (bus-side faults) were also simulated. Figures 15 and 16 illustrate the results for a phase-a-g fault. It can Ibe seen from the figure that the comparators do not operate. 90 9 0 3 -90 -180 - 180 T .......................... I .I .. I .. .. I. u i i i i m i m m i i i i m i . ' 1 . _ 180 90 2 9 a 0 -90 -180 0 - ? I! 3 :: ................. 1. Fig. 3. Angle difference between sbc and Sab for a a-b fault 50 km away from relay. - ......................... .I.. I .. I .. I I I .. I ............... * 450000 N - 300000 8 8 4 4 150000 0 -180 1 .............. 450000 1. "I 0.081 0.096 0.111 0.127 0.142 ......................... , - Time (4 8 I 2 4 6 150000 ........................ 0 , J 0.081 0.096 0.111 0.l27 0.142 Time 6) ................ \ ............. .......... 0 0.081 0.096 0.111 0.127 0.142 Time (s) Fig. 4. Magnitude square of So and S, for a a-b fault 50 km away from relay. Fig. 6. Magnitude square of So and S, for a c-a fault 190 km away from relay. Fig. 5. Angle difference between sbc and Sab for a C-afault 190 km away from relay. Fig. 7. Angle difference between sbc and sab for a b-c fault at the relay. 183 -90 I Fig. 11. Angle difference between V, and V,, for a-b-c fault 190 km away from relay. Fig. 8. Magnitude square of SO and S, for a b-c fault at the relay. .ll.ll..lllllllll I 180 T II I I . m m i 300000 T _...-_ 0 0.082 0.097 0.113 0.128 0.143 Time (a) Fig. 9. Angle difference between V, and V, for a-b-c fault 100 km away from relay. Fig. 12. Magnitude square of SO and S, for a-b-c fault 190 km away from relay. - 0 0.082 0.097 0.113 0.128 0.143 Time (9) Fig. 13. Angle difference between SI and SZ for b-g fault Fig. 10. Magnitude square sf SO and S, for a-b-c fault 100 kmaway from relay. km away from relay. 500007 - H 8 ;j 25OOo a I O + Fig. 15. Angle difference between SI and S2 for a-g fault MS. Advancements in behind the relay. Microprocessor Based Protection and Communication, IEEE Tutorial Course Text, Publication No. 97TP120-0, 1997. phase comparator, has been proposed for phase-to-phase and _ . . . - _ three-phase designs. A unique amplitude and phase comparison approach has been introduced for the polyphiise phase-to-ground design. Characteristics of the proposed -- amplitude comparators are identical to that of ithe conventional phase comparator. Both comparators benefit from the polarizing signals in detecting close-in faullts. Extensive testing showed that the tripping times for the faults on the line-side are similar for both techniques. . O- . - - - . - . - - . . -. .- .-__._--__.---.-.-_ . - 0 - - $ 3 -90 3 -180 7 [2] A.R. van C. Warrington, Protective Relays Their Theory and Practice Volume I & I1 Chapman and Hall 1974. .. " ' 8 I.............' .. ........................ [3] Applied Protective Relaying, Westinghouse Electric Corporation, Relay-Instrument Division, Newark, New Jersey, U.S.A., 1964. [4] M.S. Sachdev (coordinator), Microprocessor Relays and - w- 3oooo PI 2 Q 2oooo I 0 U2 loo00 0 - _ - _ _ _ Apparatus and Systems, Vol. PAS-98, No., Nov./Dec. 1979, pp. 2232-2240 ..- ---..___ _ _ . \ - * . . '. ' c - * , \ .- - __._-_.-____.__.______ -- .- . _